MGS7310GCP OPERATION MANUAL

■ How to Switch the Status Screen Status


You can display the status of each page by This page is a Home Page, and if you do not
operating the up and down buttons of MGS7310 operate the button for a certain period of time after
controller. The screen transitions by pressing the the transition to another page, the screen
down button is shown in the following section. automatically changes to Status, and the screen
Pressing the up button will reverse the screen will change to Status screen 2 from Status screen
transitions. When there is no button operation for a 1. When the bottom is not operated for a certain
certain period of time in the page Status, the period of time after Status screen 1 is displayed, the
automatic screen transition will take place, but screen automatically changes to Status screen 2. If
since the transition state differs depending on the the start of the engine is confirmed during Status
page, details are described in each section. screen 2 display, the screen automatically changes
to Status screen 3.
1 Operate the right/left button to
display Status screen 1.

Status

Fig. 6-7 Switch Buttons, Up and Down

Fig. 6-8 Status screen 1

2 Press the down button to display


Status screen 2.

Status 08:30

Generator at Rest
2
3
Stop Mode

Fig. 6-9 Status screen 2

1 Indicates the current time.


2 Indicates the state of the generator set.
Examples: On Load, Generator Avail-
able
3 Indicates the state of the mode.
Examples: Auto Mode, Manual Mode

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL


7
Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

3 Press the down button to display Engine


Status screen 3. When the engine
stops normally, the screen will From Engine Speed screen through Engine
return to Status screen 2. Lubricating Oil Temperature screen, the name of
values are shown at the top of screen. If you do not
operate the button for a certain period of time after
1 2 Engine screen is displayed, the screen
automatically changes to Engine Speed screen,
Generator at Rest 08:30 and the automatic screen transitions from Engine
Speed to Engine Lubricating Oil Temperature
L-N 0A 0A screen will be repeated.
L-L 0A 0.0Hz 1 Operate the right/left button to
display Engine screen.
L-L 0kW - - - - pf

Fig. 6-10 Status screen 3

1 Indicates the state of the generator Engine


set. Examples: On load, Generator
Available, Return Delay 00:06
The countdown timer is displayed
when starting and stopping.
2 Indicates the state of the generator.
Fig. 6-12 Engine screen
4 Press the down button to return to
Status screen 1. 2 Press the down button, then Engine
Speed screen is displayed.

Status

Engine Speed

1541 RPM
Fig. 6-11 Status screen 1
Fig. 6-13 Engine Speed screen

3 Press the down button, then Engine


Oil Pressure screen is displayed.

Engine Oil Pressure

5.16 bar
74 psi
516 kPa
Fig. 6-14 Engine Oil Pressure screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL 8


Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

4 Press the down button, then Engine 7 Press the down button, then Engine
Coolant Temp. screen is displayed. Lubricating Oil Temperature screen
is displayed if the sensor is
installed.

Engine Coolant Temp.

73 °C L/O Temp Sender

163 °F 72 °C
Fig. 6-15 Engine Coolant Temp. screen 161 °F
5 Press the down button, then Engine Fig. 6-18 Engine Lubricating Oil Temperature
Battery Voltage screen is displayed. screen

8 Press the down button, then the


screen returns to Engine screen.
Engine Battery Voltage

Battery 24.1 V
Engine
Charge Alt 22.7 V
Fig. 6-16 Engine Battery Voltage screen

6 Press the down button, then Engine


Run Time screen is displayed. Fig. 6-19 Engine screen

Engine Run Time

53h 33m
1995 Start(s)

Fig. 6-17 Engine Run Time screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL


9
Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

Generator 4 Press the down button, then


Generator Frequency screen is
From Generator Voltage (1) screen through Active displayed.
Config (2) screen, the name of values are shown at
the top of screen. If you do not operate the button
for a certain period of time after Generator screen
is displayed, the screen automatically changes to
Generator Voltage (1), and the automatic screen Generator Frequency
transitions from Generator Voltage (1) to Active
Config (2) will be repeated.
1 Operate the right/left button to
display Generator screen.
50.0 Hz

Fig. 6-23 Generator Frequency screen

Generator 5 Press the down button, then


Generator Current screen is
displayed.

Fig. 6-20 Generator screen


Generator Current

2 Press the down button, then L1 0 A


Generator Voltage (1) screen is
displayed.
L2 0 A
L3 0 A
Fig. 6-24 Generator Current screen

Generator Voltage 6 Press the down button, then


L1 - N 219 V Generator Earth Current screen is
displayed.
L2 - N 221 V
L3 - N 220 V
Fig. 6-21 Generator Voltage (1) screen
Generator Earth Current

3 Press the down button, then


Generator Voltage (2) screen is
displayed. 0 A

Fig. 6-25 Generator Earth Current screen

Generator Voltage

L1 - L2 381 V
L2 - L3 382 V
L3 - L1 380 V
Fig. 6-22 Generator Voltage (2) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL 10


Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

7 Press the down button, then 10 Press the down button, then
Generator Load (1) screen is Generator Load (4) screen is
displayed. displayed.

Generator Load Generator Load

L1 0 kW L1 0 kVA
L2 0 kW L2 0 kVA
L3 0 kW L3 0 kVA
Fig. 6-26 Generator Load (1) screen Fig. 6-29 Generator Load (4) screen

8 Press the down button, then 11 Press the down button, then
Generator Load (2) screen is Generator Load (5) screen is
displayed. displayed.

Generator Load Generator Load

L1 0 %
Total 0 kVA
L2 0 %
0 %
L3 0 %
Fig. 6-27 Generator Load (2) screen Fig. 6-30 Generator Load (5) screen

9 Press the down button, then 12 Press the down button, then
Generator Load (3) screen is Generator Power Factor screen (1) is
displayed. displayed.

Generator Load Generator Power factor

L1 ----
Total 0 kW
L2 ----
0 %
L3 ----
Fig. 6-28 Generator Load (3) screen Fig. 6-31 Generator Power Factor (1) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL


11
Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

13 Press the down button, then 16 Press the down button, then
Generator Power Factor screen (2) is Generator Load (8) screen is
displayed. displayed.

Generator Power factor Generator Load

847.9 kWh
Average ---- 908.6 kVAh
74.9 kVArh
Fig. 6-32 Generator Power Factor (2) screen Fig. 6-35 Generator Load (8) screen

14 Press the down button, then 17 Press the down button, then Gen
Generator Load (6) screen is Phase Sequence screen is displayed.
displayed.

Gen Phase Sequence


Generator Load

L1 0 kVAr
L3 L2 L1
L2 0 kVAr
L3 0 kVAr
Fig. 6-36 Gen Phase Sequence screen
Fig. 6-33 Generator Load (6) screen
18 Press the down button, then Active
15 Press the down button, then Config (1) screen is displayed.
Generator Load (7) screen is
displayed.

Active Config

Generator Load
116 V
50.0 Hz
Total 0 kVAr
3Phase.4Wire
0 % Fig. 6-37 Active Config (1) screen

Fig. 6-34 Generator Load (7) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL 12


Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

19 Press the down button, then Active Alarm


Config (2) screen is displayed.
In the case where three types of alarm occurs in the
order of Shutdown, Electrical trip, and Warning, the
screen transitions of Alarm Page status display are
explained hereunder. If you do not operate the
Active Config button for a certain period of time after Alarms (1)
screen is displayed, the screen automatically
changes to Alarms (2) and the automatic screen
Default Config transitions from Alarms (2) to the last screen of
Alarms (4) will be repeated. When an alarm occurs,
the screen automatically changes to the Alarms (2)
screen (the latest Alarm screen). However, if you
Fig. 6-38 Active Config (2) screen move to another page without releasing Alarm that
has been generated, the screen will not change
20 Press the down button, then the automatically even if another Alarm occurs. In the
screen returns to Generator screen. case where Warning only presented, the screen
automatically returns to ‘Home’ Page when the
cause of warning is removed.

1 Operate the right/left button to


Generator
display Alarms (1) screen.

Alarms
Fig. 6-39 Generator screen

Fig. 6-40 Alarms (1) screen

2 Press the down button, then Alarms


(2) screen is displayed.

1/3 Alarms

Coolant Water Low


2

3
Warning

Fig. 6-41 Alarms (2) screen

13 MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL


Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

Event Log
1 Indicate the number of alarms presented.
If you do not operate the button for a certain period
2 Indicates the detailed name of the alarm. Exam- of time after Event Log (1) screen is displayed, the
ples: Refer to Alarms (3) screen, Alarms (4) screen automatically changes to Event Log (2)
screen screen and the automatic screen transitions from
3 Indicates the type of alarm. Examples: Refer to Event Log (2) to the last screen of Event Log (5) will
Alarms (3) screen, Alarms (4) screen be repeated.

1 Operate the right/left button to


3 Press the down button, then Alarms display Event Log (1) screen.
(3) screen is displayed.

Event Log
2/3 Alarms

Electrical Trip

Electrical trip
Fig. 6-45 Event Log (1) screen
Fig. 6-42 Alarms (3) screen
2 Press the down button, then Event
4 Press the down button, then Alarms Log (2) screen is displayed.
(4) screen is displayed.

1 Event Log
3/3 Alarms
Coolant Water Low
Emergency Stop
Warning 2

05 Jul 2017,13:44:07 3
Shutdown
Fig. 6-46 Event Log (2) screen
Fig. 6-43 Alarms (4) screen
1 Indicates the Event number. (Maximum 250)
5 Press the down button, then the
screen returns to Alarms (1) screen. 2 Indicates the Event details. Examples: Refer to
Event Log (3), (4), (5) screens.
3 Indicates the date and time in which the event
occurred. Examples: Refer to Event Log (3),
(4), (5) screens.
Alarms

Fig. 6-44 Alarms (1) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL 14


Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

3 Press the down button, then Event 6 Press the down button, then the
Log (3) screen is displayed. screen returns to Event Log (1)
screen.

2 Event Log
Event Log
Electrical Trip

Electrical trip

05 Jul 2017,13:44:00

Fig. 6-47 Event Log (3) screen


Fig. 6-50 Event Log (5) screen
4 Press the down button, then Event
Log (4) screen is displayed.

3 Event Log

Emergency Stop

Shutdown

05 Jul 2017,13:43:46

Fig. 6-48 Event Log (4) screen

5 Press the down button, then Event


Log (5) screen is displayed.

250 Event Log

Engine Stopped

27 Jul 2017,11:22:38

Fig. 6-49 Event Log (5) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL


15
Pub. No. SZR97-00100
MGS7310GCP OPERATION MANUAL

About
Serial Port
If you do not operate the button for a certain period
The details are shown at the bottom of the Serial of time after About (1) screen is displayed, the
Port (2) screen. When the button is not operated for screen automatically changes to About (2) screen,
a certain period of time after Serial Port (1) is and the automatic screen transitions from About (2)
displayed, the screen automatically changes to to About (4) will be repeated.
Serial Port (2) screen. 1 Operate the right/left button to
1 Operate the right/left button to display About (1) screen.
display Serial Port (1) screen.

About
Serial Port

Fig. 6-54 About (1) screen


Fig. 6-51 Serial Port (1) screen
2 Press the down button, then About
2 Press the down button, then Serial (2) screen is displayed.
Port (2) screen is displayed.

About
Serial Port
Variant 7310
Baud 57600 Application V14.1.7
Slave ID 1 USB ID 6D1D2F9031

RS485 Fig. 6-55 About (2) screen


Fig. 6-52 Serial Port (2) screen
3 Press the down button, then About
3 Press the down button, then the (3) screen is displayed.
screen returns to Serial Port (1)
screen.

About

Serial Port Bootloader V1.4.0

Analogue V2.0.1

Fig. 6-56 About (3) screen

Fig. 6-53 Serial Port (1) screen

MITSUBISHI GENERATOR SERIES MGS7310CGP OPERATION MANUAL 16


Pub. No. SZR97-00100