Professional Documents
Culture Documents
Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys
Device presentation Direct starter connected to an automation controller through a bus coupler
Operational only when connected to a bus coupler
[Ie] rated operational current 66 A (at <50 °C) at <= 440 V AC-3
80 A (at <50 °C) at <= 440 V AC-1
13 Oct, 2022 1
Thermal overload class Class 5…30
Complementary
Mechanical durability 6 Mcycles
Safety performance level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Product certifications UL
CSA
CCC
EAC
Connections - terminals EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) rigid
EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) rigid
EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) flexible without cable end
EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) flexible without cable end
EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) flexible with cable end
2
13 Oct, 2022
EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) flexible with cable end
Width 55 mm
Height 167 mm
Depth 125 mm
Environment
Ambient air temperature for -25…70 °C
storage
Pollution degree 2
Protective treatment TC
Vibration resistance 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibility Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4
Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5
Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
Packing Units
Unit Type of Package 1 PCE
Offer Sustainability
Sustainable offer status Green Premium product
13 Oct, 2022 3
Mercury free Yes
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Contractual warranty
Warranty 18 months
4
13 Oct, 2022