656GB

Clamp-on
Flow Sensor

FD-Q Series
IO-Link Instruction Manual
This instruction manual explains the IO-Link specifications for the clamp-on Flow Sensor FD-Q
Series (hereinafter abbreviated as FD-Q). Details about the FD-Q functions and how to use the
unit can be found in the "FD-Q Series Instruction Manual". A copy of the "FD-Q Series Instruction
Manual" can be downloaded off of the KEYENCE website. Alternatively, contact a local KEYENCE
representative.
The settings file can also be downloaded off of the KEYENCE website. If it is not possible to gain
access to the internet to download the file, contact your KEYENCE representative.
Keyence Website: http://www.keyence.com

1. Specifications 2. Wiring

FD-Q10C
M12 connector
FD-Q20C
Model
FD-Q32C ②
FD-Q50C ③ ①

IO-Link approved standard v. 1.1
Baud rate COM2 (38.4kbps)
Pin No. Symbol Color Name
Min. cycle time 2.3 ms
1 L+ Brown DC20 - 30V
Process data length 2 Byte
2 Other White Selectable*1
Process data format UInt (unsigned integer)
3 L- Blue 0V
4*2 Q1/C Black Output 1*3/IO-Link

*1 Assignment choices: not used, output 2, external input, or analog output.


*2 Assignment changes according to the settings on the IO-Link master.
*3 When IO-Link is not connected, output 1 is assigned.

3. Process Data
Process data is a function that communicates specific data in a constant cycle.
The format in which the process data is output, can be selected from the 4 types below.
Refer to "Index 146" in "Device Parameter" on page 3, or "5-24. Process data output format" in "5-3 Menu Structure" on page 6 for information on how to select the format type.

 Process Data Structure : 0 = Instantaneous flow rate (default)

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 0 Instantaneous flow rate*1, *2

 Process Data Structure : 1 = Output 2 + Output 1 + Instantaneous flow rate

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Output 2 Output 1 Instantaneous flow rate*1, *2

 Process Data Structure : 2 = Instantaneous flow rate + Output 2 + Output 1

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Instantaneous flow rate*1, *2 Output 2 Output 1

 Process Data Structure : 3 = Instantaneous flow rate (one tenth) + Stability level + Output 2 + Output 1

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Instantaneous flow rate*1, *3 0 Stability level*4 Output 2 Output 1

*1 If the sensor displays something other than a value, one of the following will be output.

Sensor display Output


ErC Normal
ErE Normal
rEv 0
--- 0

*2 The range of the instantaneous flow rate is 0 to 9999. Units used are: 0.01 for FD-Q10C, or 0.1 for other models.
*3 The range of the instantaneous flow rate is 0 to 999. Units used are: 0.1 for FD-Q10C, or 1 for other models.
*4 The stability of the ultrasound detection is indicated through one of five level: 0 to 4. The higher the stability level, the more stable detection becomes.

-1-
4. Service Data
Service data is a function that refreshes information between the IO-Link master and slave only when there is a send request.
Reading/writing of the sensor settings and status, and execution of operation commands (tuning, etc.) can be carried out.

Meaning of each item

Item Value Meaning


Reference item – Shows the notation in the instruction manual
Record Data structure
Bit (x) Bit No. x in Record
Format
String Text string
UInt Unsigned integer
R Read possible
R/W Read/write possible
Access
W Write possible
C Operation command
○ Compatible with the data storage function*1
Data storage
– Not compatible with the data storage function

*1 Sensor settings are backed up with the IO-Link master. This allows settings to be restored if the sensor is replaced.

4-1 Parameter List

Predefined parameter
Index Name Format Length Access Data storage Default value Range Remark
12 Device Access
Record 2 Byte R/W – – – –
(0x0C) Locks
2 0 = Unlock
Data Storage Lock*1 Bit (1) 1 Bit – – 0 –
(0x02) 1 = Lock
16
Vendor Name String 64 Byte R – Keyence –
(0x10)
17
Vendor Text String 64 Byte R – www.keyence.com –
(0x11)
18
Product Name String 64 Byte R – (Differs for each model)*2 –
(0x12)
19
Product ID String 64 Byte R – (Differs for each model)*2 –
(0x13)
20
Product Text String 64 Byte R – Clamp-on Flow Sensor –
(0x14)
22
Hardware Version String 64 Byte R – – – –
(0x16)
23
Firmware Version String 64 Byte R – – – –
(0x17)
0xFF91 = Data Storage Upload
Request
0x1800 = Reverse flow - The
fluid flows in the oppositer
37 Detailed Device
Record 16 Byte R – 0 direction of the setting 'Refer to "6. Events"
(0x25) Status
0x5000 = Device hardware fault -
Device Exchange
0x7710 = Short circuit - Check
installation
40
Process Data Input UInt 2 Byte R – – – –
(0x28)

*1 Back-up and restoring in the data storage function can be locked.


*2 The following models are applicable: FD-Q10C/FD-Q20C/FD-Q32C/FD-Q50C

Device Parameter
Data
Index Name Reference item Format Length Access Default value Range Remark
storage
0 = Off
100 Selecting ch.1 and Selecting ch.2 1 = Control output
UInt 1 Byte R/W ○ 0 –
(0x64) ch.2 functions function 2 = External input
3 = Analog output
101 Selecting NPN/ 0 = NPN output
Selecting NPN/PNP UInt 1 Byte R/W ○ 0 –
(0x65) PNP 1 = PNP output
0 = 0.5 sec
1 = 1 sec
2 = 2.5 sec
102 Response time
Response Time UInt 1 Byte R/W ○ 3 3 = 5 sec –
(0x66) (refer to 5-3)
4 = 10 sec
5 = 30 sec
6 = 60 sec
Analog output
103 0 = 4 - 20 mA
Analog output current current UInt 1 Byte R/W ○ 0 Linked to Index 105/106
(0x67) 1 = 0 - 20 mA
(refer to 5-9)
0 = Reset integrated flow
1 = Perform condition monitoring
104 Command 2 = Cancel condition monitoring
Command request UInt 1 Byte C – – –
(0x68) request 3 = Reset hold values
4 = Perform origin adjustment
5 = Cancel origin adjustment
Analog output
105 Units: 0.01 for FD-Q10C,
Analog lower limit lower limit *3 UInt 2 Byte R/W ○ 0 0 to 9999
(0x69) or 0.1 for other models.
(refer to 5-10)

-2-
Data
Index Name Reference item Format Length Access Default value Range Remark
storage
FD-Q10C:3000
Analog output
106 FD-Q20C:1000 Units: 0.01 for FD-Q10C,
Analog upper limit upper limit*3 UInt 2 Byte R/W ○ 0 to 9999
(0x6A) FD-Q32C:3000 or 0.1 for other models.
(refer to 5-11)
FD-Q50C:5000
Output 1 output
110 0 = N.O.
Output 1 output logic logic UInt 1 Byte R/W ○ 0 –
(0x6E) 1 = N.C.
(refer to 5-2)
0 = Instantaneous flow rate mode
Output 1
111 Output 1 detection 1 = Area mode
detection mode UInt 1 Byte R/W ○ 0 –
(0x6F) mode 2 = Pulse output mode
(refer to 5-1)
3 = Integrated flow mode
FD-Q10C:300
Output 1 set
112 FD-Q20C:100 Units: 0.01 for FD-Q10C,
Lower set value1 value/Output 1 UInt 2 Byte R/W ○ 0 to 9999
(0x70)
lower limit value FD-Q32C:300 or 0.1 for other models.
FD-Q50C:500
FD-Q10C:1800
113 Output 1 upper FD-Q20C:600 Units: 0.01 for FD-Q10C,
Upper set value1 UInt 2 Byte R/W ○ 0 to 9999
(0x71) limit value*4 FD-Q32C:1800 or 0.1 for other models.
FD-Q50C:3000
Output 2 output
118 0 = N.O.
Output 2 output logic logic*5 UInt 1 Byte R/W ○ 0 –
(0x76) 1 = N.C.
(refer to 5-7)
Output 2 0 = Instantaneous flow rate mode
119 Output 2 detection
detection mode*5 UInt 1 Byte R/W ○ 0 1 = Area mode –
(0x77) mode
(refer to 5-6) 2 = Error output mode
FD-Q10C:600
Output 2 set
120 value/Output 2 FD-Q20C:200 Units: 0.01 for FD-Q10C,
Lower set value2 UInt 2 Byte R/W ○ 0 to 9999
(0x78) FD-Q32C:600 or 0.1 for other models.
lower limit value*6
FD-Q50C:1000
FD-Q10C:1500
121 Output 2 upper FD-Q20C:500 Units: 0.01 for FD-Q10C,
Upper set value2 UInt 2 Byte R/W ○ 0 to 9999
(0x79) limit value*7 FD-Q32C:1500 or 0.1 for other models.
FD-Q50C:2500
Selecting input 0 = Integrated flow reset input
129 Selecting input
function*8 UInt 1 Byte R/W ○ 0 1 = Flow rate zero input –
(0x81) function
(refer to 5-8) 2 = Origin adjustment input
FD-Q10C:30 Linked to Index 112/113/
131 Hysteresis FD-Q20C:10 120/121
Hysteresis UInt 2 Byte R/W ○ 0 to 9999
(0x83) (refer to 5-14) FD-Q32C:30 Units: 0.01 for FD-Q10C,
FD-Q50C:50 or 0.1 for other models.
138 Power-saving mode 0 = Normal
Power-saving mode UInt 1 Byte R/W ○ 0 –
(0x8A) (refer to 5-17) 1 = Power-saving mode
139 0 = Unlock
Key lock Key lock UInt 1 Byte R/W ○ 0 –
(0x8B) 1 = Lock
140 Key lock method 0 = Normal (without password)
Key lock method UInt 1 Byte R/W ○ 0 Linked to Index 141
(0x8C) (refer to 5-18) 1 = Password-protected key lock
Password for
141
Key lock password password- UInt 2 Byte R/W ○ 0 0 to 9999 Linked to Index 140
(0x8D)
protected key lock
Extended functions
142 Extended functions 0 = Settings complete
menu UInt 1 Byte R/W ○ 0 –
(0x8E) menu 1 = Extended functions menu
(refer to 5-5)
144
User tag1 UInt 4 Byte R/W ○ 0 0 to 4294967295 –
(0x90)
User tag*9
145
User tag2 UInt 2 Byte R/W ○ 0 0 to 65535 –
(0x91)
0 = Instantaneous flow rate
1 = Output 2 + Output 1 +
Instantaneous flow rate
Process data
146 2 = Instantaneous flow rate +
Process data structure output format UInt 1 Byte R/W ○ 0 –
(0x92) Output 2 + Output 1
(refer to 5-24)
3 = Instantaneous flow rate(one
tenth) + Stability level + Output 2 +
Output 1
148 Instantaneous flow
Instantaneous flow UInt 2 Byte R ー ー 0 to 9999
(0x94) rate
149
Integrated flow Integrated flow UInt 2 Byte R ー ー 0 to 9999
(0x95) Units: 0.01 for FD-Q10C,
160 Instantaneous flow or 0.1 for other models.
Peak hold flow UInt 2 Byte R ー ー 0 to 9999
(0xA0) peak value
161 Instantaneous flow
Bottom hold flow UInt 2 Byte R ー ー 0 to 9999
(0xA1) bottom value
0 = Detection not possible
1 = Low
180
Stability level Stability level*10 UInt 1 Byte R ー ー 2 = Medium-low –
(0xB4)
3 = Medium-high
4 = High
Identify if origin
181 adjustment is 0 = OFF
Origin adjustment currently being UInt 1 Byte R ー 0 –
(0xB5) 1 = ON
used*11
182 Condition monitoring Condition 0 = OFF
UInt 1 Byte R ○ 0 –
(0xB6) function monitoring display 1 = ON
Reference point of
191 Units: 0.01 for FD-Q10C,
Reference flow rate condition UInt 2 Byte R ○ 0 0 to 9999
(0xBF) or 0.1 for other models.
monitoring function
FD-Q10C:100
192 Zero-cut flow rate FD-Q20C:25 Units: 0.01 for FD-Q10C,
Zero-cut flow rate UInt 2 Byte R/W ○ 0 to 9999
(0xC0) (refer to 5-15) FD-Q32C:50 or 0.1 for other models.
FD-Q50C:250

-3-
Data
Index Name Reference item Format Length Access Default value Range Remark
storage
Adjusting flow rate
193 Adjusting flow rate
span*12 UInt 1 Byte R/W ○ 100 10 to 250 Unit; 0.01
(0xC1) span
(refer to 5-23)
194 Integrated flow set Set value for
UInt 2 Byte R/W ○ 150 0 to 9999 –
(0xC2) value integrated flow
0 = No correction
Correcting flow rate
200 Correcting flow rate 1 = Selecting pipe schedule
value UInt 1 Byte R/W ○ 0 –
(0xC8) value 2 = Setting flow rate magnification
(refer to 5-21)
(Span adjustment)
0 = SGP
Selecting pipe
201 Selecting pipe 1 = Sch20
schedule*13 UInt 1 Byte R/W ○ 0 –
(0xC9) schedule 2 = Sch40
(refer to 5-22)
3 = Sch80
When FD-Q10C is used:
0 = 1/4, 1 = 3/8
When FD-Q20C is used:
Selecting bore
202 Selecting bore 0 = 1/2, 1 = 3/4
diameter of pipe UInt 1 Byte R/W ○ 0 –
(0xCA) diameter of pipe When FD-Q32C is used:
(refer to 5-20)
0 = 1, 1 = 1 1/4
When FD-Q50C is used:
0 = 1 1/2, 1 = 2
0 = 0.1 (FD-Q10C, Q20C)
1=1
203 Integrated flow unit 2 = 10
Integrated flow unit UInt 1 Byte R/W ○ 1 Linked to Index 149
(0xCB) (refer to 5-4) 3 = 100
4 = 1000
5 = 10000 (FD-Q32C, Q50C)
204 Flow direction 0 = From left to right
Flow direction UInt 1 Byte R/W ○ 0 –
(0xCC) (refer to 5-19) 1 = From right to left
205 0 = liter
Flow units Flow unit UInt 1 Byte R/W ○ 0 –
(0xCD) 1 = gallon
220 Simulation mode 0 = OFF
Simulation mode UInt 1 Byte R – 0 –
(0xDC) current state*14 1 = ON
221 0 = OFF
Flow rate zero input Flow rate zero input UInt 1 Byte R/W – 0 –
(0xDD) 1 = ON
0 = Green lighting - light off
Display indicator 1 = light off - Red lighting
230 Display indicator
illumination mode UInt 1 Byte R/W ○ 0 2 = Green lighting - Red lighting –
(0xE6) illumination mode
(refer to 5-16) 3 = PMI (predictive maintenance
information)
231 Display averaging
Display averaging UInt 1 Byte R/W ○ 1 0 to 10 –
(0xE7) (refer to 5-13)
0 = 0.01
232 Display resolution
Display resolution UInt 1 Byte R/W ○ 1 1 = 0.1 –
(0xE8) (refer to 5-12)
2=1
0 = 0.01
233 0 for FD-Q10C, or
Flow resolution Unit of setting UInt 1 Byte R – 1 = 0.1 –
(0xE9) 1 for other models.
2 = Unread
*3 Valid only when "Analog output" is selected at index 100 "Selecting ch.2 function".
*4 Valid only when "Area mode" is selected at index 111 "Ouput 1 detection mode".
*5 Valid only when "Control output" is selected at index 100 "Selecting ch.2 function".
*6 Valid only when "Control output" is selected at index 100 "Selecting ch.2 function" and then "Instantaneous flow rate mode" or "Area mode" is selected at index 119 "Ouput 2 detection mode".
*7 Valid only when "Control output" is selected at index 100 "Selecting ch.2 function" and then "Area mode" is selected at index 119 "Ouput 2 detection mode".
*8 Valid only when "External input" is selected at index 100 "Selecting ch.2 function".
*9 Sensor specific number can be allocated.
*10 Indicates level of stability of the ultrasound detection. The higher the stability level, the more stable detection becomes.
*11 Indicates change in zero position from factory setting.
*12 Valid only when "Flow rate (span adjustment) setting" is selected at index 200 "Correcting flow rate value".
*13 Valid only when "Selecting pipe schedule" is selected at index 200 "Correcting flow rate value".
*14 Indicates if the sensor is currently in simulation mode.

Standard Command
Data
Index Name Reference item Format Length Access Default value Range Remark
storage
2
System command Initialization UInt 1 Byte W – 130 Initialization –
(0x02)

-4-
5. Settings
5-2 Switching the Display and Configuring Settings
Some of the items that can be set in "4-1 Parameter List" on page 2 can also be set using the
sensor itself. This section shows how to configure certain settings using the sensor. ● Instantaneous flow rate display
Refer to "6. Detailed Settings" of the FD-Q Series Instruction Manual for more details.
Output 1 set value/Output 1 lower limit value

5-1 Setting when the power is turned on for the first time
(at initialization) Current value

Set value [P1(P1-L)] Index 112


To return to a previous screen, press MODE +.

MODE
A. Selecting NPN/PNP (Press  or  to select.)
NPN output Output 1 upper
limit value*1
PNP output Index 101
Current value
B. Selecting ch.1 and ch.2 functions (Press  or  to select.)
MODE
Selection Mode
ch.1 ch.2 Set value [P1-H] Index 113
(pin (4)) (pin (2))
A 1 Control Output Mode Control output ―

B MODE
2 Control Output Mode Control output Control output
Control Output + Output 2 set value/
C Control output External input
External Input Mode Output 2 lower limit value*2
D Control Output +
Control output Analog output
MODE Analog Output Mode

Index 100 Current value

Set value [P2(P2-L)] Index 120


C. Selecting flow direction (Press  or  to select.)
Flow direction: From left to right
Flow direction: From right to left MODE
Index 204
MODE Output 2 upper
D. Selecting bore diameter of pipe (Press  or  to select.) limit value*3

Model Selection NPS DN


Current value
1/4" 8A
FD-Q10C
3/8" 10A Set value [P2-H] Index 121
MODE 1/2" 15A
FD-Q20C
3/4" 20A
MODE
1" 25A
FD-Q32C
1 1/4" 32A
1 1/2" 40A
FD-Q50C
MODE 2" 50A ● Instantaneous flow rate hold values
Index 202
Initial setting complete

Peak value Index 160

Bottom value Index 161

* This can be reset when "Reset hold" is


MODE executed in index 104 "Command request".

● Integrated flow display*4

Current value

Set value Index 194

* This can be reset when "Reset integrated flow"


MODE is executed in index 104 "Command request".

Only when the Condition monitoring function is enabled

● Condition monitoring display Index 182

Set value (interlocked with P1)

* Flow equivalent to 100% can be set in


MODE index 191.

*1 Valid only when "Area mode" is selected in index 111 "Output 1 detection mode".
*2 Valid only when "Control output" is selected in index 100 "Selecting ch.2 function"
and "Instantaneous flow rate mode" or "Area mode" is selected in index 119
"Output 2 detection mode".
*3 Valid only when "Control output" is selected in index 100 "Selecting ch.2 function"
and "Area mode" is selected in index 119 "Output 2 detection mode".
*4 Valid only when "Integrated flow mode" is selected in index 111 "Output 1
detection mode".

-5-
5-3 Menu Structure

5-6. Output 2 detection mode


• To return to the previous screen, press + . (Press  or  to select.)
B
MODE Instantaneous flow rate mode
Normal screen Area mode
Error output mode Index 119
Press and
MODE
MODE hold 5-7. Output 2 output logic
(Press  or  to select.)
Normally Open
5-1. Output 1 detection mode Normally Closed Index 118
(Press  or  to select.)
MODE
Instantaneous flow rate mode
MODE Area mode
Pulse output mode 5-8. Selecting input function
C
Integrated flow mode Index 111 (Press  or  to select.)
In pulse
output Integrated flow reset input
5-2. Output 1 output logic Flow rate zero input
mode (Press  or  to select.)
MODE Origin adjustment input Index 129
Normally Open
Normally Closed Index 110
MODE
D

B C D 5-9. Analog output current


(Press  or  to select.)
A 4-20mA
5-3. Response time
(Press  or  to select.) 0-20mA Index 103
MODE
Setting range (Unit: seconds)
0.5/1.0/2.5/5.0/10.0/30.0/60.0 Index 102 5-10. Analog output lower limit
Integrated (Press  or  to select.)
MODE flow value Setting range
5-4. Integrated flow unit FD-Q10C 0.00 to 99.99
(Press  or  to select.) Other than FD-Q10C 0.0 to 999.9
Setting range
MODE Index 105
FD-Q10C/Q20C 0.1/1/10/100/1000
FD-Q32C/Q50C 1/10/100/1000/10000
MODE 5-11. Analog output upper limit
Index 203
(Press  or  to select.)
MODE
Setting range
5-5. Extended functions menu
FD-Q10C 0.00 to 99.99
(Press  or  to select.)
Other than FD-Q10C 0.0 to 999.9
Settings complete MODE
MODE Extended Functions Menu Index 142 Index 106

Setting complete

 More advanced settings (Extended function settings)


5-12. Display resolution (Press  or  to select.) 5-18. Key lock method
(Press  or  to select.)
Setting range Normal (without password)
FD-Q10C 0.01/0.1/1 Password-protected key lock Index 140
Other than FD-Q10C 0.1/1 Index 232
MODE MODE 5-19. Flow direction (Press  or  to select.)
5-13. Display averaging (Press  or  to select.) Flow direction: From left to right
Setting range (Unit: seconds) 0 to 10 Flow direction: From right to left
Index 231 Index 204

5-14. Hysteresis (Press  or  to select.) 5-20. Selecting bore diameter of pipe


MODE
Setting range MODE (Press  or  to select.)
When
Model Selection NPS DN
FD-Q10C 0.00 to 99.99
Instantaneous 1/4" 8A
Other than FD-Q10C 0.0 to 999.9 Index 131 FD-Q10C
flow rate or 3/8" 10A
Area mode is FD-Q20C
1/2" 15A

not selected 5-15. Zero-cut flow rate (Press  or  to select.) MODE


3/4" 20A
MODE 1" 25A
Setting range FD-Q32C
1 1/4" 32A
FD-Q10C 0.00 to 99.99 1 1/2" 40A
FD-Q50C
Other than FD-Q10C 0.0 to 999.9 Index 192 2" 50A Index 202

5-16. Display indicator illumination mode MODE


5-21. Correcting flow rate value
MODE
(Press  or  to select.) (Press  or  to select.)
Green lighting - light off mode No correction
Setting complete Selecting pipe schedule
Light off - Red lighting mode Setting flow rate magnification Index 200
Green lighting - Red lighting mode (Span adjustment)
PMI (predictive maintenance information)
MODE mode (Green, Green blinking, Red) Index 230 5-22. Selecting pipe schedule
Selecting the pipe thickness SGP pipe
5-17. Power-saving mode (schedule) correctly will Sch20
(Press  or  to select.) Sch40
MODE improve flow rate readings. Sch80
:Normal/ :Power-saving mode Index 138
(Press  or  to select.)
Index 201
MODE Simulation mode (Press  or  to select.)
5-23. Adjusting flow rate span
:Off / :Perform Simulation
The flow rate value can be adjusted by 0.1x to
MODE
2.5x the initial values of the instantaneous flow
MODE MODE Simulation flow rate (Press  or  to select.)
rate value detected by the FD-Q Series.
Setting range
(Press  or  to select.)
FD-Q10C 0.00 to 99.99 MODE Index 193
Setting range: 0.10 to 2.50
Other than FD-Q10C 0.0 to 999.9

5-24. Process data output format *1


Refer to "3 Process Data" on page 1.
(Press  or  to select.) Setting
MODE range: 0 to 3. Index 146
Setting complete *1 Can only be set when IO-Link is connected.

-6-
6. Events
5-4 Useful Functions
When an event occurs the event flag in the process data telegram turns ON.
 Origin Adjustment Index 104 The master detects the event flag and reads the value that corresponds to the event that has
occurred.
Point Perform this function when the pipe is filled with fluid and the fluid is not moving. (Err) This allows the status of the sensor to be forwarded to a PLC or monitor through the IO-Link
is displayed when the function fails due to the pipe not being completely filled, liquid master.
isn’t stationary, etc. Service data exchange is not carried out while an event is being read.

Value Name Meaning

Performing origin Settings were changed on the


0xFF91 Data Storage Upload Request
When failed ( ) adjustment sensor.
The origin adjustment Flow is in moving in the
takes approx. 20 Reverse flow - The fluid flows in the
0x1800 direction opposite of the
seconds to complete. oppositer direction of the setting
Press  or  to select. settings.
Normal screen (Instantaneous flow rate)

An error (ErE) has occurred on


Press and hold  0x5000 Device hardware fault - Device Exchange
simultaneously. Canceling origin the sensor.
adjustment An overcurrent error (ErC) has
Restores the origin 0x7710 Short circuit - Check installation
occured.
to the factory default
state.

MODE

Normal screen (Instantaneous flow rate)

 Key lock
 Enabling/Disabling key lock Index 139

Enabled
Normal screen

Press and hold


 simultaneously.
MODE

Disabled

 Enabling/Disabling password-protected key lock Index 140/141


Normal screen

Enabled
Press and hold Enter password.
 simultaneously.
MODE

Press
MODE and
hold

Press  or  to select. Press MODE to move digit.


Disabled
At input error ( )

 Initializing Index 2

Press  or  to
While pressing select.
Normal screen

and holding ,
press ×5. MODE To initial
setting
MODE
screen
Initialization
performed

Normal screen

Copyright (c) 2016 KEYENCE CORPORATION. All rights reserved.