d i s co n n ec t co n fi g u r at i o n 3 0a d i s co n n ec t

Site electrical input voltage : knock-outs


Number of 20 0 -240V motors :  5hp & lower: 2×ø25/ø32+ø16
on the top and bottom

 7.5hp & 10hp: and ø25 on the base
Number of 380 -480V motors :  10hp & below:

144 mm (5.67 inch) 131 mm (5.16 inch)


fu s e d d i s co n n ec t fo r wa ll mo u nti n g
131 mm (5.16 inch) 96 mm
(3.78 inch)

177 mm (6.97 inch)


190 mm (7.48 inch)

Weight: 3.5 lbs (1.6 kg)

6 0a d i s co n n ec t
t ec h n i c a l data 203 mm 203 mm
(8 inch) (8 inch)

Enclosure: ul /nema 4 x rated

Terminals
Number of poles: 3-poles, ground
254 mm 273 mm
Terminal size acceptability: Copper conductors only, 75°c, 14-8awg (10 inch) (10.75 inch)

Electrical/Environmental
Up to 600V / Up to 60A, 50/60Hz
Minimum short circuit rating: 10kA
152 mm
Ambient operating temperature: -10°c to +50°c (+14°f to +122°f) (6 inch)
Weight: 9 lbs (4.1 kg)
Ambient storage temperature: -30°c to +65°c (-22°f to +149°f)
su bmi tta l Fused disconnect switches
for wall mounting

armstrong disconnect switch and fuse r ating - 20 0 -230v input


power for use with design envelope permanent magnet motors
r ated ma ximum driver
disconnect fuse fuse cl ass
power input current (a )
switch r ating r ating t ypes
hp kw 200 vac 230 vac
1 0 .75 10A 3.1 2.7
1 . 5 1 .1 10A cc fa st-ac ting 4.2 3.7
2 1.5 3 0A 15A j fa st-ac ting 6.0 4.8
3 2.2 2 0A rk 1 fa st-ac ting 8.8 7.2
5 4 3 0A 15.7 14.0
7. 5 5 . 5 5 0A j fa st-ac ting 20.7 18.5
6 0A
10 7. 5 6 0A rk 1 fa st-ac ting 28.1 25.1

armstrong disconnect switch and fuse r ating - 380 -480v input


power for use design envelope permanent magnet motors
r ated ma ximum driver
disconnect fuse fuse cl ass
power input current (a )
switch r ating r ating t ypes
hp kw 380 vac 480 vac
1 0 .75 6A 2.1 1.7
1 . 5 1 .1 6A 2.8 2.3
2 1.5 10A 4.8 4.1
cc fa st-ac ting
3 2.2 10A 6.5 5.8
3 0A j fa st-ac ting
4 3 15A 6.1 4.9
rk 1 fa st-ac ting
5 4 2 0A 9.2 7.1
7. 5 5 . 5 2 5A 12.5 8.2
10 7. 5 3 0A 18.5 14.5

armstrong disconnect switch and fuse r ating - 575v- 660v input


power for use design envelope permanent magnet motors
r ated ma ximum driver
disconnect fuse fuse cl ass
power input current (a )
toronto switch r ating r ating t ypes
hp kw 575 vac 660 vac
+1 416 755 2291
1 0 .75 5A 1.6 1.3
buffalo 1 . 5 1 .1 6A 2.2 1.8
+1 716 693 8813 2 1.5 8A cc fa st-ac ting 2.0 1.6
3 2.2 3 0A 10A j fa st-ac ting 3.4 2.8
birmingham 5 4 2 0A rk 1 fa st-ac ting 5.5 4.9
+44 (0) 8444 145 145 7. 5 5 . 5 2 5A 7.2 6.0
10 7. 5 3 0A 9.8 9.4
manchester
+44 (0) 8444 145 145
All cabling and must comply with national and local regulations on cable cross-
bangalore sections and ambient temperature
+91 (0) 80 4906 3555

shanghai
+86 (0) 21 5237 0909
a r m s t r o n g f lu i d t e c h n o lo g y
são paulo established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m
+55 11 4785 1330

You might also like