You are on page 1of 10

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

Robust Analytic Design of


Power-Synchronization Control
Lennart Harnefors, Fellow, IEEE, Marko Hinkkanen, Senior Member, IEEE, Usama Riaz,
F. M. Mahafugur Rahman, and Lidong Zhang, Senior Member, IEEE

Abstract—This paper addresses robust design of stiff, but not when the grid is very weak and the PCC voltage
the active-power and dc-link control loops of power- varies to a great extent with the injected current [8].
synchronization control. Robustness is obtained by an- The active-power control loop of PSC is often cascaded with
alytic gain selections which give large enough stability
margins. The proposed design allows robust stability irre- an outer control loop for the dc-link voltage (or, equivalently,
spective of the grid strength and of the operating point, for the stored dc-link energy). Clearly, the selections of the
the latter with one exception. The proposed design is com- active-power and dc-link control gains are critical for obtaining
pared to design based on the principle virtual synchronous satisfactory performance in terms of bandwidth and stability
machine. Experiments show that the time-domain results margins. Even though since its conception, PSC has received
correlate well with the frequency-domain results.
significant attention in the scientific community [5], [9]–
Index Terms—Grid-connected converters, robustness, [13], design recommendations for the mentioned two gains
stability analysis, voltage-source converters. are, to the best knowledge of the authors, so far missing.
Selection is often made by trial and error. This is undesirable,
I. I NTRODUCTION since robustness of the closed-loop system is not guaranteed.
Analytic gain selection whereby robustness is achieved is
OWER-SYNCHRONIZATION CONTROL (PSC) of
P grid-connected voltage-source converters belongs to a
family of control schemes where the dynamics of a syn-
preferable, which is the main focus of the paper.
The contributions and outline of the paper are as follows.
After setting the stage in Section II, in Section III the
chronous machine are emulated. The principle is believed first converter–grid interaction analysis for a purely inductive grid
to be suggested in [1], there called a virtual synchronous impedance made in [3] is revisited and slightly amended. The
machine (VSM). The PSC variant first appeared in [2], [3], principal result thereof is an analytic selection recommen-
followed a year later by the synchronverter [4]. dation for the active-power control gain, whereby adequate
The three variants of synchronous-machine emulating con- stability margins of the active-power control loop always are
trol share the main features, fundamentally that the active obtained. This gives a robust design, which allows the same
power is controlled—as in a synchronous machine—by adjust- controller tuning to be used, irrespective of the short-circuit
ing the converter-voltage angle [3]–[7]. A phase-locked loop ratio (SCR) of the grid and of the operating conditions. Both
(PLL) does not have to be used, at least not during normal may vary, the former perhaps in an unknown way. For the
operation [3], [6]. recommended gain selection, a transfer function for the closed-
Yet, the objectives are different. Whereas the VSM and loop system from the active-power reference to the obtained
the synchronverter were conceived mainly for the purpose of active power is derived. This allows the properties of the
grid forming—including the provision of a virtual inertia— closed-loop system to be quantified, which is useful for the
PSC was conceived in order to enable a stable converter design of the dc-link control loop. Under the assumption that
interconnection with a very weak grid. In such a situation, the the integral action of the dc-link controller can be kept weak,
standard principle of vector current control with outer loops a robust design of the dc-link control gain is made, also
is ineffective. This is because the active power is controlled in Section III. Robust performance with adequate bandwidth
by injecting a current component in phase with the point-of- is verified, except in certain cases of high reactive-current
common-coupling (PCC) voltage, whose angle is tracked by a injection.
PLL. This works well as long as the PCC voltage is reasonably In Section IV, VSM design, where the active-power con-
trol gain is selected based on a specified frequency droop
Manuscript received March 28, 2018; revised August 22, 2018; ac-
cepted September 13, 2018.
and where virtual inertia may be included, is revisited and
This work was supported in part by ABB, in part by the Finnish Foun- compared to the proposed design.
dation for Technology Promotion, and in part by the Walter Ahlström Experimental results are presented in Section V.
Foundation.
L. Harnefors and L. Zhang are with ABB, Corporate Research,
72178 Västerås, Sweden (e-mail: lennart.harnefors@se.abb.com; li- II. S YSTEM M ODEL AND PSC P RINCIPLE
dong.zhang@se.abb.com).
M. Hinkkanen, U. Riax, and F. M. Mahafugur Rahman are with The traditional grid model consisting of an inductance L
the School of Electrical Engineering, Aalto University, 02150 Es-
poo, Finland (e-mail: marko.hinkkanen@aalto.fi; usama.riaz@aalto.fi; behind an infinite bus is adopted [3], see Fig. 1. The series
f.rahman@aalto.fi). resistance R is henceforth neglected. L is the sum of the filter

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

Fig. 1. Circuit model of a grid-connected voltage-source converter.

inductance of the converter, the inductance of the transformer Fig. 2. Block diagram of PSC.
which interfaces the converter to the grid (if such is used),
and the grid inductance. The circuit model shown in Fig.
That is, PSC inherently adds a frequency droop, with droop
1 is obtained, where vs and vgs respectively are the space
vectors for the converter voltage and the grid voltage, whereas gain 1/Kp , to the active-power reference [16].
is is the space vector for the converter output current. The Equation (3) shall not be implemented as it stands, because
superscript s denotes that the space vector is expressed in a poorly damped closed-loop system would result. The remedy
the stationary (αβ) frame, i.e., it rotates with the angular is to subtract a term with gain Ra —the so-called active
synchronous frequency ω1 . The corresponding dq-frame space resistance—from the converter voltage [3]. The term consists
vector is denoted without a superscript, e.g., i. of a high-pass filtering of the synchronous (dq)-frame current
The grid voltage is considered stiff, i.e., its magnitude Vg vector i = e−jθ is
is constant and the space vector rotates with the synchronous s
v = V − Ha (s)i, Ha (s) = Ra . (7)
frequency. Fig. 1 gives s + ωb

vs − sLis = vgs = Vg ejω1 t (1) The filter bandwidth ωb shall be selected smaller than ω1 ,
typically in the range 0.1ω1 —0.2ω1 , i.e., 0.1—0.2 p.u. [9],
where s = d/dt. To avoid having to split L into the grid [12]. Vector v is then αβ transformed as vs = ejθ v, still
and converter inductances, the SCR is here defined as seen with θ given by (4). Vector vs serves as reference to the
from the converter terminals. This gives a lower value than pulsewidth modulator, whose impact (time delay and added
the SCR seen from the PCC, but has otherwise no impact on harmonics) here is disregarded. Fig. 2 shows the resulting
the results. With this definition, the SCR is the inverse per-unit block diagram. In addition to the algorithm described above,
(p.u.) value of L the block diagram includes an embedded current controller
1
SCR = . (2) (CC). It is transparent during normal operation but acts to
L [p.u.] limit the current during transients when needed [2], [3]. This
The fundamental principle of PSC is to select the converter is particularly important for fault ride-through [15]. The CC
voltage as is not impacted by the robust design proposed in this paper
vs = V ejθ (3) and is therefore not considered further.
where V is the converter-voltage magnitude. V may be varied
in a closed control loop for the PCC voltage or the reactive III. A NALYSIS AND R OBUST D ESIGN
power [3], [14]. However, for space constraints it is assumed Based on analysis of the dynamics obtained by PSC, a
that this control loop—if used—is slow enough to be dis- robust design of the active-power control loop is made in this
regarded, allowing V to be considered constant. Angle θ is section, followed by a robust design of the dc-link control
governed by the control law loop.

= ω1 + Kp (Pref − P ) (4)
dt A. Open-Loop Dynamics
where Kp is the active-power control gain, P is the active
output power of the converter In [3], the response ∆P in the active power to an angular
perturbation ∆θ is derived, i.e., the open-loop response. In
3 Appendix I, a variant of this derivation is presented. Unlike
P = κRe{vs (is )∗ } = κRe{vi∗ }, (5) κ=
2K 2 [3], the effect of the active resistance is accounted for from
and Pref is the active-power reference. In (5), K is the space- the beginning, whereas R is neglected. This gives a different
vector scaling constant. For p.u. normalization
p of the quantities numerator of the open-loop transfer function GθP (s) from
or power-invariant vector scaling (K = 3/2), κ = 1. ∆θ to ∆P than that derived in [3]. Another difference is
Remark: Throughout the paper, ω1 is considered to be the that the numerator coefficients—which are operating-point
nominal angular synchronous frequency. Particularly during dependent—are here expressed in the components of the
grid disturbances, the local instantaneous angular grid fre- steady-state dq-frame converter current i0 = id0 + jiq0 . As the
quency ωg = dθ/dt may differ from ω1 . Then, from (4) steady-state complex output power at the converter terminals
1 is given by
P = Pref + (ω1 − ωg ). (6) κv0 i∗0 = κV (id0 − jiq0 ) (8)
Kp

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

stability margins may impair the bandwidth of the closed-loop


system. A design which aims at the minimum recommended
gain margin as therefore sought. This is formulated as the
following theorem.
Theorem 1: Selecting
ω1 Ra
Fig. 3. Linearized closed-loop system. Kp = (13)
κV 2
gives gm ≥ 2 of Gp (s) for a negligible ωb [implying Ha (s) =
it follows that id0 and −iq0 respectively are proportional to the Ra ], irrespective of the operating point (V, id0 , iq0 ) and the
active and reactive output powers. Hence, iq0 < 0 and iq0 > 0 SCR.
respectively correspond to injection and absorption of reactive Proof: See Appendix II.
current. From Appendix I, the following transfer function is The following may be noted concerning the recommended
obtained: gain selection.
κV 2 as2 + [1 + a + b(s)]ω12 • Since the desired gain margin is always obtained and (13)
GθP (s) = (9) is free of L, i.e., knowledge of the SCR is not needed,
ω1 L s2 + 2Ha (s) s + ω12 + [ Ha (s) ]2
L L the design gives robust stability provided that the phase
where margin is sufficient. That so is the case is exemplified
  later.
ω1 Liq0 H 2 (s) iq0 |i0 |2
a= b(s) = − a + . (10) 2
• Kp is selected inversely proportional to V and should be
V V ω1 L V
gain scheduled with any variations in V . During normal
The following observations can be made. operation, this has a marginal effect, as V is kept at or
• A marginally stable system is obtained for Ra = 0 ⇒ near the nominal voltage (1 p.u.). On the other hand,
Ha (s) = 0. (Since, in practice, 0 < R ≪ Ra , asymptotic it is important during fault-ride-through situations, when
stability is yet obtained, but with very poor damping [3].) V temporarily may need to be reduced to a value much
• As ωb → 0, the high-pass filter reduces to the pure lower than the nominal, in order to avoid overcurrent.
active resistance, i.e., Ha (s) → Ra . Consequently, (9) Keeping Kp at its nominal value during such situations
reduces to a second-order system. The poles of (9) are may give insufficient gain.
then located at s = −Ra /L ± jω1 , i.e., the damping 2) Closed-Loop Transfer Function: Applying (13), inter-
increases with the SCR. esting observations of the closed-loop transfer function can be
• The static gain GθP (0) is proportional to 1 + a + b(0) made. Again, assuming a negligible ωb —giving Ha (s) = Ra
and is, thus, operating-point dependent. High injection of and making b independent of s—the following transfer func-
reactive current, giving a < 0, reduces the gain. This, in tion is obtained:
turn, reduces the bandwidth of the closed-loop system, Ra 2
L [as + (1 + a + b)ω12 ]
see Section III-B. Gc (s) = .
(2+a)Ra 2 (1+a+b)ω12 Ra
• Equation (10) shows that the static gain is affected by the s3 + L s + [ω12 + ( RLa )2 ]s + L
active resistance as well, via b(s). (14)
• For reactive-current injection, there is a right-half-plane An approximate factorization of the denominator is available
zero, giving nonminimum-phase behavior. This too has a Ra 2 2
L [as + (1 + a + b)ω1 ]
limiting effect on the closed-loop bandwidth [3]. Gc (s) ≈ (1+a+b)Ra
. (15)
[s + L ][s2 + (1−b)R
L
a
s+ ω12 ]
Expanding the denominator polynomial of (15), all coefficients
B. Closed-Loop Dynamics except that for s match those of (14). The mismatch of the
The active-power control law (4) can be expressed in coefficient for s is negligible for |a| ≪ 1 and |b| ≪ 1.
perturbation variables as The following observations of (15) can be made.
Kp • There is a pole pair, whose relative damping increases
(∆Pref − ∆P ).
∆θ = (11) with the SCR, as
s
Equations (38) (in Appendix I) and (11) together form the (1 − b)Ra
ζ= . (16)
closed-loop system shown in Fig. 3, whose open-loop and 2ω1 L
closed-loop transfer functions respectively are given by • There is a real pole, at s = −(1 + a + b)Ra /L, which
Kp GθP (s) Gp (s) dominates for a weak grid with Ra /L < ω1 . The
Gp (s) = Gc (s) = . (12) minimum bandwidth of Gc (s) for low converter current
s 1 + Gp (s)
(a and b small) is thus
1) Gain Selection for Robust Stability: The stability of
Gc (s) can be analyzed by applying the Nyquist criterion to Ra
ωc,min ≈ (17)
Gp (s). For robustness, the phase and gain margins φm and gm Lmax
need to be sufficiently large; an established recommendation where Lmax is the maximum expected grid inductance
is φm ≥ 45◦ and gm ≥ 2 [17]. On the other hand, too large (Lmax = 1 p.u. if SCR ≥ 1).

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

• For a strong grid with Ra /L > ω1 , the pole pair


dominates. If ζ < 1, the pole pair is complex and the
distance from each pole to the origin is ω1 ; consequently,
the maximum obtainable bandwidth of Gc (s) is
ωc,max ≈ ω1 . (18)
This explains why PSC has been found to be inferior to Fig. 4. DC-link control loop.
vector current control for strong grids: the bandwidth of
the closed-loop system is inherently limited.
approximated as a proportional controller Fd (s) = Kd . Gain
• Too large Ra may give a significant bandwidth reduction
Kd has the dimension angular frequency; it can be considered
for weak as well as for strong grids. Suppose, for exam-
as the ideal dc-link control-loop bandwidth.
ple, that Ra = 1 p.u., iq0 = 0, and V = 1 p.u. Then it
Together with the active-power control loop, (22) and (23)
follows from (10) that b → −1 as |id0 | → 1 p.u., i.e.,
form the closed-loop system shown in Fig. 4, whose open-
the real pole approaches the origin and the bandwidth
loop transfer function is Gd (s) = Kd Gc (s)/s. Robust design
approaches zero. As a compromise between low impact
of the dc-link control gain can be made in a similar fashion as
on the bandwidth and good enough damping of the pole
of the active-power control gain. To allow for a large enough
pair, it is suggested to select
phase margin (as exemplified below), a minimum gain margin
Ra = 0.2 p.u. (19) of 4 is this time aimed at.
Theorem 2: Selecting
Then b may be neglected and the relative damping as r
given by (16) can be expressed as ω1 1 − b
Kd ≤ (24)
ζ = 0.1 SCR. (20) 4 2+a
gives gm ≥ 4 of Gd (s) for a negligible ωb .
• High reactive-current injection (iq0 < 0) may signifi- Proof: See Appendix IV.
cantly limit the bandwidth, to Due to selection recommendation (19) of Ra ,√b can be
 
Ra ω1 Liq0 Ra neglected in (24). Yet, because of the factor 1/ 2 + a =
ωc,rci ≈ (1 + a) = 1+ . (21) p
L V L 1/ 2 + ω1 Liq0 /V , (24) requires knowledge of L, i.e., of the
SCR. However, this is an issue only for high reactive current,
This is a risk particularly in fault-ride-through situations,
as otherwise a can be neglected. Furthermore, if restriction is
where grid codes often require reactive-current injection,
made to (high) reactive-current injection,1 i.e., −1 ≤ a < 0
see [18] and the publications cited therein. The risk is
(where the lower limit −1 is established in Appendix III), then
present for weak grids (L large) as well as for strong grids
(24) is fulfilled by the selection recommendation
(when V may need to be reduced to avoid overcurrent).
Since the lower limit for a is −1, see Appendix III, ω1
Kd = √ ≈ 0.18ω1 . (25)
ωc,rci approaches zero in the worst of situations [but then, 4 2
on the other hand, the accuracy of the factorization in Recommendation (25) for a 50-Hz grid gives an ideal band-
(15) deteriorates, as no longer |a| ≪ 1]. Nevertheless, width of Kd = 56 rad/s, which should be sufficient in many
bandwidth reduction of Gc (s) for high reactive-current cases.
injection needs to be accounted for if the PSC is cascaded Example 1: Fig. 5 shows Nyquist diagrams for the active-
with a dc-link controller, which is considered next. power and dc-link control loops, all for V = ω1 = 1 p.u.,
κ = 1, ωb = 0.1 p.u., and the recommended parameter selec-
C. DC-Link Control Loop tions (13), (19), and (25) [(12)—not the special case (14)—
DC-link control can be added as an outer loop in cascade is used for Gc (s) in Gd (s) = Kd Gc (s)/s]. Two operating
with the active-power control loop. If the converter losses are conditions are considered, both for full current (|i0 | = 1
neglected, the dc-link dynamics can be expressed in the energy p.u.): high active-current injection (upper subplots) and high
Wd stored in the dc link as reactive-current injection (lower subplots). The latter condition
is characteristic for a fault situation, when the grid voltage is
dWd depressed and reactive current is injected to keep the converter
= Pd − P (22)
dt voltage up. Three values of L are considered, corresponding
where Pd is dc-source power. The dc-link energy is related respectively to SCR = 10, SCR = 3, and SCR = 1, i.e., a
to the dc-link voltage vd and the dc-link capacitance Cd as strong, a fairly weak, and a very weak grid.
Wd = (Cd /2)vd2 . Often, Pd is known and can be fed forward, For Gp (s) it can be observed that gm > 2 in all cases,
possibly low-pass filtered (Pdf ), in the dc-link control law even though ωb > 0, contrary to the restriction in Theorem 1.
Interestingly, the smallest phase margin is obtained for SCR =
Pref = Fd (s)(Wd − Wdref ) + Pdf (23)
10.
where Wdref is the reference energy and Fd (s) dc-link con- 1 This restriction is relevant, as high reactive-current injection, e.g., for
troller transfer function. With feedforward, the dc-link con- grid-code compliance, is more common a scenario than high reactive-
troller can be given weak integral action, allowing Fd (s) to be current absorption [18].

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

id0=0.95 p.u., iq0=0.2 p.u. id0=0.95 p.u., iq0=0.2 p.u.

0.6 0.6
0.4 0.4
Im{Gp(j )}

Im{Gd(j )}
0.2 0.2
0 0
-0.2 -0.2
-0.4 -0.4
Fig. 6. PSC with an added low-pass filter for virtual inertia and damping.
-0.6 -0.6

-1.5 -1 -0.5 0 -1.5 -1 -0.5 0


Re{Gp(j )} Re{Gd(j )} ωf is a low-pass filtering of ωg through αf /(s + αf ) [22].
id0=0.2 p.u., iq0=-0.95 p.u. id0=0.2 p.u., iq0=-0.95 p.u. Thus, (26) can be equivalently expressed as
0.6 0.6 1
0.4 0.4 [sM + D(s)]ωg = Pg − P θ = ωg (27)
s
Im{Gp(j )}

Im{Gd(j )}

0.2 0.2
0 0
where D(s) = KD s/(s + αf ). M can be expressed in the
-0.2 -0.2
inertia constant H (with dimension time) and in the rated
-0.4 -0.4 apparent power of the converter Sbase as [23], [24]
-0.6 -0.6 2Sbase H
M= . (28)
-1.5 -1 -0.5 0 -1.5 -1 -0.5 0 ω1
Re{Gp(j )} Re{Gd(j )}
Unlike the governor of a synchronous machine, Pg can be
Fig. 5. Nyquist diagrams for (solid) SCR = 10, (dashed) SCR = 3, and adjusted without lag and is set by adding a frequency droop
(dashed-dotted) SCR = 1. to the active-power reference [16], [22]
Sbase
Pg = Pref + Kg (ω1 − ωg ), Kg = (29)
For Gd (s) some curves show slightly smaller gain margin σω1
than the desired minimum 4, because ωb > 0, contrary to the where σ is the droop in percentage of the VSM power rating.
restriction in Theorem 2. Yet, sufficient stability margins are Combining (27) and (29), the feedback loop formed by the
obtained in all cases but for the very-weak-grid case with high frequency droop can be resolved in a low-pass filter with unity
reactive-current injection. Low phase margin in this case is a static gain
result of the reduced bandwidth of Gc (s) according to (21).  
1 Kg 1
A similar reduction of the phase margin is obtained with high θ= ω1 + (Pref − P ) . (30)
s sM + D(s) + Kg Kg
reactive-current injection for a stronger grid and a depressed
voltage magnitude (V significant smaller than 1 p.u.). (For KD = 0 ⇒ D(s) = 0, a first-order low-pass filter with
time constant M/Kg = 2σH is obtained.) Since ω1 is the
nominal angular synchronous frequency and thus is constant,
IV. VSM D ESIGN the entry point of ω1 can be relocated to the output of the low-
The objective of the VSM is to provide grid forming by pass filter, as shown in Fig. 6. The frequency droop (29) gives
means of frequency droop and virtual inertia. The former is the gain selection [which can also be obtained by comparing
inherent in PSC, see (6), whereas the latter can be introduced (6) and (29)]
1 σω1
by adding a low-pass filter to the PSC control law [2], [16]. Kp = = . (31)
The purpose of this section is to compare the robust design Kg Sbase
proposed in Section III to typical VSM designs. If the droop is selected similar to that of the synchronous
For a VSM, the dc-source power Pd has to be controllable to machines in the grid, typically σ = 0.04—0.05, the VSM
allow the active output power P to respond to grid-frequency gives a corresponding contribution to the primary frequency
variations. This requires either dc-side energy storage [19], control. With V = ω1 = 1 p.u., the proposed design (13),
[20] or a dc-side power source with headroom for increased with (19), gives Kp = 0.2 p.u. VSM design (31), on the other
output [21]. For VSM design it is therefore preferable to hand, gives Kp = σ [p.u.] for Sbase = 1 p.u., i.e., typically
perform dc-link control via Pd rather than in cascade with the a much smaller gain. The implications thereof are studied in
active-power control loop (the latter would, in fact, counteract the following two examples.
the grid-forming property). Example 2: VSM design with H = 0 (called VSM0H [25]),
Virtual inertia can be added by emulating the swing equation KD = 0, and σ = 0.05 is compared to the proposed design.
of a synchronous machine For completeness also cascaded dc-link control is studied, even
though this is not recommended for VSM design. Fig. 7 shows
dωg dθ
M = Pg − P − KD (ωg − ωf ) = ωg (26) Nyquist diagrams for the active-power and dc-link control
dt dt loops, both for V = ω1 = Sbase = 1 p.u., κ = 1, and the
where M is the ω1 -scaled virtual inertia, ωg is the virtual ma- recommended parameter selections (19) and (25). A relatively
chine speed (which, since θ is formed by integrating ωg , also weak grid (SCR = 2) and relatively high active- and reactive-
is the local angular grid frequency), Pg is the virtual governor current injection (id0 = −iq0 = 0.7 p.u.) are considered. The
power, KD is the virtual mechanical damping constant, and following can be observed.

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

(a) (b) TABLE I


T EST-S YSTEM D ATA
0.5 0.5
Variable/parameter Actual value Normalized value
Im{G (j )}

Im{G d (j )}
Rated power p12.7 kVA 1 p.u.
p

0 0
Rated voltage √2/3 · 400 V 1 p.u.
-0.5 Rated current 2 · 18.3 A 1 p.u.
-0.5
Base impedance 12.6 Ω 1 p.u.
Nominal grid frequency 50 Hz 1 p.u.
-1.5 -1 -0.5 0 -1.5 -1 -0.5 0
Re{G (j )} Re{G (j )}
DC-link voltage vd 650 V 2 p.u.
p d DC-link capacitance Cd 2.1 mF 8.3 p.u.
Sampling frequency 8 kHz 160 p.u.
Fig. 7. Nyquist curves for (solid) the proposed design (13) and (dashed) Switching frequency 4 kHz 80 p.u.
VSM design (31), in both cases with Kd selected as (25). The dashed-
Active resistance Ra 4.4 Ω 0.2 p.u.
dotted curve shows VSM design with Kd selected as 30% of (25).
Filter bandwidth ωb 31 rad/s 0.1 p.u.
DC-link control gain Kd 56 rad/s 0.18 p.u.

0.6

0.4
Im{G p (j )}

0.2

-0.2

-0.4

-0.6

-1.5 -1 -0.5 0
Re{G p (j )}

Fig. 8. Nyquist curves for VSM design with (solid) H = KD = 0,


(dashed) H = 5 s and KD = 0, and (dashed-dotted) H = 5 s, KD = 50
p.u., and αf = 1 rad/s.
Fig. 9. Photo of the experimental setup.

• Because of a much smaller Kp , VSM design gives larger V. E XPERIMENTAL R ESULTS


stability margins of Gp (s) than the proposed design, i.e.,
further improved robustness of the active-power control The proposed robust PSC design is here verified exper-
loop. This may explain why an active resistance is absent imentally on a back-to-back (grid and dc-source) two-level
in the synchronverter [4]. converter system, which is illustrated in Figs. 9 and 10 and
• The smaller Kp of VSM design is paid for by reduced whose data are given in Table I. The converter is controlled
robustness of Gd (s) in the form of a fairly small phase by a dSPACE DS1006 processor board. Forward-difference
margin. To obtain a similar phase margin as with the discretization of the continuous-time transfer functions is used.
proposed design, Kd needs to be reduced to 30% of (25), Peak-value space-vector scaling (i.e., K = 1) is used. The
see the dashed-dotted curve in Fig. 7(b). Consequently, active-power control loop uses gain selection (13).
the dc-link capacitance has to be 3.3 times larger than for
the proposed design if similar dc-link-voltage fluctuations A. Active-Power Control Only
during transients and disturbances are to be obtained. This
clearly shows that, with VSM design, it is preferable to Pref is here set manually; the dc-link voltage is controlled
control the dc link via the dc-source power. by the dc-source converter. Figs. 11, 12, and 13 show results
for four successive steps in Pref , respectively for three SCRs,
Example 3: A virtual inertia H = 5 s (for a synchronous i.e., very weak, semi-weak, and strong grids. The following
frequency of 50 Hz) is now included in the control law (30), observations can be made.
still with σ = 0.05. This significantly reduces the phase margin • Adequate performance is verified for all three SCRs,
of Gp (s) as compared to H = 0, as demonstrated by the solid showing that the design is robust.
and dashed curves in Fig. 8. As shown by the dashed-dotted • For SCR = 1—owing to the (complex-conjugated) pole
curve, the phase margin can be increased by introducing virtual pair in (15)—there is slight ringing in the step-response
mechanical damping. Cascaded dc-link control is effectively transients. However, there is no overshoot, since the real
impossible with H in the range of seconds. The lag incurred pole in (15) dominates the step response.
from the low-pass filter in (30) would require Kd to be much • For SCR = 3, the real pole in (15) is located further from
smaller than (25), for the dc-link control loop to be stable. the origin, so the rise time is shorter. Improved damping

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

Grid
Source Test inverter 400 V
50 Hz
L
LCL

DS1006

Fig. 10. Schematic of the experimental setup.

Fig. 12. Active-power control only for SCR = 3.

Fig. 11. Active-power control only for SCR = 1.

of the pole pair in (15) reduces the ringing to a small


overshoot.
• For SCR = 10, yet slightly shorter rise time is obtained,
but because of the reduced phase margin of Gp (s)—see
Fig. 5—larger overshoot is obtained.
In addition, Fig. 14 illustrates the effect of transients in the
grid frequency. In adherence with (6), for Kp = 0.2 p.u. there
is a 0.1-p.u. power increase for a 0.02-p.u. frequency drop.
Fig. 13. Active-power control only for SCR = 10.
B. Cascaded DC-Link and Active-Power Control
Here, steps of ±0.2 p.u. about the nominal dc-link-voltage
derivations rely on some simplifying assumptions, robust
reference 2 p.u. are made, again for three SCRs, see Figs. 15,
performance irrespective of the SCR and of the operating
16, and 17. The best performance in terms of short rise time
point (with the possible exception of very high reactive-current
and small overshoot (ringing) of the dc-link voltage is obtained
injection) was verified experimentally. The proposed design
for SCR = 3. This is consistent with the Nyquist curves of
was compared to VSM design, showing that for zero virtual
Gd (s) for id0 = 0.95 p.u. (although here id0 = 0.6 p.u.) shown
inertia (VSM0H), even better robustness of the active-power
in Fig. 5. The curve for SCR = 3 has the lowest sensitivity
control loop is typically obtained than for the proposed design.
peak, i.e., the largest minimum distance to −1. Yet, all three
With virtual inertia, adding virtual mechanical damping is rec-
cases show satisfactory performance, verifying the robustness
ommended in order to obtain an adequate phase margin. With
of (25).
VSM design, cascaded dc-link control is not recommended
or is impossible. The proposed design recommendation for
VI. C ONCLUSION the active-power control gain is thus particularly suitable for
Robust design recommendations for the active-power and cascaded dc-link control.
dc-link control gains of PSC were presented. Although the A suitable topic for further research is to study the impact

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

Fig. 14. Active-power control only for SCR = 10, respose to grid-
frequency transients in the active power and the phase-a current.

Fig. 16. Cascaded dc-link and active-power control for SCR = 3.

tion of (3) and (5), θ is expressed as


θ = ω1 t + θ0 + ∆θ i = i0 + ∆i (32)
where the load angle is confined to −π/2 ≤ θ0 ≤ π/2. This
allows (1) to be transformed to the dq frame as
˙ ]Li = Vg e−j(θ0 +∆θ) .
v − [s + j (ω1 + ∆θ) (33)
| {z }
θ̇

From (7), ∆v = −Ha (s)∆i, which is substituted in (33).


Approximating e−j∆θ ≈ 1 − j∆θ, and neglecting cross terms
between perturbation variables yields, after simplification
[Ha (s) + (s + jω1 )L]∆i =j(Vg e−jθ0 − sLi0 )∆θ
+ V − jω1 Li0 − Vg e−jθ0 . (34)
The last three terms on the right-hand side of (34) must sum
up to zero, i.e.,
V − jω1 Li0 = Vg e−jθ0 . (35)
Fig. 15. Cascaded dc-link and active-power control for SCR = 1. Equation (34) now yields the following complex-transfer-
function relation between ∆θ and ∆i:
j[V − (s + jω1 )Li0 ]
of fast-acting PCC-voltage or reactive-power control together ∆i = ∆θ (36)
Ha (s) + (s + jω1 )L
with the proposed design. As shown in [14], the active- | {z }
and reactive-power control loops may have a nonnegligible Gθi (s)

interaction. where (35) is used in the numerator. Introducing perturbation


variables in (5) allows the active power to be expressed as
A PPENDIX I P = κRe{(V + ∆v)(i0 + ∆i)∗ }
≈ κRe{V i∗0 } + κRe{V ∆i∗ + i∗0 ∆v} (37)
Unlike in [3], complex transfer functions are here used, | {z } | {z }
thereby obtaining simpler expressions. To facilitate lineariza- P0 ∆P

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

A PPENDIX IV
Solving for ω in Im{Gd (jω)} =p0 for ωb = 0 yields the
phase crossover frequency ωπ = (1 − b)/(2 + a)ω1 . The
gain margin is found to be
 
1 1 (1 − b)ω12 L Ra
gm = − = + . (42)
Gd (jωπ ) Kd (2 + a)Ra 2L

The minimum value of (42) is obtained for L = 2Ra /ω1
and is given by
r
ω1 1 − b
gm,min = . (43)
Kd 2 + a
Hence, to get gm ≥ 4, (24) should be observed.

R EFERENCES
[1] H.-P. Beck and R. Hesse, “Virtual synchronous machine,” in Proc. 9th
Int. Conf. Electr. Power Quality Util., Oct. 2007, pp. 1–6.
[2] L. Harnefors, “Control of a voltage source converter using synchronous
machine emulation,” International Patent WO 2010/022766, Mar. 2010.
[3] L. Zhang, L. Harnefors, and H.-P. Nee, “Power-synchronization control
of grid-connected voltage-source converters,” IEEE Trans. Power Syst.,
vol. 25, no. 2, pp. 809–920, May 2010.
[4] Q. C. Zhong and G. Weiss, “Synchronverters: Inverters that mimic
synchronous generators,” IEEE Trans. Ind. Electron., vol. 58, no. 4,
pp. 1259–1267, Apr. 2011.
[5] L. Zhang, H.-P. Nee, and L. Harnefors, “Analysis of stability limitations
of a VSC-HVDC link using power-synchronization control,” IEEE
Fig. 17. Cascaded dc-link and active-power control for SCR = 10. Trans. Power Syst., vol. 26, no. 3, pp. 1326–1337, Aug. 2011.
[6] Q. C. Zhong, P. L. Nguyen, Z. Ma, and W. Sheng, “Self-synchronized
synchronverters: Inverters without a dedicated synchronization unit,”
where ∆v = −Ha (s)∆i. Substitution of (36) in (37) then IEEE Trans. Power Electron., vol. 29, no. 2, pp. 617–630, Feb. 2014.
[7] M. Ashabani, F. D. Freijedo, S. Golestan, and J. M. Guerrero, “In-
gives the desired relation between ∆θ and ∆P ducverters: PLL-less converters with auto-synchronization and emulated
inertia capability,” IEEE Trans. Smart Grid, vol. 7, no. 3, pp. 1660–1674,
∆P = κRe{V G∗θi (s) − Ha (s)i∗0 Gθi (s)} ∆θ (38) May 2016.
| {z } [8] G. Wu, J. Liang, X. Zhou, Y. Li, A. Egea-Alvarez, G. Li, H. Peng,
GθP (s) and X. Zhang, “Analysis and design of vector control for VSC-HVDC
connected to weak grids,” CSEE J. Power Energy Syst., vol. 3, no. 2,
where the real part is evaluated for s real, giving (9). pp. 115–124, Jun. 2017.
[9] L. Zhang, L. Harnefors, and H.-P. Nee, “Interconnection of two very
A PPENDIX II weak ac systems by VSC-HVDC links using power-synchronization
control,” IEEE Trans. Power Syst., vol. 26, no. 1, pp. 344–355, Feb.
Solving for ω in Im{Gpp (jω)} = 0 yields the phase 2011.
crossover frequency ωπ = ω12 + (Ra /L)2 . The gain margin [10] K. M. Alawasa and Y. A. R. I. Mohamed, “Impedance and damping
characteristics of grid-connected VSCs with power synchronization
is found to be control,” IEEE Trans. Power Syst., vol. 30, no. 2, pp. 952–961, Mar.
1 2ω1 Ra 1 + ( ωR1aL )2 2015.
gm = − = [11] A. A. A. Radwan and Y. A. R. I. Mohamed, “Power synchronization
Gp (jωπ ) κKp V 2 1 + b − ( ωRaL )2 a control for grid-connected current-source inverter-based photovoltaic
1
R
systems,” IEEE Trans. Energy Conv., vol. 31, no. 3, pp. 1023–1036,
2
2ω1 Ra 1 + ( ω1aL ) Sep. 2016.
= . (39) [12] S. I. Nanou and S. A. Papathanassiou, “Grid code compatibility of VSC-
κKp V 2 1 − ( Ra |i0 | )2 HVDC connected offshore wind turbines employing power synchroniza-
V
tion control,” IEEE Trans. Power Syst., vol. 31, no. 6, pp. 5042–5050,
Applying (13) yields Nov. 2016.
[13] Q. Fu, W. Du, C. Chen, H. F. Wang, and L. L. Fan, “Vector and power
1 + ( ωR1aL )2 synchronization control for connecting a VSC-MTDC to an ac power
gm = 2 ≥ 2. (40) system – A comparative study of dynamic interactions between the dc
1 − ( RaV|i0 | )2 and ac network based on PSCAD simulation,” in Proc. 12 IET Int. Conf.
| {z }
≥1
AC DC Power Transm., May 2016, pp. 1–6.
[14] H. Wu, X. Ruan, D. Yang, X. Chen, W. Zhao, Z. Lv, Q. C. Zhong,
“Small-signal modeling and parameters design for virtual synchronous
A PPENDIX III generators,” IEEE Trans. Ind. Electron., vol. 64, no. 7, pp. 4292–4303,
Jul. 2016.
Taking the real part of (35) gives V + ω1 Liq0 = Vg cos θ0 , [15] P. Mitra, L. Zhang, and L. Harnefors, “Offshore wind integration to a
which also can be expressed as weak grid by VSC-HVDC links using power-synchronization control: A
case study,” IEEE Trans. Power Del., vol. 29, no. 1, pp. 453–461, Feb.
ω1 Liq0 Vg 2014.
a= = cos θ0 − 1. (41)
V V [16] J. Liu, Y. Miura, and T. Ise, “Comparison of dynamic characteristics
between virtual synchronous generator and droop control in inverter-
Since the load angle is confined as |θ0 | ≤ π/2, cos θ0 ≥ 0, based distributed generators,” IEEE Trans. Power Electron., vol. 31, no.
and consequently a ≥ −1. 5, pp. 3600–3611, May 2016.

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIE.2018.2874584, IEEE
Transactions on Industrial Electronics

[17] R. H. Middleton and G. C. Goodwin, Digital Control and Estimation – Usama Riaz received the B.E. degree in elec-
A Unified Approach. Englewood Cliffs, NJ: Prentice Hall, 1994. trical engineering from the National University
[18] Ö. Göksu, R. Teodorescu, C. L. Bak, F. Iov, and P. C. Kjaer, “Instability of Science and Technology (NUST), Islamabad,
of wind turbine converters during current injection to low voltage grid Pakistan, in 2015 and M.Sc.(Tech.) degree in
faults and PLL frequency based stability solution,” IEEE Trans. Power automation and electrical engineering from Aalto
Syst., vol. 29, no. 4, pp. 1683–1691, Jul. 2014. University, Espoo, Finland, in 2018. He is cur-
[19] K. C. Divya and J. Østergaard, “Battery energy storage technology for rently working as a research assistant at the
power systems – An overview,” Electr. Power Syst. Res., vol. 79, no. 4, school of electrical engineering, Aalto University,
pp. 511–520, Apr. 2009. Espoo, Finland.
[20] U. Manandhar, A. Ukil, G. H. Beng, N. R. Tummuru, S. K. Kollimalla, His research interests include control of elec-
B. Wang, and K. Chaudhari, “Energy management and control for tric drives and grid converters, power systems,
grid connected hybrid energy storage system under different operating and renewable energy systems.
modes,” IEEE Trans. Smart Grid, early access, 2017.
[21] H. Bevrani, A. Ghosh, and G. Ledwich, “Renewable energy sources and
frequency regulation: survey and new perspectives,” IET Renew. Power
Gen., vol. 4, no. 5, pp. 438–457, Sep. 2010.
[22] O. Mo, S. D’Arco, and J. A. Suul, “Evaluation of virtual synchronous
machines with dynamics or quasi-stationary machine models,” IEEE
Trans. Ind. Electron., vol. 64, no. 7, pp. 5952–5962, Jul. 2017.
[23] M. P. N. van Wesenbeeck, S. W. H. de Haan, P. Varela, and K.
Visscher, “Grid tied converter with virtual kinetic storage,” in Proc. IEEE
Bucharest PowerTech, Jun. 2009, pp. 1–7.
[24] W. Zhang, D. Remon, and P. Rodriguez, “Frequency support charac-
teristics of grid-interactive power converters based on the synchronous
power controller,” IET Renew. Power Gen., vol. 11, no. 4, pp. 470–479,
2017.
[25] M. Yu, A. J. Roscoe, C. D. Booth, A. Dyśko, R. Ierna, J. Zhu, and F. M. Mahafugur Rahman received the
H. Urdal, “Use of an inertia-less virtual synchronous machine within B.Sc.(Tech.) degree in electrical and electronic
future power networks with high penetrations of converters,” in Proc. engineering from Chittagong University of
2016 Power Syst. Comput. Conf. (PSCC), Jun. 2016, pp. 1–7. Engineering and Technology, Chittagong,
Bangladesh, in 2011. He received the
M.Sc.(Tech.) degree in electronics and electrical
engineering from Aalto University, Espoo,
Finland, in 2016, where he is currently working
towards the D.Sc.(Tech.) degree in electrical
engineering.
Lennart Harnefors (S’93–M’97–SM’07–F’17)
His research interests include optimization
received the M.Sc., Licentiate, and Ph.D. de-
and control of grid-connected converters.
grees in electrical engineering from the Royal
Institute of Technology (KTH), Stockholm, Swe-
den, and the Docent (D.Sc.) degree in industrial
automation from Lund University, Lund, Sweden,
in 1993, 1995, 1997, and 2000, respectively. Be-
tween 1994–2005, he was with Mälardalen Uni-
versity, Västerås, Sweden, from 2001 as a Pro-
fessor of electrical engineering. Between 2001–
2005, he was, in addition, a part-time Visiting
Professor of electrical drives with Chalmers University of Technology,
Göteborg, Sweden. Since 2005, he has been with ABB, where he is
currently a Senior Principal Scientist at Corporate Research, Västerås,
Sweden. He is, in addition, a part-time Adjunct Professor of power
electronics with KTH.
Dr. Harnefors is an Associate Editor of the IEEE T RANSACTIONS Lidong Zhang (M’07–SM’11) was born in
ON I NDUSTRIAL E LECTRONICS . His research interests include control Shanxi province, China. He received the B.Sc.
and dynamic analysis of power electronic systems, particularly grid- degree from the North China Electric Power
connected converters and ac drives. University, Baoding, China, the Licentiate de-
gree from Chalmers University of Technology,
Göteborg, Sweden, and the Ph.D. degree from
KTH Royal Institute of Technology, Stockholm,
Sweden, in 1991, 1999, and 2010, respectively.
From 1991 to 1996, he worked as a Lecturer
Marko Hinkkanen (M’06–SM’13) received the with the North China Electric Power University,
M.Sc.(Eng.) and D.Sc.(Tech.) degrees in electri- Beijing, China. From 1999 to 2011, he worked as
cal engineering from the Helsinki University of a System Engineer with ABB Power Systems, Ludvika, Sweden. Since
Technology, Espoo, Finland, in 2000 and 2004, 2012, he has been with the ABB Corporate Research, Västerås, Swe-
respectively. den, where he is currently a Principal Scientist. His research interests
He is an Associate Professor with the School include HVDC, power system stability and control, and power quality. He
of Electrical Engineering, Aalto University, Es- is active in the Cigre working groups C4/C1/B4 and B4-57.
poo. His research interests include control sys-
tems, electric drives, and power converters.
Dr. Hinkkanen was a General Co-Chair for the
2018 IEEE 9th International Symposium on Sen-
sorless Control for Electrical Drives (SLED). He was the co-recipient of
the 2016 International Conference on Electrical Machines (ICEM) Brian
J. Chalmers Best Paper Award and the 2016 and 2018 IEEE Industry
Applications Society Industrial Drives Committee Best Paper Awards.
He is an Editorial Board Member of IET Electric Power Applications.

0278-0046 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like