• CT Fan-1B
• Power: 110 KW
• Current: 187 A
• After the motor base strengthen, we measured vibration. The vibration was reduced but still higher side. In spectrum rotating
frequency with harmonics indicating.
• Then modified the shaft (Carbon shaft) and measure the vibration and found a reduced trend.
• Due to shaft diameter and weight of shaft creating high amplitude of 1.0X of the assembly.
• After shaft modification and motor base strengthening of the equipment, the vibration gets in Normal condition.
Motor Base Modification
Before Shaft
Modification
• After the shaft is Carbon Shaft and the Shaft diameter is 4 Inches.
After Shaft
Modification
After Correction Vibration Trends
Motor NDE Horizontal Trend: Motor DE Axial Trend: