Foreword
This manual describes the installation and function of the Ethernet expansion
card IFC ETTP.
The card can be connected to the operator terminals with expansion slots.
Besides this manual is the manual for the operator terminals and the
programming tool for the operator terminals also available.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any
nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequen-
tial damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written permission from
ABB, and the contents thereof must not be imparted to a third party nor used for any unauthorized pur-
pose.
The software or hardware described in this document is furnished under a license and may be used, copied,
or disclosed only in accordance with the terms of such license.
ABB, 1SBC159004M0401
Foreword
ABB, 1SBC159004M0401
Safety precautions
Safety precautions
General
– Read the safety precautions carefully.
– Check the delivery for transportation damage. If damage is found, notify the
supplier as soon as possible.
– The product fulfills the requirements of article 4 of EMC directive 89/336/
EEC.
– Do not use the product in an environment with high explosive hazards.
– The supplier is not responsible for modified, altered or reconstructed equip-
ment.
– Use only parts and accessories manufactured according to specifications of
the supplier.
– Read the installation and operating instructions carefully before installing, us-
ing or repairing the product.
– Only qualified personnel may operate the product.
During installation
– The product is designed for stationary installation on a plane surface.
– Put the product on a stable surface during installation. Dropping it or letting
it fall may cause damage.
– Install the product according to the accompanying installation instructions.
– Ground the product according to the accompanying installation instructions.
– Only qualified personnel may install the product.
– Do not place the product where it might be exposed to strong magnetic fields.
– Do not install the product in direct sunlight.
– Peripheral equipment must be appropriate for the application.
ABB, 1SBC159004M0401
Safety precautions
UL installation
– Power, input and output (I/O) wiring must be in accordance with Class I,
Division 2 wiring methods (Article 501-4 (b) of the National Electrical Code,
NFPA 70) and in accordance with the authority having jurisdiction.
ABB, 1SBC159004M0401
Contents
Contents
1 Installation................................................................................................ 7
1.1 Installation of one expansion card ................................................ 7
1.2 Installation of two expansion cards............................................... 9
1.3 The LEDs on IFC ETTP........................................................... 10
ABB, 1SBC159004M0401
Contents
ABB, 1SBC159004M0401
Installation
1 Installation
The expansion card IFC ETTP is used to connect the operator terminals to an
Ethernet network for communication via TCP/IP. The connection is made by
twisted pair cable.
Further information about configuration of the terminals to TCP/IP network is
available in the manual for the terminals.
This chapter describes how to mount the expansion card in the terminal.
Slot 2
Slot 1
ABB, 1SBC159004M0401 7
Installation
4. Put the jumper J1 on the expansion card in the position SLOT 1 if the
expansion card is mounted in Slot 1, and in position SLOT 2 if the card is
mounted in Slot 2.
J1
X1
X2
X1
X2
5. Mount the expansion cables with the components of the expansion card
placed upwards. One of the expansion cables is mounted between X1 on the
CPU card and X1 on the expansion card, and the other cable between X2
on the CPU card and X2 on the expansion card.
6. Fasten the card with the spacers or the screws. Use the screws if the
expansion card is mounted in Slot 1, and the spacers if the card is mounted
in Slot 2.
7. Check that the expansion cable is correctly mounted.
8. Mount the cover plates.
8 ABB, 1SBC159004M0401
Installation
X1
Card in
Slot 2
X1
Card in
Slot 1
X2
X1
X2
ABB, 1SBC159004M0401 9
Installation
The expansion card IFC ETTP has four LEDs . The LEDs have the following
functions:
SEL, YELLOW. The LED is activated when the port on the expansion card is
accessed from the processor in the terminal.
TxD, YELLOW. The LED is activated by Ethernet transmit activity.
RxD, YELLOW. The LED is activated by Ethernet receive activity.
LINK, GREEN. The LED is activated when the Ethernet (twisted pair) cable is
connected correctly.
10 ABB, 1SBC159004M0401
Settings in the programming tool
ABB, 1SBC159004M0401 11
Settings in the programming tool
2. Right-click on the slot defined with jumper J1 on the expansion card and
select Properties.
12 ABB, 1SBC159004M0401
Settings in the programming tool
ABB, 1SBC159004M0401 13
Settings in the programming tool
14 ABB, 1SBC159004M0401
Settings in the programming tool
In this menu the name of the connection, the IP address and subnet mask are
defined.
Connection name
Enter a mnemonic name of the connection. This parameter is optional.
Host configuration
Select Manual to use the TCP/IP settings stated in the dialog. Select the other
alternatives when a server provides the terminal with one or several of the
TCP/IP parameters.
TCP/IP Settings
IP address and subnet mask
State the node’s network identity. Connection in a network is made according
to Ethernet standards. For a local network between the terminals, using the
addresses 192.168.1.1 – 192.168.1.254 is recommended.
Gateway
State the network unit in the local network that can verify the identifiers for the
other networks on Internet.
Primary DNS and Secondary DNS
State the servers containing information about a part of the DNS database.
3. Click OK after filling out the form.
ABB, 1SBC159004M0401 15
Settings in the programming tool
Ethernet connections
The section below shows two examples of Ethernet connections between two
terminals.
1 3
2 6
3 1
6 2
The maximum length between the terminals is 100 m. The cable is a CAT5 pair
twisted cable, screened or not screened, equipped with RJ45 connectors.
Note:
If the communication does not work properly, and the LED marked Link on the
IFC ETTP card is off, connections 3 and 6 are probably switched.
16 ABB, 1SBC159004M0401
Settings in the programming tool
Connection with more than two terminals via pair twisted cable
Hub
1 1
2 2
3 3
6 6
The maximum length between terminal and hub is 100 m. The number of
terminals per hub is limited by the number of connections to the hub. The cable
is a CAT5 pair twisted cable, screened or unscreened, equipped with RJ45 con-
nectors.
Note:
Settings for the expansion cards can also be made under Setup in the terminal.
Select slot and IFC ETTP from the dialog Expansion cards. See the manual for the
operator terminals for further information.
ABB, 1SBC159004M0401 17
Settings in the programming tool
18 ABB, 1SBC159004M0401
Vorwort
Vorwort
Dieses Dokument enthält eine Installationsanleitung und Funktions-
beschreibung für die Ethernet-Erweiterungskarte IFC ETTP.
Die Karte können an Bedienterminals mit Erweiterungssteckplätzen
angeschlossen werden.
Neben diesem Dokument liegt ebenfalls ein Handbuch für die Bedienterminals
und die zugehörige Programmiersoftware vor.
ABB, 1SBC159004M0401
Vorwort
ABB, 1SBC159004M0401
Sicherheitsvorschriften
Sicherheitsvorschriften
Allgemeines
– Sicherheitsvorschriften sorgfältig durchlesen.
– Überprüfen Sie die Lieferung beim Empfang auf etwaige Transportschäden.
Informieren Sie den Lieferanten umgehend, wenn Schäden entdeckt werden.
– Das Produkt erfüllt die Anforderungen gemäß Artikel 4 der EMC-Richtlinie
89/336/EEC.
– Setzen Sie das Produkt nicht in Umgebungen ein, in denen Explosionsgefahr
besteht.
– Der Lieferant übernimmt keine Verantwortung für modifizierte, geänderte
oder umgebaute Ausrüstung.
– Es dürfen nur Ersatzteile und Zubehör verwendet werden, die im Einklang
mit den Spezifikationen des Lieferanten hergestellt wurden.
– Die Installations- und Benutzeranweisungen sorgfältig lesen, bevor das
Produkt installiert, in Betrieb genommen oder repariert wird.
– Das Produkt darf nur von speziell ausgebildetem Fachpersonal bedient
werden.
ABB, 1SBC159004M0401
Sicherheitsvorschriften
UL installation
– Power, input and output (I/O) wiring must be in accordance with Class I,
Division 2 wiring methods (Article 501-4 (b) of the National Electrical Code,
NFPA 70) and in accordance with the authority having jurisdiction.
ABB, 1SBC159004M0401
Inhaltsverzeichnis
Inhaltsverzeichnis
1 Installation................................................................................................ 7
1.1 Erweiterungskarte installieren ...................................................... 7
1.2 Zwei Erweiterungskarten installieren............................................ 9
1.3 LED’s an IFC ETTP.................................................................. 10
ABB, 1SBC159004M0401
Inhaltsverzeichnis
ABB, 1SBC159004M0401
Installation
1 Installation
Die Erweiterungskarte IFC ETTP wird benutzt, um die Bedienterminals in ein
Ethernet-Netzwerk mit TCP/IP-Kommunikation einzubinden. Der Anschluss
ist über Twistedpairkabel (TP) möglich.
Nähere Informationen zur Konfiguration des TCP/IP-Netzwerks entnehmen
Sie dem Handbuch für die Bedienterminals.
In diesem Kapitel erfahren Sie, wie eine Erweiterungskarte im Terminal
installiert wird.
Steckplatz 2
Steckplatz 1
ABB, 1SBC159004M0401 7
Installation
J1
X1
X2
X1
X2
8 ABB, 1SBC159004M0401
Installation
X1
Karte in
Steckplatz 2
X1
Karte in
Steckplatz 1 X2
X1
X2
ABB, 1SBC159004M0401 9
Installation
Die Erweiterungskarte IFC ETTP verfügt über vier LED’s an der Vorderseite.
Die LED’s besitzen folgende Funktionen:
SEL, GELB. Die LED leuchtet, wenn zwischen Terminalprozessor und dem
Anschluss an der Erweiterungskarte ein Kontakt besteht.
TxD, GELB. Die LED leuchtet beim Senden von Ethernet-Daten.
RxD, GELB. Die LED leuchtet beim Empfangen von Ethernet-Daten.
LINK, GRÜN. Die LED leuchtet, wenn das Ethernet-Kabel (Twistedpairkabel)
korrekt angeschlossen ist.
10 ABB, 1SBC159004M0401
Einstellungen in der Programmiersoftware
2 Einstellungen in der
Programmiersoftware
Führen Sie folgende Schritte aus, um die Erweiterungskarte IFC ETTP für eine
Ethernet-Verbindung zu konfigurieren.
ABB, 1SBC159004M0401 11
Einstellungen in der Programmiersoftware
2. Wählen Sie den Steckplatz aus, der per Steckbrücke J1 auf der
Erweiterungskarte bezeichnet ist. Rechtsklicken Sie und wählen Sie den
Eintrag Eigenschaften aus.
3. Wählen Sie den Typ der Erweiterungskarte aus, in diesem Fall IFC ETTP.
12 ABB, 1SBC159004M0401
Einstellungen in der Programmiersoftware
2.2 TCP/IP-Einstellungen
1. Die TCP/IP-Einstellungen werden unter Peripheriekonfiguration
vorgenommen.
ABB, 1SBC159004M0401 13
Einstellungen in der Programmiersoftware
14 ABB, 1SBC159004M0401
Einstellungen in der Programmiersoftware
Verbindungsname
Tragen Sie einen beliebigen Namen für die Verbindung ein. Dieser Parameter
muss nicht angegeben werden.
Hostkonfiguration
Bei Auswahl von Manuell werden die im Dialogfeld vorgenommenen TCP/IP-
Einstellungen verwendet. Alle übrigen Optionen werden verwendet, wenn ein
Server dem Terminal einen oder mehrere TCP/IP-Parameter zuweist.
TCP/IP-Einstellungen
IP-Adresse und Subnetz-Maske
Geben Sie die Netzwerkidentifikation für den Knoten an. Der Netzwerk-
anschluss erfolgt gemäß Ethernet-Standard. Für ein lokales Netzwerk, das
lediglich aus Terminals besteht, werden IP-Adressen im Bereich zwischen
192.168.1.1 und 192.168.1.254 empfohlen.
Gateway
Geben Sie die Netzwerkeinheit im lokalen Netzwerk an, die andere Netzwerke
im Internet identifizieren kann.
Primär-DNS und Sekundär-DNS
Geben Sie den oder die Server an, die Informationen zu einem Teil der DNS-
Datenbank enthalten.
3. Klicken Sie nach der Festlegung aller Einstellungen auf OK.
ABB, 1SBC159004M0401 15
Einstellungen in der Programmiersoftware
Ethernet-Verbindungen
Im folgenden Abschnitt werden zwei Beispiele für Ethernet-Verbindungen
aufgeführt.
1 3
2 6
3 1
6 2
Die maximale Länge zwischen den Terminals beträgt 100 m. Beim Kabel
handelt es sich um ein CAT5-Twistedpairkabel, abgeschirmt oder nicht
abgeschirmt, mit RJ45-Anschlüssen.
Hinweis!
Wenn die Kommunikation nicht korrekt abläuft und die LED mit der Beschriftung
Link an der Karte IFC ETTP nicht leuchtet, sind wahrscheinlich Anschlüsse 3 und 6
vertauscht.
16 ABB, 1SBC159004M0401
Einstellungen in der Programmiersoftware
Hub
1 1
2 2
3 3
6 6
Die maximale Länge zwischen Terminal und Hub beträgt 100 m. Die maximale
Terminalanzahl pro Hub richtet sich nach der Anzahl der Anschlüsse am Hub.
Beim Kabel handelt es sich um ein CAT5-Twistedpairkabel, abgeschirmt oder
nicht abgeschirmt, mit RJ45-Anschlüssen.
ABB, 1SBC159004M0401 17
Einstellungen in der Programmiersoftware
18 ABB, 1SBC159004M0401