Professional Documents
Culture Documents
IEEE 1584-2018
The new IEEE 1584-2018 arc flash model supersedes the IEEE 1584-2002 model. The
development of this new edition of the standard has taken over fifteen years of work and is a
result of thousands of hours of research, development and validation. The following sections
provide a summary of the main changes of IEEE 1584. ETAP has actively participated in the
development and validation of this model to ensure its correct application in power system
analysis software.
Model Development
The new model was developed based on over 1800 tests to incorporate different electrode
configurations which was much more extensive than the 300 tests used in 2002.
Electrode Configuration
The most important step in implementing the calculations based on the new IEEE 1584-2018
model, is to identify which one of the five electrode configurations are present in the
equipment being analyzed, while also understanding that it is possible to have one or more
electrode configurations present in a piece of equipment.
Table 9 of IEEE 1584-2018 is a good starting point for some guidelines on how to identify the
potential electrode configuration(s) present in the equipment.
VCB
VCBB
HCB
VOA
HOA
(3-P kV LL)
Height 14 to 49 (in)*
Parameter Value
Frequency 50 ~ 60 Hz
Phases 3-Phase
*Larger opening sizes may be modeled but the correction factor is calculated at 49
(in).
IEEE 1584-2018, Section 4.11 still recommends that the model can be used for single-phase
systems and expects the results to be conservative.
Summary of the actual sizes of the test enclosures used to develop the model range:
5 kV Switchgear
5 kV Switchgear
Voltage Levels
The voltage range applicable to IEEE 1584 remains unchanged at 208V through 15kV.
In previous versions of IEEE 1584 (2002) a reference to the Ralph Lee method allowed the
possibility to use this method for this condition, yet its results were found to be totally
unrealistic. Also, the physical behavior of the arcs and the mode of failure are totally different
for overhead open-air equipment. The following table presents a concise view of the
application of different models across voltage levels between 0.208 kV to 15 kV and higher.
Method 208 V to 600 V 601 V to 15 kV 15.1 kV to 38
kV
Phases1 3ɸa 3ɸb 1ɸa 1ɸb 3ɸa 3ɸb 1ɸa 1ɸb 3ɸa 3ɸb 1ɸa 3ɸa
IEEE 1584- G G Y Y G G Y Y Y Y
2002
IEEE 1584- G G Y Y G G Y Y
2018
*ArcFault™ G Y Y Y G Y
Green (G) – Directly Applicable / Yellow (Y) – Extended with Engineering Assumptions
Note that the Ralph Lee method should not be used at all for voltages above 15 kV, however, since it was
previously applied by ETAP as an alternative to the IEEE 1584-2002 method, ETAP still has this option available
but with a warning.
The new model centers around the calculation of the arc current at three different voltages
which are 600, 2700 and 14300 Volts AC. The following plot shows the results of a parameter
sweep for short-circuit current for the medium-voltage arc current model.
The physical concept of arc current variation is not changed, however, it was improved.
Based on the analysis done during the new arc flash model development phase, it was found
that the variation in the arc current was higher at voltages below 480 Volts and far less at
voltages such as 600 Volts and 2700 Volts ac.
The value of the arc current variation is no longer fixed to 15% but calculated continuously
based on the equations provided in section 4.5 of IEEE 1584-2018.
The arc current variation was determined from the median of the measured variation at each
voltage level. The plot below shows the median arc current variation in percent for each of
the five electrode configurations.
Low Voltage Arc Sustainability Limit
The reason the limits were revised is because additional electrode configurations such as
VCBB used in the testing revealed that arcs can sustain at much lower short-circuit currents
than previously presented in the 2002 standard.
Previous versions of IEEE 1584 suggested a limit for sustainability at around 240 Volts ac with
approximately 125 kVA (or 10 kA with a 3.5% impedance transformer). This left a substantial
amount of equipment out of the scope of incident energy calculations. However, since the
limit has been lowered to 240 Volt ac with 2.0 kA of short-circuit current, it means that more
systems had to be analyzed. An overly-conservative incident energy correction factor was
removed from the low-voltage model for IEEE 1584-2018 as shown in the plot below:
As can be observed in this plot, the incident energy results of the new IEEE 1584-2018 model
are more accurate and also less over conservative.
The incident energy model follows the same principle as the arc current. An interpolation
process is done to determine the incident energy. The interpolation takes place by obtaining
intermediate incident energy values at 600, 2700 and 14300 Volts ac.
Incident Energy Model – (0.6 kV to 15 kV)
The plot below shows a comparison of the incident energy for both IEEE 1584-2018 and
2002 models. The results reveal consistently that if the equipment is determined to now be
HCB configuration that the incident energy can be significantly more. In the plot below the
incident energy for a VCB configuration, using the 2002 model is 20 cal/cm2 while it is
predicted to be over 45 cal/cm2 using the 2018 model if the HCB electrode configuration is
used.
The plot below shows the arc-flash boundary vs the arc duration and compares the
2018 AFB vs the 2002 AFB results. This comparison was made for a system voltage
of 2700 Volts ac.
ebook.com/etappower)
s://twitter.com/ETAPsoftware)
ogy-inc-)
/ETAPsoftware)
Support
Partners
Resources
Full Name
Subscribe
Contact Us (/contact-us)
Legal Notices (/legal-notices)
Privacy Policy (/privacy-policy)
Sitemap (/sitemap)
(/products/quality-assurance/qa-standards)