SOP Of Variable Frequency Drives

The purpose of this method statement is to define the step by step method to implement the correct  
practices for the Testing & Commissioning Of Starter Panels Variable Frequency Drives VFD’s through
the guidelines contained herein so as to ensure that the job execution complies with the project
 requirements and serves the intended function to satisfactory level.

Precommissioning Procedure for Starter Panel / VFD

1.      Ensure that the Starter panel on the installation inspections are incorporated.
installation is complete and mechanical completion is approved & all the comments
2.      Ensure that no damage has occurred to the Starter panel.
3.      Repair / replace damaged components, if any.
4.      Ensure that the tagging is complete & the starter panels/VFDs are identified location wise & service wise.
5.      Check & record insulation resistance values of all incoming & outgoing power wiring / cabling.
6.      Ensure that all the incoming & outgoing cables / wires have been terminated to their
respective equipment with proper polarity.
7.      Ensure that all BMS wiring are completed.
8.      Ensure that the cable dressing is complete inside the starter panel.
9.      Ensure that all control wiring is done as per the approved scheme and terminated properly.
10.     Ensure that required jumper is provided as per the wiring diagram.
11.    Check the ratings of all MCCBs / MCBs are as per approved drawings and load schedules.
12.    Check the ratings of ALR as per approved drawings.
13.    Ensure all the wiring terminations are tight.
14.    Ensure the ratings of all protective fuses are correct.
15.    Check the manual operations of door mounted switches, push buttons, etc.
16.    Check the earthing connections for tightness.
17.    Check the overload relay settings to respective load fed by the starter panel / VFD.
18.    Check the ratios of CTs and ensure that is matching with relays / meters feeding to.
19.    Check the connection to exhaust fan.

Commissioning Procedure for Starter Panel / VFD


1.      Ensure that all pre-commissioning checks have been completed successfully.
2.      Keep all the Isolators / Switches in ‘Off’ condition.
3.      Check the phase sequence
4.      Measure the Incoming Voltage.
5.      Switch ‘ON’ all control MCBs.
6.      Check the healthiness of all control fuses and rack into the base units.
7.      Remove the outgoing power cable / wiring connections.
8.      Check the operations of selector switches and meters.
9.      Check the operations of Push buttons and related sequential operations.
10.    Check the operations of Timers, Controllers and ensure the proper functioning and sequence.
11.    Check the proper functionality of all door mounted components.
12.    After ensuring the proper control sequential checks, switch ‘off’ the main incoming isolator.
13.    Reconnect the outgoing power cables / wires after ensuring the polarity of connections in panel
end & equipment end.
14.    Checks for the proper tightness of connections.
15.    Keep all the switches in ‘OFF’ condition.
16.    Switch on the incoming power supply.
17.    Turn ‘On’ the required selector switches for manual operations.
18.    Observe the proper functions and sequences of operations of connected equipment.
19.    Check the direction of rotation of motors, if wrong, swap connections as required.
20.    Turn ‘Off’ the manual operations through push button / selector switch.
21.    Now ‘On’ the Starter panel in Auto mode & give the remote signal.
22.    Observe the proper function and sequences of operations of the equipment.
23.    Record the required parameters.

Final Testing Checkpoint of VFD


1.      Check the incoming voltage & phase sequence before switching ‘ON’ the incomer.
2.      Check control supply and stop lock provision and operation.
3.      Check bypass starter operation with the motor disconnected.
4.      Check VFD operation with the motor disconnected, from the control keypad.
5.      Set parameters as required and record the parameters.
6.      Check VFD operations from keypad after connecting the motor, also check motor’s direction of rotation.
7.      Check bypass starter operation with the motor connected, also check motor’s direction of rotation.
8.      Check external (remote) control of the VFD & Bypass.
e correct  
 through
ject

ise & service wise.


cabling.

erly.

es.

uence.

ator.
s in panel

ection of rotation.
n of rotation.
Invertek Drives Commissioning

Notes:
1.The VFD Contains capacitors inside which takes time to discharge after removal of main power , It is therefore
recomeneded to wait for at least 10 minutes for capacitors to discharge at safe voltage levels.
2.Load monitoring fuction and PID Control process function notes are separately provided , If these fuctions required at
site than implement it accordingly .
3.Factroy Reset Press up+down+start+stop key simulataneously until P-DEF come on display than press stop t

4. Refrence Scaling of Inputs P-30 to P-34 matters a lot for input format either 0-10 V or 0-20 MA OR 4 -20 Ma, likewise sca
The scaling detmines the speed control e.g 0 Volt 0hz and 10 Volts 60 Hz
Invertek Drives
ODV-2-64090-3KF1N-FW
ID VALUE Description
P1-01 60HZ Maximum Frequency
P1-02 0HZ Minimum Frequency
P1-03 30S Acceleration Time
P1-04 30S Deceleration Time
P1-05 0 Ramp to Stop
P1-06 Disable Energy optimiser
P1-07 Motor Rated Voltage

Motor Data
P1-08 Motor Rated Current
AS Per name plate of motor
P1-09 Motor Rated Frequency
P1-10 Motor Rated Speed
P1-11 Drive Dependent V/F mode Voltage Boost
P1-12 0 Terminal Mode
P1-13 1 Digital Input Functions
P2-12 & P2-14 U 0-10 V Analog output 1 & 2 format * This parameter can b
P2-39 0- Disable Parameter Acess lock * By enabling this para
P4-07 110% Maximum motoring current Limit
P6-05 Linear V/F Characteristics
Drives Commissioning

ctions required at

display than press stop to reset.

OR 4 -20 Ma, likewise scaling need to be adjusted accordingly

* This parameter can be set to 0-20 ma or 4-20 Ma


* By enabling this parameter you can see the display but cannot chnage.
GE AF 60LP™ MICRODRIVE BASIC PROGRAMING SETTINGS
Notes:
1.       The VFD Contains capacitors inside which takes time to discharge after removal of main power , It is therefore recom
2.       By default analog Input Terminal 53 is asigned for voltage mode. It can be change to current mode if required 6-19[1]
3.       By default analog output Terminal 42 is asigned for 0-20mA. It can be change to 4-20mA if required by 6-19[1].
4.       Limits / Warning can be adjusted by going into group 4.
5.       Phase Sequence is not Important.
6.       Main Menue Password is 0. Parameter 0-60
7.       Protections
                                 i.            Motor Thermal Protection 1-90 as needed.

                               ii.            Over Voltage Control 2-17 [2]

                             iii.            Low & High current 4-50 & 4-51 as required.

                             iv.            Missing Motor Phase Function 4-58 [1]

Parameter # Description Value

0 Operaion Display 0-03 [ 1]

Hand key reset key and auto key enabling make


0-4 Keypad
it as default no need to change.

0-50 [1]
0-5 Copy/ Save
0-50 [2]

1--20 Motor Power


1--22 Motor Voltage
1--23 Motor Frequency Enter the value as given at name plate of Motor
1--24 Motor Current
1--25 Motor Nominal Speed
3--2 Minimum Refrence 0
3--3 Maximum Refrence 60

3-41 Acceleration Time 5 Sec

3-42 Deceleration Time 5 Sec


4--12 Motor Speed Low Limit 0 Hz
4--14 Motor Speed High Limit 60 Hz

5--10 Terminal 18 Dig input

5--11 Terminal 19 Dig input


5--12 Terminal 27 Dig input Default

5-40 Function Relay [5]

6--10 0.07 V
Analog input 1
6--11 10 V

Term 53 low Ref/Feedb


6--14 0
Value
Term 53 High Ref/Feedb
6--15 60
Value

6--19 Terminal 42 analog output Feedback

Keypad Potm Low


6-81 0
Refrence
Keypad Potm High
6-82 60
Refrence
Terminal 42 Output Min
6-93 0%
Scale
Terminal 42 Output Max
6-94 60%
Scale
14-22 Restore Factory Settings [2]
14-26 Action At drive fault [0]
14-20 Reset Mode [0]
SIC PROGRAMING SETTINGS
e after removal of main power , It is therefore recomeneded to wait for at least 10 minutes for capacitors to discharge at safe voltage levels.
It can be change to current mode if required 6-19[1] .
n be change to 4-20mA if required by 6-19[1].

Remarks

US 60 Hz

eset key and auto key enabling make


as default no need to change.

All to keypad

All from Keypad

alue as given at name plate of Motor

0
60

Depends upon load one


should set this parameter

0 Hz
60 Hz

For all digital inputs


configuration Must
Follow The drawing &
change if required.
Configure all digital
inputs used in drawing.

Drive Running again set


this parameter as per
drawing requirement
Terminal 53 Lov Voltage
Terminal 53 High
Voltage

60

Depends upon DCS &


accordingly change it.

60

0%

60%

Factory reset
Trip
Manual Reset
scharge at safe voltage levels.
ABB ACH550 Main Settings
Sr# Group Parameter Description Value
1 99 1 Language English

2 99 2 Appl Macro Hvac Default

3 99 5 Motor Nom Voltage As required

4 99 6 Motor Nom Current As required

5 99 7 Motor Nom Freq As required

6 99 8 Motor Nom Speed As required

7 99 9 Motor Nom Power As required


20% for (4 to 20 mA)
8 13 1 Minimum AI1
0% for ( 0 to 10V)
9 13 2 Maximum AI1 100%
10 11 04 &05 Minimum 0 and maximum 60 Hz
11 16 1 Run Enable DI2
12 16 4 Fault Reset From Keypad
13 16 6 hand lock On or off depends upon customer

14 16 8 Start Enable Not select


15 16 9 Start Enable(2) Not select
16 20 3 Maximum Current As required
15 Hz (To be used for fans)

17 20 7 Minimum Frequency
20 Hz (To be used for pumps and
cooling towers using gearbox
design fan)
18 20 8 Maximum Frequency 60 hz

19 20 6 Undervolatge Enable
20 21 1 Start Function Ramp to start
21 21 2 Stop Function Ramp to stop
22 22 2 Acceleration time 30s
23 22 3 Deceleration Time 30s
24 22 4 Ramp Shape Linear
25 26 5 U/F Ratio Linear
26 30 2 Panel Comm Err Last Speed
27 30 5 Mot Thermal Port Not Sel
28 30 17 Earth Fault Enable
29 31 4 AR Overcurrent Disable

30 31 5 AR Overvoltage Disable
Danfoss VLT (VFD) Main setting.
1.       0-** Operation Display
0-* basic Setting
0-01 Language - English

2.       0-0* Clock Setting


0.70 Date and Time
0-71 Date format
0-72Time format

3.       1-** Load and Motor


1-2* Moto Data
1-20 Motor Power (KW)
1-21 Motor Power (HP)
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Current

4.       3-** Reference Ramp


3-0* Reference Limit
3-02 Minimum Reference – 0.000 Hz
3-03 Maximum Reference – 60 Hz

5.       5-** Digital In/Out


5-1* Digital Input
5-10 Terminal 18 Digital Input – (8) Start

6.       6-** Analog In/Out


6-20 terminals 54 Low Voltage – 0.07V

7.       6-5* Analog Output 42


6-50 Terminal 42 Output – (130) Output Frq 0 – 100 4 - 2..
Param. No. Description Set Point
99.01 LANGUAGE ENGLISH
99.02 APPLICATION MACRO USER 1
99.03 APPLIC RESTORE N/A
99.04 MOTOR CTRL MODE SCALAR
99.05 MOTOR NOM VOLTAGE 575 V
99.06 MOTOR NOM CURRENT
99.07 MOTOR NOM FREQ 60 Hz
99.08 MOTOR NOM SPEED 1725 rpm
99.09 MOTOR NOM POWER 2.24 kW
99.1 MOTOR ID RUN MODE N/A
99.11 DEVICE NAME N/A
10.01 EXT1 STRT/STP/DIR DI1
10.02 EXT2 STRT/STP/DIR DI1
10.03 REF DIRECTION FORWARD
10.06 JOG SPEED SELECT NOT SEL
10.07 NET CONTROL 0 (Inactive)
10.08 NET REFERENCE 0 (Inactive)
11.01 KEYPAD REF SEL REF2
11.02 EXT1/EXT2 SELECT EXT1
11.03 EXT REF1 SELECT AI2
11.04 EXT REF1 MINIMUM 0%
11.05 EXT REF1 MAXIMUM 100%
11.06 EXT REF2 SELECT KEYPAD
11.07 EXT REF2 MINIMUM 0%
11.08 EXT REF2 MAXIMUM 100%
12.01 CONST SPEED SEL DI5
12.06 DI5(SPEED5) 1725 RPM/60 Hz
13.01 MINIMUM AI1 0V
13.02 MAXIMUM AI1 10 V
13.03 SCALE AI1 100%
13.04 FILTER AI1 0.10 s
13.05 INVERT AI1 NO
13.06 MINIMUM AI2 4 mA
13.07 MAXIMUM AI2 20 mA
13.08 SCALE AI2 100%
13.09 FILTER AI2 0.10 s
13.1 INVERT AI2 NO
14.01 RELAY RO1 OUTPUT READY
14.02 RELAY RO2 OUTPUT RUNNING
14.03 RELAY RO3 OUTPUT FAULT (-1)
14.04 RO1 TON DELAY 0
14.05 RO1 TOFF DELAY 0
14.06 RO2 TON DELAY 0
14.07 RO2 TOFF DELAY 0
14.08 RO3 TON DELAY 0
14.09 RO3 TOFF DELAY 0
15.01 ANALOGUE OUTPUT1 NOT USED
15.02 INVERT AO1 NO
15.03 MINIMUM AO1 4 mA
15.04 FILTER AO1 0.10 s
15.05 SCALE AO1 100%
15.06 ANALOGUE OUTPUT2 NOT USED
15.07 INVERT AO2 NO
15.08 MINIMUM AO2 4 mA
15.09 FILTER AO2 0.10 s
15.1 SCALE AO2
16.01 RUN ENABLE YES
16.02 PARAMETER LOCK OPEN
16.03 PASS CODE N/A
16.04 FAULT RESET SEL NOT SEL
16.05 USER MACRO IO CHG NOT SEL
16.06 LOCAL LOCK OFF
16.09 CTRL BOARD SUPPLY INTERNAL 24V
20.01 MINIMUM SPEED N/A
20.02 MAXIMUM SPEED N/A
20.03 MAXIMUM CURRENT 5:00 AM
20.04 TORQ MAX LIM1 300%
20.05 OVERVOLTAGE CTRL ON
20.06 UNDERVOLTAGE CTRL ON
20.07 MINIMUM FREQ 15
20.08 MAXIMUM FREQ 60 Hz
20.11 P MOTORING LIM 300%
20.12 P GENERATING LIM -300%
20.13 MIN TORQUE SEL MIN LIM1
20.14 MAX TORQUE SEL MAX LIM1
20.15 TORQ MIN LIM1 0.00%
21.01 START FUNCTION AUTO
21.03 STOP FUNCTION COAST
21.04 DC HOLD NO
21.08 SCALAR FLY START YES
21.09 START INTRL FUNC OFF2 STOP
21.1 ZERO SPEED DELAY 0.5 sec
22.01 ACC/DEC SEL ACC/DEC 1
22.02 ACCEL TIME 1 5 sec
22.03 DECEL TIME 1 5 sec
22.06 ACC/DEC RAMP SHPE 0
27.01 BRAKE CHOPPER CTRL OFF
30.01 AI<MIN FUNCTION NO
30.02 PANEL LOSS LAST SPEED
30.03 EXTERNAL FAULT NOT SEL
30.04 MOTOR THERM PROT NO
30.05 MOT THERM P MODE DTC
30.1 STALL FUNCTION FAULT
30.11 STALL FREQ HI 20 Hz
30.12 STALL TIME 20 sec
30.13 UNDERLOAD FUNC NO
30.16 MOTOR PHASE LOSS FAULT
30.17 EARTH FAULT FAULT
30.18 COMM FLT FUNC NO
30.19 MAIN REF DS T-OUT 15 sec
30.2 COMM FLT RO/AO LAST VALUE
30.21 AUX DS T-OUT 15 sec
30.22 IO CONFIG FUNC WARNING
30.23 LIMIT WARNING 0
31.01 NUMBER OF TRIALS 3

31.02 TRIAL TIME 30 SEC


31.03 DELAY TIME 3 SEC
31.04 OVERCURRENT YES
31.05 OVERVOLTAGE YES
31.06 UNDERVOLTAGE YES
31.07 AI SIGNAL < MIN YES
31.08 LINE CONV YES

Notes
1. 2. 3. 4. 5. Parameter not applicable for SCALAR mode. See parameter 20.07. Parameter not applicable for SCALAR mode.
20.08. Adjust scaling factor so 20 mA output is at 5 A motor current. Minimum frequency to be determined via commissioning on
supplied by fan manufacturer.
 
Notes
1. 2. 3. 4. 5.
Parameter not applicable for SCALAR mode. See parameter 20.07. Parameter not applicable for SCALAR mo
current. Minimum frequency to be determined via commissioning on site. To be supplied by fan manufacturer.
Note

5
3

1
2
eter not applicable for SCALAR mode. See parameter
o be determined via commissioning on site. To be
ameter not applicable for SCALAR mode. See parameter 20.08. Adjust scaling factor so 20 mA output is at 5 A motor
e. To be supplied by fan manufacturer.