VFD Commissioning
VFD Commissioning
The purpose of this method statement is to define the step by step method to implement the correct
practices for the Testing & Commissioning Of Starter Panels Variable Frequency Drives VFD’s through
the guidelines contained herein so as to ensure that the job execution complies with the project
requirements and serves the intended function to satisfactory level.
1. Ensure that the Starter panel on the installation inspections are incorporated.
installation is complete and mechanical completion is approved & all the comments
2. Ensure that no damage has occurred to the Starter panel.
3. Repair / replace damaged components, if any.
4. Ensure that the tagging is complete & the starter panels/VFDs are identified location wise & service wise.
5. Check & record insulation resistance values of all incoming & outgoing power wiring / cabling.
6. Ensure that all the incoming & outgoing cables / wires have been terminated to their
respective equipment with proper polarity.
7. Ensure that all BMS wiring are completed.
8. Ensure that the cable dressing is complete inside the starter panel.
9. Ensure that all control wiring is done as per the approved scheme and terminated properly.
10. Ensure that required jumper is provided as per the wiring diagram.
11. Check the ratings of all MCCBs / MCBs are as per approved drawings and load schedules.
12. Check the ratings of ALR as per approved drawings.
13. Ensure all the wiring terminations are tight.
14. Ensure the ratings of all protective fuses are correct.
15. Check the manual operations of door mounted switches, push buttons, etc.
16. Check the earthing connections for tightness.
17. Check the overload relay settings to respective load fed by the starter panel / VFD.
18. Check the ratios of CTs and ensure that is matching with relays / meters feeding to.
19. Check the connection to exhaust fan.
erly.
es.
uence.
ator.
s in panel
ection of rotation.
n of rotation.
Invertek Drives Commissioning
Notes:
1.The VFD Contains capacitors inside which takes time to discharge after removal of main power , It is therefore
recomeneded to wait for at least 10 minutes for capacitors to discharge at safe voltage levels.
2.Load monitoring fuction and PID Control process function notes are separately provided , If these fuctions required at
site than implement it accordingly .
3.Factroy Reset Press up+down+start+stop key simulataneously until P-DEF come on display than press stop t
4. Refrence Scaling of Inputs P-30 to P-34 matters a lot for input format either 0-10 V or 0-20 MA OR 4 -20 Ma, likewise sca
The scaling detmines the speed control e.g 0 Volt 0hz and 10 Volts 60 Hz
Invertek Drives
ODV-2-64090-3KF1N-FW
ID VALUE Description
P1-01 60HZ Maximum Frequency
P1-02 0HZ Minimum Frequency
P1-03 30S Acceleration Time
P1-04 30S Deceleration Time
P1-05 0 Ramp to Stop
P1-06 Disable Energy optimiser
P1-07 Motor Rated Voltage
Motor Data
P1-08 Motor Rated Current
AS Per name plate of motor
P1-09 Motor Rated Frequency
P1-10 Motor Rated Speed
P1-11 Drive Dependent V/F mode Voltage Boost
P1-12 0 Terminal Mode
P1-13 1 Digital Input Functions
P2-12 & P2-14 U 0-10 V Analog output 1 & 2 format * This parameter can b
P2-39 0- Disable Parameter Acess lock * By enabling this para
P4-07 110% Maximum motoring current Limit
P6-05 Linear V/F Characteristics
Drives Commissioning
ctions required at
iii. Low & High current 4-50 & 4-51 as required.
0-50 [1]
0-5 Copy/ Save
0-50 [2]
6--10 0.07 V
Analog input 1
6--11 10 V
Remarks
US 60 Hz
All to keypad
0
60
0 Hz
60 Hz
60
60
0%
60%
Factory reset
Trip
Manual Reset
scharge at safe voltage levels.
ABB ACH550 Main Settings
Sr# Group Parameter Description Value
1 99 1 Language English
17 20 7 Minimum Frequency
20 Hz (To be used for pumps and
cooling towers using gearbox
design fan)
18 20 8 Maximum Frequency 60 hz
19 20 6 Undervolatge Enable
20 21 1 Start Function Ramp to start
21 21 2 Stop Function Ramp to stop
22 22 2 Acceleration time 30s
23 22 3 Deceleration Time 30s
24 22 4 Ramp Shape Linear
25 26 5 U/F Ratio Linear
26 30 2 Panel Comm Err Last Speed
27 30 5 Mot Thermal Port Not Sel
28 30 17 Earth Fault Enable
29 31 4 AR Overcurrent Disable
30 31 5 AR Overvoltage Disable
Danfoss VLT (VFD) Main setting.
1. 0-** Operation Display
0-* basic Setting
0-01 Language - English
Notes
1. 2. 3. 4. 5. Parameter not applicable for SCALAR mode. See parameter 20.07. Parameter not applicable for SCALAR mode.
20.08. Adjust scaling factor so 20 mA output is at 5 A motor current. Minimum frequency to be determined via commissioning on
supplied by fan manufacturer.
Notes
1. 2. 3. 4. 5.
Parameter not applicable for SCALAR mode. See parameter 20.07. Parameter not applicable for SCALAR mo
current. Minimum frequency to be determined via commissioning on site. To be supplied by fan manufacturer.
Note
5
3
1
2
eter not applicable for SCALAR mode. See parameter
o be determined via commissioning on site. To be
ameter not applicable for SCALAR mode. See parameter 20.08. Adjust scaling factor so 20 mA output is at 5 A motor
e. To be supplied by fan manufacturer.