Professional Documents
Culture Documents
Installation Instructions
NOTE: Accessory installation should be complete
before the circuit breaker is mounted and
connected. (See installation instructions
Hazardous Voltage.
Will cause death or severe
supplied with the Accessory before pro-
injury. ceeding.)
Turn off and lock out all power supplying this
device before removing cover(s) or device C. Depress the red trip button (See Fig. 4) or turn
and while cover(s) are removed.
the breaker off before installation.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750, TA3N8750, D. To mount the device, perform the following steps:
OR TA4N8500 ARE USED.
Replace all covers and shields before power 1. For enclosures, panelboards and switch
supplying this device is turned on. boards manufactured by Siemens Energy &
Automation, Inc., follow instructions provided
with the equipment.
SAFETY INSTRUCTIONS
Installation
The MD and ND Frame circuit breaker devices are
for use in individual enclosures, panelboards or
other approved equipment.
The installation procedure consists of inspecting,
attaching required accessories, mounting the de-
vice and connecting and torquing the line and load
wire connectors.
Mounted hardware and unmounted wire connec-
tors (where required) are available as separate cata-
log items.
Fig. 1
Released Production, C
B v1, Apr
Dec 18, 2011
1998
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A. Hazardous Voltage.
Will cause death or severe
injury.
Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.
Installation Instructions
2. For applications where mounting is on a flat Manual Operation
surface of the equipment, drill and tap
Manual operation of the device is controlled by the
mounting bolt holes as shown in Fig. 2. For circuit breaker handle and the PUSH-TO-TRIP
handle escutcheon cutout, refer to Fig. 3. button. The device handle has three indicating posi-
3. Ensure that any internal breaker accessory tions, two of which are molded into the handle to in-
terminals can be properly connected with the dicate ON and OFF. The third position indicates a
circuit breaker in the mounted position. TRIP position and is between ON and OFF positions.
(See Fig. 4)
4. Position the circuit breaker in the mounting
location, install the mounting hardware and A. Device Reset
tighten securely. After tripping, the device is reset by moving the
5. Connect the line and load terminals and device handle to the reset position and then mov-
torque using the values shown on the circuit ing the handle to the ON position.
breaker nameplate. B. The PUSH-TO-TRIP Button
The PUSH-TO-TRIP button checks the tripping
6. Connect all accessory terminals, if present. function and is used to manually exercise the op-
7. Check all mounting hardware for secureness. erating mechanism.
Check wire connectors for correct torque
requirements.
3.75
1.87
4.87 OF HANDLE
OF HANDLE
14.25 2.43
C
L
OF HANDLE
2.62
6.28
3.87
Fig. 2 Fig. 3
Released Production, C
B v1, Apr
Dec 18, 2011
1998
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A. Hazardous Voltage.
Will cause death or severe
injury.
Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.
Installation Instructions
Inspection and Field Test tenance. However, some industrial users may choose
to establish an inspection and maintenance proce-
MD and ND Frame devices are designed to provide dure to be carried out on a regular basis. For de-
years of maintenance free service. Sensitrip III Solid tailed information, consult applicable NEMA publica-
State Molded Case circuit breakers may be tested tions or your local Siemens sales office.
for electronic functionality by the use of TS-31 test
set available from local Siemens sales offices.
NOTE: Do not spray or allow any petroleum based
chemicals, solvents or paints to contact the molded
Maintenance parts or nameplates.
Experience has shown that properly applied molded
case circuit breakers normally do not require main-
Handle
Push-To- On
Trip Button Trip
Off
Reset
Load
Cover
Fig. 4
Released Production, C
B v1, Apr
Dec 18, 2011
1998
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A. Hazardous Voltage.
Will cause death or severe
injury.
Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.
Installation Instructions
ELECTRONIC OPERATION Short Time Pickup xIr (optional)
The setting dials on the face of the electonic trip Circuit breakers with the letters “NT” in the catalog
unit are rotary switches that must be properly set number have adjustments to set the Short Time
to mechanical detent (click stop) positions. An Pickup and the Short Time Delay.
improper switch setting will cause the trip unit to
default (as a fail safe condition) to the lowest The adjustable short time pickup switch allows for
permissive setting and, consequently, may result selection of short time pickup in a range from 1.5
in unintentional or nuisance tripping. to 10 times the setting of the Adjustable Continu-
ous Amps Switch. The OFF position disables the
function. The diagram below illustrates the possible
settings for this switch.
Continuous Current Switch Ir=%In
Adjustments made to this switch can change the Short Time
continuous amps rating of the breaker to 20, 30, Pickup
40, 50, 60, 70, 80, 90 or 100% of the maximum xI r
continuous amps rating (In) of the circuit breaker.
The diagram below shows the settings possible on
this switch. 8
Continuous Amps
Ir = %I n
Released Production, C
B v1, Apr
Dec 18, 2011
1998
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A. Hazardous Voltage.
Will cause death or severe
injury.
Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.
Installation Instructions
Instantaneous Trip Switch xIr The adjustable ground fault pickup and delay switch
allows for the selection of ground fault pickup at
The adjustable instantaneous trip switch allows se- various percentages of the maximum ampere rat-
lection of a tripping point from 2 to 40 times the ing (% In), with an I2t delay @.5x In of .1, .2, or .4
ampere rating. The MAX setting sets the instanta- seconds. The diagram below illustrates the possible
neous pickup to the override level (see note be- settings for this switch.
low). The diagram below illustrates the possible set-
tings for this switch.
Ground Fault
Pickup
Instantaneous Ig = %I n .2s
Pickup
xIr .1s
2
It
Delay
@.5 In .4s
MAX 40
Released Production, C
B v1, Apr
Dec 18, 2011
1998
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A. Hazardous Voltage.
Will cause death or severe
injury.
Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.
Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.
Page 6 of 6 Replace all covers and shields before power
supplying this device is turned on.
Installation Instructions
Neutral Sensing Transformer. Electronic Testing
An external transformer is required for circuit break- Senstrip III solid state molded case circuit break-
ers equipped with ground fault protection when op- ers may be tested for electronic functionality by
erating in the RESIDUAL mode on 3 phase 4 wire the use of a TS-31 test set available from local
systems and when operating in the GROUND RE- Siemens sales offices.
TURN mode on any system. The sensors listed
below must be used for these applications. The NOTE: Time current characteristic curves and
sensor catalog number must be matched to the cir- information on factory installed accessories can
cuit breaker Maximum Continuous Current rating be obtained from local Siemens sales offices.
(In) as shown in the table. Please note that sen-
sors used with other breaker types cannot be used
with the SMD/SND circuit breakers. Installation in-
structions are included with the sensors.
Released Production, C
B v1, Apr
Dec 18, 2011
1998