CP328 Electrical Plan

GENERAL NOTES: Please prepare the Electrical Plan to comply with IBS 2018 which is the Code in effect in
Marana Arizona at this time. Other than the specific items show below, all that is required is the minimum
number of outlets per code and basic lighting. There will be no home automation, low voltage controls or
any other frills.
Lighting: The lighting will be mostly done with LED lights in the ceiling, as shown by dark green dots on
the plan. Lights to be Halo HLBSL 120V using 12Watts each.
Ceiling Fans: 120V with lights, wall switch to control fan and light

Major Electrical:
Voltage kW Amps Breakers Wire
Master Bath
WILL NEED RUNS FOR BOTH UNITS: STEAMER + WATER HEATER
Mr Steam Super 1E 240 10 42 50A 8 Single phase
Stiebel Eltron Tempra 24 240 24 kW [2] 50A

Garage
Stiebel Eltron Tempra 20 240 19 kW [2] 40A 2x 8/2 Single phase 50/60
For Subpanel
Lincoln Welder 167741 230 180A
Electric Kiln 240 6300W 30A Oly 1823HE
Garage Door Openers

Kitchen
Range Hood 120 2 UVC9300SLSS
Cafe Microwave 120 1.7 CVM517P3RD1
Cafe 30" Electric Range 240 1.3kW 40 CES700P3MD1
Cafe Refrigerator 120 15 CFE28TP3MD1
Cafe Dishwasher 120 7.2A CDT845P3ND1