Preface

Table of Contents

Introduction 1
Reyrolle 7SR5 Devices and Front Fascia Panels 2
Hardware
Device Modules 3
V2.31 Technical Data 4

Manual

C53000-T7040-C013-1
NOTE

i For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of Liability Copyright


Subject to changes and errors. The information given in Copyright © Siemens 2022. All rights reserved.
this document only contains general descriptions and/or The disclosure, duplication, distribution and editing of this
performance features which may not always specifically document, or utilization and communication of the content
reflect those described, or which may undergo modifica- are not permitted, unless authorized in writing. All rights,
tion in the course of further development of the products. including rights created by patent grant or registration of a
The requested performance features are binding only when utility model or a design, are reserved.
they are expressly agreed upon in the concluded contract.
Document version: C53000-T7040-C013-1.01
Edition: 05.2022
Version of the product described: V2.31
Preface

Purpose of the Manual


This manual describes the hardware of the Reyrolle 7SR5 device family and provides general information on
the product structure, the modules, and technical data.

Target Audience
This manual is mainly intended for protection system engineers, commissioning engineers, persons entrusted
with the setting, testing and maintenance of automation, selective protection and control equipment, and
operational crew in electrical installations and power plants.

Scope
This manual applies to the Reyrolle 7SR5 device family.

Further Documentation

[dw_7SR5_furtherdocumentation_hardwaremanual, 4, en_US]

Reyrolle 7SR5, Hardware, Manual 3


C53000-T7040-C013-1, Edition 05.2022
Preface

• Device manuals
Each device manual describes the functions and applications of a specific Reyrolle 7SR5 device. The
printed manual for the device has the same informational structure.

• Hardware manual
The hardware manual describes the hardware building blocks and device combinations of the Reyrolle
7SR5 device family.

• Operating manual
The operating manual describes the basic principles and procedures for operating and installing the
devices of the Reyrolle 7SR5 range.

• Communication protocol manual


The communication protocol manual contains a description of the protocols for communication within
the Reyrolle 7SR5 device family and to higher-level network control centers.

• Security manual
The security manual describes the security features of the Reyrolle 7SR5 devices and Reydisp Manager 2.

• Product information
The product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each Reyrolle 7SR5 device.

• Engineering Guide
The engineering guide describes the essential steps when engineering with Reydisp Manager 2. In addi-
tion, the engineering guide shows you how to load a planned configuration to a Reyrolle 7SR5 device and
update the functionality of the Reyrolle 7SR5 device.

• Virtual Relay
The virtual relay allows a user to view, control and manipulate a virtual Reyrolle 7SR5 device. The virtual
relay is a tool that can facilitate training and understanding of the controls and functions on a Reyrolle
7SR5 device.

• Reyrolle 7SR5 catalog


The Reyrolle 7SR5 catalog describes the system features and the devices of Reyrolle 7SR5.

• Easy Protection Relay Selector for Reyrolle and SIPROTEC


This tool gives a quick guidance to find a protection relay of SIPROTEC 5, SIPROTEC 4, SIPROTEC Compact,
Reyrolle which would fit your needs.

Indication of Conformity
This product is CE-compliant to relevant EU directives.

Additional Support
For questions about the system, contact your Siemens sales partner.

Customer Support Center


Our Customer Support Center provides a 24-hour service.
Siemens AG
Smart Infrastructure – Protection Automation Tel.: +49 911 2155 4466
Customer Support Center E-Mail: energy.automation@siemens.com

Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD Phone: +49 911 9582 7100

4 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Preface

Humboldtstraße 59 E-mail: poweracademy@siemens.com


90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany

Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:

! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.

NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.

NOTE

i Important information about the product, product handling or a certain section of the documentation
which must be given attention.

Qualified Electrical Engineering Personnel


Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this document are
people who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.

Reyrolle 7SR5, Hardware, Manual 5


C53000-T7040-C013-1, Edition 05.2022
Preface

Problem-free and safe operation of the product depends on the following:

• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenance


When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:

• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.

• Terminals are exposed when the device element is removed from the case.

Selection of Used Symbols on the Device

No. Symbol Description

1 Direct current, IEC 60417, 5031

2 Alternating current, IEC 60417, 5032

3 Direct and alternating current, IEC 60417, 5033

4 Earth (ground) terminal, IEC 60417, 5017

5 Protective conductor terminal, IEC 60417, 5019

6 Caution, risk of electric shock

7 Caution, risk of danger, ISO 7000, 0434

8 Guideline 2002/96/EC for electrical and electronic devices

9 Guideline for the Eurasian Market

10 AC 2 kV insulation test of reset coil, trip coil, and output contacts

11 5 kV impulse voltage test (type test) in compliance with Class III

12 ESD-sensitive devices

13 CE marking

6 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Preface

No. Symbol Description

14 Mandatory Conformity Mark for Electronics and Electrotechnical Products in Morocco

15 South Korea KC Certification for Electrical and Electronic Products

16 TSI chassis ground symbol, IEC 60417, 5020

OpenSSL
This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http://
www.openssl.org/).
This product includes software written by Tim Hudson (tjh@cryptsoft.com).
This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).

Reyrolle 7SR5, Hardware, Manual 7


C53000-T7040-C013-1, Edition 05.2022
8 Reyrolle 7SR5, Hardware, Manual
C53000-T7040-C013-1, Edition 05.2022
Table of Contents

Preface.......................................................................................................................................................... 3

1 Introduction................................................................................................................................................11
1.1 Design and Hardware Characteristics.................................................................................12

2 Devices and Front Fascia Panels.................................................................................................................17


2.1 Dimension Drawings......................................................................................................... 18

3 Device Modules.......................................................................................................................................... 21
3.1 Processor Module..............................................................................................................22
3.2 Power‑Supply Module....................................................................................................... 23
3.3 Binary Input/Binary Output Modules.................................................................................. 24
3.4 CT Module........................................................................................................................ 25
3.5 VT Module........................................................................................................................ 26
3.6 Arc Flash Detector Inputs/High Speed Binary Outputs (Auxiliary I/O, Module 'A')................. 27
3.7 Temperature Sensor Inputs............................................................................................... 28

4 Technical Data............................................................................................................................................ 31
4.1 Analog Inputs................................................................................................................... 32
4.2 Supply Voltage..................................................................................................................33
4.3 Binary Inputs.....................................................................................................................36
4.4 Binary Outputs.................................................................................................................. 38
4.5 Communication Interfaces................................................................................................ 39
4.6 Electrical Tests.................................................................................................................. 43
4.7 Mechanical Tests...............................................................................................................45
4.8 Environmental Conditions................................................................................................. 46
4.9 Operating Conditions........................................................................................................ 47
4.10 Reference Conditions and Influencing Variables.................................................................48
4.11 Approvals and Certification............................................................................................... 49
4.12 Design Data...................................................................................................................... 50
4.13 Labeling............................................................................................................................51
4.14 Display Resolution.............................................................................................................53

Reyrolle 7SR5, Hardware, Manual 9


C53000-T7040-C013-1, Edition 05.2022
10 Reyrolle 7SR5, Hardware, Manual
C53000-T7040-C013-1, Edition 05.2022
1 Introduction

1.1 Design and Hardware Characteristics 12

Reyrolle 7SR5, Hardware, Manual 11


C53000-T7040-C013-1, Edition 05.2022
Introduction
1.1 Design and Hardware Characteristics

1.1 Design and Hardware Characteristics


Reyrolle 5 (7SR5) devices are supplied in size 6, size 8, and size 12 cases.

[sc_7SR5_size6_front angle, 2, --_--]

Figure 1-1 Size 6 Device

The devices can be panel mounted or fitted into standard 19 inch rack systems.
Dimensions are shown in Figure 2-1 and Figure 2-3.

12 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Introduction
1.1 Design and Hardware Characteristics

[sc_7SR5_size8_FrontViewPartWithdrawn, 1, --_--]

Figure 1-2 Size 8 Device with Element Part Withdrawn from Case

The relay element can be withdrawn from the relay case.

! CAUTION
Inserting and removing the Device Element
² When inserting the device element into the case, handle only from the front of the device fascia and
ensure no objects obstruct insertion of the element.
² Ensure correct orientation of the device before insertion.
² The captive screws on the front of the device should be loosened before withdrawal.
² The rear retaining screw must be removed to allow withdrawal of the device from the case.

Reyrolle 7SR5, Hardware, Manual 13


C53000-T7040-C013-1, Edition 05.2022
Introduction
1.1 Design and Hardware Characteristics

[sc_7SR5_Size6_rear, 1, --_--]

Figure 1-3 Size 6 Device Rear (Device with 2 x Optical LC Ethernet Ports)

NOTE

i Connector arrangement may differ depending on MLFB.

14 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Introduction
1.1 Design and Hardware Characteristics

[sc_7SR5 Fascia - Example Mimic Displays, 3, --_--]

Figure 1-4 Example Mimic Display

Reyrolle 7SR5, Hardware, Manual 15


C53000-T7040-C013-1, Edition 05.2022
16 Reyrolle 7SR5, Hardware, Manual
C53000-T7040-C013-1, Edition 05.2022
2 Devices and Front Fascia Panels

2.1 Dimension Drawings 18

Reyrolle 7SR5, Hardware, Manual 17


C53000-T7040-C013-1, Edition 05.2022
Devices and Front Fascia Panels
2.1 Dimension Drawings

2.1 Dimension Drawings

[dw_7SR5_E6_dimensions, 5, en_US]

Figure 2-1 Size 6 Case

(1) Overall length with AFD/RS485 plugs


(2) Overall length to standard terminal blocks
(3) Earth screw

NOTE

i 3.6 mm holes are suitable for M4 thread-forming screws supplied with the device for typical panel thick-
ness.

18 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Devices and Front Fascia Panels
2.1 Dimension Drawings

[dw_7SR5_E8_dimensions, 2, en_US]

Figure 2-2 Size 8 Case

(1) Overall length with AFD/RS485 plugs


(2) Overall length with TSI plugs
(3) Overall length to standard terminal blocks
(4) Earth screw

NOTE

i 3.6 mm holes are suitable for M4 thread-forming screws supplied with the device for typical panel thick-
ness.

Reyrolle 7SR5, Hardware, Manual 19


C53000-T7040-C013-1, Edition 05.2022
Devices and Front Fascia Panels
2.1 Dimension Drawings

[dw_7SR5_E12_dimensions, 5, en_US]

Figure 2-3 Size 12 Case

(1) Overall length with AFD/RS485 plugs


(2) Overall length with TSI plugs
(3) Overall length to standard terminal blocks
(4) Earth screw

NOTE

i 3.6 mm holes are suitable for M4 thread-forming screws supplied with the device for typical panel thick-
ness.

20 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
3 Device Modules

7SR5 devices comprise electronic modules housed in size 6, 8, or 12 cases.


All devices include the front fascia HMI, a processor module, CT module, and a power supply module. Addi-
tional modules are added dependent on the device functionality.
3.1 Processor Module 22
3.2 Power‑Supply Module 23
3.3 Binary Input/Binary Output Modules 24
3.4 CT Module 25
3.5 VT Module 26
3.6 Arc Flash Detector Inputs/High Speed Binary Outputs (Auxiliary I/O, Module 'A') 27
3.7 Temperature Sensor Inputs 28

Reyrolle 7SR5, Hardware, Manual 21


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.1 Processor Module

3.1 Processor Module


Table 3-1 Data Communications Ports

Description Terminals Information


Serial port X1 RS485
2 Electrical ethernet ports (optional) X2 RJ45 (Channel 1)
X3 RJ45 (Channel 2)
2 Optical ethernet ports (optional) X4 LC (Channel 1)
X5 LC (Channel 2)

NOTE

i Electrical and Optical Ethernet ports cannot be fitted at the same time.

22 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.2 Power‑Supply Module

3.2 Power‑Supply Module


Table 3-2 Power-Supply Module Details

Description Information
Auxiliary input supply DC 24 V to DC 250 V
AC 100 V to AC 230 V rms
Earth/Ground connection (terminal B28)
4 Standard binary outputs (BO) 1 binary output typically used for Device Healthy
(2 changeover, 1 make, 1 break) contact

The case earth stud should be solidly earthed to the panel earth. Terminal B28 (power supply unit) should be
connected to the case earth stud. A minimum wire size of 2.5 mm2 is recommended.

Reyrolle 7SR5, Hardware, Manual 23


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.3 Binary Input/Binary Output Modules

3.3 Binary Input/Binary Output Modules


Table 3-3 Binary Input/Binary Output Modules Details

Description Information
5 Binary inputs Universal hardware, independent segregated connec-
tion terminals.
Individual operate voltage levels selectable in soft-
ware:

• Range 1: DC 24 V/DC 48 V/DC 60 V


• Range 2: DC 110 V/DC 125 V
• Range 3: DC 220 V/DC 250 V
2 Standard binary outputs (BO) Make contacts
Independent circuits/terminals

24 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.4 CT Module

3.4 CT Module
Table 3-4 CT Module Details

Description Information
3 Current inputs Phase inputs A,B,C
1 A/5 A user selectable rating
1 Current input Earth/sensitive earth functions
1 A/5 A user selectable rating
3 Binary inputs Individual operate voltage levels selectable in soft-
ware:

• Range 1: DC 24 V/DC 48 V/DC 60 V


• Range 2: DC 110 V/DC 125 V
• Range 3: DC 220 V/DC 250 V

Reyrolle 7SR5, Hardware, Manual 25


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.5 VT Module

3.5 VT Module
Table 3-5 VT Module Details

Description Information
3 Voltage inputs 3 VT inputs which are configured as a group. The
configuration setting is dependent on the primary
system line VT connections, e.g. see Device Manual
Settings > Configuration > CT/VT

• VT1/2/3 Config: Van, Vbn, Vcn


• VT1/2/3 Config: Va, Vb, Vc
• VT1/2/3 Config: Vab, Vbc, 3V0
40 V to 160 V user selectable rating
1 Voltage input Single VT input used as per application requirements.
40 V to 160 V user selectable rating
1 Binary input Universal hardware, independent segregated connec-
tion terminals.
Individual operate voltage levels selectable in soft-
ware:

• Range 1: DC 24 V/DC 48 V/DC 60 V


• Range 2: DC 110 V/DC 125 V
• Range 3: DC 220 V/DC 250 V
2 Standard binary outputs (BO) Make contacts
Independent circuits/terminals

26 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.6 Arc Flash Detector Inputs/High Speed Binary Outputs (Auxiliary I/O, Module 'A')

3.6 Arc Flash Detector Inputs/High Speed Binary Outputs (Auxiliary I/O,
Module 'A')
Table 3-6 Arc Flash Detector Inputs/High Speed Binary Outputs

Photograph Description Information


3 Arc flash detector inputs (AFD) Point or linear sensors (e.g. PIX
series)
3 High speed binary outputs Make contacts
(HSBO) Independent circuits/terminals
AFD 1 Terminals X11
AFD 2 Terminals X12
AFD 3 Terminals X13
HSBO 1 Terminals X10:1,3
HSBO 2 Terminals X10:5,7
HSBO 3 Terminals X10:9,11
Optical LC channel 1 Terminals X4
Optical LC channel 2 Terminals X5
RS485 Terminals X1
Retaining screw RS1 (remove to allow withdrawl of
the device from the case)

Figure 3-1 AFD/HSBO Terminal


(Optical Ethernet
and RS485 Comms)

Reyrolle 7SR5, Hardware, Manual 27


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.7 Temperature Sensor Inputs

3.7 Temperature Sensor Inputs


Table 3-7 8 Temperature Sensor Inputs (Auxiliary I/O, Module 'A')

Photograph Description Information


8 Temperature sensor inputs (TSI) Compatible with RTD or thermistor
sensors
RTD Cu10, Ni100, Ni120, Ni250, Pt100,
Pt250, Pt1000
Thermistor PTC, NTC
TSI 1 Terminals X6:1 to 3
TSI 2 Terminals X6:4 to 6
TSI 3 Terminals X6:7 to 9
TSI 4 Terminals X6:10 to 12
TSI 5 Terminals X7:1 to 3
TSI 6 Terminals X7: 4 to 6
TSI 7 Terminals X7: 7 to 9
TSI 8 Terminals X7:10 to 12
RJ45 channel 1 Terminals X2
RJ45 channel 2 Terminals X3
RS485 Terminals X1
Earthing terminal x4
Figure 3-2 8 TSI Terminal Retaining screw RS1 (remove to allow withdrawl of
(Electrical Ethernet the device from the case)
and RS485 Comms)

28 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Device Modules
3.7 Temperature Sensor Inputs

Table 3-8 16 Temperature Sensor Inputs (Extended I/O)

Photograph Description Information


16 Temperature sensor inputs (TSI) Compatible with RTD or thermistor
sensors
RTD Cu10, Ni100, Ni120, Ni250, Pt100,
Pt250, Pt1000
Thermistor PTC, NTC
TSI 1 Terminals X14:1 to 3
TSI 2 Terminals X14:4 to 6
TSI 3 Terminals X14:7 to 9
TSI 4 Terminals X14:10 to 12
TSI 5 Terminals X15:1 to 3
TSI 6 Terminals X15: 4 to 6
TSI 7 Terminals X15: 7 to 9
TSI 8 Terminals X15:10 to 12
TSI 9 Terminals X16:1 to 3
TSI 10 Terminals X16:4 to 6
TSI 11 Terminals X16:7 to 9
Figure 3-3 16 TSI Terminal TSI 12 Terminals X16:10 to 12
TSI 13 Terminals X17:1 to 3
TSI 14 Terminals X17: 4 to 6
TSI 15 Terminals X17: 7 to 9
TSI 16 Terminals X17:10 to 12
Earthing terminal x8

Reyrolle 7SR5, Hardware, Manual 29


C53000-T7040-C013-1, Edition 05.2022
30 Reyrolle 7SR5, Hardware, Manual
C53000-T7040-C013-1, Edition 05.2022
4 Technical Data

4.1 Analog Inputs 32


4.2 Supply Voltage 33
4.3 Binary Inputs 36
4.4 Binary Outputs 38
4.5 Communication Interfaces 39
4.6 Electrical Tests 43
4.7 Mechanical Tests 45
4.8 Environmental Conditions 46
4.9 Operating Conditions 47
4.10 Reference Conditions and Influencing Variables 48
4.11 Approvals and Certification 49
4.12 Design Data 50
4.13 Labeling 51
4.14 Display Resolution 53

Reyrolle 7SR5, Hardware, Manual 31


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.1 Analog Inputs

4.1 Analog Inputs


Table 4-1 Current Inputs

Parameter Values
Rated frequency frated 50 Hz, 60 Hz
Rated current Irated Phase inputs 1 A/5 A 0 to 80 ⋅ Irated
Earth inputs 1 A/5 A 0 to 32 ⋅ Irated
CT Burden < 0.1 VA (CT nominal = 1 A)
< 0.2 VA (CT nominal = 5 A)
Thermal rating 100 ⋅ Irated for 1 s
30 ⋅ Irated for 10 s
6 ⋅ Irated for 2 min
5 ⋅ Irated for 3 min
4 ⋅ Irated continuously
Dynamic load‑carrying capacity 250 ⋅ Irated (1 half cycle)

All current, voltage, and power data are specified as RMS values.

Table 4-2 Voltage Inputs

Parameter Values
Rated frequency frated 50 Hz, 60 Hz
Measuring range 0 V to 200 V
VT burden < 0.1 VA @ 110 V
Thermal rating 300 V continuously
All current, voltage, and power data are specified as RMS values.

NOTE

i Further technical data for the current and voltage transformers can be found in the Device Manual >
Technical Data chapter.

NOTE

i Further information on the measuring accuracy of the analog inputs can be found in the Device Manual
> Technical Data chapter.

32 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.2 Supply Voltage

4.2 Supply Voltage


Table 4-3 Integrated Power Supply

Parameter Values
Permissible voltage ranges DC 19.2 V to DC 275 V, AC 80 V to AC 253 V
Auxiliary rated voltage Vrated DC 24 V to DC 250 V
AC 100 V to AC 230 V
50 Hz/60 Hz
Superimposed alternating voltage, peak‑to‑peak, ≤ 15 % of the DC auxiliary rated voltage (applies only
IEC 60255‑11 to direct voltage)
Recommended external protection Miniature circuit‑breaker 6 A, characteristic C
(IEC 60898)

Table 4-4 Auxiliary Supply Voltage Variation (IEC 60255‑26)

Type of Phenomena Test Level Duration Declared Operation


Voltage dips (DC auxiliary 0 V 50 ms Normal operation
supply) 40% Rated Voltage 200 ms Normal operation except
where dip falls below the
relay minimum voltage
then relay restart
70% Rated Voltage 500 ms Normal operation except
where dip falls below the
relay minimum voltage
then relay restart
Voltage dips (AC auxiliary 0% Rated Voltage 2.5/3 cycles @ 50 Hz/ Normal operation
supply) 60 Hz (claimed)
40% Rated Voltage 10/12 cycles @ 50 Hz/ Normal operation
60 Hz
70% Rated Voltage 25/30 cycles @ 50 Hz/ Normal operation
60 Hz
Voltage interruptions (DC 0% Rated Voltage 5s Relay reset
auxiliary supply)
Voltage interruptions (AC 0% Rated Voltage 250/300 cycles @ Relay reset
auxiliary supply) 50 Hz/60 Hz
Alternating component in 15% maximum and Continuous Normal operation
DC (ripple) DC aux minimum Rated Voltage
Gradual shut‑down / Maximum & minimum 60 s Relay reset
start‑up (DC auxiliary Rated Voltage to 0 V
supply) 0V 5 min Relay off
0 V to maximum & 60 s Relay reset
minimum Rated Voltage
Reversal of DC power Maximum reversed Rated 1 min Normal operation
supply polarity Voltage

Reyrolle 7SR5, Hardware, Manual 33


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.2 Supply Voltage

Power Supply Burden

Table 4-5 Device Burdens DC (IEC 60255-1)

Energizing Voltage VDC 19 24 48 60 110 125 220 250 300


IEC 60255‑1
Minimum condition Watt 10.0 9.9 9.3 9.1 8.9 8.8 8.1 8.3 8.4
IEC Load (Half BI, BO) Watt 12.8 12.4 11.6 11.3 10.8 10.8 10.1 10.2 10.2
Maximum load Watt 15.5 14.9 14.0 13.8 13.2 13.2 12.3 12.5 12.5

Table 4-6 PSU Inrush Current (IEC 60255-1)

Energizing Voltage VDC 24 250


IEC 60255‑1
Inrush current Amps ≤ 28 ≤ 210
Duration ms 0.6 0.6

Table 4-7 Device Burdens DC (IEC 60255-27)

Energizing Voltage VDC 19.2 24 48 60 110 125 220 250 300


IEC 60255‑27
Minimum condition Watt 10.0 9.9 9.3 9.1 8.9 8.8 8.1 8.3 8.4
Backlight (W) Watt 0.36 0.24 0.24 0.3 0.22 0.25 0.22 0.25 0.3
LED – red or green (W) Each 0.01 0.01 0.01 0.02 0.02 0.03 0.02 0.03 0.03
LED
LED – yellow (W) Each 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01
LED
Binary output Each 0.33 0.41 0.41 0.3 0.26 0.31 0.33 0.3 0.27
output

NOTE

i The addition of the optional 3 AFD inputs will increase the device burden by < 0.8 W. The AFD module also
includes 3 HSBO. The additional burden for these is Binary output, as shown in the previous table.
The addition of the optional 8 TSI will increase the device burden by < 0.6 W, 16 TSI will increase the device
burden by < 1.2 W.

Table 4-8 Device Burdens AC (IEC 60255-1)

Energizing Voltage VAC 80 100 110 115 120 200 230 265
IEC 60255‑1
Minimum condition VA 19.8 20.8 20.9 21.0 21.1 23.2 24.6 26.8
IEC Load (Half BI, BO) VA 23.3 25.0 25.4 25.4 25.6 28 29.4 31.3
Maximum load VA 27.3 29.2 30.1 30.1 30.6 33.2 34.7 36.8

Table 4-9 Device Burdens AC (IEC 60255-27)

Energizing Voltage VAC 80 100 110 115 120 200 230 265
IEC 60255‑27
Minimum condition VA 19.8 20.8 20.9 21.0 21.1 23.2 24.6 26.8
Backlight (W) VA 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.6
LED – red or green (W) Each 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01
LED

34 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.2 Supply Voltage

Energizing Voltage VAC 80 100 110 115 120 200 230 265
IEC 60255‑27
LED – yellow (W) Each 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01
LED
Binary output Each 0.6 0.6 0.6 0.6 0.6 0.7 0.8 0.8
output

Reyrolle 7SR5, Hardware, Manual 35


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.3 Binary Inputs

4.3 Binary Inputs


Table 4-10 Binary Inputs (BI)

Parameter Values
Rated voltage range DC 24 V to DC 250 V (The inputs are bipolar)
Maximum DC current for operation 24 V 1.5 mA
30 V 1.5 mA
48 V 1.5 mA
60 V 1.6 mA
110 V 1.6 mA
125 V 1.6 mA
220 V 1.8 mA
250 V 1.8 mA
Pickup time Approx. 3 ms
Dropoff time 1 Capacitive load (supply‑line capaci- Dropout time
tance)
< 5 nF < 4 ms
< 10 nF < 6 ms
< 50 nF < 10 ms
< 220 nF < 35 ms
Control voltage DC binary‑input threshold setting
Range 1: 24 V, 48 V, and 60 V Vlow ≤ 10 V
Vhigh ≥ 19 V
Range 2: 110 V and 125 V Vlow ≤ 44 V
Vhigh ≥ 88 V
Range 3: 220 V and 250 V Vlow ≤ 88 V
Vhigh ≥ 176 V
Maximum permitted voltage DC 300 V

Table 4-11 Arc Flash Detector (AFD) Inputs

Parameter Values

Connector type AVAGO AFBR-4526Z


Number of sensor connections Up to 3 sensors – point or line (e.g. P1X series)
Fiber type Polymer Optical Fiber (POF) 1 mm

1 For time-critical applications with low-active signals, consider the specified dropoff times. If necessary, provide for active discharge of
the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).

36 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.3 Binary Inputs

Parameter Values
Receiver
Type = Point -20 dBm ± 2 dBm
Type = Line -31.5 dBm ± 2 dBm
Type = Custom -34 to -10 dBm ± 2 dBm
Spectrum Spectrum 400 nm to 1100 nm
Light sensitivity 8,000 to 10,000 lux
Attenuation For polymer optical fibres a path attenuation of 0.2
dBm is typical. Additional attenuation comes from the
plug and the sensor head
Optical budget 2 Minimal 25 dB
Transmitter
Type LED
Wavelength λ = 650 nm
Transmitter power Minimum -6 dBm
Maximum 2 dBm
Numerical aperture 0.5 3
Signal rate connection test 1 pulse per second
Loop integrity test pulse width 11 μs

Table 4-12 Temperature Sensor Inputs

Parameter Values
RTD 100 Ω platinum
250 Ω platinum TCR = 0.00385
1000 Ω platinum
100 Ω nickel TCR = 0.00618
120 Ω nickel TCR = 0.00672
250 Ω nickel TCR = 0.00618
10 Ω copper TCR = 0.00427
Thermistor (100 Ω to 40 kΩ) NTC
PTC
Supported RTD resistance range 0 to 2 kΩ
Connectors Pin crimp
Recommended cable Screened
Maximum RTD lead resistance 25 Ω per lead RTD
2.5 Ω per lead 10 Ω copper RTD
Response time <3s
Sensing current ≤ 0.5 mA

2 All values in combination with sensors approved by Siemens.


3 Numerical aperture (NA = sin θ [launch angle])

Reyrolle 7SR5, Hardware, Manual 37


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.4 Binary Outputs

4.4 Binary Outputs


Table 4-13 Standard Binary Outputs (BO)

Parameter Values
Operating voltage AC 250 V/DC 250 V
Contact operate time 8 ms typical
Release time 6 ms typical
Making capacity ≥ 1000 W at L/R ≤ 40 ms
Contact current
Continuous 5A
Short time duty cycle (DC 250 V) 30 A, 200 ms On, 15 s Off
Short time single 30 A, 1 s
Breaking capacity
DC inductive 30 W at L/R = 40 ms
DC resistive 75 W
AC resistive 1250 VA
Mechanical/electrical endurance
Loaded cycles ≥ 10000
Making cycles ≥ 1000
Breaking cycles ≥ 1000

Table 4-14 High Speed Binary Outputs (HSBO)

Parameter Values
Operating voltage AC 200 V/DC 250 V
Contact operate time ≤ 1 ms
Release time ≤ 9 ms
Making capacity ≥ 1000 W at L/R ≤ 40 ms
Contact current
Continuous 5A
Short time duty cycle (DC 250 V) 30 A, 200 ms On, 15 s Off
Short time single 30 A, 1 s
Breaking capacity
DC inductive 30 W at L/R = 40 ms
DC resistive 75 W
AC resistive 1250 VA
Mechanical/electrical endurance
Loaded cycles ≥ 10000
Making cycles ≥ 1000
Breaking cycles ≥ 1000

38 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.5 Communication Interfaces

4.5 Communication Interfaces


Table 4-15 USB Interface (Fascia)

Parameter Values
USB User interface
Connection (USB type B)

Insulation class PELV (Protective Extra Low Voltage) (IEC 60255‑27)

A USB connection type B is provided for local connection to a PC on the device front fascia. A cover provides
environmental protection.

Table 4-16 RS485 Data Communication Interface

Parameter Values
Physical layer Electrical
Connection (RS485)

Recommended cable 120 Ω screened twisted pair (STP) cable


Recommended external RTU 120 Ω, 0.5 W
terminating resistor Last relay 120 Ω, 0.5 W
Connectors Pin crimp

[dw_connection2wire, 1, en_US]

Figure 4-1 Connection – 2 Wire: OV (System Common) Not Connected

Reyrolle 7SR5, Hardware, Manual 39


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.5 Communication Interfaces

[dw_connection_1.5wire, 2, en_US]

Figure 4-2 Connection – 1.5 Pair Wire

Table 4-17 Electrical Ethernet Interface (RJ45)

Parameter Values
Interface Integrated ethernet interface
Connection

(1) LED 1: Green


(2) LED 2: Yellow
Connector type 2 x RJ45
Baud rate 100 Mbit/s
Maximum line length 20 m with ethernet patch cable CAT 5/CAT 6
Insulation class SELV (IEC 60255‑27)
Connector interface design Corresponds to IEEE 802.3, 100Base‑TX

40 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.5 Communication Interfaces

Table 4-18 RJ45 Connection Details

Pin Signal Signal Description


1 ETH_TX_P Transmit data +
2 ETH_TX_N Transmit data -
3 ETH_RX_P Receive data +
4 – –
5 – –
6 ETH_RX_N Receive Data -
7 – –
8 – –
– Screen Shield potential

Table 4-19 LEDs of the RJ45 Terminals – Integrated Ethernet Interface

Ethernet Interface (RJ45) Signal Color Operating Status


LED 1 ETH_LED1_N Yellow Continuously lit: 100 Mbit/s
Not lit: 10 Mbit/s
LED 2 ETH_LED0_N Green Flashing: Comms active
Continuously lit: No communication

Table 4-20 Fibre Optic Ethernet Data Communication Interface (Option)

Parameter Values
Physical layer Fibre optic. LED Class 1
Connectors

Recommended fibre 62.5 μm/125 μm glass fibre with duplex‑LC connector


Transmission speed 100 MBit/s
Optical wavelength 1300 nm
Max. line length 2 km for 62.5 μm/125 μm and 50 μm/125 μm optical fibres
Transmit Power Minimum Typical Maximum
50 μm/125 μm, NA4 = 0.2 -24 dBm -21 dBm -17 dBm
62.5 μm/125 μm, NA4 = 0.275 -20 dBm -17 dBm -14 dBm
Reciever sensitivity Maximum -12 dBm
Minimum -31 dBm
Optical budget Minimum 7 dB for 50 μm/125 μm, NA4 = 0.2
Minimum 11 dB for 62.5 μm/125 μm, NA4 = 0.275

4 Numerical aperture (NA = sin θ (launch angle))

Reyrolle 7SR5, Hardware, Manual 41


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.5 Communication Interfaces

Parameter Values
Interface design Corresponds to IEEE 802.3, 100Base-FX
Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical
fibres

42 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.6 Electrical Tests

4.6 Electrical Tests


Table 4-21 Installation Requirements

Parameter Values
Overvoltage category III
Degree of pollution 2
Protection class 1

Table 4-22 Voltage‑Immunity and Safety Tests (IEC 60255-27)

Parameter Values
Insulation - Dielectric withstand Between any terminal and earth AC 2.5 kV RMS for 1 min
Between independent circuits
Across open contacts AC 1.0 kV RMS for 1 min
Impulse voltage Between all terminals and earth or 5 kV, 1.2/50 μs, 0.5 J
between any 2 independent
circuits (excluding communication
interfaces)
Insulation resistance > 100 MΩ @ DC 500 V

Table 4-23 EMC Immunity Tests (Type Tests under Mounting Conditions) (IEC 60255-1 and IEC 60255-26)

Parameter Values
Electrostatic discharge test Enclosure Contact discharge 8 kV
IEC 61000‑4‑2 Air discharge 15 kV
(USB cover closed)
Radiated electromagnetic field Enclosure Sweep 10 V/m, 80 MHz to 1 GHz
immunity 10 V/m, 1.4 GHz to 2.7 GHz
Frequency sweep 80 % AM, 1kHz sine wave
IEC 61000‑4‑3
Radiated electromagnetic field Enclosure Spot 10 V/m, 80 MHz/160 MHz/380
immunity MHz/450 MHz/900 MHz
Spot frequencies 1.85 GHz/2.15 GHz
IEC 61000‑4‑3 80 % AM 1 kHz
Dwell time ≥ 10 s
Power frequency magnetic field Enclosure 100 A/m (continuous)
immunity test 1000 A/m for 3 s
IEC 61000‑4‑8
Conducted RF disturbance ampli- Auxiliary PSU 10 VRMS
tude‑modulated IEC 61000‑4‑6 Comms port 150 kHz to 80 MHz
frequency sweep Measuring inputs
Binary inputs
Binary outputs
Conducted RF disturbance ampli- Auxiliary PSU 10 VRMS
tude‑modulated IEC 61000‑4‑6 Comms port 27 MHz/68 MHz
spot frequencies Measuring inputs dwell time ≥ 10 s
Binary inputs 80 % AM, 1 kHz
Binary outputs

Reyrolle 7SR5, Hardware, Manual 43


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.6 Electrical Tests

Parameter Values
Electrical fast transient/burst Auxiliary PSU 4 kV (peak), 5 ns/50 ns, 5 kHz
immunity Measuring inputs
IEC 61000‑4‑4 Binary inputs
Binary outputs
Comms port 2 kV (peak), 5 ns/50 ns, 5 kHz
Damped oscillatory wave immunity Auxiliary PSU 1 kV (peak) differential (transverse)
IEC 61000‑4‑18 Comms port mode
Measuring inputs 2.5 kV (peak) common (longitu-
Binary inputs dinal) mode
Binary outputs
High‑energy surge voltages Pulse: 1.2 μs/50 μs
IEC 61000‑4‑5 Auxiliary PSU Line‑to‑line: 2 kV
Line‑to‑earth: 4 kV
Source impedance: 2 Ω
L-L coupling resistance: 0 Ω
L-E coupling resistance: 10 Ω
Communications port Line‑to‑earth: 4 kV
Source impedance: 2 Ω
L-L coupling resistance: 0 Ω
L-E coupling resistance: 10 Ω
Measuring inputs Line‑to‑line: 2 kV
Binary inputs Line‑to‑earth: 4 kV
Binary outputs Source impedance: 2 Ω
L-L coupling resistance:40 Ω
L-E coupling resistance: 40 Ω
Power‑frequency disturbance test Binary inputs Differential (transverse) mode: 150
IEC 61000‑4‑16 VRMS
Common (longitudinal) mode: 300
VRMS

Table 4-24 EMC Electromagnetic Emission Tests (Type Tests, Test under Mounting Conditions) (IEC
60255-26)

Parameter Values
Conducted emission on auxiliary- CISPR 22 150 kHz to 30 MHz limit class A
voltage lines
Radiated emission CISPR 11 30 MHz to 1000 MHz limit class A
CISPR 22 1 GHz to 6 GHz limit class A

44 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.7 Mechanical Tests

4.7 Mechanical Tests


Table 4-25 Vibration and Shock Stress (IEC 60255-21)

Standard Type Level Variation


Vibration test (sinus- Vibration response 0.5 gn
oidal) Vibration endurance 1 gn
IEC 60255‑21‑1,
class 1
Shock test Shock response 5 gn, 11 ms
IEC 60255‑21‑2, Shock withstand 15 gn, 11 ms
class 1 Bump test 10 gn, 16 ms ≤5%
Seismic tests Seismic response X-plane – 3.5 mm displacement
IEC 60255‑21‑3, below crossover frequency (8
class 1 to 9 Hz) 1 gn above.
Y-plane – 1.5 mm displacement
below crossover frequency (8
to 9 Hz) 0.5 gn above.

Reyrolle 7SR5, Hardware, Manual 45


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.8 Environmental Conditions

4.8 Environmental Conditions


Table 4-26 Temperatures (IEC 60255-1)

Parameter Values
Operating range IEC 60068-2-1 -10 °C to +55 °C
IEC 60068-2-2 -20 °C to +70 °C, 96 hrs5
-40 °C to +85 °C, 16 hrs5
Storage range IEC 60068-2-1 -25 °C to +70 °C
IEC 60068-2-2 -40 °C to +85 °C, 96 hrs5
Change of temperature IEC 60068-2-14 -10 °C to +55 °C
5 cycles:
-40 °C to +85 °C5

Table 4-27 Humidity (IEC 60255-1)

Parameter Values
Damp heat, steady state IEC 60068-2-78 40 °C, 93 % relative humidity, 56
days
Damp heat, cyclic IEC 60068-2-30 6 cycles:
25 °C, 97 % relative humidity
40 °C, 93 % relative humidity

Table 4-28 Other Tests (IEC 60255-1)

Parameter Values
Corrosive gas IEC 60068-2-60 Test Ke: Flowing mixed gas

5 Basic hardware tested

46 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.9 Operating Conditions

4.9 Operating Conditions


The device is designed for mounting in conventional relay rooms and systems such that electromagnetic
compatibility (EMC) is ensured.
Siemens additionally recommends:

• Use contactors and relays that work within the same cabinet or the same relay panel with digital protec-
tion equipment, only with suitable quenching equipment.

• Removing or inserting the withdrawable element under live voltage is prohibited. Some components are
electrostatically sensitive in the removed state, no special precautions are required when in normal
service conditions.

Reyrolle 7SR5, Hardware, Manual 47


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.10 Reference Conditions and Influencing Variables

4.10 Reference Conditions and Influencing Variables


Table 4-29 Accuracy Reference Conditions

Parameter Values
Auxiliary supply DC 24 V to DC 250 V nominal
AC 100 V to AC 230 V nominal
AC Current (Irated) Nominal or Rated (1 A/5 A)
AC Voltage (Vrated) Nominal or Rated (40 to 160 V)
Frequency (frated) Nominal or Rated (50 Hz/60 Hz)
Ambient temperature (Tamb) 20 °C

48 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.11 Approvals and Certification

4.11 Approvals and Certification


Common Requirements
IEC 60255-1: Measuring relays and protection equipment – common requirements

CE Certification
This product is CE compliant to relevant EU directives:
2014/35/EU: ‘Low Voltage Directive’ for electrical equipment designed for use within certain voltage limits
Council Directive
2014/30/EU: EMC Directive.
2015/863/EU: Restriction of Hazardous Substances Directive (RoHS3)

Other Certification
ISO 9001 Quality Management

Reyrolle 7SR5, Hardware, Manual 49


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.12 Design Data

4.12 Design Data


Table 4-30 Dimensions and Weights

Parameter Values
Width 7SR5 Size 6 device 153 mm
7SR5 Size 8 device 205 mm
7SR5 Size 12 device 308 mm
Height 177 mm
Depth behind panel 243 mm (includes terminal
(including clearance for wiring and fibre) wiring)
288 mm (includes F/O
cabling)
Projection (from front of panel) 31 mm
Weight 7SR5 Size 6 device < 3.85 kg
7SR5 Size 8 device < 5.6 kg
7SR5 Size 12 device < 7.5 kg
7SR5 Size 6 device with packaging < 5.5 kg
7SR5 Size 8 device with packaging < 7.1 kg
7SR5 Size 12 device with packaging < 9.5 kg

Mounting is front of panel/flush mounting or 19” rack mounting.

Table 4-31 Degree of Protection According to IEC 60529

Parameter Values
Installed front face IP 54
Rear enclosure (case) IP 40
Rear wiring terminal access IP 10
IP 20 achieved with optional terminal covers fitted

Table 4-32 Minimum Bending Radius of the Connecting Cables

Parameter Values
Fiber‑optic cable Radius = 70 mm
Electrical ethernet Radius = 50 mm (minimum bending radius)

Table 4-33 Tightening Torques for Screws

Parameter Values
Fascia lever handles – captive screw 0.3 Nm

50 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.13 Labeling

4.13 Labeling
There are labels located on the device.
In the following table, there is an example unified label (side label, MLFB ID label, and a Case Serial No. label)
with explanations as to what some of the symbols and terms mean.

[sc_7SR5_TypicalSideDeviceLabel, 2, --_--]

Figure 4-3 Example Label

Table 4-34 List of Symbols Used

Text or Symbol Description


7SR5 Device type
Vaux Rated voltages for the power supply
BI Rated voltages for the binary inputs (all inputs)
Irated, Vrated, frated Nominal rated values for current and/or voltage transformer
inputs
QR code that can be scanned using a QR code reader appli-
cation. This allows the device serial number to be quickly
identified.

Reyrolle 7SR5, Hardware, Manual 51


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.13 Labeling

Text or Symbol Description


AC 2 kV insulation test of reset coil, trip coil, and output
contacts

5 kV impulse voltage test (type test) in compliance with


Class III

Electrical Hazard

European CE marking

Refer to device documentation

Waste Electrical and Electronic Equipment Directive (WEEE)

Guideline for the Eurasian Market

Mandatory Conformity Mark for Electronics and Electrotech-


nical Products in Morocco

South Korea KC Certification for Electrical and Electronic


Products

52 Reyrolle 7SR5, Hardware, Manual


C53000-T7040-C013-1, Edition 05.2022
Technical Data
4.14 Display Resolution

4.14 Display Resolution


The LCD (liquid crystal display) graphic display measures 128 x 128 pixels.

NOTE

i The display is in greyscale.

Reyrolle 7SR5, Hardware, Manual 53


C53000-T7040-C013-1, Edition 05.2022
54 Reyrolle 7SR5, Hardware, Manual
C53000-T7040-C013-1, Edition 05.2022

You might also like