CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Seismic Design for Buckling-Restrained Braced Frames Based on AISC 360-05 & AISC 341-05
DESIGN CRITERIA
1. Bracing member self shall be composed of a structural steel core & a system that restrains the steel core from buckling.
The each end of brace to gusset plate may be standard bolted connections, modified bolted connections, or true pin
connections. Selecting bracing members are based on the tested & approved manufacture's lists.
2. The lateral capacity of BRBF, selected bracing members with steel beams and columns, must also be checked by a special
loads combination of DL + LL + 2 dx/1.5 (AISC 341-05, 16.2b, 16.5b & ASCE 7-05, 12.8.6).
3. For the connection of gusset plate to beam and column, the interface dimensions of a and b may not satisfy the basic
relationship of the Uniform Force Method: a - b tanq = eb tanq - ec. This software can determine gusset dimensions
based on geometry and can check the gusset interface weld capacities with moment loads.
GUSSET DIMENSIONS 2b= 24.0 in
2a= 10.1 in
ANALYSIS
DETERMINE REQUIRED STRENGTH OF BRACING CONNECTION (AISC 341-05, 16.3a & 16.2d)
T = (1.1 / 1.5) b w Ry Pysc = 247.1 kips, ASD
Where b = 1.20 , (AISC 341-05, 16.2d. May be verified by nonlinear time-history or analyses.)
w = 1.44 , (AISC 341-05, 16.2d. May be verified by nonlinear time-history or analyses.)
Ry = 1.30 , (AISC 341-05, Table I-6-1)
DETERMINE BEST FILLET WELD SIZE PER THICKNESS OF GUSSET & FLANGES (AISC 360-05 J2.2b)
> wMIN = 0.25 in
w= 7/16 in
< wMAX = 0.5625 in [Satisfactory]
DETERMINE CONNECTION INTERFACE FORCES ( AISC Manual 13th Edition, Page 13-10)
b= 12.00 in
a= 5.07 in > (eb + b) tanq - ec = 3.05 in
[the original Uniform Force Method not apply]
K = eb tanq - ec = -2.55 in
D = tan2q + (a / b)2 = 0.39605
K' = a ( tanq + a / b) = 4.50812
aIdeal = (K' tanq + K (a / b)2 ) / D = 4.16 in
bIdeal = (aIdeal - K) / tanq = 14.38 in
r = [(eb + bIdeal)2 + (ec + aIdeal)2] 0.5 = 24.86 in
Vc = (bIdeal / r) T = 143.0 kips
CHECK LOCAL BUCKLING LIMITATION (AISC 341-05 Tab. I-8-1) < = does not apply for top flange continuously braced.
bf / (2tf ) = 7.67 < 0.3 (Es / Fy) 0.5
= N/A [Satisfactory]
Where Es = 29000 ksi
3.14(Es/Fy)0.5(1-1.54P2DWo/Py) = N/A , for P2DWo/Py < 0.125
h / tw = 34.33 <
1.12(Es/Fy) (2.33-P2DWo/Py) =
0.5
N/A , for P2DWo/Py > 0.125
[Satisfactory] Where Wo = 2.0 , (AISC 341-05, Table R3-1)
Py = FyA = 1000 kips
2
E Jc 0.7 F y S x h 0
L r 1.95 r ts 1 1 6.76
E 26.24 ft
0.7 F y S xh0 Jc
Mp = Fy Zx = 550.0 ft-kips
2
C b 2E Jc L b 138.688 ksi
F cr 1 0.078
S x h 0 r ts
2
Lb
r ts