Professional Documents
Culture Documents
Dps 005
Dps 005
IM 1125-7
Group: Applied Air Systems
Part Number: IM 1125
Date: November 2015
3–6 tons
7–15 tons
Shown with Energy Recovery
16–28 tons
Shown with Energy Recovery
DPS 003–015 (only) Gas Furnace Ignition and Control Cleaning Option E Coated Coils . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Service and Warranty Procedures . . . . . . . . . . . . . . . . . . . . . . . . . 103
VB-1200 Trouble Shooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
DPS 016–028 Gas Furnace Ignition Troubleshooting . . . . . . . . . . . 60 Scroll Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Optional Hot Water Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 In-Warranty Return Material Procedure . . . . . . . . . . . . . . . . . . . . . 103
Hot Water Heater Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Warranty Registration Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Optional Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Quality Assurance Survey Report . . . . . . . . . . . . . . . . . . . . . . . . 108
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Appendix – Keypad/Display Menu Structure . . . . . . . . . . . . . . . . 110
Optional Outdoor Air Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Thermal Dispersion Airflow Measurement Technology . . . . . . . . . . 69
Introduction
DPS – 010 – A H H G 4
Mechanical Installation
Filter
Access Filter
Access
Plenum Discharge,
Electric Heat & Supply Fan
Supply Fan Access Access
Control
48 .00 Control
Panel Gas 48 .00
(1219 mm) Panel Gas
Access 59 .2" (1219 mm)
(1504 mm) Access 59 .2"
(1504 mm)
Large Cabinet
016—028
Assembly Instructions
Assembly of a typical roof curb is shown in Figure 2, Figure 3
on page 8 and Figure 4 on page 9.
1. Set curbing parts A thru G per dimensions shown over roof
opening or on a level surface. Note location of supply air
opening. Check alignment of all mating screw holes.
2. Screw curbing parts together using fasteners provided.
Leave all screws loose until curb is checked to be square.
3. Square entire curbing assembly and securely tighten all
screws.
4. Position curb assembly over roof openings. Curb must
be level within 0.25 inches from side to side and 1.50
inches over its length. Check that top surface of curb is
flat with no bowing or sagging.
5. Weld curb assembly in place. Caulk all seams watertight.
Remove backing from 0.25 × 1.50 wide gasket and apply
to surfaces shown by crosshatching.
6. Check that electrical connections are coordinated.
BACK SIDE
G
28.69
INSIDE
B
D
IR
L YA
PP H
SU
9.84
INSIDE RE E
TU
RN
AIR
A F
28.76
INSIDE
9.64 C
INSIDE
44.24 61.50
RIGHT SIDE
FRONT SIDE
44 .38
Inside
44 .38
Inside
2 .0
2 .0
18 .5
9 .5 Return
Inside Opening
9 .5 Return
Supply 28 .55 Inside Opening
Opening Inside
19 .1
19 .1
28 .69 9 .69
Inside Inside
57 .5
Inside
A A
Curb Detail
A A
A–A
Electrical 14.0" 2"×4"
Nailer 2.0"
Entrance or Typ.
24.0"
3 .9
Electrical 2"×4"
Entrance 14.0" Nailer
3 .9 4.0" or
24.0"
6 .4 3 .9
3 .9
4.0"
6 .4
BACK SIDE
LEFT SIDE
A
E
SUPPLY
B AIR
F
E
RETURN
AIR
A D C
RIGHT SIDE
FRONT SIDE
Unit Tag: Units: Sheet: __ of __ DPS 007–012 Roofcurb with ERW Certified Draw
Horizontal above the roof gas connection only McQuay International certifies that its equipment will conform to this drawing and McQuay’s Model: DPS
published specifications, subject to its published warranty. Purchaser must determine that the
equipment is fit and sufficient for the job specifications. No change to this drawing may be made
unless approved in writing by McQuay . www.DaikinMcQuay.com © 2012 McQuay International Date:
Standard Roof Curb – Medium Cabinet Roof Curb for ERW – Medium Cabinet
Unit Tag: Units: Sheet: __ o
8 .8 8 .8
6 .9 6 .9
2 .0 2 .0
3 .4 3 .4
Electrical Electrical
Entrance Entrance
30 .5 Supply 30 .5 Supply
Inside Opening Inside Opening
34 .88
Inside A A 34 .88 A A
Curb Detail Inside
24 .25 A–A 24 .25
2.0" Curb Detail
81 .5 Typ. 101 .5
Inside A–A
Inside
2.0"
Typ.
14.0" 2"×4"
or Nailer
13 .5 Return 24.0" Return
Inside 13 .5
Opening Inside Opening 2"×4"
14.0" Nailer
or
24.0"
4.0"
48 .38
Inside
20 .0 4.0"
48 .38
Inside
BACK SIDE
LEFT SIDE
A
E
SUPPLY
B AIR
F
E
RETURN
AIR
D D C
A RIGHT SIDE
FRONT SIDE
WARNING
Use all lifting points. Improper lifting can cause property
damage, severe personal injury, or death.
REMOVE THE FORKLIFT
CHANNELS BEFORE
CAUTION SETTING THE UNIT ON
THE ROOF CURB
Rigging holes for shackles are integral on the unit base. Use
four independent lines, securing one end of a line to a
unit base lifting point and the other end of the line to an
associated spreader bar lifting point. Figure 5 and Figure 6
are examples of instruction labels shipped with each unit.
Use spreader bars to prevent damage to the unit cabinet. Avoid
twisting or uneven lifting of the unit. The cable length from the
bracket to the hook should always be longer than the distance
between the outer lifting points.
If the unit is stored at the construction site for an intermediate
period, take these additional precautions:
1. Support the unit well along the length of the base rail.
2. Level the unit (no twists or uneven ground surface).
3. Provide proper drainage around the unit to prevent
flooding of the equipment.
4. Provide adequate protection from vandalism, mechanical
contact, etc.
5. Securely close the doors.
6. Cover the supply and return air openings.
Economizer Dampers
As the single actuator modulates, the outside air dampers
open, the return air dampers close, and the exhaust air exits
the unit through the gravity relief dampers.
The economizer comes with manually adjustable linkage (Figure
8). The damper is set so that the crank-arm moves through
a 90-degree angle to bring the economizer dampers from full
open to full close. Mechanical stops are placed in the crank-arm
mounting bracket. Do not remove stops. Driving the crank-arm
past the stops results in damage to the linkage or damper.
Figure 10: Duct Static Pressure Sensing Tubing Installation 3. Locate the building tap so it is not influenced by any
Main Control Panel Condenser Section source of moving air (velocity pressure). These sources
may include air diffusers or outside doors.
4. Route the building tap tube through the curb and feed
it into the unit through the knockout in the bottom of the
control panel (refer to Figure 9). Connect the 3/16" ID
tube to the (high) fitting for sensor SPS2.
5. Locate the reference pressure (low) tap on the roof.
Keep it away from the condenser fans, walls, or anything
else that may cause air turbulence. Mount it high
SPS1
enough above the roof so it is not affected by snow. Not
LO Line
connecting the reference tap to the sensor results in
Roof
HI Line unsatisfactory operation.
6. Use an outdoor static pressure tip (Dwyer A306 or
Remote Sense Point
equivalent) to minimize the adverse effects of wind.
To Sensor Ductwork Place some type of screen over the sensor to keep out
(Remote Location)
HI Input
Rubber
insects. Loosely packed cotton works well.
To Sensor Grommet
LO Input 7. Route the outdoor tap tube out of the main control panel
Tubing Extends
Through Approx. 3/16"
through a small field-cut opening in the upright. Seal the
penetration to prevent water from entering. Connect the
3/16" ID tube to the (low) fitting for sensor SPS2.
Pressure Sensing
Tubing Discharge Air Temperature Sensor
The discharge air temperature sensor must be installed in the
Installing Building Static Pressure Sensor Taps discharge air duct, downstream of the rooftop unit. Locate the
sensor in a location that closely approximates the average
CAUTION duct temperature. To avoid the effects of radiation, the sensor
Fragile sensor fittings. If you must remove tubing should not be in the line-of-sight of a gas furnace or electric
from a pressure sensor fitting, use care. Do not use heater. Generally, locate sensor in the center of a duct wall,
excessive force or wrench the tubing back and forth to 5′ – 10′ from unit opening to allow for air mixing. Do not mount
remove or the fitting can break off and damage sensor. down stream of VAV boxes or other dampers.
Installation: Drill 7/8" diameter hole in duct, insert sensor probe
If a unit has building static pressure control capability, you and secure plate to duct with 2 – #10 screws. Be sure to apply
must field install and connect static pressure taps to the static gasket or silicone sealant to back of mounting plate prior to
pressure sensor SPS2 in the unit. This sensor is located at the screwing plate to the duct to create an air-tight seal.
bottom of the main control panel next to SPS1.
Carefully locate and install the two static pressure sensing Figure 11: Discharge Air Temperature Sensor Installation
taps. Improper location or installation of the sensor taps causes
unsatisfactory operation. Below are pressure tap location and
installation recommendations for both building envelope and
lab, or “space within a space” pressure control applications.
The installation must comply with local code requirements.
Electrical Installation
DANGER Pre-Construction
Hazardous voltage. Can cause severe injury or The Rebel unit comes equipped with a Microtech III controller
death. and can be used for sites that are still under construction. The
Disconnect electric power before servicing equipment. following conditions must be met.
More than one disconnect may be required to de- 1. Ductwork has to be installed. The fan proving switch
energize the unit. and furnace might not run correctly without the specified
external static pressure
WARNING 2. Filters must be installed.
Provide proper line voltage and phase balance. 3. Follow furnace commissioning instructions found in the
Improper line voltage or excessive phase imbalance furnace section.
constitutes product abuse. It can cause severe damage
4. After substantial completion of the construction process
to the unit’s electrical components.
the unit is to be thoroughly cleaned. Special attention
should be paid to the indoor DX coil and the furnace.
WARNING Filters should be changed
Electrical shock hazard. Can cause severe injury or 5. Furnace operation, rate, and temperature rise should be
death. re-verified. See instructions found in the furnace section.
Connect only low voltage NEC Class II circuits to
terminal block TB2. Lab Pressurization Applications
1. Install a “T” fitting with a leak-tight removable cap in each
DANGER tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
Overheating or failure of the gas supply to shut off can
cause equipment damage, severe personal injury or 2. Use different colored tubing for the controlled space
death. Turn off the manual gas valve to the appliance before pressure (high) and reference pressure (low) taps, or tag
shutting off the electrical supply. the tubes.
3. Regardless whether the controlled space is positive or
negative with respect to its reference, locate the high
pressure tap in the controlled space (the setpoint can be
set between -0.2" and 0.2" wc).
4. Locate the reference pressure (low) tap in the area
surrounding the controlled space. Not locating the
reference tap to the sensor results in unsatisfactory
operation.
5. Locate both taps so they are not influenced by any source
of moving air (velocity pressure). These sources may
include air diffusers or doors between the high and low
pressure areas.
6. Route the building tap tube between the curb and the
supply duct and feed it into the unit through the knockout
in the bottom of the control panel.
7. Connect the tube to the (high) fitting for sensor SPS2.
Table 6: 003–015 Electric Heat Data1 Table 7: DPS 016–028 Electric Heat Data
kW Voltage Amps kW Voltage Amps KW Voltage Amps KW Voltage Amps
208 16.7 208 99.9 208 83.4 208 250.1
230 15.1 230 90.4 230 75.4 230 226.2
6 36 30 90
475 7.3 475 43.8 460 37.7 460 113.1
575 6.0 575 36.1 575 30.2 575 90.5
208 33.3 208 149.9 208 125.1 208 333.5
230 30.1 230 135.6 230 113.1 230 301.6
12 54 45 120
475 14.6 475 65.6 460 56.5 460 150.8
575 12.0 575 54.2 575 45.2 575 120.6
208 50.0 208 N/A 208 166.7 208 416.9
230 45.2 230 N/A 230 150.8 230 377.0
18 72 60 150
475 21.9 475 87.5 460 75.4 460 188.5
575 18.1 575 72.3 575 60.3 575 150.8
208 83.3
230 75.3
30
475 36.5
575 30.1
NOTE: 1. Maximum temperature rise equals 60ºF
Supply Fan FLA (DPS 003–015) Exhaust Fan FLA (DPS 003–028) Supply Fan FLA (016–028)
Horse Voltage Voltage Voltage
Power
208 230 460 kW 208 230 460 kW 208 230 460 575
1.3 3.1 2.8 1.4 1.0 3.1 2.8 1.4 1.0 — — — —
2.3 5 4.6 2.3 1.7 5 4.6 2.3 1.7 — — — —
3 — — — — — — — — 9.9 9.0 4.5 3.4
4 8.8 7.4 4.0 3.0 8.8 7.4 4.0 3.0 — — — —
5 — — — — — — — — 16.1 14.0 7.0 5.3
7.5 — — — — — — — — 25.0 21.6 10.8 8.2
8 13.5 12.2 6.1 6.0 — — — — — — — —
10 — — — — — — — — 33.0 28.0 14.0 11.0
15 — — — — — — — — 44.8 40.6 20.3 16.2
20 — — — — — — — — 61.0 50.0 25.0 20.0
NOTE: DPS 007–015 575V Amp Draws: Compressors and motors will be run off a 575 to 460V transformer. Motors will be nameplated at 460V.
EAF FLA are per motor. Some DPS 016–028 units have (2) EAFs and motors.
Refrigeration System
Piping System
The Rebel piping system varies significantly between the
multiple possible configurations; heat pump, cooling only, and
modulating hot gas reheat. In spite of this multiplicity there
are some consistent characteristics. All units have a single
circuit with a single or tandem compressor. All units use
an electronic expansion valve (EVI) and a start-up by pass
solenoid valve (SVB).
Figure 12: Typical Refrigeration Circuit for Cooling Only Unit with
Modulating Hot Gas Reheat (DPS 007–015 shown)
Figure 13: Typical Refrigeration Circuit for Heat Pump Unit with Modulating Hot Gas Reheat (DPS 007–015 shown)
Item Description
Indoor coil electronic
EVI expansion valve
Outdoor coil electronic
EVO expansion valve
CV Check Valve, size 3-15 only
REC Refrigerant Receiver
IDF Indoor fan
ODF Outdoor fan
COMP1 Inverter compressor
Fixed speed compressor
COMP3 (7½ thru 15 ton and 25-28
only)
SVB Bypass solenoid valve
RHV Reheat step valve
SVR Receiver solenoid valve
CHV Condenser step valve
Outdoor electronic
OVI expansion valve
4WV 4-way heat pump valve
OS Oil separator, size 3-15 only
Compressor Discharge Line Figure 16: Receiver on Medium Cabinet (7.5T) Heat Pump
(DPH)
“Vapor Bleed”
leading to SVR
Y-Joint connecting
COMP1 and COMP2
Hot Gas Discharge
Entering
Outdoor Coil
CAUTION!
Correct Orientation
Must Be Observed
Discharge Gas
from Compressor
Secondary
Oil Separator
Refrigerant Screen
During manufacturing, service, and repair there is always the Cooling Mode:
potential for debris to accidentally enter the sealed refrigeration Discharge Gas to
system. Filter screens are positioned around the refrigerant
circuit to prevent any possible debris from entering critical
Outdoor Coil
components; expansion valves, compressors, etc. These
screens are not bi-direction and must be installed in a specific Heating Mode:
direction if replaced. Please be aware that these screens are Suction Vapor from
not desiccant filters and provide no moisture protection for
compromised systems.
Outdoor Coil
Refrigerant Screen
Short Circuit between When configured for Standard during heating mode the EVI
will modulate to fully open and remain in this position. When
High Pressure Discharge configured for heating mode the EVI will modulate to maintain
and Low Pressure Suction the Subcooling Set-Point.
Indoor
Refrigerant
Temperature
Sensor (IRT)
Indoor
Expansion
By-Pass Valve (EVI)
Solenoid
Valve
Heating Defrost
The unit’s heating mode of operation is determined by the (DPS 003–015 ton)
control temperature and the heating setpoint temperature. The
unit enters the heating mode of operation by comparing the Defrost is a temporary and infrequent period during normal
control temperature to the heating setpoint. heating operations on Rebel heat pumps. The purpose of
defrost is to remove frost that has built up on the outdoor coil
The control temperature can be either the return temperature during mechanical heating. In heating mode the outdoor coil
or the space temperature. acts as an evaporator to “pull” heat out of the ambient air. As a
The return temperature is typically used for VAV units and the result the surface temperature of the outdoor coil is below the
space temperature is typically used for CAV units. ambient temperature and depending on conditions maybe below
freezing. During prolonged mechanical heating while the surface
The unit goes into the heating mode of operation when the
temperature of the outdoor coil is below 32ºF frost will form.
control temperature (return or space temperature) is below the
heating setpoint by more than ½ the deadband. The defrost operation is similar to mechanical cooling. In defrost
the four way valve will de-energize and the hot gas from the
For example, a standard air conditioning unit with supplemental
compressor will be forced into the outdoor coil, rejecting heating
gas, electric, or hot water heat with a heating setpoint of 68.0ºF
to the ambient, and melting any frost formed on the coil. To
and a deadband of 1.0ºF would enter heating mode if the
speed up the melting process during a defrost cycle the OA
control temperature reached 67.4ºF. When this takes place,
damper will close and the outdoor fan will de-energize. During
the heating mode of operation will begin and the 1st Stage of
this period the supplemental (gas, electric, hot water) heat will
heating operation will start.
ramp/stage up to maintain the unit’s DAT Setpoint.
Heat Pump Rebel heat pump unit’s have demand based defrost control
and will operate in defrost only as long as necessary to remove
(DPS 003–015 ton) frost from the outdoor coil.
The heating mode of operations will be slightly different for heat Charging
pump units. It is the manufacturer’s recommendation that all
Rebel heat pump units be purchased with supplemental gas, Rebel units have advanced charge management systems
electric, or hot water heat. When the control temperature drops that obsolete many common techniques for determining
below the heating setpoint by half the deadband the unit will over or under charged conditions. The charge management
energize the four way valve and initiate mechanical heating. system means that super heat and subcooling values will
float to achieve the peak real time energy efficiency possible
On heat pumps mechanical heating is the primary source of at current operating conditions (building load and ambient
heat and will always be the unit’s first attempt to meet the temperature). Rebel units also use electronic expansion valves
application’s load. After start-up the variable compressor that can not be adjusted manually. Refrigerant should never
will ramp up to meet the DAT Setpoint. If the mechanical be added or removed from the system based on the desire to
heating capacity at the ambient conditions is capable of achieve an arbitrary subcooling value. It will always be Daikin's
meeting the building load the variable speed compressor will recommendation that unit’s suspected of being over/under
stabilize at some value below its maximum speed. If the heat charged have all of their refrigerant removed, leak tested with
pump’s capacity is insufficient at the ambient conditions the nitrogen, and then re-charged based on the unit name plate.
supplemental (gas, electric, hot water) heat will be enabled and
gradually ramp/stage on to make up the capacity shortage.
Table 9: Refrigerant Charge
If the combined capacity of the heat pump’s mechanical and
supplemental heating is greater than the building load the Cooling Model Heat Pump Model
supplemental supply will ramp/stage down. The unit will always Unit Size Standard Unit Standard Unit
Standard Unit Standard Unit
seek to operate with mechanical heating as much as possible. w/ MHGRH w/ MHGRH
3C 10.5 12.9 12.0 14.4
Periodically during heating operations the unit will need to 3M 6.6 11.3
enter defrost to remove frost build up from the outdoor coil.
4C 11.1 13.5 12.6 15.0
During defrost mechanical heating will be unavailable and the
4M 6.5 11.3
supplemental heat will ramp/stage up to meet the DAT set-point.
5 15.3 18.2 16.8 19.7
6 15.3 18.2 16.8 19.7
7.5 11.1 17.8 26.0 31.2
10 20.0 25.8 40.0 45.8
12 20.0 25.8 40.0 45.8
15 24.4 30.2 46.0 51.8
3C & 4C with fin tube outdoor coils
3M & 4M with micro-channel outdoor coils
Refrigerant Screen
During manufacturing, service, and repair there is always the
potential for debris to accidentally enter the sealed refrigeration
system. Filter screens are positioned around the refrigerant
circuit to prevent any possible debris from entering critical
components; expansion valves, compressors, etc. These
screens are not bi-direction and must be installed in a specific
direction if replaced. Please be aware that these screens are
not desiccant filters and provide no moisture protection for
compromised systems.
Bypass Solenoid
The bypass solenoid (SVB) is used to “short circuit” the high
pressure compressor discharge to the low pressure suction
side during startup. This increases compressor life by reducing
the startup torque and inrush current.
If the oil balance mode fails to resolve the low oil condition, VFD Compressor Protection Unloading Control
or the fixed speed compressor was not running when the low
There are several modulating control functions that adjust the
oil indication occurred, or the VFD compressor was not part
speed control range of the VFD compressor to protect it from
of a tandemized compressor set, when the low oil indication
damage under abnormal operating conditions. The following
occurred, the unit will enter boost mode
functions are provided by the unit controller
Upon entering oil boost mode, the VFD compressor speed is
• High Pressure Unloading Control
increased to the oil boost value shown in Table 20. If the VFD
compressor is part of a tandem arrangement, the fixed speed • High Discharge Line Temperature Unloading Control
compressor is started as well. The VFD compressor runs • High/Low Discharge Superheat Control
at this condition until the optical oil sensor verifies that oil is • Condenser Coil Splitter Valve Control (For Low Ambient
present for 3 continuous minutes. Unit Controller default is set Option)
for a 10 minute max boost.
High Pressure Unloading Control
During the oil balance/boost sequence the DAT temperature is
overridden to allow the VFD compressor to continue operating The VFD compressor has an upper operating sat discharge
until oil balance/boost sequence termination. pressure limit of 575 PSIG. If the discharge pressure exceeds
575 PSIG, the compressor speed is reduced 1 rps every 10
Oil balance/boost sequences and durations are logged in the seconds until the discharge pressure is at or below 575 psig.
unit controller.
If the discharge pressure does not drop below 575 PSIG with
If low oil indication does not clear, the VFD compressor will be the VFD compressor operating at minimum speed (30 rps), the
shut down and oil level will be monitored for an additional 15 compressor is locked out on alarm.
minutes. If low oil indication still does not clear within these 15
minutes, the VFD compressor will be locked out on alarm. In addition, when the VFD compressor is operating above a
sat discharge pressure of 525 PSIG, the VFD compressor
The low oil problem is also generated and the VFD compressor maximum speed is limited to 90 rps and the minimum speed is
circuit is disabled if the oil boost sequence is initiated more limited to 30 rps.
than 4 times in a 24 hour period. If the oil balance/boost
sequence successfully restores the VFD compressor oil level A high side pressure transducer is standard on the VFD circuit
the fixed compressor stage is returned to its pre-oil balance/ allowing the discharge pressure of the refrigerant circuit to be
boost condition and normal compressor sequencing and viewed at the unit controller display.
modulation resumes If the unit controller needs to reduce the compressor speed in
order to limit discharge pressure, the action is recorded in unit
controller event log section.
VFD Compressor Emergency Stop Control Figure 31: Compressor Nameplate Information
If the VFD compressor enable output signal has been ON for
30 seconds and the controller fails to receive the VFD run
verification input, VFD Compressor Emergency Stop Control is
activated. When this function is active, VFD compressor enable
output will be turned OFF for 5 seconds and then turned
ON and ramp VFD compressor speed to 60Hz. If controller
receives a VFD run verification input, a log event is set on VFD
Emergency Stop Control. If controller fails to receive the VFD
run verification input after 3 attempts in 30 minutes, the VFD
compressor is locked out and the problem is logged.
Once active the VFD Compressor Emergency Stop Control
function remains active until one of the conditions are met.
• VFD compressor enable output signal has been ON for
30 seconds and VFD compressor status Input is ON
A. Model number
• VFD compressor is OFF B. Serial number
If the controller fails to receive the VFD run verification input C. Refrigerant
after the VFD compressor enable output signal has been ON D. Supply voltage to CDS303 frequency converter
E. Housing service pressure
for 30 seconds, the circuit is shut OFF on VFD Compressor
F. Factory charged lubrication
Emergency Stop Control alarm.
G. Compressor frequency and MaxMust trip current
Whenever this protection function becomes active a VFD
Compressor Emergency Stop Control event is recorded in the
Figure 32: Compressor Components
Event Log with date and time stamp. Whenever this protection
function returns to normal a VFD Compressor Emergency Stop
Control return to normal event is recorded in the Event Log
with date and time stamp.
Figure 37: Dual 2-Way Valve Refrigeration Schematic (Cooling Model Shown)
Daikin Tubular Heater Series Hooded and screened openings for combustion air have been
provided in the furnace(s) access door. The air opening provides
Package Heater Module unrestricted combustion air to the burners and sized such that
a minimum free area is maintained. The minimum free area is
ANSI Z83.8-2013/CSA 2.6-2013 defined as 1 in2 (625 mm2) per 4000 BTUH (2.345 kW).
WARNING The access door provides direct access to the furnace
Fire or explosion hazard. vestibule where the burners, combustion inducer fan, ignition
controls and ignition safeties are housed.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier. The vent discharge is sized such that it is equal to or larger
than the discharge area of the combustion exhaust inducer fan.
Failure to follow safety warnings exactly could result
in serious injury, death or property damage. Be sure A non-adjustable High Limit Switch will shut off the gas supply
to read and understand the installation, operation and to the main burners should the outlet air reach a temperature
service instructions in this manual. Improper installation, exceed 250°F (121°C).
adjustment alteration, service or maintenance can The cabinet supply air flow delivery package has been
cause serious injury, death or property damage. designed to provide sufficiently well distributed air flow across
Do not store or use gasoline or other flammable vapors the heat exchanger to limit temperature rise as follows:
or liquids in the vicinity of this or any other appliance. • Aluminized Steel: 1030°F (575°C)
What to do if you small gas: • 409 Stainless Steel: 1080°F (600°C)
• Do not try to light an appliance Clearance from combustibles to be no less than as listed below:
• Do not touch any electrical switch • Sides and back . . . . . . . . . . . . . . . . . . . . . . 6 in (152 mm)
• Do not use any telephone in the building • Bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 in (51 mm)
• Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 in (152 mm)
• Leave the building immediately
• Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 in (914 mm)
• Call the gas supplier immediately and follow the gas • Vent pipe to any combustible surface . . . . . 6 in (152 mm)
supplier's instructions
Do not use this package heater if any part has been under
• If you cannot reach the gas supplier, call the fire water. Immediately call a qualified service technician to inspect
department the heater and any gas control which has been under water.
7 6 3 2 1 Item Description
1 Furnace
2 Inducer Combustion Blower
3 Plate-Inducer Orifice
4 Transformer – 40 VA
11 5 Spark Igniter (2)
6 Ignition Control #1
17
7 Ignition Control #2
4 8 Gas Safety Valve #1
9 Gas Safety Valve #2
10 Gas Modulating Valve
11 Gas Modulating Control
12 Burner In-Shot (Typ)
13 Flame Roll-Out Switch (2)
14 Flame Sensor (2)
15 High Limit Temperature Switch
16 Proof of Airflow Switch
10 17 Control Relay (Typ)
8
16
14 5
12
15 13
9
WARNING CAUTION
Snow levels must be controlled to prevent moisture
Hot surface hazard. Can cause severe equipment
and air flow blockage to the furnace enclosure and
damage, personal injury, or death. Allow burner
combustion air stream.
assembly to cool before servicing equipment.
Installation
WARNING
IMPORTANT
Units equipped with gas heating must not be operated
in an atmosphere contaminated with chemicals which Connect this unit only to gas supplied by a commercial
will corrode the unit such as halogenated hydrocarbons, utility. This furnace must be installed by an experienced
chlorine, cleaning solvents, refrigerants, swimming pool professional installation company that employs fully
exhaust, etc. Exposure to these compounds may cause trained and experienced technicians. Install the gas
severe damage to the gas furnace and result in improper piping in accordance local codes and regulations of the
or dangerous operation. Operation of the gas furnace in local utility company. In the absence of local codes, follow
such a contaminated atmosphere constitutes product abuse the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the
and will void all warranty coverage by the manufacturer. CSA B149.1, Natural Gas and Propane Installation Code –
Questions regarding specific contaminants should be referred latest editions. Note: The use of flexible gas connectors
to your local gas utility. is not permitted.
WARNING
Sharp edges hazard. Can cause personal injury or death.
Sheet metal parts, self-tapping screws, clips, and similar
items inherently have sharp edges, and it is necessary that
the installer exercise caution when handling these items.
Table 16: Specific Gravity Other Than 0.60 Table 17: Pressure Drop Other Than 0.3"
Specific Gravity Multiplier Pressure Drop Multiplier Pressure Multiplier
0.50 1.100 0.1 0.577 1.0 1.83
0.60 1.000 0.2 0.815 2.0 2.58
0.70 0.936 0.3 1.000 3.0 3.16
0.80 0.867 0.4 1.16 4.0 3.65
0.90 0.816 0.6 1.42 6.0 4.47
1.00 0.775 0.8 1.64 8.0 5.15
PROPANE-AIR
1.10 0.740
PROPANE
1.55 0.622
BUTANE
2.00 0.547
Figure 50: Honeywell VR8305Q Gas Safety Control Valve Figure 51: Maxitrol M520B Modulating Valve
Used for Both Staged and Modulating Furnaces
Modulating Control
The following details the sequence of operation for the low
heat option.
1. Unit DDC controller calls for heat.
2. Furnace DDC control module receives a call for heat.
3. Furnace safety switches and DDC control are checked
for safe conditions.
4. 45 second prepurge cycle starts. Proof of airflow switch
is checked for combustion airflows.
5. Spark ignitor is activated.
6. Gas valve receives a signal to open fully.
7. Burner is ignited and runs for 20 seconds in high fire.
Note: if call for heat is interrupted during this timing, the
furnace will be locked in for the 20 seconds cycle.
8. Gas valve and induction blower motor receives a signal
to modulate burner output to match the unit discharge air
temperature setting.
Start-Up Preliminary
Close gas main.
1. Check the burner fan wheel for binding, rubbing, or loose
setscrews.
2. Check power.
3. Purge the gas lines.
4. Leak check. Using a rich soap-water mixture and a
brush, check the gas lines for leaks. Correct all leaks
before starting furnace.
Operating Procedures
Turning OFF Gas to the Appliance
DANGER
1. Set the controller to the lowest setting.
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, 2. Turn OFF all electrical power to the appliance if service
personal injury, or loss of life. is to be performed.
A. This appliance does not have a pilot. It is equipped 3. Open the control access panel.
with an ignition device which automatically lights the
burner. Do not try to light the burner by hand. 4. Turn the gas control knob clockwise to “OFF”. Do not
B. Before operating, smell all around the appliance area force.
for gas. Be sure to smell next to the floor because 5. Close the control access panel.
some gas is heavier than air and will settle on the
floor. Service
WHAT TO DO IF YOU SMELL GAS: The furnace DDC controller has diagnostic information for
• Do not try to light any appliance. troubleshooting the furnace operation. The ignition control
• Do not touch any electric switch, do not use any module has a LED light that will flash when an abnormal
phone in your building. condition occurs. See Table 21 on page 52 & Table 14 on
• Immediately call your gas supplier from a neighbor’s page 41 for an explanation of the diagnostic information.
phone. Follow the gas supplier’s instructions.
Maintenance
• If you cannot reach your gas supplier, call the fire
department. Planned maintenance is the best way to avoid unnecessary
C. Use only your hand to push in or turn the gas control expense and inconvenience. Have this system inspected
knob. Never use tools. If the knob will not push in at regular intervals by a trained and experienced service
or turn by hand, don’t try to repair it, call a qualified technician. The following service intervals are typical for
service technician. Force or attempted repair may average situations but will have to be adjusted to suit your
result in a fire or explosion. particular circumstances.
D. Do not use this appliance if any part has been under
Fuel pressure settings and control settings should be made
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of only by persons thoroughly experienced with the burner and
the control system and any gas control which has control system, and must not be tampered with by persons
been under water. without such experience.
Always replace covers on burner controls and boxes as the
1. Set the controller to the lowest setting. electrical contacts are sensitive to dust and dirt. Perform
maintenance of controls, gas valves, and other components in
2. Turn off all electric power to the appliance.
accordance with instructions contained in the manufacturer’s
3. This appliance is equipped with an ignition device which bulletins.
automatically lights the burner. Do NOT try to light the
pilot by hand. Monthly
4. Open the control access panel. Check air filters and replace if dirty.
5. Turn the gas control clockwise to “OFF”. Twice Yearly
6. Wait five (5) minutes to clear out any gas. Then, smell 1. Burner Air - Check burner fan wheel for dirt buildup and
for gas, including near the floor. If you smell gas, STOP! lint. Check combustion air intake louver and flue box/vent
Follow step “B” in the DANGER label on this page. If you for dirt buildup and accumulation of wind borne debris.
don’t smell gas, proceed to the next step.
2. Cleaning - Inspect flue tubes and combustion chamber,
7. Turn the gas control counter-clockwise to “ON”. clean as required. Keep burner vestibule clean. Dirt and
8. Close the control access panel. debris can result in burner air blockages.
12. If the appliance will not operate, refer to “Turning Off Gas Gas Train - Check all valves, piping and connections for
to the Appliance”, and call a qualified service technician. leakage. Inspect and clean flame rod, ignition electrode, and
burner manifold.
Condensate Pan/Drain - Check pan and drain for
accumulation of debris.
DPS 003–015 (only) Ignition Control Module for Staged Gas Furnace
Figure 52: Typical Staged Gas Furnace Electrical Schematic with Sensor
Table 21: LED Indicator and Fault Conditions Figure 53: Ignition Control Wiring
L1
Indicator Fault Condition INDUCER
120/240 VAC IND
Steady Off No power or control hardware fault MAIN
GAS VALVE
MV
Steady On Power applied, control OK
PRESSURE SWITCH
PS2
1 Flash Combustion fan motor energized, pressure switch open
PSI
2 Flashes Combustion fan motor off, pressure switch closed
T'STAT LIMIT
W
3 Flashes Ignition lockout from too many trials
FS
Ignition lockout from too many flame losses within single
4 Flashes call for heat R
1016-4XX
5 Flashes Control hardware fault detected X
120VAC 24VAC
C
HIGH
VOLTAGE
COM
BURNER
SENSE
SPARK
GAS
DPS 003–015 (only) Ignition Control Module for Modulating Gas Furnace
Figure 54: Typical Modulating Gas Furnace Electrical Schematic with Sensor
CAb
400 Furnace size in 1000’s of BTU, for example, 400 kBTU.
6AS or LP
1.01 Software version, for example, v1.01
Off OFF Mode System Idle - Control board has power, no faults found, no call for heat.
System is purging the heat exchanger – No gas on, no flame, inducer runs for the specified purge
PVr PURGE Mode timings. Purge cycles occur immediately before and after each burner operation.
System is initiating burner operation – Igniter energized, modulating valve moved to ignition setting, gas
I9n IGNITION Mode on. Maintained for the trial-for-ignition period and the five second flame stabilization period.
HEA WARM-UP Mode Period between Ignition and Run – System checks completed before modulation control begins.
System has had a failed ignition attempt or has lost flame during burner operation and is beginning
rEt Ignition Retry another ignition cycle.
Table 26: 300/450/600 MBH Staged Ignition Control Troubleshooting Guide (UTEC 1016 Ignition Board)
LED Indicator System Status Fault Description Possible Causes and Corrective Action
Steady ON System Normal N/A N/A
1. Check 120V is being supplied to heater transformer.
LED OFF Lockout LED is OFF 2. Check that 24 VAC is being supplied by transformer. Replace transformer if not being
supplied 24 VAC.
1. Check air pressure switch hose and hose connection between switch and fan.
Combustion air pressure switch contact 2. Check reset switch is not tripped for rollout switch(s).
1 Flashes Lockout is open with inducer fan running. 3. Check high limit switch is not open
4. Replace pressure switch if contact does not close when fan is running.
1. Check wiring between PS1 and PS2 on ignition control board for correct connection
Combustion air pressure switch contact and proper wiring.
2 Flashes Lockout is closed when inducer fan is not 2. Check pressure switch functions correctly with and without pressure.
running.
3. Replace pressure switch if fails to function correctly.
1. Verify gas supply is present.
2. Verify gas safety valve is working correctly.
Ignition locked out from too many 3. Verify gas manifold pressure is adequate and correct.
3 Flashes Lockout ignition attempts 4. Check spark igniter is not cracked or dirty. Check spark igniter wire is not covered
with oil and debris or cracked. Check wire is connected correctly.
5. Check flame sensor wiring. Check to see if flame sensor is grounded.
1. Check pressure switch hose for leaks or poor connection
2. Check for condensate in pressure switch hose.
Ignition lockout from too many flame
4 Flashes Lockout 3. Check pressure tap on combustion blower and combustion pressure switch for
losses within a single heat.
blockage.
4. Check functionality of combustion inducer fan.
5 Flashes Lockout Control hardware fault detected 1. Change ignition board.
601
T01
TB10 602A TB10
602B TB10
602 115VAC
101 102 GND
T3
603 Class II
40VA
604A 604B TB10
604 24VAC
GND
605
606
Ignition Module #1
IM01
607
UTEK 1016-575
604A 608A
608 X COM
Gas Safety Shutoff Valve #1
GSSV01
609
HW VR8305Q Vlv (for NG)
HW VR8205Q Vlv (for LPG)
610 C Air Pressure Switch
PS01
611A 611B 611C
611 C PS1
612A 612B
612 2/A HI LO MV
Roll-out Roll-out
613
Switch #2 Switch #1
614B TS04 614C
TS03
614 PS2
615
616
Flame Sensor
617A 617B FS01
617 1/A W FS
618
Hi-Limit Aux Hi-Limit
619 Switch Switch Spark Igniter
620A
TS02 TS01 620D SI01
620B 620C
620 R/A R HV
(Daikin P/N 910172859; includes ignitor and wire)
remotely
621 mounted
Inducer Fan Motor
IFM01
622
624
Figure 56: Typical 2 Stage Control Gas Furnace, 450/600 MBH — DPS 016–028 shown
600
601
T01
TB10 602A TB10 TB10
602B
602 115VAC
101 102 GND
T3
603 Class II
40VA
604A 604B TB10
604 24VAC
GND
605
606
Ignition Module #1
IM01
607
UTEK 1016-575
604A 608A
608 X COM
Gas Safety Shutoff Valve #1
609 GSSV01
HW VR8305Q Vlv (for NG)
HW VR8205Q Vlv (for LPG)
610 C Air Pressure Switch
PS01
611A TB10 611B 611C 611D
611 C PS1
103
612A 612C 612D
612 2/A HI LO
TB10
105 Gas Safety Shutoff Valve #2 Roll-out Roll-out
613 GSSV02 Switch #2 Switch #1
HW VR8305Q Vlv (for NG)
HW VR8205Q Vlv (for LPG) TB10 614A 614B TS04 614C
TS03
614 C MV PS2
104
615A
615
612B 616A
616 HI LO
Flame Sensor
617A 617B FS01
617 1/A W FS
618
624
601 T01
TB10 602A 602B TB10 TB10
602 115VAC
101 102 GND
T3
603 Class II
40VA
604A 604B
604 Aux Hi-Limit Switch 24VAC
Hi-Limit Switch 1R
TB10 605A TS01 605B TS02 605C TB10 604E TB10
605D
605 103 A1 A2 105 GND
X COM
104 106
611
Gas Safety Shutoff Valve #1
GSSV01
612
2R-1
613B
602D
613A 613C
613 PS1
11 14
C
614
C
HW VR8305Q Valve (for NG)
615 HW VR8205Q Valve (for LPG)
616A HI 616B
616 2/A LO MV PS2
617
610D
618 Flame Sensor
FS01
619A 619B
619 1/A W FS
620
626
630 C
HW VR8305Q Valve (for NG)
631 HW VR8205Q Valve (for LPG) Flame Sensor
632A 632B 632C FS02
632 2/B HI LO MV FS
633
639
640
601
TB10
602 GND
T01
TB10 603A 603B TB10
603 101
115VAC
102
T3
604 Class II
40VA
605A 605B
605 Aux Hi-Limit Switch Hi-Limit Switch
24VAC
2R TB10
TB10 606A TS01 606B TS02 606C 606D 606E TB10
606
103 A1 A2 108 GND
GSSV01
613
614 C
615A 615B
615 C PS1
616
HW VR8305Q Valve (for NG)
617 HW VR8205Q Valve (for LPG) 3R-1 4R-1
638
T9 5R
639A T4 (NO) 639B 639C TB10
639 (Mod)
A1 A2 109
-
640
641
1R
642A T12 T7 642B 642C TB10
642 +/A
(+) (NO) 110
A1 A2
643
605A
644
645A T13 645B TB10
T1
645 - /A
(-) (com) 110
646
647
Gas Safety Shutoff Valve #2
648 GSSV02
Ignition Module 2
649 C UTEC 1016-578
650A 650B
C COM
650
If the 10th digit of the model number is a “W”, the rooftop unit
was furnished with a factory installed hot water coil (Example:
DPS010AHCW). The hot water coil comes with a piping Field Installed Freeze Stats
vestibule for field supplied and installed control valve and Field installed freeze stats can be added. The freeze stat
piping. The coil is furnished with ODM copper connections. contacts should be wired to the MicroTech III digital input X5
The Rebel commercial rooftop units are available with a low as shown in . MicroTech III will turn the fans OFF, shut the
heat (one row coil) or a high heat (two row coil) configuration (3 outdoor air damper, open the valve and issue an alarm when
rows also offered on DPS 016–028). the normally closed contact opens between terminals 111 and
Hot water coils are not recommended for use with entering 112.
air temperatures less than 40°F (4°C). No control system can Field Installed Freeze Stat Schematic
guarantee a 100% safeguard against coil freeze up. Glycol TB2 TB2 EXPD
solutions or brines are the only freeze-safe media for operation 160A
111
MJ
Freezestat 112
160A
DI1
Table 28: Heating Capacity and Water Pressure Drop – Hot Water Coils
Unit MBH GPM WPD Connection Size
3 61.4 6.1 1.0 1.375 Sweat
4 72.9 7.3 1.4 1.375 Sweat
5 82.6 8.2 1.7 1.375 Sweat
6 91.6 9.2 2.2 1.375 Sweat
7.5 149.7 15.0 3.1 1.375 Sweat
10 176.9 17.8 4.2 1.375 Sweat
12 195.9 19.6 5.1 1.375 Sweat
15 221.4 22.1 6.4 1.375 Sweat
16 347 35.5 0.7 1.375 Sweat
18 376 38.4 1.2 1.375 Sweat
20 403 41.1 1.3 1.375 Sweat
25 464 47.3 1.4 1.375 Sweat
28 497 50.7 1.6 1.375 Sweat
Nominal airflow, 60°EAT, approximately 180°–160° water. WPD does not include a field supplied valve pressure drop. 2-row performance shown, 1-row coil also available.
System Description
When a unit is equipped with an optional enthalpy wheel, energy Purge - A small segment of supply air defined by the gap
recovery is provided by drawing outside air across half of the between the inner seal on the outdoor air edge of the center
enthalpy wheel and drawing exhaust air across the other half. post and the supply air edge of the center post. The purge angle
Latent heat and sensible heat are transferred from the hotter is adjustable. The purge captures the small amount of supply air
and moist exhaust air to the colder and dry outside air during captive in the enthalpy wheel when the wheel moves from return
winter conditions. Latent heat and sensible heat are transferred to supply and routes it to return to minimize cross contamination.
from the hotter and moist outside air to the cooler and dry Return air - The air stream that is returned from the building.
exhaust air during summer conditions. Energy recovery control Return air becomes exhaust air after going through the enthalpy
consists of starting and stopping an exhaust fan, modulating wheel.
the speed of the exhaust fan, starting and stopping an enthalpy
wheel, optionally controlling the speed of the enthalpy wheel Rotor - The part of an enthalpy wheel that performs the energy
and opening and closing a set of bypass dampers. The outdoor exchange and consists of the wheel media, hub, spokes and
dampers are controlled in the normal manner. band.
Sensible heat - Sensible energy, in the context of enthalpy
Definitions
wheel discussion, is the work done by the enthalpy wheel to
The following are descriptions of various components related transfer heat from one air stream to another. Sensible work is
to the enthalpy wheel construction (Figure 60): accompanied by temperature changes in the air stream.
Bearing, external - The wheel and bearing rotate on the shaft, Supply air - The air stream that is supplied to the building
no field lubrication is required. space. Supply air is outdoor air that has been run through the
Brush seal - The seal used for both the circumferential seal enthalpy wheel.
and the inner seal in the cassettes. They are constructed of
nylon brush and configured to seal against the enthalpy wheel Arrangements
band in the case of the circumferential seal, and against the
Two arrangements are offered for the enthalpy wheel:
wheel face in the case of the inner seal. These seals are full
contact seals, have an integral clip, and they are clipped to the 1. Single enthalpy wheel with economizer and bypass
cassette face panel cutout (circumferential) or to the (inner) (Figure 60). This arrangement is available for all units.
post. 2. Single enthalpy wheel without economizer (100%
Cassette - The steel structure that houses the rotor. Cassettes outdoor air unit).
are of punched sheet metal panel construction.
Wheel Construction
Enthalpy wheel - A generic name for an energy conservation
wheel. The term “enthalpy” refers to an air stream’s total Your Daikin enthalpy wheel is delivered completely assembled
energy (temperature and humidity level). and ready to run. The wheel is built to provide many years of
trouble free service following proper installation and performance
Exhaust air - The air stream that is exhausted to the outside. of the minimal maintenance requirements.
Exhaust air is building return air that has been run through the
enthalpy wheel.
Heat wheel - Synonymous with an enthalpy wheel, energy
conservation wheel, or total energy recovery wheel. Some heat
wheels are sensible only wheels and should not be confused
with Daikin total energy recovery wheels.
Hub - The center support of an enthalpy wheel.
Latent energy - Latent energy, in the context of enthalpy wheel
discussions, is the work done by the wheel to transfer moisture
from one air stream to another. Latent work is accompanied by
humidity changes in the air streams.
Media - The chemical composite part of the enthalpy wheel
which actually performs the latent and sensible exchange.
Outdoor air - The air stream that is brought in from the outside.
Outdoor air becomes supply air after going through the enthalpy
wheel.
(1) Currently, only the Over-Under configuration is offered on Daikin rooftop systems and air handlers.
Saturated
Plenum Exhaust Fan Air
draws a negative pressure NOTE:
Maintain the pressure gradient to Frost
prevent cross contamination from the Conditions
Exhaust to Outside Supply Air Saturated
Temperature
Humidity
Figure 62: Purge Detail Ratio
No Frost
Adjust purge in this Conditions
direction to decrease
OUTSIDE AIR capacity and increase
purge
Saturated
Air
Dry Bulb
EXHAUST AIR
Variable Speed Frost Prevention Enthalpy wheel speed will be controlled by exhaust
temperature measurement.
When there is a threat of frost on the enthalpy wheel, the
wheel is slowed down so that less enthalpy transfer occurs Slide-Out Wheel
and frosting of the wheel is avoided. Frosting can occur on
The wheel can be pulled out to facilitate cleaning and servicing
the enthalpy wheel when the exhaust air leaving the wheel is
(Figure 64). Unplug the control wires before sliding the wheel
saturated. This condition occurs when two lines intersect on
out of position.
a psychrometric chart, and it does not occur when these two
lines do not intersect (see Figure 63).
Figure 64: Slide-Out Energy Recovery Wheel
Energy Recovery Exhaust Hoods
Units with the optional energy recovery section have one
or two (depending on model) exhaust hoods. Each hood is
shipped in three pieces, consisting of one top and tow sides.
Install exhaust hood over the barometric relief dampers by
installing tow sides first and then install the top.
Transmitter
Connector
• Go into the MicroTech III keypad / display [see OM 1141 5. At the Microtech III controller enter a level 2 password of
for detailed instructions] 6363 and click on “About This AHU” to verify if code 101
is being used (310 for
• On the main menu, go to commission unit
Maverick). If any other
• Go to SF [or RF/EF] set up menu codes are being used,
• find Max SAF [or EAF] RPM please consult with
• Enter the desired maximum RPM McQuay Warranty Service
group for technical
Table 32: ECM Motor Fan Size Maximum RPM support.
16. The controller will revert back to the “ECM Config” menu
but now the SF MB Status will show fault while the RF
MB Status will show ok. In a smoke situation, the field wired smoke detector would
eliminate 24VAC to the DI4 terminal at the Microtech controller
17. Hit the middle rectangular button to go back to the main
issuing an emergency fault at the Microtech keypad. The entire
menu.
unit would shut down in which case the field would need to
18. Click on the “Unit configure the NO to close upon a smoke shutdown and allow
Configuration” menu and the return/exhaust fan to run. Setting the speed of the drive
set the SAF type back to during ventilation override is described below.
the original setting.
Setting the RF/EF max vent speed:
1. After entering the
19. Scroll up and set “Apply controller password 6363,
changes” to yes. click on “Commission Unit”
20. Reset MMPs for the supply and energy recovery drive to
observe ER MB Status and SF MB Status show “OK” 2. Scroll down and click on
“RF/EF Set-Up”
3. Scroll down to
“MaxVentSpd” and select
the desired speed for the
ECM during a smoke
shutdown.
Unit Options
VOLTAGE PRI.
460V LINE
Wiring Diagrams
Figure 72: Typical CAV_VAV 208-230 VAC Wiring (1 of 4) — DPS 003–006 shown
101
DS1
PB1
102 208V, 3 Phase, 60Hz
L1 T1 103B
L1
103 CUSTOMER L2 T2 104B
SUPPLIED L2
104 POWER
L3 T3 105A
L3
105 Wire for CW
phase monitor
MMP1
106 DS6 PB1 PB1
GLG1 103A L1 T1 110A
107A L1 T1
107 T1 T1 EVB208-I EVB
104A L2 T2 110B
108A L2 T2 108B (350)
108 T2 T2 1
FILTER
T6 X77A
208V 109A L3 T3 109B
109 2kVA T3 T3 3
H1 H2 EVBF
GND2
110
112D
112A
112C
112B
111
120V
X1 X3 A4PPWR-E
114A 114B M1F CMP1
112
CMP1-PE U U
113A NB
114B U
113 REC1 L1A L2A L3A E1
FILTER
1
F6C
2 114D LN-H LN-N A4P V
114C V V M
114 3
G (350) W W GND
115A
LD-H LD-N 114B W
115
TB2 G
OF1F
U OFN1
116 BLK U
1 NB
PC0615-2(A)
V V M
X501A
117 WHT
2
3
FILTER
MMP10 INDOOR_FAN W W CTRL
118 PB1 RED
IFN-PI NB 3
119A L1 T1 119B 1 L1
119 T1 1 YEL
P1 1
2 BLU
120A L2 T2 120B 2 L2 M 2
X502A
120 T2 3 ORG
3 LR1 3
L3 T3 3 L3 4 PNK
121A 121B 4
121 T3 P2 5 GRY
5
GND10 4
122A GND X504A X5A
122 1 2 1 2 N3 P3
123
126
T2
126A L2 T2 126B 2 L2 M
3
127 127A L3 T3 127B 3 L3
T3 A5PF
FILTER
GND51 4
128 128A GND
131A
131B
131E
131F
WHT
A4/41-I
129
A4/5-I
BLK
A4/7-I
130
MMP3 CMP3 OF2F OFN2
PB1 CMP3-PE U U
131 M3 NB BLK NB
1 2 1 2 N1 P1 1
132A L1 T1 132B L1 T1 132C U
T1
FILTER
V
132 X3A X5A WHT V M
X1A
2
FILTER
T2
133A L2 T2 133B L2 T2 133C V M 3
133 RED W W CTRL
3 3
134A L3 T3 134B L3 T3 134C W GND A5P
T3 PC0715-2(A)
134 1 YEL
1
M3F 2 BLU
2
135 3 ORG
X2A
3
4 PNK
X4A 4
136 5 GRY
1 2 5
137
BLK
138 A5PJMP-I
137A
139
140
141
142
PB1
143
T1
144
R-CCH1 PL10 CCH1 PL10
1 9 CCH1-I 2 x1 x2 1 CCH1-I
145B 145C 145A
145 T3
NB
(305)
146
PL11 CCH3 PL11
M3 CCH3-I 2 1 CCH3-I
145B 22 21 147A x1 x2 145A
147
NB
(307)
148
149
PB1 F1A
150A 1 2 153A
150 T1
6A
151
F1B
T1
152A 1 2 153B 208V PRI.
152 T3 500VA
6A H1 H2
153
154
TB1 F1C X1 X3 TB1
155 1 159A 2 1 155A 155B 3
120V SEC.
1 7A 3
156
1 3
157 3G
155B
158
159A 155B
159 1 2 T2B
120V
CLASS 2
160
120V_H 75VA 120V_N
161 (202) (202)
24V
(302) TB1 3 4 TB1 (302)
(333) 4 162A 162B 5 (333)
162
5
163 5G 162B
T2B_24V T2B_N
164
(248) (248)
(354) (355)
Figure 72 continued: Typical CAV_VAV 208-230 VAC Wiring (2 of 4) — DPS 003–006 shown
(160) (160)
201
120V_H 120V_N
202
203
159A 155B
204 1 2 T2A
120V
CLASS 2
205 75VA
TB1 24V TB1
206 6 3 4 7
207A 207B
207 6 7
6 7G 207B
208
MCB
207A
209 G-24V 207B
GO-24C
TIME CLOCK OR
210 TENNANT OVERIDE
TB2 TB2 207B
T_CLOCK R3-4
207A 101 102 211A
211 NB DI3
212 (345)
RA Smoke SA Smoke Emergency A+ A1+ /
Mod Bus (358)
Detector Detector Off
213 TB2 TB2 TB2 TB2 Connection (346)
SD2-E SD2 SD2-E 104 R63 B- B1- /
103 105 106 (359)
207A 207A 214A MJ MJ 214A 214B 301G Mount Sensor
214 DI4 RS485 (347)
9 10 9 (244) 5 GND1 / In Supply Air Duct
(359)
PC7 R63 DAT-I DAT
215
1 2 216A 216B WHT
DI1 AI1
216 PC5 12 (244) 8
BLK NB
217A 1 3 217B M
DI2
217 DRN 301G
217A PL1 RAT-E RAT
218 M RAT-I
WHT 1 RED
CBL217-I TB8 AI2
219 BLK 311 219C
SPS1 TB1 + 24VDC 219B BLK 2 BLK NB
M
MB TB1 - WHT TB8 301G
220 X6-AI DRN 3 DRN
301G 302
DRN
OAT
221 OAT-I
BLK
CBL221-I
222 BLK NB
SPS2 TB1 + AI3
BLK
MB TB1 - WHT
223 X8-AI
301G
DRN
224
CBL225-I
TB2 WHT TB2 S ZNT1
225 HUM1 219C X3-AI NB
24VDC OVERRIDE
NB 131 120
226A 226B BLK
226 OUT X5-AI M
126 TB8 303 C
Humidity 227A 121
Sensor COM M DRN
227 127
}
121G
228 CBL229-I
WHT TB2
LCT LCT-E PL2 LCT-I X4-AI DISCHARGE AIR
229 Leaving Coil RED 1 WHT 132 TEMPERATURE
X2-AI BLK
Temperature EXTERNAL RESET
230 NB BLK 2 BLK 133
M DRN
DRN 3 DRN 301G
}
231 CBL232-I 121G
WHT TB2
X1-AI
232 CO2/MIN OA
124
BLK /OA FLOW
233
125
DRN
234
121G
NO NC
241 OAE-E OAE-I
242A 242B 2 242B 13 14
RAE + + 1
(311)
242 242C 207B 3 207B 207B
S SR COM
RAE-E
243 R63
DHL
NO NC
249 NB
PL5 4WV-E 4WV 4WV-E PL5 4WV-I
DO4 DO4 4WV-I 1 2
250 250A 250A 1 2 162B 162B
251 NB
SVB-I PL8 SVB PL8
C3-4 DO3 DO3 SVB-I
252 162A 252A 1 1 2 2 162B
PTS-I NB
253 WHT
PTS S X1
NB BLK 254A
254 - M
TB8 304 R-HP1
RED DO1
+ +5V / (259) DO1
255 255C 12 8 RED
DRN 301G 255 / (354)
PTD-I (303)
256 PTD BLK C1
- WHT
NB 256 / (354)
WHT
257 S X2 SRT
SRT-I
RED BLK
+ +5V / (259) X6
258 301G TB8 TB8
DRN
(255) 305 255A 258B 307 BLK NB
/ +5V +5VDC M
259 DRT1 (258)
DRT1-I
BLK DIP SWITCH
X3
260 ON
NB TB8 DFT
BLK 260A OFF
M DFT-I
261 306 1 2 3 4 5 6 BLK
SW6 MUST
DRT3 NB
262 DRT3-I BE ON BLK
BLK X7
WHEN LAST
263 NB BLK
X4
264
Figure 72 continued: Typical CAV_VAV 208-230 VAC Wiring (3 of 4) — DPS 003–006 shown
(160) (160)
301
120V_H HP1 120V_N
PL4 NB PL4 R-HP1
NO NC
302 HP1-I 1 2 HP1-I
159A H C 303A 13 14 155B
(307)
(255)
303
MCB
(145)
304 R-CCH1
NO NC
C1 DO1 DO1B
159A 305A 13 14 155B
305
HP3
(132) (147)
306 PL3 NB PL3 R-HP1 M3
HP3-I 2 HP3-I 307A DO2
NO NC
1 H C 9 5 C2 DO2B A1 A2
159A 307B 307C 155B
(133)
(134)
307
(303)
308
313
314
315
316
317
318
319
320
HEAT1 HEAT-E HEAT-I
321 PL19 PL15
GRN GRN
HEAT-E G
3 6
322 HEAT-I PL19
RED 4 RED WHT WHT
L1 L2
323 PL15 1 2 5
EXPD
HEAT-E
324 HEAT-I 1 PL18
WHT WHT
X5-AO +
325 PL15 3
RHV1
WHT 328A
W - 328B
M 301G NB
328 GRN 328C 330A
G -24V
RED 329A 330B
329 R CN2 +24V
3 4
CHV-I 24V
330
BLK 328A T7
CLASS 2
331 WHT 327A
120V
CHV1 1 2
GRN 328C
332
159A
155B
RED 329A
333
120V_H 120V_N
334 (160) (160)
335
336
337
338
339
340
341
{
344 TB2 WHT
+
128 CBL345-I
345 Bacnet MSTP BLK WHT
- A1+ /(212)
Building COM BLK
129 B1- / (213)
346 RED
REF
DRN
130 DRN GND1 / (214)
347
130G A2+ /(361)
348 EVBJMP-I
WHT
B2- / (361)
349
GND2 / (362)
EVI EVI-E
350 ORG 1 5 WHT A4P
1 + - GND
RED 2 4 BLK 1 3 EVB/88-I (112)
2 A4/4-I
351 YEL 3 BRN WHT MODBUS 351E
X86A
3 3 X89A 1 1 1 1
EVI BLK 2 RED
ACS3
ACS1
X88A
4
X4A
NB 4
352 GRY 5 1 GRN EVB BLK 352B
5 2 2 2 2
EVO EVO-E (107) A4P-X6A-I
353 ORG IFB 255 A4P-X6A-E
1 5 WHT 256 PL17
1 / T2B_24V IFB-I
RED 2 4 BLK (163) 162A 354A (255) (257) WHT 1 WHT
2 3 3
X87A
24VAC
16V
354 YEL BRN
TN2
3 3 DIP SWITCH
FILTER
ON K SD 24
BLK 4 2 RED (163) 1 GND 2
NB 4 X79A X80A
355 GRY 5 1 GRN 1234 DIP SWITCH
5 1 1 2 RED 3 RED
2 2
1
356 1234 IFBF
357 IFN_MOTOR
IFN-CI NB
WHT 1
358 (212) / A1+
BLK 2
(213) / B1-
359 DRN
(214) / GND1
360 EXH_MOTOR
EXH-CI
WHT 1 NB
BLK
BLK
BLK
(348) / A2+
BLK
361 BLK 2
IRT-E ORT-E (349) / B2-
DRN
362 (349) / GND2
364
T7
GND2
PB1 A5P
GND51 GND10
OAT-I - 62" EVB
A4/4-I - 59"
PL17 (A4P-X6A) - 0"
F6C EVB/88-I - 59"
R-CCH1 OAER A4P-PI - 59"
M3 EVB-230-I - 59"
IFN-PI - 3"
IFN-CI - 3" T2B EVB-208-I - 59"
Short Red - Air IFB
DS1
Pressure Tube - 10" F1A F1B F1C
H X
www.DaikinApplied.com
R63 R-HP1
208/230V INVERTER PANEL
T2A T1
A4P
SPS2 SPS1
DS6
Magnesense Magnesense
F1A F1B F1C
DHL REC1 H T6 X
81
CHV1 Valve, Condenser Coil PTD Discharge Refrigerant Pressure Sensor
Comm Mod. Communication Module (BACnet, Lonworks, ...) PTS Suction Refrigerant Pressure Sensor
D3 DIII-NET Communication Gateway PVM1 Phase Voltage Monitor
DAT Temperature Sensor, Discharge Air R60 Energy Recovery Face and Bypass Damper Relay
DFT Defrost Temperature Sensor R63 Relay, Duct High Limit Switch
DHL Duct Hi-limit, Switch RAE Enthalpy Sensor, Return Air
DRT1,3 Discharge Refrigerant Temperature Sensor RAT Temperature Sensor, Return Air
DS1 Disconnect Switch, Unit Power R-CCH1 Crankcase Heater Relay
DS6 Disconnect Switch, Powered GFCI Receptacle REC1 Receptacle, GFCI
EVB Expansion Valve Board RES3,4 Resistor
EVBF Expansion Valve Board Electrical Noise Filter RHB1 Reheat Board, Hot Gas
EVI Indoor Expansion Valve R-HP1 High Pressure Compressor 1 Relay
EVO Outdoor Expansion Valve RHV1 Valve, Reheat Coil
EXPB,D Expansion Control Board SD1/SD2 Smoke Detector, Supply Air/Return Air
F1A,B Fuse, Control Circuit Transformer (T1), Primary SHS1 Space Humidity Sensor
F1C,D Fuse, Control Circuit Transformer (T1), Secondary SPS1 Static Pressure Sensor, Duct
F4A,B,C Fuse, 460V 3-Phase Transformer (T4), Primary SPS2 Static Pressure Sensor, Building
F6C Fuse, Powered GFCI Transformer (T6), Secondary SRT Suction Refrigerant Temperature Sensor
HEAT1 Heater Module SVB Refrigerant Bypass Solenoid Valve
HL Hi-Limit Switch, Gas Heat SVR Refrigerant Receiver Solenoid Valve
HP1,3 Hi-Pressure Switch, Refrigeration Circuits 1, 3 T1 Transformer, Main Control
IFB Interface Board T12 575/460V Primary Power Transformer
IFBF Interface Board Electrical Noise Filter T1F Main Transformer Electrical Noise Filter
IRT Indoor Refrigerant Temperature Sensor T2A,B Transformer, Control Input (115/24VAC)
LCT Temperature Sensor, Leaving Coil T4 Transformer, 230V Single Phase (460/397VAC)
LR1 Compressor Line Reactor T6 Transformer, Powered GFCI Receptacle (Line/115VAC)
Field Wiring
M1F Compressor 1 Electrical Noise Filter T7 Transformer, Reheat Control Board (115/24VAC)
M3 Contactor, Compressor 3 TB1 Terminal Block, Internal Power Distribution
Figure 72 continued: Typical CAV_VAV 208-230 VAC Wiring (4 of 4) — DPS 003–006 shown
Factory Wiring MCB Main Control Board TB2 Terminal Block, Field -24V
MJ Mechanical Jumper TB8 Terminal Block, Internal Signal Distribution
Factory Terminal MMP1 Manual Motor Protector, A4P Board VFD60 Variable Frequency Drive, Energy Recovery Wheel
MMP10 Manual Motor Protector, Supply Fan
Field Terminal MMP3 Manual Motor Protector, Compressor 3
MMP51 Manual Motor Protector, Exhaust Fan
MMP60 Manual Motor Protector, Energy Recovery Wheel
Plug Connection
Figure 73: Typical CAV_VAV 460 VAC Wiring (1 of 4) — DPS 003–006 shown
101
DS1
PB1
102 460V, 3 Phase, 60Hz
L1 T1 103B
L1
103 CUSTOMER L2 T2 104B
SUPPLIED L2
104 POWER
L3 T3 105A
L3
105 Wire for CW
phase monitor
MMP1
106 DS6 PB1 PB1
GLG1 T4-I
103A L1 T1 110A F4A 2
107A L1 T1 107B 1 110B
107 T1 T1
104A L2 T2 110C
FILTER
108A L2 T2 F4B 2
108B 1 110D
108 T2 T2
460V T6 F4C 1
109A L3 T3 109B 2 110E
109 2kVA T3 T3
H4 H2 H3 H1 T4F 0.5A L1 L2 L3 T4
110 1290VA
111
120V
114A X1 X2 114B TB1 T1 T2 T3 N TB1
112 8 11
113B 113A
114B 11
113 REC1
F6C
116B
1 2 114C LN-H LN-N
114
G CCH_230V / (144) (145) / CCH_N
LD-H LD-N 114B
115
TB2 G
TB1 TB1 113A EVB
9 10 3
116 116A 116B (350)
1 X77A
117 EVB230-I
120C
120A
116A
113A
120B
120 T2
120D L2 T2 120E 2 L2 M A4P-PI
3
121A L3 T3 121B 3 L3
121 T3 3 2 1 1 3
GND10 4 X10A X1A
122A GND
122
A4P
LR1-I PC0702-1(A) M1F CMP1
123 CMP1-PE U
124A 124B U NB
1
P1
124 MMP51 EXH_FAN1
FILTER
125A V V M
X11A
PB1 EXH-PI LR1 2
NB
125 L1 T1 1 L1 3
125C 125D P2 W W GND
T1 125B X41A X5A 126A
1 2 1 2 N3 P3 3
126
T2
126B L2 T2 126C 2 L2 M
3
127 127A L3 T3 127B 3 L3
T3 A5PF
FILTER
GND51 4
128 128A GND
131A
131B
131E
131F
WHT
A4/41-I
129
A4/5-I
BLK
A4/7-I
130
MMP3 CMP3 OF1F OFN1
PB1 CMP3-PE U U
131 M3 NB BLK NB
1 2 1 2 N1 P1 1
132A L1 T1 132B L1 T1 132C U
T1
132 X3A X5A FILTER WHT
V V M
X1A
2
FILTER
T2
133A L2 T2 133B L2 T2 133C V M 3
133 RED W W CTRL
3 3
134A L3 T3 134B L3 T3 134C W GND A5P
T3 PC0511-1(A)
134 1 YEL
1
M3F 2 BLU
2
135 3 ORG
X2A
3
4 PNK
X4A X51A 4
136 N2 P2 5 GRY
1 2 1 2 5
137
138
142E
142F
WHT
139
BLK
A5/51-I
142D
142C
A5/4-I
140
141 OFN2
OF2F NB
142 U U
BLK
1 2 1 2 N1 P1 1
FILTER
V
143 X3A X5A
WHT V M
X1A
2
(114) / CCH_230V 3
144 W W CTRL
PL10 PL10 RED
R-CCH1 CCH1 3
1 9 CCH1-I 2 x1 x2 1 CCH1-I A5P+
113A 145A 113B PC0511-2(A)
145 (114) / CCH_N
NB 1 YEL
(305) 1
146 2 BLU
PL11 CCH3 PL11 2
M3 CCH3-I 2 1 CCH3-I 3 ORG
X2A
149 BLK
PB1 F1A A5PJMP-I
1 2 149A
150A 153A
150 T1
4A
151
F1B
460V PRI. T1
152A 1 2 153B
152 T3 500VA
4A H1 H3 H2 H4
153
154
TB1 F1C X1 X4 TB1
155 1 159A 2 1 155A 155B 3
1 120V SEC. 3
3A
156
1 3
157 3G
155B
158
159A 155B
159 1 2 T2B
120V
CLASS 2
160
120V_H 75VA 120V_N
161 (202) (202)
24V
(302) TB1 3 4 TB1 (302)
(333) 4 162A 162B 5 (333)
162
5
163 5G 162B
T2B_24V T2B_N
164
(248) (248)
(354) (355)
Figure 73 continued: Typical CAV_VAV 460 VAC Wiring (2 of 4) — DPS 003–006 shown
(160) (160)
201
120V_H 120V_N
202
203
159A 155B
204 1 2 T2A
120V
CLASS 2
205 75VA
TB1 24V TB1
206 6 3 4 7
207A 207B
207 6 7
6 7G 207B
208
MCB
207A
209 G-24V 207B
GO-24C
TIME CLOCK OR
210 TENNANT OVERIDE
TB2 TB2 207B
T_CLOCK R3-4
207A 101 102 211A
211 NB DI3
212 (345)
RA Smoke
Detector
SA Smoke Emergency
Detector Off Detail A Mod Bus
Connection
A+ A1+ /
(358)
213 TB2 TB2 TB2 TB2 (346)
SD2-E SD2 SD2-E 104 R63 B- B1- /
103 105 106 (359)
207A 207A 214A MJ MJ 214A 214B 301G Mount Sensor
214 DI4 RS485 (347)
9 10 9 (244) 5 GND1 / In Supply Air Duct
(359)
PC7 R63 DAT-I DAT
215
1 2 216A 216B WHT
DI1 AI1
216 PC5 12 (244) 8
BLK NB
217A 1 3 217B M
DI2
217 DRN 301G
217A PL1 RAT-E RAT
218 M RAT-I
WHT 1 RED
CBL217-I TB8 AI2
219 BLK 311 219C
SPS1 TB1 + 24VDC 219B BLK 2 BLK NB
M
MB TB1 - WHT TB8 301G
220 X6-AI DRN 3 DRN
301G 302
DRN
OAT
221 OAT-I
BLK
CBL221-I
222 BLK NB
SPS2 TB1 + AI3
BLK
MB TB1 - WHT
223 X8-AI
301G
DRN
224
CBL225-I
TB2 WHT TB2 S ZNT1
225 HUM1 219C X3-AI NB
24VDC OVERRIDE
NB 131 120
226A 226B BLK
226 OUT X5-AI M
126 TB8 303 C
Humidity 227A 121
Sensor COM M DRN
227 127
}
121G
228 CBL229-I
WHT TB2
LCT LCT-E PL2 LCT-I X4-AI DISCHARGE AIR
229 Leaving Coil RED 1 WHT 132 TEMPERATURE
X2-AI BLK
Temperature EXTERNAL RESET
230 NB BLK 2 BLK 133
M DRN
DRN 3 DRN 301G
}
231 CBL232-I 121G
WHT TB2
X1-AI
232 CO2/MIN OA
124
BLK /OA FLOW
233
125
DRN
234
121G
NO NC
241 OAE-E OAE-I
242A 242B 2 242B 13 14
RAE + + 1
(311)
242 242C 207B 3 207B 207B
S SR COM
RAE-E
243 R63
DHL
NO NC
249 NB
PL5 4WV-E 4WV 4WV-E PL5 4WV-I
DO4 DO4 4WV-I 1 2
250 250A 250A 1 2 162B 162B
251 NB
SVB-I PL8 SVB PL8
C3-4 DO3 DO3 SVB-I
252 162A 252A 1 1 2 2 162B
PTS-I NB
253 WHT
PTS S X1
NB BLK 254A
254 - M
TB8 304 R-HP1
RED DO1
+ +5V / (259) DO1
255 255C 12 8 RED
DRN 301G 255 / (354)
PTD-I (303)
256 PTD BLK C1
- WHT
NB 256 / (354)
WHT
257 S X2 SRT
SRT-I
RED BLK
+ +5V / (259) X6
258 301G TB8 TB8
DRN
(255) 305 255A 258B 307 BLK NB
/ +5V +5VDC M
259 DRT1 (258)
DRT1-I
BLK DIP SWITCH
X3
260 ON
NB TB8 DFT
BLK 260A OFF
M DFT-I
261 306 1 2 3 4 5 6 BLK
SW6 MUST
DRT3 NB
262 DRT3-I BE ON BLK
BLK X7
WHEN LAST
263 NB BLK
X4
264
Figure 73 continued: Typical CAV_VAV 460 VAC Wiring (3 of 4) — DPS 003–006 shown
(160) (160)
301
120V_H HP1 120V_N
PL4 NB PL4 R-HP1
NO NC
302 HP1-I 1 2 HP1-I
159A H C 303A 13 14 155B
(307)
(255)
303
MCB
(145)
304 R-CCH1
NO NC
C1 DO1 DO1B
159A 305A 13 14 155B
305
HP3
(132) (147)
306 PL3 NB PL3 R-HP1 M3
HP3-I 2 HP3-I 307A DO2
NO NC
1 H C 9 5 C2 DO2B A1 A2
159A 307B 307C 155B
(133)
(134)
307
(303)
308
313
314
315
316
317
318
319
320
HEAT1 HEAT-E HEAT-I
321 PL19 PL15
GRN GRN
HEAT-E G
3 6
322 HEAT-I PL19
RED 4 RED WHT WHT
L1 L2
323 PL15 1 2 5
EXPD
HEAT-E
324 HEAT-I 1 PL18
WHT WHT
X5-AO +
325 PL15 3
RHV1
WHT 328A
W - 328B
M 301G NB
328 GRN 328C 330A
G -24V
RED 329A 330B
329 R CN2 +24V
3 4
CHV-I 24V
330
BLK 328A T7
CLASS 2
331 WHT 327A
120V
CHV1 1 2
GRN 328C
332
159A
155B
RED 329A
333
120V_H 120V_N
334 (160) (160)
335
336
337
338
339
340
341
{
344 TB2 WHT
+
128 CBL345-I
345 Bacnet MSTP BLK WHT
- A1+ /(212)
Building COM BLK
129 B1- / (213)
346 RED
REF
DRN
130 DRN GND1 / (214)
347
130G A2+ /(361)
348 EVBJMP-I
WHT
B2- / (361)
349
GND2 / (362)
EVI EVI-E
350 ORG 1 5 WHT A4P
1 + - GND
RED 2 4 BLK 1 3 EVB/88-I (120)
2 A4/4-I
351 YEL 3 BRN WHT MODBUS 351E
X86A
3 3 X89A 1 1 1 1
EVI BLK 2 RED
ACS3
ACS1
X88A
4
X4A
NB 4
352 GRY 5 1 GRN EVB BLK 352B
5 2 2 2 2
EVO EVO-E (115) A4P-X6A-I
353 ORG IFB 255 A4P-X6A-E
1 5 WHT 256 PL17
1 / T2B_24V IFB-I
RED 2 4 BLK (163) 162A 354A (255) (257) WHT 1 WHT
2 3 3
X87A
24VAC
16V
354 YEL BRN
TN2
3 3 DIP SWITCH
FILTER
ON K SD 24
BLK 4 2 RED (163) 1 GND 2
NB 4 X79A X80A
355 GRY 5 1 GRN 1234 DIP SWITCH
5 1 1 2 RED 3 RED
2 2
1
356 1234 IFBF
357 IFN_MOTOR
IFN-CI NB
WHT 1
358 (212) / A1+
BLK 2
(213) / B1-
359 DRN
(214) / GND1
360 EXH_MOTOR
EXH-CI
WHT 1 NB
BLK
BLK
BLK
(348) / A2+
BLK
361 BLK 2
IRT-E ORT-E (349) / B2-
DRN
362 (349) / GND2
364
T7
PB1
A5P+
GND51 GND10 A5P
OAT-I - 62" A4P
A4/4-I - 59"
PL17 (A4P-X6A) - 0"
F6C EVB/88-I - 59"
F1D
R-CCH1 OAER A4P-PI - 59"
M3 EVB-230-I - 59"
IFN-PI - 3"
IFN-CI - 3" T2B EVB-208-I - 59"
Short Red - Air IFB
DS1
Pressure Tube - 10" F1A F1B F1C
H X
www.DaikinApplied.com
R63 R-HP1
460V INVERTER PANEL
T2A T1
EVB
LR1
Dwyer Dwyer
SPS2 SPS1
DS6
Magnesense Magnesense
F1A F1B F1C
DHL REC1 H T6 X
85
CCH Crankcase Heater PC7 Pressure Control, Proof Airflow Switch
CHV1 Valve, Condenser Coil PTD Discharge Refrigerant Pressure Sensor
Comm Mod. Communication Module (BACnet, Lonworks, ...) PTS Suction Refrigerant Pressure Sensor
D3 DIII-NET Communication Gateway PVM1 Phase Voltage Monitor
DAT Temperature Sensor, Discharge Air R60 Energy Recovery Face and Bypass Damper Relay
DFT Defrost Temperature Sensor R63 Relay, Duct High Limit Switch
DHL Duct Hi-limit, Switch RAE Enthalpy Sensor, Return Air
DRT1,3 Discharge Refrigerant Temperature Sensor RAT Temperature Sensor, Return Air
DS1 Disconnect Switch, Unit Power R-CCH1 Crankcase Heater Relay
DS6 Disconnect Switch, Powered GFCI Receptacle REC1 Receptacle, GFCI
EVB Expansion Valve Board RES3,4 Resistor
EVBF Expansion Valve Board Electrical Noise Filter RHB1 Reheat Board, Hot Gas
EVI Indoor Expansion Valve R-HP1 High Pressure Compressor 1 Relay
EVO Outdoor Expansion Valve RHV1 Valve, Reheat Coil
EXPB,D Expansion Control Board SD1/SD2 Smoke Detector, Supply Air/Return Air
F1A,B Fuse, Control Circuit Transformer (T1), Primary SHS1 Space Humidity Sensor
F1C,D Fuse, Control Circuit Transformer (T1), Secondary SPS1 Static Pressure Sensor, Duct
F4A,B,C Fuse, 460V 3-Phase Transformer (T4), Primary SPS2 Static Pressure Sensor, Building
F6C Fuse, Powered GFCI Transformer (T6), Secondary SRT Suction Refrigerant Temperature Sensor
HEAT1 Heater Module SVB Refrigerant Bypass Solenoid Valve
HL Hi-Limit Switch, Gas Heat SVR Refrigerant Receiver Solenoid Valve
HP1,3 Hi-Pressure Switch, Refrigeration Circuits 1, 3 T1 Transformer, Main Control
IFB Interface Board T12 575/460V Primary Power Transformer
IFBF Interface Board Electrical Noise Filter T1F Main Transformer Electrical Noise Filter
Figure 73 continued: Typical CAV_VAV 460 VAC Wiring (4 of 4) — DPS 003–006 shown
IRT Indoor Refrigerant Temperature Sensor T2A,B Transformer, Control Input (115/24VAC)
LCT Temperature Sensor, Leaving Coil T4 Transformer, 230V Single Phase (460/397VAC)
LR1 Compressor Line Reactor T6 Transformer, Powered GFCI Receptacle (Line/115VAC)
Field Wiring
M1F Compressor 1 Electrical Noise Filter T7 Transformer, Reheat Control Board (115/24VAC)
M3 Contactor, Compressor 3 TB1 Terminal Block, Internal Power Distribution
Factory Wiring MCB Main Control Board TB2 Terminal Block, Field -24V
MJ Mechanical Jumper TB8 Terminal Block, Internal Signal Distribution
Factory Terminal MMP1 Manual Motor Protector, A4P Board VFD60 Variable Frequency Drive, Energy Recovery Wheel
MMP10 Manual Motor Protector, Supply Fan
Field Terminal MMP3 Manual Motor Protector, Compressor 3
MMP51 Manual Motor Protector, Exhaust Fan
MMP60 Manual Motor Protector, Energy Recovery Wheel
Plug Connection
Figure 74: Typical 575 Volt Wiring (1 of 4) — DPS 007–015 shown with 460 to 575 Transformer
T12
(106)
101
DS1 T12-1I 22kVA HEAT1575-PI
T12-2E PB2 DS1
347/575V, 3 Phase, 60Hz T12-2E T12-1I
102 F12A F13A HEAT1
L1 T1 103A 1 2 103B 103C 1 2 103D 103E
L1 T1 (318)
H1 X1 L1
103 CUSTOMER F12B F13B
L2 T2 104A 1 2 104B 104C 1 2 104D 104E ELECTRIC HEATER
SUPPLIED L2 T2
H2 X2 L2 575V, 3 Phase, 60Hz
104 POWER F12C F13C
L3 T3 105A 1 2 105B 105C 1 2 105D 105E 34.6 FLA
L3 T3
(102) 30A H3 X0 X3 35A L3
105 Wire for CW 575V 460V
Electric Heater
phase monitor 105F MMP1
106 PB2 PB2
GLG1 GFR1
107A L1 T1 110A
107 T1 T1
108A L2 T2 110B
108 T2 T2
109A L3 T3 110C
109 T3 T3
(140) L1 L2 L3 T4
/ CMP_L1 GFR1
110 1290VA
(141)
/ CMP_L2
111 (142)
/ CMP_L3
T1 T2 T3 N TB1
112 1 F4 2 113B 11
114A 113A
113 TB1 11
8
116B
CCH_230V / (150) (152) / CCH_N
114
115
TB1 TB1
116 9 116A 10
GFR1
GF-I GF-I
117 116B X3A 113A
3 1
118
119
120C
120A
116A
113A
120B
A4P-PI
120
121 3 2 1 1 3
X10A X1A
122
PB2 PVM1 A4P
REC1 LR1-I PC0702-1(A) CMP1
123 123A CMP1-PI
T1 3 124A U U
LN-H LN-N 1 NB
124B G P1
124 T2 4 125A V V M
X11A
LD-H LD-N 2
125 125B LR1 3
T3 5 P2 126A W W GND
X41A X5A 3
1 2 1 2 N3 P3
126
MMP10 INDOOR_FAN
PB2 IFN-PI NB
127 1
128A L1 T1 128B L1
T1
128
T2
129A L2 T2 129B 2 L2 M
3
A4/41-I
A4/5-I
A4/7-I
129 3
130A L3 T3 130B L3
T3
130 GND10 4
131A GND
OFN1
U U
131 BLK NB
1 2 1 2 N1 P1 1
V
132 X3A X5A WHT V M
X1A
MMP51 EXH_FAN1 2
3
EXH-PI NB W W CTRL
133 1 RED
L1 T1 134A L1 A5P 3
L3 T3 136A L3 3
4 PNK
X4A X51A 4
136 GND51 4 1 2 1 2 N2 P2 5 GRY
137A GND 5
137
138
MMP3 CMP3
CMP3-PI
139 M3 NB
A5/7-I
A5/51-I
A5/4-I
L1 T1 L1 T1 140A U
(110) / CMP_L1
140
(111) / CMP_L2
L2 T2 L2 T2 141A V M
141 3
L3 T3 L3 T3 W GND OFN2
142A
(111) / CMP_L3 NB
142 U U
BLK
1 2 1 2 N1 P1 1
V
143 X3A X5A WHT V M
X1A
2
3
144 W W CTRL
RED
3
A5P+
145 PC0511-2(A)
1 YEL
1
146 2 BLU
2
3 ORG
X2A
3
147 4 PNK
X4A 4
1 2 5 GRY
5
148
149
PB2 F1A A5PJMP-I
150A 1 2
150 T1
(114) / CCH_230V
2A
151 R-CCH1 CCH1
F1B 1 9 CCH1-I x1 x2 CCH1-I
460V PRI. T1 113A 152A 114A
152B 1 2 (114) / CCH_N
152 T3 300VA
MB.HB
2A H1 H3 H2 H4 (305)
153 M3 CCH3
22 21 CCH3-I x1 x2 CCH3-I
113A 154A 114A
154
MB.HB
TB1 F1C X1 X2 (307) TB1
155 1 160A XF 155A 3
1 120V SEC. 3
4A
156
1 3
157 3G
155A
158
160A 155A
159 SPD SPD-I
160A 120 COM T2B
1
160 155A 120V CLASS 2
120V_H 2 120V_N / (160) 120V_N
75VA
161 (202) 161A (160)
(302) GND TB1 3G (202)
24V
TB1 TB1 (302)
162 24 COM
4 163A 163B 5
163 5
T2B_24V T2B_N
164 (248) (248)
(357) (357)
165
Figure 74 continued: Typical 575 Volt Wiring (2 of 4) — DPS 007–015 shown with 460 to 575 Transformer
(160) (160)
201
120V_H 120V_N
202
PVM1
203
160A 204A 155A
1(123) 8 120 COM T2A
204
120V CLASS 2
205 75VA
}
228 (DDC Sensor Only)
101
WALLSTAT
LCT LCT-I
229 Leaving Coil WHT DISCHARGE AIR
T8-X2
Temperature GRN TEMPERATURE
230 NB BLK EXTERNAL RESET
T8-M1 DRN 133
}
231 301G CBL232-I 132G
DRN TB2
WHT
T8-X1 CO2/MIN OA
232 (217)
124 /OA FLOW
BLK (SEE IM 919-3 PAGE 29)
233
125
DRN
234
121G
241 OAE-I
242A 242B WHT 13 14
RAE + + 1
(311)
244
TB2 SD1 TB2
209A 207B
245
122 NB 123
SD2
246
(163) (163)
EXPD
247 T2B_24V T2B_N
SVR
C2 DO2 DO2 SVR-I SVR-I
248 163A 248A 1 2 163B
249 MB.HB
PL5 4WV PL5 4WV-I
DO4 DO4 4WV-I 1 2
250 250A 1 2 163B
251 NB
SVB-I SVB SVB-I
C3-4 DO3 DO3
252 163A 252A 1 2 163B
PTS-I MB.HB
253 WHT
PTS S X1
NB BLK 254A
254 - T8-M1
TB8 304 R-HP1
RED DO1
+ +5V / (259) DO1
255 255C 12 8 RED
DRN 301G 255 / (362)
PTD-I (303)
256 PTD BLK C1
- WHT
NB 256 / (362)
WHT
257 S X2 SRT
SRT-I
RED BLK
+ +5V / (259) X6
258 301G TB8 TB8
DRN
(255) 305 255A 258B 307 BLK NB
/ +5V +5VDC T9-M1
259 DRT1 (258)
DRT1-I
BLK DIP SWITCH
X3
260 ON
MB.HB TB8
BLK 260A OFF
T8-M2
261 306 1 2 3 4 5 6
SW6 MUST
DRT3
262 DRT3-I BE ON
BLK WHEN LAST
263 MB.HB BLK
X4
264
265
Figure 74 continued: Typical 575 Volt Wiring (3 of 4) — DPS 007–015 shown with 460 to 575 Transformer
(160) (160)
301
120V_H HP1 120V_N
PL4 NB PL4 R-HP1
NO NC
302 HP1-I 1 2 HP1-I
160A H C 303A 13 14 155A
(307)
(255)
303
MCB
(152)
304 R-CCH1
NO NC
C1 DO1 DO1B
160A 305A 13 14 155A
305
HP3
(140) (154)
306 PL3 NB PL3 R-HP1 M3
HP3-I 2 HP3-I 307A DO2
NO NC
1 H C 9 5 C2 DO2B A1 A2
160A 307B 307C 155A
(141)
(142)
307
(303)
308
313
314
315
316
317
HEAT1
DO3 DO3 HEAT1ES-CI
318 318A RED
C
319
C3
320A BLK
I
320
ELECTRIC
321 HEATER
SCR CONTROL
322
NB
323 HEAT1ES-CI
EXPD 324A WHT
X5-AO +W
324 (247)
325A BLK
T9-M1 -R
325 301G
DRN
326
327
328
329
330
331
332
333
334
335
336
337
IRT
338 IRTD-I
BLK
AI1
339
BLK
T7-M1
340 ORT
ORTD-I
341 BLK
AI2
342 BLK
T7-M2
343 DFT
DFT-I
BLK
344
NB
BLK
AI3
345
346
347 EVID-I
BLU
M1+
348 BLK
M1-
EVI BRN SM1
M2+
349 NB WHT
M2-
COM
350 EVOD-I
BLU
M3+
351 BLK
M3-
EVO BRN SM2
M4+
352 NB WHT
M4-
COM
353
163A
IFB-I IFN-CI NB
WHT 1
358 CHK1 (212) / A1+
+ - GND BLK 2
(213) / B1-
1 3 MOD A4/4-I
359 359A A4P DRN
1 1 1 (214) / GND1
ACS3
ACS1
(120)
X4A
16V
362 (357) / GND2
TN2
363A BLK
X6A
1 GND 2
363 DIP SWITCH
RED
2
1
364 1234
365
PB2
www.DaikinApplied.com
F4
GND51 GND10
M3
TB2 TB1
X
GFR1 R63 R-CCH1R-HP1OAER
IFB
ACS3
N
Modbus
ACS2
T3
ACS1
T2 T1
T4 T1
L3
24V L2
DS1 Customer Wiring Only L1
CHK 1
H
SPD1
ON
T2A T2B
SPS1 SPS2
REC1
FOR HIGH VOLTAGE WIRING
DO NOT RUN HIGH VOLTAGE WIRES INSIDE WIRE TRACK
DHL
PC5
89
575V Transformer Fuse Panel
Sequence of Operation
Operating States
The transition from any operating state to another is graphically Fan Only
represented in Figure 75. The outside air damper will modulate to the minimum position
and based upon the sensor inputs, the unit will go into one of
Figure 75: Operating State Diagram the four running states - “Heating,” “Cooling,” “Economizing,”
or “Minimum DAT.” If the control temperature is between its
setpoint and its dead band, the unit will remain in the “Fan
Only” state.
Mechanical Cooling The unit goes into the cooling mode of operation when the
control temperature (return temperature) is above the change-
Constant Volume (Space Comfort Controller) over setpoint by more than ½ the deadband.
The control temperature for a CAV unit is typically the space Example - If the change over temperature is 70.0°F and the
temperature. A space temperature sensor must be field deadband is 1.0°F, the unit will not go into the cooling mode of
installed into the occupied space and connected to the unit operation until the return temperature reaches 70.6°F.
controller.
When this takes place, the cooling mode of operation will begin
The unit goes into the cooling mode of operation when the and the 1st stage of compressor operation will start.
control temperature (space temperature) is above the cooling
The unit controller will turn ON the next stage of compressor
setpoint by more than ½ the deadband.
operation, or turn off a stage of compressor operation, to
Example - the cooling setpoint is set to 70.0°F and the maintain the discharge air temperature setpoint within the
deadband is 1.0°F, the unit will not go into the cooling mode of deadband. When a compressor stage turns ON, the next
operation until the space sensor reaches 70.6°F. compressor stage up or down will not take place for the next 4
When this takes place, the cooling mode of operation will begin minutes. This “4 minutes” is called the stage timer.
and the 1st stage of compressor operation will start. When a cooling stage is initiated no further operation will
The unit controller will turn ON the next stage of compressor take place within the stage timer limit. Reference the Cooling
operation, or turn off a stage of compressor operation, to Setup menu for the adjustable stage time value. In the above
maintain the cooling setpoint temperature within the deadband. example, the unit will stage down or turn OFF the cooling mode
When a compressor stage turns ON, the next compressor of operation when the return temperature reaches 69.4°F.
stage, up or down, will not take place for the next 4 minutes.
This “4 minutes” is called the stage time. Reference the Economizer
“Cooling Setup” menu for the adjustable stage time value.
When the economizer is enabled, the outside air temperature
When a cooling stage is initiated no further operation will take is below the changeover setpoint, and the differential enthalpy
place within the stage timer limit. In the above example, the switch (if installed) is made, the economizer becomes the
unit will stage down or turn OFF the cooling mode of operation first stage of cooling. It will modulate to control to either the
when the cooling setpoint reaches 69.4°F. discharge air temperature (VAV) or space temperature (CV).
Variable Air Volume (Discharge Air Controller) Every 4 minutes, the unit can then either add mechanical
cooling if the economizer is at 100% open, continue
The unit’s cooling mode of operation is controlled by the
economizing, or if the control temperature is satisfied, return to
control temperature, the change-over temperature, and the
minimum position and transition back to “Fan Only” mode.
discharge air temperature. The unit goes into the cooling mode
of operation by analyzing the control temperature. The control If the enthalpy switch breaks or the outside air warms, the unit
temperature for a VAV system is the return temperature. will exit economizing and continue to mechanically cool while
returning to the minimum position for ventilation.
7. Verify the phase voltage imbalance is no greater than 4. Verify the rotation is correct.
2%.
8. Verify that gas piping is complete and leak tight.
9. Verify that the shutoff cock is installed ahead of the
furnace, and that all air has been bled from the gas lines.
10. Verify installation of gas flue and outside air vents.
11. Manually rotate all fans and verify that they rotate freely.
12. Verify that the evaporator condensate drain is trapped
and that the drain pan is level.
13. If unit is curb mounted, verify that the curb is properly
flashed to prevent water leakage.
14. Review the equipment and service literature, the
sequences of operation, and the wiring diagrams to
become familiar with the functions and purposes of the
controls and devices.
15. Determine which optional controls are included with the
unit.
Maintenance
Supply Fans
1. Depending on local climate conditions, condensate
may collect on components inside the units. To prevent
surface rust and discoloration, spray all bare metal parts
with a rust preventive compound.
Cabinet Sections
Once a month, open a door on each section and verify that no
moisture or debris is accumulating in the unit.
Control Compartment
1. Daikin Applied recommends that the electronic control
equipment in the unit be stored in a 5% to 95% RH (non-
condensing) environment.
2. It may be necessary to put a heat source (light bulb) in
the main control panel to prevent the accumulation of
atmospheric condensate within the panel. The location
and wattage of the heat source is dependent on local
environmental conditions. Fans
3. Check the control compartment every two weeks to The supply, condenser and exhaust fan motors are
confirm that the heat source is functional and is adequate permanently lubricated and require no periodic lubrication.
for current conditions.
Vibration Levels
Filter Replacement Each unit as shipped is trim balanced to operate smoothly. To
This unit is provided with filters are show in Table 33. These provide satisfactory operation after shipping and installation,
filters are disposable and should be replaced periodically. use accepted industry guidelines for field balancing fans.
Unit is equipped with a filter pull to assist in this process. See NOTE: Excessive vibration from any cause contributes to
Figure 78. premature fan and motor bearing failure. Monitor
overall vibration levels every six months of operation.
Table 33: Filter Sizes An increase in levels is an indication of potential
trouble.
Cabinet Size Filter Size
Vibration Causes
003—006 4 - 16" × 16"
1. Wheel imbalance.
007—015 4 - 24" × 24"
016—028 9 - 18" × 24" a. Dirt or debris on wheel blades.
b. Wheel distorted from overspeed.
Restart 2. Bent shaft.
After extended storage, perform a complete start up. Inevitable 3. Motor imbalance.
accumulations of dirt, insect nests, etc. can contribute to
4. Fan section not supported evenly on foundation.
problems if not cleaned out thoroughly prior to start up. In
addition, thermal cycling tends to loosen mechanical and
electrical connections. Following the startup procedure helps Periodic Service and Maintenance
discover these and other issues that may have developed • Check all moving parts for wear every six months.
during the storage interval.
The Rebel unit is equipped with a direct drive,variable
speed fan/motor combination. When equipped, the
exhaust fan will be the same. There are no belts or
pulleys to maintain. The bearing are permanently sealed
and do not require periodic greasing.
Refrigerant Charge
The Rebel unit has many configurable options that can affect MicroTech III keypad instructions for charging and/
the refrigerant charge. Actual unit charge is given on the unit’s or evacuation
data plate found on the inside of the control panel. The Rebel
Evacuating the charge:
unit uses electronic expansion valves that maintain peak
efficiency. Liquid sub-cooling and suction super heat float and • Navigate to the Exp Valve Set-Up Menu
should not be used as an indication that charge needs to be • Set ManCtrl EV Op=Man
added or removed from the system. If a leak is suspected, the
• Navigate to the Manual Control Menu
full charge should be removed and weighed. Weight should be
compared against the unit nameplate data. Unit should be re- • Set Manual Ctrl=ManCtrl
charged with the amount given on the unit nameplate. • Set RcvSol Valve=Open (Heat Pump only)
POE and PVE oil is hygroscopic and does absorb moisture • Set BP Sol Valve=Open
when exposed to atmosphere. Steps should be taken • Set EVO Cmd=100% (Heat Pump only)
to minimize exposure time to atmosphere during any • Set EVI Cmd=100%
maintenance where the sealed system is to be opened. • Reclaim refrigerant
Rebel 003–015 refrigerant systems use only Polyvinylether
(PVE) oil. Rebel 016–028 refrigerant systems use only Charging the system:
Polyester (POE) oil.
Static Charge (Step 1)
IMPORTANT • Navigate to the Manual Control Menu
Do not use POE oil in DPS 003–015 refrigerant systems • Set RcvSol Valve=Close (Heat Pump only)
and do not use PVE oil in DPS 016–028 refrigerant
• Set Reheat Valve=50% (if present)
systems.
• Set EVO Cmd=30% (Heat Pump only)
• Set EVI Cmd=30%
Re-charging the unit
• → When PTS>20psi: Navigate to Exp Valve Set-Up
The entire system must be evacuated using a suitable vacuum • Set ManCtrl EV Op=Auto
pump. The quality of vacuum is measured using a suitable
micron gauge that has been calibrated. The vacuum level Dynamic Charge (Step 2)
reading should be taken directly from the sealed system, not at • Clear any active alarms (ex: Charge Loss: Problem
the vacuum pump. The minimum vacuum level is 300 microns generated while removing charge)
Hg. The vacuum pump should be isolated from the system and
• Navigate to Manual Control
the observed. Decay should not be greater than 500 microns
after 15 minutes. • Set BP Sol Valve=Close
The crankcase heaters should be on during the evacuation • Set Supply Fan=On
procedure. This will help boil any dissolved refrigerant in the oil. • Set SAF Spd Cmd=50%
R410A is a zeotropic refrigerant that is made up of more • Set INV/OF Ena=On
than one compound. It must be charged as a liquid from the • Set INV=On
canister. Charging is to be done by weight and must match the • → When Clg State=Normal:
unit nameplate found on the inside of the control panel door. • Navigate to Manual Control
When re-charging the unit there might be alarms in the MT III • Set INV Cmp Cmd=50%
controller and the Building Automation System that need to be • Set BP Sol Valve=Open
cleared.
• Set OA Fan=On
• Set OA Fan Cmd=50%
Replacement Parts Order the replacement compressor through the Daikin Parts
Department (Minneapolis).
When contacting Daikin for service or replacement parts,
provide the model number, serial number, and unit part 1. Contact the Daikin Parts Department for compressor
number of the unit as stamped on the serial plate attached availability.
to the unit. For questions regarding wiring diagrams, provide 2. Send a completed parts order form to the Daikin Parts
the number on the specific diagram. If replacement parts are Department.
required, include the date of unit installation, the date of failure,
3. The Parts Department processes the order and
an explanation of the malfunction, and a description of the
the compressors are shipped from our Dayton, OH
replacement parts required.
warehouse via ground transportation. If next-day air
is required, indicate this on the parts order form and a
Scroll Compressor freight charge will be billed to your account. Air freight
All Daikin Rooftop products include a first-year parts only costs are not covered under the Daikin warranty.
warranty. The warranty period extends 12 months from startup 4. After the failed compressor is replaced, return it to Daikin
or 18 months from date of shipment, whichever comes first. Parts Department with a Return Goods Tag attached,
Labor to install these parts is not included with this warranty. which you will receive in the mail. It must be attached to
Compressors are considered a part and are included in this the compressor. The Return Goods Tag has instructions
standard warranty. on where to send the compressor. If the compressor
is not returned, you will be billed for the replacement
All Compressors compressor.
Replacement compressors for Daikin Rooftop Units can be 5. Consideration may be given at this time to a compressor
obtained from the Daikin Service Parts department. teardown analysis, depending on the history of failures.
The decision to replace the failed portion of the compressor
tandem, as opposed to replacing the entire tandem, must be In-Warranty Return Material Procedure
decided based on the following.
Material other than compressors may not be returned except
1. In warranty: Warranty only covers replacement of the by permission of authorized personnel of McQuay International
failed portion of the tandem. at Minneapolis, Minnesota.
2. Out of warranty: The customer decides whether to A “return goods” tag will be sent to be included with the
replace the entire tandem or just a portion. returned material. Enter the information as called for on the tag
3. Some equipment may include the extended 2nd - 5th in order to expedite handling at out factories and issuance of
year compressor warranty option. credits. All parts shall be returned to the factory designated on
the return goods tag, transportation charges prepaid.
The return of the part does not constitute an order for
replacement. A purchase order for the replacement part
must be entered through your nearest Daikin representative.
The order should include the component’s part number and
description and the model and serial numbers of the unit
involved.
If it is determined that the failure of the returned part is due to
faulty material or workmanship within the standard warranty
period, credit will be issued on the customer’s purchase order.
NOTE: 1. Unit does not require high pressure switch testing
2. Refrigerant pressures can be checked from the
MT III controller. Refrigerant gages are not needed.
3. Ensure proper unit phasing
4. Compressor 3 might not operate during startup
due to ambient conditions and compressor
operating envelope.
GENERAL INFORMATION
UNIT INFORMATION
Select Yes or No. If not applicable to the type of unit, select N/A.
I. INITIAL CHECK
B. Has the discharge static pressure reference been properly located in the building? . . . . . . . . . . . . . Yes No N/A
F. Is the main disconnect adequately fused and are fuses installed? . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
G. Are crankcase heaters operating, and have they been operating 24 hours prior to start-up? . . . . . . . . Yes No N/A
B. Voltage at supply fan motor: . . . . . . . . . . . . . . . . . . . . . . . . 1–2 __________ V 2–3 __________ V 1–3 __________ V
C. Supply fan motor amp draw per phase: . . . . . . . . . . . . . . . . . . 1–2 __________ A 2–3 __________ A 1–3 __________ A
F. Record return static pressure at unit (with outside air dampers closed) in inches of H20: . . . . . . . . . . . . . . . . . __________
E. Compressor amperage:
13F-4157 (05/15) 2
Select Yes or No. If not applicable to the type of unit, select N/A.
I. Are all control refrigerant lines secure to prevent excessive vibration and wear? . . . . . . . . . . . . . . . Yes No N/A
J. Are all valve caps and packing tight after start-up? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
H. Operate electric heat with fans off. Electric heat must cycle on high limit control . . . . . . . . . . . . . . . Yes No N/A
13F-4157 (05/15) 3
Select Yes or No. If not applicable to the type of unit, select N/A.
Thank you for completing this form. Please sign and date below.
13F-4157 (05/15) 4
Installation address:____________________________________________________________________________________________________
Purchasing contractor:__________________________________________________________________________________________________
Address: ____________________________________________________________________________________________
City/State/Zip: _______________________________________________________________________________________
2. How would you rate the overall appearance of the product; i.e., paint, fin damage, etc.?
Excellent Good Fair Poor
3. Did all sections of the unit fit together properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
4. Did the cabinet have any air leakage? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Comments _______________________________________________________________________________________
8. Did the labeling and schematics provide adequate information? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Comments _______________________________________________________________________________________
Please list any additional comments which could affect the operation of this unit; i.e., shipping damage, failed components, adverse installation applications, etc. If additional comment
space is needed, write the comment(s) on a separate sheet, attach the sheet to this completed Quality Assurance Survey Report, and return it to the Warranty Department with the
completed preceding “Equipment Warranty Registration Form”.
Addendum follows
IM 1125-7 109
The following is a description of the MicroTech III menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration.
Commission Unit Manual Control Service Menus Trending Unit Maintenance BMS Communications
Unit Set-Up ► Manual Control= Normal Timer Settings ► Trending Ena= No Operating Hours LON Set-Up ►
Timer Settings ► Supply Fan= Off Operating Hours ► Apply Chgs= No BACnet MSTP Set-Up ►
SAF Set-Up ► SAF Spd Cmd= 0% Save/Restore Settings ► Sample Time= 300s BACnet IP Set-Up ►
RF/EF Set-Up ► INV/OF Ena= Off Active Alarms ► TrendOnOff= Off D-Net Set-Up ►
Htg/Clg ChgOvr Set-Up ► INV Comp= Off Alarm Log ► Auto Exp Time= Network Unit Set-Up ►
Cooling Set-Up ► INV Spd Cmd= 0% Event Log (65300) Export Data= No
INV Cmp Set-Up ► Comp 3= Off Data Snapshots (65500) Clear Trend= Done
Econo Set-Up ► OA Fan= Off Alarm/Event Config Trend Full=
For more detail go to:
Min OA Set-Up ► OA Fan Cmd= 0% Analog Input Status ► Points 1–8 (Fixed) ► Figure 85, page 118
Heating Set-Up ► 4 Way Valve= Cool Universal I/O Status ► Points 9–24 (from List) ►
OA Fan Set-Up ► RcvrSol Valve= Closed Digital Input Status ► Points 25–27 (with IDs) ►
Exp Valve Set-Up ► BP Sol Valve= Closed Digital Output Status ► Points 28–30 (with IDs) ►
Defrost Set-Up ► EVI Cmd= 0% Network Input Status ►
Dehum Set-Up ► EVO Cmd= 0% Modbus Status ►
Energy Rec Set-Up ► RF/EF VFD= Off IP Set Up
For more detail go to:
D3 Set-Up ► RF/EF Spd Cmd= 0% D3 Status ► Figure 86, page 118
Alarm Configuration ► Var Cmp= Sensor Offsets ►
Var Cmp Cmd= Reset Counte= XXXX
VComp Emg Stop= Last Reset Info
Htg Valve= 0%
For more detail go to:
SCR Out= 0%
Figure 83, page 114
Htg Stg 1= Off
SCR Ena 1= Off
Htg Stg 2= Off
For more detail go to:
Htg Stg 3= Off
Figure 84, page 116
Htg Stg 4= Off
Reheat Valve= 0%
RH Output=
ERec Wheel= Off
ER Whl Cmd= 0%
ER BP Dmpr Cl= Off
ER BP Dmpr Op= Off
Alm Output= Off
Fan Op Out= Off
View/Set Unit
Unit Status/Settings ►
Occupancy ►
Temperatures ►
Flow Status ►
SAF Spd Control ►
RF/EF Control ►
Cooling ►
Economizer ►
Min OA Damper ►
Heating ►
Dehumidification ►
Date/Time/Schedules ►
Unit Status/Settings Occupancy Temperatures Flow Status SAF Speed Control RF/EF Control
Unit State= ___________ Occupancy= __________ Control Temp= XXX°F Airflow= ______________ SAF Speed= XXX% RF/EF Cap= XXX%
Unit Status= __________ Occ Mode= Auto/Net Disch Temp= XXX°F Supply Fan= __________ Speed Cmd= XXX% Speed Cmd= XXX%
MWU Status=__________ OccSrc= _____________ Return Air= XXX°F Ret/Exh Fan= _________ Duct Press= X.Xin Bldg Press- X.XXin
Dehum Status= ________ UnoccSrc= ___________ Space Temp= XXX°F DuctSP Spt= 1.0in BldgSP Spt= 0.050in
Ctrl Mode= Off Tnt Ovrde Tm= 0 min OA Temp= XXX°F IAQ PPM= XXXXPPM
Clg Status= ___________ EF/LC Temp= XXX°F OA Flw= XXXXXCFM
Htg Status= ___________ ER LAT= XXX°F MinOAFlw Spt= 2000CFM
Sup/Htg Status= _______ ER EAT= XXX°F Bldg Press= X.XXin
Econo Status= _________ DRT1= XXX°F BldgSP Spt= 0.05in
Clg Capacity= XXX% DRT3= XXX°F
Htg Capacity= XXX% SRT= XXX°F
Supl Htg Cap= XXX% DFT= XXX°F
Reheat Cap= XXX% IRT= XXX°F
SAF Speed= XXX% ORT= XXX°F
RF/EF Cap= XXX%
OAD/Econo Cap=XXX%
Rel Humidiy= XXX%
Net Emrg Ovrd= Normal
Net App Mode= Auto
Commission Unit
Unit Set-Up ►
Timer Settings ►
SAF Set-Up ►
RF/EF Set-Up ►
Htg/Clg ChgOvr Set-Up ►
Cooling Set-Up ►
INV Cmp Set-Up ► Unit Set-Up Timer Settings SAF Set-Up
Econo Set-Up ► Apply Changes= Service Time= 0min SAF Ctrl= DSP 1 ZONE VAV CONTROL CFM CONTROL
Min OA Set-Up ► RAT Sensor= Start Up= 180s AplyInputChgs= No Min Clg Spd= 40% Min CFM= 0CFM
Heating Set-Up ► 100% OA SCU= Recirculate= 180s CO2 Input= None Max Clg Spd= 100% Max CFM= 10000CFM
OA Fan Set-Up ► OAT Sensor= Zero OA Time= 0min CFM Input= None Min Htg Spd= 40% V/A @ Min CFM= 0V
Exp Valve Set-Up ► Space Sensor= Loc/Net Tnt Override= 120min BSP Input= No Max Htg Spd= 100% V/A @ Max CFM= 10 V
Defrost Set-Up ► Eng Units= English Post Heat= 0s SPEED CONTROL Space Period= 30s SAF CFM DB= 3%
Dehum Set-Up ► Unit Name= xxxxxxxxxxxx Pwd Timeout= 10min Rem SAF Cap= 25% Space Gain= 1.5 SAF CFM Period= 30s
Energy Rec Set-Up ► Rapid Start= No Low DAT= 6min DSP CONTROL Space PAT= 100s SAF CFM Gain= 0.1
D3 Set-Up ► Rapid Start Tm= 10min ClgStateDelay= 300s DSP DB= Space Max Chg= 10% SAF CFM MxChg= 5%
Alarm Configuration ► DO10 Clg= FanOp Clg Stg Time= 5min SAF Ramp Time= 60s CO2 CONTROL BSP CONTROL
Alarm/Event Config Htg Stg Time= 5min Min Period= Min PPM= 0PPM BSP DB= 0.01in
MinExStrtTm= 120s Max Spd Chg= Max PPM= 2000PPM BSP Period= 5s
MinExStopTm= 120s Duct Press 1= V/A @ Min PPM= 0V BSP Gain= 0.2
ER Whl Stg Tm= 5min Duct Press 2= V/A @ Max PPM= 10V Max Spd Chg= 4%
ER Whl Off Tm= 20min Min SAF PPM= 800PPM SAF SETUP
Max SAF PPM= 1100PPM SAF Ctrl Dly= 30s
Min PPM Spd= 50% Min Speed= 25%
Max PPM Spd= 100% VAVBox Out= _________
Max SAF Hz=
Max Vent Speed= 100%
Max SAF RPM= 2600
Max SAF Hz=
ECM Status= _________
SAF Status=
RF/EF Set-Up Htg/Clg ChgOvr Set-Up Cooling Set-Up INV Cmp Set-Up
RF/EF Ctrl= None Ctlr Temp Src= RAT Clg Stage Time= 5min COMPRESSOR STATUS COMPRESSOR SETUP
SPEED CONTROL Use Tstat Spt= No Clg DB= 2.0°F Clg State= ____________ Clg Lo OAT Lk= 55°F
Rem ExhF Cap= 5% Occ Clg DB= 2.0°F Clg Lo OAT Lk= 55ºF Htg State= ____________ Htg Lo OAT Lk= 0.0ºF
Rem RAF Cap Clg Period= 60s OAT Diff= 2.0°F INV Cmp Spd= XXX.X% Htg Hi OAT Lk= 55.0ºF
BSP CONTROL Clg Gain= 0.1 Clg Reset= None INV Spd Cmd= XXX.X% EffHtgOATLk= 55.0ºF
BSP DB= 0.010in Clg PAT= 600s Min Clg Spt= 55.0°F VCmp Oil Status= OAT Diff= 2ºF
BSP Period= Max Clg Chg= 5.0°F Min Clg Spt @= 0 Comp 3=_____________ INV Period= 20s
BSP Gain= Occ Htg DB= 2.0°F Max Clg Spt= 65.0°F Fault Code Details ► INV Gain= 2.5
Max Spd Chg= Htg Period= 60s Max Clg Spt@= 100
RF/EF SET UP Htg Gain= 0.1 Unocc Diff= 3°F
INV Port Temp= XXX.XºF
INV Fin Temp= XXX.XºF
1 INV PAT= 10s
INV Max Chg= 15%
RFEF Ctrl Dly= Htg PAT= 600s INV Amps= XX.XA Oil Management=
Min Speed= Max Htg Chg= 5.0°F REFRIG CIRCUIT STATUS Low Oil Time=
MinExStrtTm= Cal D Rem Spt @10°C= PTS= XXX.Xpsi Oil Boost Time=
MinExStopTm= Cal D Rem Spt @50°F= PTD= XXX.Xpsi Inv Man Dsbl=
MinExOAPos= Cal D Rem Spt @30°C= 4 Way Valve=__________ Comp 3 Man Dsbl=
MinExSAFCap= Cal D Rem Spt @80°F= RcvrSol Valve=_________ VFD Status=
ExhOnOAPos= 40% Demand Shed= BP Sol Valve=_________ VFD Alm/Wrn=
ExhMxOAPos= 100% Clg Demd Shed= IFB COMM STATUS ►2
Max Vent Spd= 100% Htg Dmd Shed=
Max RFEF RPM= 2600 Clg Shed Rate=
ECM Status= _________ Htg Shed Rate=
Exp Valve Set-Up Defrost Set-Up Dehum Set-Up Energy Rec Set-Up D3 Set-Up
EXP VALVE STATUS EXP VALVE SETUP Defrost State= _________ Dehum Method= None Energy Rcvy= Yes Itouch Vers= __________
EVI Pos= XXX% SSH DB= 2.0ºF Manual DF= No RH DB= 2% ER Wheel= ___________ Unit D3 Addr= 1–00
EVO Pos= XXX% SH Lo Base= 5.0ºF MinCmpOpTm= 10min Dewpoint DB= 2°F Wheel Speed= XXX% Set D3 Addr= No
EVStatus=____________ SH Hi Base= 9.0ºF MinAccCmpTm= 40min RH Period= 30s Whl Spd Cmd= XXX% OA Unit Num= 0
REFRIG CIRCUIT STATUS Htg EVI Meth= SbC MaxFrostTm= 120min RH Gain= 1 ER LAT= XXX°F OA Unit Amps= 0
PTS= XXX.Xpsi IC SC Spt= 9.0ºF Defrost Temp= XXºF LCS Lo Gain= ER EAT= XXX°F OA Unit Addr= 0
PTD= XXX.Xpsi IC SC DB= 2.0ºF Tdef Adj= 0.0ºF RH PAT= 30s Min ExhT Diff= 2.0°F Set OA Unit= No
Suction SH= XX.XºF HtgSC EVI Min= 0% CmpOpTime= XXXmin RH Max Chg= 10% Max ExhT Diff= 6.0°F Rst All OA= No
Discharge SH= XX.XºF Clg EVO Meth= SbC AccCmpOpTm= XXXmin Dehum Ctrl= Occupied ER Whl Stg Tm= 5min Min Load= 20%
Subcooling= XX.X°F OC SC Spt= 9.0ºF LoFrstAccTm= XXXmin Sensor Loc= Return ER Whl Off Tm= 20min Max Load= 50%
Eff SSH Spt= XX.X°F OC SC DB= 2.0ºF HiFrstAccTm= XXXmin Mn Lvg Coil T= 45.0°F Rel Humidity= XXX% HiCapReset= No
EffSH Base= XX.X°F ClgSC EVO Min= 0% Mx Lvg Coil T= 52.0°F Min Whl Spd= 5% DATLoDiff= 10.0ºF
Eff SC Spt= XX.X°F ManCtrl EV Op= Auto Min Rheat Spt= 55.0°F Intersect Pt= XXX.XºF Eco Method= None
Eff SC Lo Lmt= XXX% Max Rheat Spt= 65.0°F Fst Mgnt Meth= Timed DATHiDiff= 10.0ºF
SRT= XXX°F RH Sens Type= VDC OA Frst Temp= -5.0°F OA Enth Max= 25.5 BTU/lb
Disch Sat Tmp= XXX.X°F RH Min Sig= 0V Defrost Time= 5min OA Hum Max= 0.0107lb/lb
Sucn Sat Tmp= XXX.X°F RH Max Sig= 10V Defrost Period= 60min OAT Max= 84ºF
IRT= XXX°F Min Dehum Spd= 33% Defrst On Tm= 1s Temp Display= DAT
ORT= XXX°F Max Dehum Spd= 100% Defrst Off Tm= 24s Low Speed= 33%
RH Min Pos= 15% ER Whl Period= 30s Med Speed= 66%
RH Dec Rate= 1.0%/s ER Whl Gain= 1.0 Hi Speed= 100%
RH OutMaxV= ER Whl PAT= 30s
BackUp RH Ena= ER Whl Chg= 10%
Lo ERLAT Cnplk=
Cap Limiting=
Service Menus
Timer Settings ►
Operating Hours ►
Save/Restore Settings ►
Active Alarms ►
Alarm Log ►
Alarm Configuration ►
Analog Input Status ►
Universal I/O Status ►
Digital Input Status ►
Digital Output Status ►
Network Input Status ►
Modbus Status ►
D3 Input Status ► Timer Settings Operating Hours Save/Restore Active Alarms
Sensor Offsets ► Service Time= 0min Supply Fan= XXXXXh Settings Alm Count: xx Clr Alms= No
Reset Counte= XXXX Start Up= 180s Ret/Exh Fan= XXXXXh Save Params= +Alarm 1: Alarm Type ►
Recirculate= 180s Cmp Cooling= XXXXXh Rstr Params= +Alarm 2: Alarm Type ►
Zero OA Time= 0min INV Comp= XXXXXh Rstr Factory= ●
Tnt Override= 120min Comp 3= XXXXXh SaveToCard= ●
Post Heat= 0s Heating= XXXXXh LoadFromCard= ●
Pwd Timeout= 10min Cmp Heating= XXXXXh Create Trace=
Trace to SD=
+Alarm 10: Alarm Type ►
Low DAT= 6min Economizer= XXXXXh
ClgStateDelay= 300s Tnt Override= XXXXXh
Bypass Valve= 300s Dehumid= XXXXXh
Clg Stg Time= 5min ER Wheel= XXXXXh
Htg Stg Time= 5min
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
Alarm Log Alarm/Event Analog Input Status Universal I/O Status Digital Input Status Digital Output Status
Configuration
Log Count: xx Clr Log= No ► MCB Al1= XXXXXXXX MCB X1= XXXXXXXX MCB DI1= ____________ MCB DO1= __________
+/-Alarm 1: Alarm Type ► ALARM LIMITS MCB Al2= XXXXXXXX MCB X2= XXXXXXXX MCB DI2= ____________ MCB DO2= __________
+/-Alarm 2: Alarm Type ► Hi Disch Temp= 170°F MCB Al3= XXXXXXXX MCB X3= XXXXXXXX MCB DI3= ____________ MCB DO3= __________
● Lo Disch Temp= 40°F EMD AI1= XXXXXXXX MCB X4= XXXXXXXX MCB DI4= ____________ MCB DO4= __________
● Hi Return Temp= 120°F EMD AI2= XXXXXXXX MCB X5= XXXXXXXX MCB DI5= ____________ MCB DO5= __________
● ALARM OUT CONFIG EMD AI3= XXXXXXXX MCB X6= XXXXXXXX MCB DI6= ____________ MCB DO6= __________
+/-Alarm 10: Alarm Type ► Faults= Fast MCB X7= XXXXXXXX EMA DI1= ____________ MCB DO7= __________
Problems= Slow MCB X8= XXXXXXXX EMB DI2= ____________ MCB DO8= __________
Warnings= Off EMB X1= XXXXXXXX EMD DI1= ____________ MCB DO9= __________
ALARM DELAYS EMB X2= XXXXXXXX EMD DI4= ____________ MCB DO10= __________
Frz Delay Time= 30s EMB X3= XXXXXXXX EMB DO1= __________
Air Flw Ing=120s EMB X4= XXXXXXXX EMB DO2= __________
Sens Alm Dly= 30s EMB X5= XXXXXXXX EMB DO3= __________
Temp AlmDly= 30s EMB X6= XXXXXXXX EMB DO4= __________
ALARM CONFIG EMB X7= XXXXXXXX EMB DO5= __________
Emerg Stop= ManClr EMB X8= XXXXXXXX EMB DO6= __________
Alm Log to SD= EMD X1= XXXXXXXX EMD DO1= __________
EVENT CONFIG EMD X2= XXXXXXXX EMD DO2= __________
Show Events= EMD X3= XXXXXXXX EMD DO3= __________
Event Log to SD= EMD X4= XXXXXXXX EMD DO4= __________
SNAPSHOT CONFIG EMD X5= XXXXXXXX EMD DO5= __________
Ena SnapShots= EMD X6= XXXXXXXX EMD DO6= __________
Show SnapShots= EMD X7= XXXXXXXX
SnapShots to SD= EMD X8= XXXXXXXX
BMS Communications
LON Set-Up ►
BACnet MSTP Set-Up ►
BACnet IP Set-Up ►
D-Net Set-Up ►
Network Unit Set-Up ►
Trending
Trending Ena= No
Apply Chgs= No
Sample Time= 300s
TrendOnOff= Off
Export Data= No
Clear Trend= Done
Points 1–8 (Fixed) ►
Points 9–24 (from List) ►
Points 25–27 (with IDs) ►
Points 28–30 (with IDs) ►
Points 1–8 (Fixed) Points 9–24 (from List) Points 25–27 (with IDs) Points 28–30 (with IDs)
Point 1= UnitSt Point 9= None Point 25 Point 28
Point 2= Clg% Point 10= None ID= F0AF0000 ID= F0AF0000
Point 3= Htg% Point 11= None Type= 0000 Type= 0000
Point 4= SAF% Point 12= None Mem Num= 0100 Mem Num= 0100
Point 5= OAD/Eco% Point 13= None Point 26 Point 29
Point 6= CtrlTmp Point 14= None ID= F0AF0000 ID= F0AF0000
Point 7= DAT Point 15= None Type= 0000 Type= 0000
Point 8= OAT Point 16= None Mem Num= 0100 Mem Num= 0100
Point 17= None Point 27 Point 30
Point 18= None ID= F0AF0000 ID= F0AF0000
Point 19= None Type= 0000 Type= 0000
Point 20= None Mem Num= 0100 Mem Num= 0100
Point 21= None
Point 22= None
Point 23= None
Point 24= None
Figure 87: Optional Outdoor Air Monitor – Changing the System of Units
Enter
↑/↓ (Select) Enter (Move →) Enter (Move →) (Action, Move →→)
During
Normal Operation Esc (Move ←) Esc (Move ←) Esc
(Move ←←)
Set Up ↓↑
IP/SI=SI SYS ↑
Comm Set Up ↓↑
Sets system of units to S-I
(MPS, LPS, sq.M., Pa., °C)
Ethernet Set Up ↓↑
Diagnostics ↑
Enter (Move →) Enter (Move →) Enter (Move →) Enter (Action, Move →→)
Esc (Normal Operation) Esc (Move ←) Esc (Move ←) Esc (Move ←←)
Set Up ↓↑
1
FS1=5000FPM ↓↑
1
LCD1 U/M=FPM ↓ 1
AR1=0.000 SQF ↓↑ 1
OUT1 U/M=FPM ↓↑ 1
OUT1=4-20mA ↓↑
1
FS1=10000FPM for GF1
or
1
FS1=5000CFM ↓↑
1
FS1=10000CFM for GF1
FS1=5000FPM ↓↑
LCD1 U/M=FPM ↓ AR1=0.00SQF ↑ OUT1 U/M=FPM ↓ 2
OUT1=0–10V ↓
FS1=10000FPM for GF1
or
Set area between In addition, “SW1” must be set
Displays airflow in FPM. 0.00 and 999.99 sq.ft. Area Outputs airflow in FPM. to the VDC position to change FS1=5000CFM ↓↑
affects the LCD display reading airflow output to 0–10VDC.
and output when set for CFM. FS1=10000CFM for GF1
2
OUT1=4–20mA ↑
1
FILTER1=0 ↓↑ 1
FLOW BUFF=30 ↓↑ 1
ALT=0 ↓↑ 1
OUT2 TYP=TEMP↓↑ 1
OUT2=4-20mA ↓↑
Adjust Filter1? Set Flow Buff? Set Altitude Set Out2 Type? 3
Set Out2?
OUT2 TYPE=ALRM ↑ 3
OUT2=0-5V ↓↑
3
OUT2=4-20mA ↑
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your
local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.