GENERAL NOTES AND SPECIFICATION

1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE RULES AND REGULATIONS OF THE LATEST EDITION OF THE
PHILIPPINE ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCE OF THE LOCAL GOVERNMENT AND WITH THE REQUIREMENTS OF
THE LOCAL POWER COMPANY.
2. SERVICE VOLTAGE TO THE BUILDING SHALL BE 230 VOLTS, 60 Hz, AND SINGLE PHASE.
3. ALL WIRING SHALL BE INSTALLED IN STANDARD POLYVINYL CHLORIDE RUN EMBEDDED INSIDE HOLLOW BLOCK AND CONCRETE
STRUCTURES, SLAB, COLUMNS, WALLS PARTITIONS, AND/OR RUN CONCEALED BETWEEN DOUBLE WALL WOODEN PARTITION AND
INSIDE CEILING SPACES.
4. ALL LIGHTING CIRCUIT HOME RUN TO PANEL BOARD MORE THAN 30 METERS IN LENGTH SHALL BE WIRED WITH NOT LESS THAN
3.5mm dia. IN SIZE UNLESS OTHER WISE INDICATED IN THE PLANS.
5. WHENEVER REQUIRED AND NECESSARY PULL BOX OR JUNCTION BOXES OF PROPER SIZES SHALL BE INSTALLED AT CONVENIENT
AND IN CONSPICIOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN IN THE PLANS NOR MENTIONED IN THE
SPECIFICATION.
6. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE.
7. ALL MOUNTING HEIGHT SHALL BE AS FOLLOWS:
A. LOCAL SWITCHES = 1.4 m ABOVE FINISH FLOOR LINE
B. RECEPTACLE = 0.31 m ABOVE FINISH FLOOR LINE
C. LIGHTING AND POWER PANEL BOARD = 1.980 m ABOVE FINISH FLOOR LINE
8. ALL CIRCUIT BREAKER SHALL BE BOLT-ON TYPE AND HAVE MINIMUM OF 10 KAIC.
9. ALL WORKS SHALL BE DONE UNDER DIRECT AND IMMEDIATE SUPERVISION OF DULY LICENSED ELECTRICAL ENGINEER.
10. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND APPROVAL OF THE DESIGNER AND THE
OWNER, ANY SUCH REVISION DONE WITHOUT APPROVAL SHALL CAUSE RESPONSIBILITY OF THE DESIGNER TO CEASE AS A WHOLE.