CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL
M 2
2 DETAILS, SEE DOCUMENT
3
3 V
4
1
3
PHASE
RWS112
SUPPLY
U
3 1 TR AN S F OR ME R TAP P IN G OP TION S
6

5 T ap Nominal 50/60Hz
U V W E TYP E 1
FS1
W 220/230
X 380/400
C1 C2 Y 400,415/420
U W X Y Z
Z 440/460
F US E F S 1= 250mA A NTI-S UR G E
SK2 TYP E 2
0VAC 1 W 346/380
TRANSISTOR SWITCHING FOR
PS1 X 480/500
24VDC CONTACTORS (IQ10-35) 120VAC 4
RELAYS ONLY FITTED WHEN Y 240/240
0VDC
120VAC CONTACTOR IS FITTED 3 4 Z 550/575
24VDC
FOR IQ40,70,90,91 & 95 24VDC 6 F US E F S 1= 250mA A NTI-S UR G E
_ 5 NOMINAL SUPPLY

+
(OUTPUT)
TYP E 3
SK14
X 660/660-690
0VDC 1
Y 690/-
24VDC 2 F US E F S 1= 150mA A NTI-S UR G E
SK13

26 WAY
REFER TO SHEET 2 FOR NOTES
& OPTION PCB'S IF FITTED

SK3 SK13 SK14


6 1 42
MONITOR RELAY
5 3 43
TORQUE 4 2 44
3
2 SK7
SENSOR 1 1 6
SK8 MAKE AT FULLY SHUT S1 8 7
POSITION 10 WAY
SENSOR
2 8
MAKE AT FULLY OPEN S2 7 9
SK9 3 10
BATTERY - 4
BREAK AT FULLY SHUT S3 6 11
1
4 12
+ BREAK AT FULLY OPEN S4 5 13
FS2 (IF FITTED) 100mA
BBC REMOTES MODULE SK1
SK4
CLOSE 6 33
50% SK6
9 SK1-5
COMMON -VE
5
8
SK4-9
40
2 SK1-7 7 SK4-2
18 WAY OPEN 2 35
8 SK1-1 1 SK4-8
REMOTE
CLOSED
STOP COMMON -VE 4 36
OPEN
1 SK1-3 3 SK4-1
LOCAL
ESD 14 25
12 SK1-13 13 SK4-12
COMMON -VE 16 31
5 SK1-15 15 SK4-5

STOP/MAINTAIN 10 34
COMMON -VE 3

OPEN INTERLOCK 13 37
COMMON -VE 6

CLOSE INTERLOCK 14 38
COMMON -VE 7 32
SK1 SK2
SLOT A SLOT B

Iss Date Chkd Revision Details IQ + BBC REMOTES


1 270813 PJW FIRST ISSUE www. .com
2 160614 MR 400v added to type 1 ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: JC1 Circuit Diagram Number Issue Sheet
tapping Y. Note added to Date : 270813 No
BATH, BA1 3JQ ROCHESTER
sheet 2 note 1.
ENGLAND NY 14624, USA
Base WD: 100B0200
Job No : - -
100B0200 2
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF

NOTES 3.INDICATION:
1.FUSES: -For typical position, status and alarm indication see PUB002-041.
-PS1 is a self-resetting fuse. -“S” contacts are user configurable and are shown in their default
-Refer to publication PUB002-039 for approved fuses FS1 and FS2. setting.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -Refer to PUB002-040 for functions and configuration instructions.
applies for rated torque performance; duty cycle is not guaranteed. -Monitor Relay indicates actuator availability for remote control (shown
2.REMOTE CONTROL: “unavailable”). It can be configured to exclude local/remote selection.
-For typical remote control circuits refer to: -Refer to PUB002-040 for monitored functions and configuration
-RWS indicated or PUB002-041. instructions.
-For DC control, connect –ve/0V to terminal 32. -Voltage applied to indication contacts must not exceed 150Vac
-(For negative switch / positive common, refer to RWS indicated). -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-Control signal threshold voltages: and no more than 8A in total for all 4 contacts.
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc.
-Control signal duration to be 300ms minimum. 4.BATTERY:
-Maximum current drawn from remote control signals is: -Battery maintains local and remote “S” contact indication only.
-8mA at 24Vdc. -Refer to installation manual for approved replacement battery types.
-Supply provided on terminals 4 & 5:
-Intended for remote control.
-Max external load 5W at 24Vdc.

Circuit Diagram Number Issue Sheet


No
100B0200 2 2
See Sheet 1 for all Revision details/information of 2