General Performance Table
MODEL MCR
(BASIC CEILING CONCEALED TYPE)
3 Rows Concealed Ceiling Mounted FCU
er 12Pa 13 15 16.5 18 19 28 31 34 40
code*17 m/3 h Weight (kg) 30Pa 13 15 16.5 18 20 28 31.5 35.5 41.5
B-with back plenum 50Pa 13.5 15.5 17 18.5 20.5 29 32.5 37 43
Default: Standard Default- without plenum
or
Water tray
Z: DC Brushless motor 2 Rows Concealed Ceiling Mounted FCU
Default: standard
E- Lengthening
Model 20 30 40 50 60 80 100 120 140
Pipe H 340 510 680 850 1020 1360 1700 2040 2380
S-12Pa, M-30Pa, 2-2 rows, 3-3rows 3
Rated air flow ( m /h) M 266 370 520 645 745 975 1265 1615 1780
H-50 Pa, 21-3 rows 4pipes
31-4rows, 4pipes L 210 265 395 475 560 735 960 1130 1490
G- Dry type Cooling capacity (W) H 1770 2650 3550 4220 5450 7100 8750 10260 11980
D- Large temper
Heating capacity (W) H 2655 3975 5320 6715 8175 10650 12970 15390 17960
Water flow (kg/h) H 304 455 610 760 937 1221 1505 1764 2060
Water resistance (kpa) H 4 8 17 21 37 39 24 33 48
12Pa 31 46 62 75 94 126 150 189 228
Input power( W) 30Pa 43 54 71 86 108 142 171 212 253
50Pa 48 65 84 100 118 174 210 250 300
12Pa 12 14 15.5 16.5 17.5 26 29 31 36
Weight (kg) 30Pa 12 14 15.5 16.5 18.5 26 29.5 32.5 37.5
50Pa 12.5 14.5 16 17 19 27 30.5 34 39
3
4
General Performance Table Entering Air Condition DB=24 C, WB=17.9 C,
O O
REMARK:
1. The rated condition is based on < Fan Coil Unit> standard( GB/T 19232-2003) 5
Cooling: Return air DB=27 C, WB= 19.5 C, Cooling Water: Water in=7 C, Water rising= 5 C
O O O O
Heating: Return air DB=21 C, Heating Water: Water in=60 C, Water flow is the same as cooling.
O O 6
2. The standard working pressure of coil is 1.6 Mpa, if you require for more than 1.6 Mpa, please mark out when order.
3. 21- 3 rows 4 pipes’ weight refer to 3 rows.
Entering Air Condition DB=26 C, WB=18.7 C, Entering Air Condition DB=26 C, WB=19.5 C,
O O O O
7
8
Entering Air Condition DB=27 C, WB=19.5 C, Entering Air Condition DB=20 C, WB=20.4 C,
O O O O
9
10
–
Entering Air Condition DB=28 C, WB=22 C, Entering Air Condition DB=16 C,
O O O
11
12
Entering Air Condition DB=18 C, Entering Air Condition DB=20 C,
O O
13
14
Entering Air Condition DB=22 C, MCR - Dry Type Fan Coil Unit Performance
O
Water Water in temperature ( ) This type save the energy of water condensed by changing the serpentine, the selection is based on sensible
W.P.D heating, it can decrease the energy consumption of the chiller and the whole system in thermal moisture control
Model flow 40 45 50 60 70 80
(kPa) system.
(l/min) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw)
3 1 1.4 1.78 2.17 2.95 3.72 4.49
6 5 1.62 2.07 2.53 3.43 4.33 5.23 20 30 40 50 60 80 100 120 140
20 Model
9 8 1.71 2.19 2.66 3.61 4.56 5.51 H 340 510 680 850 1020 1360 1700 2040 2380
12 12 1.72 2.2 2.67 3.62 4.57 5.52 3
M 266 370 520 645 745 975 1265 1615 1780
Rated air flow ( m /h)
4 2 1.93 2.47 3 4.08 5.15 6.22 L 210 265 395 475 560 735 960 1130 1490
6 5 2.14 2.74 3.33 4.52 5.71 6.9 Cooling capacity W 680 1020 1360 1700 2040 2720 3400 4080 4760
30
9 12 2.3 2.94 3.58 4.86 6.13 7.41 Water flow kg/h 117 175 234 292 351 468 585 702 819
12 14 2.39 3.05 3.71 5.04 6.36 7.69 Water resistance kPa 5 11 18 21 38 39 24 35 48
6 6 2.7 3.45 4.2 5.7 7.2 8.69 Heating capacity W 1490 2240 2990 3740 4500 5980 7480 8970 10470
8 9 2.88 3.68 4.48 6.08 7.69 9.29 12Pa 46
40 31 62 75 94 126 150 189 228
12 19 3.09 3.94 4.8 6.51 8.23 9.94 Input power W 30Pa 43 54 71 86 108 142 171 212 253
15 27 3.17 4.05 4.93 6.7 8.46 10.22
50Pa 48 65 84 100 118 174 210 250 300
8 9 3.43 4.38 5.33 7.24 9.15 11.05 Fan type Double-sized intake multiple blade
12 17 3.72 4.75 5.78 7.84 9.9 11.97 Motor Single phase guide capacity motor
50
15 24 3.84 4.9 5.97 8.1 10.23 12.36 Coil type Crossed coils
18 33 3.92 5.01 6.1 8.28 10.46 12.63 Water in and return connection 3/4 FPT (Inner screw)
8 12 3.82 4.88 5.94 8.06 10.18 12.3 Condensing water connection 3/4 FPT (Inner screw)
60 16 37 4.38 5.6 6.81 9.25 11.68 14.11 12Pa 14 16 18 31 34 44
19.5 21 38
20 53 4.51 5.76 7.01 9.51 12.01 14.52 4rows 4 pipes Weight kg 30Pa 14 16 18 19.5 22 31 34 39.5 45.5
10 10 5.16 6.59 8.03 10.89 13.73 16.63 50Pa 15 17.5 20 22 24 35 37 44 53
15 20 5.68 7.26 8.81 12 15.16 18.32
80
20 32 5.94 7.63 9.29 12.61 15.93 19.25
NOTES:
30 63 6.28 8.03 9.77 13.26 16.75 20.24
1. The rated condition is based on < Fan Coil Unit> standard( GB/T 19232-2003)
15 9 6.38 8.15 9.92 13.46 17 20.55 Cooling: Return air DB=26 C, WB= 18.7 C, Cooling Water: Water in=16 C, Water rising= 5 C
O O O O
20 15 6.81 8.71 10.6 14.39 18.17 21.96 Heating: Return air DB=21 C, Heating Water: Water in=40 C, Water flow is the same as cooling.
O O
100 2. The standard working pressure of coil is 1.6Mpa, if you require for more than 1.6Mpa, please mark out when order.
25 22 7.1 9.07 11.04 14.99 18.93 22.87
35 35 7.45 9.51 11.58 15.72 19.86 23.99
15 10 6.78 8.67 10.55 14.32 18.08 21.85
22 19 7.45 9.52 11.59 15.74 19.88 24.02
120
30 32 7.88 9.01 12.26 16.64 21.02 25.4
40 52 8.19 10.47 12.75 17.3 21.85 26.4
25 26 8.67 11.08 13.49 18.31 23.12 27.94
30 35 8.97 11.46 13.96 18.94 13.93 28.91
140
35 45 9.19 11.75 14.3 19.41 24.51 29.62
45 69 9.5 12.14 14.78 20.01 25.34 30.62
15
16
MCR - Large Temperature Difference Dimensions
Fan Coil Unit Performance
This type save the energy of water condensed by changing the serpentine, the selection is based on sensible 1. Condensing water outlet 3/4MPT
heating, it can decrease the energy consumption of the chiller and the whole system in thermal moisture control 2. Wiring box
system. 3. Water outlet 3/4 FPT
4. Water inlet 3/4 FPT
Model 20 30 40 60 80 100
H 340 510 680 1020 1360 1700 NOTES:
1. M- Motor quantity.
3
Rated air flow ( m /h) M 266 370 520 745 975 1265
2. F- Fan quantity.
L 210 265 395 560 735 960 3. Return air box can be selected as back return air or bottom return air.
Cooling capacity W 2370 7650 9490
4. Can be changed to back return air or bottom return air at site.
3130 3690 5320
5. Return air inlet size 205 x E.
Water flow kg/h 117 175 234 351 468 585 6. Common drip tray (L=175) and Lengthen drip tray (L=300).
Water resistance kPa 5 11 18 38 39 24 7. Heating water outlet 3/4 FPT.
8. Heating water inlet 3/4 FPT.
Heating capacity W 1490 2240 2990 4500 5980 7480
12Pa 31 46 62 94 126 150
Input power W 30Pa Four Pipes
43 54 71 108 142 171
50Pa 48 65 84 118 174 210
Fan type Double-sized intake multiple blade
Motor Single phase guide capacity motor
Coil type Crossed coils
Water in and return connection 3/4 FPT (Inner screw)
Condensing water connection 3/4 FPT (Inner screw)
12Pa 14 16 18 21 31 34 Installation of four pipes
return air box
4rows 4 pipes Weight kg 30Pa 14 16 18 22 31 34 Installation of return air box
50Pa 15 17.5 20 24 35 37
Back
return
Installing hole 4-10 x 20 air
NOTES: outlet
1. The rated condition is based on < Fan Coil Unit> standard( GB/T 19232-2003)
Cooling: Return air DB=26 C, WB= 18.7 C, Cooling Water: Water in=16 C, Water rising= 5 C
O O O O
Back return air outlet Bottom return air outlet
Heating: Return air DB=21 C, Heating Water: Water in=40 C, Water flow is the same as cooling.
O O
2. The standard working pressure of coil is 1.6Mpa, if you require for more than 1.6Mpa, please mark out when order.
17
18
–
General Performance Table
MODEL MCE Horizontal/Vertical Exposed Type-2 pipes
Design Reference
Cooling capacity Total H W 1800 2700 3600 4500 5400 7200 9000 10800 12600
Heating capacity H W 2700 4050 5400 6750 8100 10800 13500 16200 18900
6 Air discharge way Input power H W 37 52 62 76 96 134 152 189 228
3
Water flow H m/ h 0.31 0.46 0.62 0.77 0.93 1.23 1.54 1.85 2.16
Water resistance kPa 7 15 18 23 28 30 22 30 36
( face the air out spigot) Water in&out pipe dia. ZG3/4"
Pipe Cooling coil type Copper tube, aluminum fins
Default-2 pipes , F-4 pipes Maximum working pressure Mpa 1.6
Condensate pipe size mm 16
3
/h
4. 6 discharge air way. Heating: Return air DB=21 C, Heating Water: Water in=60 C, Water flow is the same as cooling.
O O
2. The standard working pressure of coil is 1.6Mpa, if you require for more than 1.6Mpa, please mark out when order.
19
A B C D E F 20
–
Dimensions
CASSETTE FAN COIL UNIT
MKM2 0B L
Design Reference
3
spec*17 m/h
Features
1. 4 way air flowing, which can uniform temperature distribution in the room.
4.2mm
20 -70
Model 20 30 40 50 60 80 100 120 140
A 858 908 1058 1208 1258 1608 1758 1908 2058
B 608 658 808 958 1008 1358 1508 1658 1808 2. Easy to be installed, low installation cost. Compare to concealed fcu, no need install inlet and outlet seperately.
C 583 633 793 933 983 1333 1483 1633 1783 Neither connect to the duct and do insulation work.
Motor No. 1 2 2 2 2 4 4 4 4 3. Remote controller is standard and wire controller is optional.
Fan No. 1 1 1 1 1 2 2 2 2 4. Using scroll centrifugal fan with big diameter, quiet running.
5. Fan and motor is easy to maintain; Remove the grill, the wind guide ring can be taken out, the fan is smaller
than the foam wind ring, it is easy to take out the fan and motor.
panel
fan and motor
drain tray
6. Square panels, which can choose the direction of inlet/outlet water connection freely.
21
22
Performance Table Dimensions
MKM MKM MKM MKM MKM MKM MKM MKM MKM MKM
3. Heating Condition: Air on DB=21 C, Water in=60 C, Water flow is the same as cooling.
O O
23
24
– –
WIRING DIAGRAM IMPORTANT NOTICE ON INSTALLATION
3 Speed Type
AND RUNNING
1. Run the fan and impeller before installation, to check no attrition and blockage.
WIRING DIAGRAM 2. When installing the unit, use valve for the water outlet, keep good insulation between pipes and valve.
3. The weight of air duct and water pipe connected to the unit can’t be supported by the unit itself.
Operate 4. The drain pipe can’t be squeezed or bent, must keep enough slope.
Terminal board 5. Open the air vent valve before using; close it after the air exhaust and water flow out, then start the unit.
220V 50H z
6
6. Clean the filter regularly.
yellow
7. There are ground screw holes on the casing, connect them to the safety system during installing.
5
8. Connect the wire according to the wiring diagram of unit, wrong wiring will cause motor damage.
Motor
4 9. Mark out the pipe direction when ordering, the pipe direction can be changed at site.
8
red 3 10. AW standard unit are without return air box, please note if you need return air box when ordering.
3
blue 2 11. Set the unit horizontally, don’t supply cooling water when the fan has stopped.
2 5
black 1
1
H M L OFF • Prevent frosting
If the temperature on the ceiling or in the room is lower than 0 , the heat exchanger will be damaged by water
for users frost. Circulate the water by running the water circulate pump.
• Don’t stop the fan coil unit when cooling water is supplied.
NOTE: If cooling water is supplied continuous, the temperature of fan coil unit will be decreased, which will cause
Please use 1.6mm (or above) 600V PVC wire to connect the 3 speed switch and terminal board as dotted line at site. moisture condensation on the unit, causing water to drop on the ceiling or floor.
When the fan coil unit has been stopped for more than 8 hours, please close the water outlet valve and water
supply. If you can’t stop supplying the cooling water, please turn the switch to “L”.
DC Brushless Motor Type
• Please note, there will be moisture condensation if the high temperature and high humidity air comes in the unit.
Please install the unit far away from busy doors, opened air exchange window or steams, although the room will
WIRING DIAGRAM be air-conditioned, but the above situation will cause moisture condensation.
1PH\220V\50H z
• There will be frost if the units are used in the wet place, such as new building.
N
Black 1 If the unit is running in a humid place, the outside of fan coil unit will be frosted. So please run the unit by
red 2 L increasing the water temperature or decreasing the water flow.
Motor 3
yellow 4
high • There will be moisture condensation on the ceiling at high temperature and high humidity or caused by cooling
5
middle at low temperature.
brown
6
low The unit installed on the ceiling will be frosted, when cooling at low temperature or high temperature and
orange
humidity on the ceiling.
blue 7 con
3-speed swith
8 • There will be moisture condensation after long operation time.
If the unit is running for 24 hours without stopping, please install electric air damper and temperature regulator.
NOTE:
Please use 1.6mm (or above) 600V PVC wire to connect the switch and terminal board as dotted line at site.
25
26
–
Johnson Controls - Hitachi Air Conditioning
The specifications of this catalog may change without prior notice to allow
Hitachi Cooling & Heating to incorporate the latest innovations for its customers.
The information contained in this catalog is merely informative.
Hitachi Cooling & Heating declines any responsibility in the broadest sense, for Find the products Hitachi Cooling & Heating
damage, direct or indirect, arising from the use and / or interpretation of the recommendations with the best service and conditions at your
in this catalog. Hitachi Distributor.