Single-phase, Three-phase/Single-phase,
Three-phase/Two-phase,Three-phase
ELECTRICAL CHARACTERISTICS :
Secondary load voltage : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V.
Couplings :
Standard : Three-phase transformer : Step-down Dyn11 - Step-up YNd1– single-phase transformer :Ii0
Specific : Three-single transformer, Leblanc three-two transformer, other couplings on request.
CONNEXION:
Primary and secondary connesion on copper slots, by the upper side of the transformer.
STANDARD ACCESSORIES :
Empty setting plugs : Three outputs on slots.
Two earthing switches.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
NOTE :
Transformers mechanical and electrical characteristics are the same
for step-down or step-up transformers. The tranformers are not
reversible.
Single-phase transformer, TMAI type, with IP21 encolsure, fuse terminal 3200 V
and locking.
2
CONSTRUCTION :
Magnetical circuits with crystal made sheet metal, oriented, with low losses.
Copper windings, vacuum impregnated of H class and applying of a fungicide varnish.
Metallic flanges.
Ironed chassis with rollers.
Wooden terminals plate bakelised.
Connexion plates
Tap changer
MV side view
rollers
Side panel dismantling
(cables passage) Signaletic plate
Fixation by screw
Bakélite matter Firm plate
To be screwed on request LV side dismantling panel
3
Three-phase dry Type Transformers
TTAI
ELECTRICAL CHARACTERISTICS :
Power rating:
16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - 250 - 400 - 500 - 630 kVA
Couplings :
Step-down Dyn11 - Step-up YNd1, other couplings on request.
CONNEXION :
Primary and secondary connexions on copper plates, by the upper side of the transformer.
STANDARD ACCESSORIES :
Voltage tapping adjustable out of voltage : +/- 2,5 % or +- 5% output on slots.
Two earthing terminals.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
Naked presentation on frame : IP00.
OPTIONAL ACCESSORIES
Painted sheet metal enclosure with natural airing upwards, IP21.
Connexion on pluggable terminals 3200 V or 5500 V.
HRC fuses protection integrated above the protection envelop.
Thermal protection by thermal probe integrated to windings, one or two thresholds protection.
Tap changers +/- 2,5 % +/- 5%.
Keyhole locking of the protection envelop and or pluggable terminals.
NOTE :
Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The
tranformers are not reversible.
Step-up transfrormers are built so that inrush currents are limited.
ELECTRICAL CHARACTERISTICS
Power rating (kVA) 16 25 32 50 63 80 100 125 160 200 250 400 500 630
Copper losses
350 470 550 800 1000 1100 1350 1400 2000 2300 2800 4200 5600 7300
at 75°C (W)
Iron losses (W) 100 180 200 250 250 380 450 450 500 550 650 900 1250 1500
Voltage drop
(% ) 3.3 3 3.07 3.14 3.4 3 3.2 3 3.4 3.2 3.15 3.5 3.5 3.5
at Cos = 0.83
CC tension
3.4 3.2 3.4 3.5 4 3.5 4 4 4 4 4 4 4.5 5
(%) at 75°C
Empty current
1 0.7 0.8 0.9 0.7 0.8 0.9 0.6 0.7 0.5 0.5 0.8 0.6 0.7
(%)
4
TTAI Dry Transformers
SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME - STEP DOWN TRANSFORMER
Power rating
16 25 32 50 63 80 100 125 160 200 250 400 500 630
(kVA)
A 636 750 825 825 840 930 930 950 980 1000 1096 1240 1400 1600
B 400 480 500 500 520 530 530 530 530 570 660 660 830 900
C 611 670 718 718 734 809 809 836 858 889 1086 1134 1300 1650
D 380 510 510 510 520 580 580 590 610 650 690 770 870 900
E 295 400 400 400 400 440 440 440 440 465 520 520 520 520
Weight (kg) 155 270 310 345 365 450 465 525 600 700 940 1185 1450 1800
Power rating
16 25 32 50 63 80 100 125 160 200 250 400 500 630
(kVA)
A 850 960 1040 1040 1050 1140 1140 1160 1190 1220 1310 1550 1610 1810
B 550 630 650 650 660 660 660 660 680 720 810 810 980 1050
C 900 970 1020 1030 1040 1100 1100 1140 1200 1200 1390 1500 1600 1950
D 380 510 510 510 520 580 580 590 610 650 690 770 870 900
E 295 400 400 400 400 440 440 440 440 465 520 520 520 520
Weight (kg) 185 300 350 400 405 535 565 630 750 900 1150 1450 1700 2050
5
Single-phase Dry Type Transformers
TMAI
ELECTRICAL CHARACTERISTICS :
Couplings :
Standard : single-phase transformer : Ii0
CONNEXION :
Primary and secondary connexions on copper plates, by the upper side of the transformer.
STANDARD ACCESSORIES :
Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties sur plages.
Two earthing terminals.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
Naked presentation on IP00 frame.
OPTIONAL ACCESSORIES
Painted sheet metal enclosure with natural airing upwards, IP21.
Connexion on pluggable terminals.
HRC fuses protection integrated above the protection envelop.
Thermal protection by thermal probe integrated to windings, one or two thresholds protection.
Tap changers +/- 2,5 % +/- 5%.
Keyhole locking of the protection envelop and or pluggable terminals.
NOTE :
Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The
tranformers are not reversible.
Step-up transfrormers are built so that inrush currents are limited.
ELECTRICAL CHARACTERISTICS
Power rating (kVA) 5 7,5 10 16 25 32 50
Copper losses
100 120 170 380 500 630 750
at 75°C (W)
Iron losses
40 60 60 80 120 150 200
(W)
Voltage drop (% )
2.92 2.47 3.35 3.7 3.53 3.55 3.7
at Cos = 0.83
Cc tension
2.95 2.67 3.75 3.86 3.78 4 4
(%) at 75°C
Empty current
3.11 2.53 2.58 2.67 2.52 2.54 2.51
(%)
6
TMAI Dry Transformers
SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME
7
AUGIER IS CERTIFIED ISO 9001 SINCE 1995
60 40152 With constant improvements, the manufacturer may alter information without prior warning