BL: 02-NOV-2022

FIRE SAFETY PLAN APPROVALS DRAWINGS


PROJECT NAME: TRACKING NUMBER-2211018
PROPOSED ( BASEMENT+G+9) 10 STORIED PROJECT DATA:
RESIDENTIAL CUM COMMERCIAL BUILDING 01 OCCUPANCY TYPE A-3,F-2
PLAN FOR ADDUHA ALI GANG AT KO - 189, 02 HAZARD GROUP LIGHT HAZARD- II
03 ROAD WIDTH ( FRONT) 22'-0" WIDE ROAD
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. 04 TOTAL BUILDING HEIGHT 100'-0"
05 TYPE OF BUILDING RCC FRAME STRUCTURE
CLIENT: 06 CODE & STANDARD BNBC-2006,2020

MRS. ADDUHA ALI GANG

CONSULTANT:

ASANTO LIMITED
P D L
P M D
ONE STOP MEP SOLUTION E

APPROVED BY:

DEPARTMENT OF FIRE SERVICE AND CIVIL DEFENCE


R A R
S D
BL : 02 NOV-2022
List Of Drawing

Sl. No. Drawing Title Sheet No


01 Fire Safety Plan Layout-Cover Page FSP-00
02 Fire Safety Plan Layout - List of Drawing FSP-01
03 Fire Safety Plan Layout - Project data and floor details information FSP-02
04 Fire Safety Plan Layout - Site Google Map FSP-03-A
05 Fire Safety Plan Layout - basement Floor Plan FSP-03
06 Fire Safety Plan Layout - Ground Floor Plan FSP-04
07 Fire Fighting & Suppression System Plan-Cover Page --
08 Fire Fighting & Suppression System Plan- Instruction FSP-05
09 Fire Fighting & Suppression System Plan- Ground Floor FSP-06
10 Fire Safety Plan Layout - 1st Floor Floor Plan FSP-07
11 Fire Safety Plan Layout - 2nd Floor Floor Plan FSP-08
12 Fire Safety Plan Layout - 3rd to 6th Floor Plan FSP-09
13 Fire Safety Plan Layout - 7th Floor Plan FSP-10
14 Fire Safety Plan Layout - 8th-9th Floor Plan FSP-11
15 Fire Safety Plan Layout - Roof Floor Plan FSP-12
16 Fire Safety Plan Layout - PUMP DETAILS & RISER DIAGRAM FSP-13
17 Fire Safety Plan Layout - SINGLE LINE DIAGRAM (SLD) FSP-14
18 PROPOSED FIRE ALARM RISER DIAGRAM FSP-15
Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, LIST OF DRAWING Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-01
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
PROJECT DATA: BL : 02 NOV-2022
01 OCCUPANCY TYPE A3, F2 Symbol Item Description

02 HAZARD GROUP LIGHT HAZARD- II Diesel


Pump ENGINE PUMP

03 ROAD WIDTH ( FRONT) 22'-0" WIDE ROAD Electric


Pump ELECTRIC PUMP

Jockey
04 TOTAL BUILDING HEIGHT

Pump
JOCKEY PUMP
100'-0"
05 TYPE OF BUILDING RCC FRAME STRUCTURE
06 CODE & STANDARD BNBC-2006,2020 SYMBOL & LEGEND:

Symbol Item Description

FLOOR DETAILS INFORMATION: Fire Alarm Control Panel


Smoke Detector
FLOOR NAME AREA(SFT) USES FOR
Heat Detector
BASEMENT FLOOR 7,050 CAR PARKING, WATER RESERVOIR,FIRE PUMP ROOM, R/F

STAIR, LIFT R/F


Multi Sensor Detector

RECEPTION, WAITING LOUNGE, COMMERCIAL SPACE, GENERATOR F Manual Pull Station


GROUND FLOOR 7,050 ROOM, ELECTRO MECHANICAL ROOM, SAFETY LOBBY, STAIR, LIFT OM Control Module
PROPOSED (B+G+9TH) COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT,
7,050 Monitor Module
10 STORIED 1ST FLOOR
TOILET
RESIDENTIAL CUM Horn-Strobe
COMMERCIAL BUILDING. 2ND FLOOR COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, Hose Cabinet With 38mm Ø 30m long Fire Hose Real
7,050
TOILET and 63mm Landing valve
COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, Upright Sprinkler K-8.0
3RD FLOOR 7,050
TOILET Fire Extinguisher(5kg ABC Type)
4TH FLOOR COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT,
7,050 Fire Extinguisher (5Kg CO2 Type)
TOILET
REVISED & PROPOSED OF TWENTY
THREE STORIED HEAD OFFICE BUILDING
WITH TWO BASEMENT
+ ONE SEMI SEMI BASEMENT
FOR PADMA OIL COMPANY LTD.
ON R.S. PLOT NO. 2447(P), 2450(P)
& B.S. PLOT NO. 1037,
MOUZA: GOSAILDANGA, P.S. BANDAR
AT AGRABAD C/A, CHATTOGRAM.

5TH FLOOR COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, PA System Speaker
7,050
TOILET
EXIT Exit Sign
6TH FLOOR COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT,
7,050
TOILET
Emergency Light
7TH FLOOR COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT,
7,050 Emergency Exit Light
TOILET

8TH FLOOR DRAWING & DINING, KITCHEN, BED ROOM, SAFETY Gas Discharge Nozzle (1" dia)
7,050
LOBBY, STAIR, LIFT, TOILET.
Lightning Arrestors
9TH FLOOR DRAWING & DINING, KITCHEN, BED ROOM, SAFETY
7,050
LOBBY, STAIR, LIFT, TOILET. S 2 hr Fire Rated Door
4 hr Fire Rated Wall
ROOF 995 LIFT MACHINE ROOM, STAIR

TOTAL AREA= 78,545 SFT

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, PROJECT DATA & FLOOR Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. DETAILS INFORMATION Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-02
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022

MRS. MRS. ADDUHA ALI GANG

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, GOOGLE MAP Engr. Md.Harunur Rashid FDS-3-A
M D
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE ISSUED FOR: REV : 00
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BASEMENT FLOOR PLAN (CAR PARKING, WATER RESERVOIR, BL : 02 NOV-2022
FIRE PUMP ROOM, STAIR, LIFT)
FLOOR AREA : 7050 SFT
750x350
MECHANICAL Ventilation Duct:

750x350
102'-0" MECHANICAL Ventilation Duct:
R/F
15000 CFM
FAN(DUCTED)

S
FIRE

EXIT
ESCAPE
ENIGNE LESEID
U.G.W.R FOR FIRE FIGHTING
SIZE=27'-6"X18'-10"X12'-0"

Qty.
F

01
01
01
OM
FD
R/F TOTAL CAPACITY=44,841 US GALLONS 15000 CFM
R/F
FAN(DUCTED)
REQUIRED FOR FIRE FIGHTING
=37,500 US GALLONS(50MIN)

ELECTRIC PUMP

JOCKEY PUMP
Item Description

ENGINE PUMP
UP
EXIT

R/F R/F R/F R/F

Diesel
Pump
LEVEL(-)5'-6"

Symbol
FIRE LIFT Jockey
Pump
8'-0"x7'-0"

Electric
Pump
F UP
74'-1"

SYMBOL & LEGEND:

64'-9"
Symbol Item Description Qty.
Fire Alarm Control Panel 00
Smoke Detector 00
R/F R/F
Heat Detector 16
R/F
Multi Sensor Detector 00
F Manual Pull Station 03

R A M P
OM Control Module 01
R/F R/F R/F R/F Monitor Module 00
Horn-Strobe 05
Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02
and 63mm Landing valve
Upright Sprinkler K-8.0 63
Fire Extinguisher(5kg ABC Type) 09
Fire Extinguisher (5Kg CO2 Type) 09
PA System Speaker 07

F EXIT Exit Sign 02


FAN(DUCTED)
15000 CFM Emergency Light 25
FAN(DUCTED)
LIFT 15000 CFM Emergency Exit Light 01
LIFT 93'-6"
R/F R/F
R/F Gas Discharge Nozzle (1" dia) 00
R/F
Early Streamer Emission 00
S 2 hr Fire Rated Door
S S
3 hr Fire Rated Door
4 hr Fire Rated Wall
MECHANICAL Ventilation Duct:
750x350 MECHANICAL Ventilation Duct:
750x350

BASEMENT FLOOR PLAN (Parking). 0 1' 2' 4' 10' 20'


Scale: 1:100 SCALE (GRAPHIC SCALE)

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, BASEMENT FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-03
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
GROUND FLOOR PLAN (RECEPTION, WAITING LOUNGE, COMMERCIAL SPACE,
GENERATOR ROOM, ELECTRO MECHANICAL ROOM, SAFETY LOBBY, STAIR, LIFT)
FLOOR AREA : 7050 SFT
R1-∅100mm Stand Pipe(Riser) S 93'-6"

Toilet F OM

WASH
FIRE ESCAPE 5'-0"X3'-7" EXIT FD

SYMBOL & LEGEND:


8'-0"x22'-4"
5'-10"

Agent (ACA) Cylinder


R/F
Toilet Symbol Item Description Qty.

Automatic Clean
5'-7"X4'-0" R/Frated wall
four hour fire A/C OUTER UNIT
R/F

LADIES Fire Alarm Control Panel 01


ELECTRO MECHANICAL ROOM
Toilet
3'-7"X5'-0"
Toilet
3'-6"X5'-0" 3'-11" 22'-0"x18'-0" Smoke Detector 01
R/F
Heat Detector 04
WASH

4'-0"

R/F
SUBSTATION ROOM
UP GENTS
1000 KVA
R/F
Multi Sensor Detector 00
S

Manual Pull Station 04


EXIT

R/F
F
GENERATOR SPACE

four hour fire rated wall


F OM
FD
22'-0"x12'-0" OM Control Module 04
LOBBY

FIRE LIFT
Monitor Module 00
8'-0"x7'-0"
Horn-Strobe 06
63'-11"

EXIT EXIT Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
F
and 63mm Landing valve
OM
Automatic Clean FD
S F OM
Automatic Clean FD
S
STAIR Agent (ACA) Cylinder Agent (ACA) Cylinder
2 hr Fire Rated Door
Upright Sprinkler K-8.0 63
RECEPTION

A/C OUTER UNIT


2 hr Fire Rated Door
(single Leaf) (single Leaf)
Fire Extinguisher(5kg ABC Type) 09
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 09


WAITING LOUNGE

RAMP
PA System Speaker 07
S
TOILET
UP DN EXIT F OM
FD
3'-6"x6'-6"
EXIT Exit Sign 04
FACP ROOM
R/F
Emergency Light 08
GUARD
6'-0"x11'-5"
SAFETY LOBBY Emergency Exit Light 04

LEVEL
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT LEVEL
+ 4'-6" RAMP
± 1'-0" Early Streamer Emission 00
UP S 2 hr Fire Rated Door
93'-6"

GREEN GREEN
GREEN S S
3 hr Fire Rated Door

UP
UP 4 hr Fire Rated Wall

DOWN TO BASEMENT

GROUND FLOOR PLAN 0 1' 2' 4' 10' 20'


SCALE: 1:100 ASSEMBLY POINT
SCALE (GRAPHIC SCALE)

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, GROUND FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-04
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
FIRE FIGHTING AND SUPPRESSION SYSTEM DRAWINGS FOR 1000 KVA SUBSTATION
ROOM, GENERATOR

PROJECT DATA:
PROJECT NAME:
01 OCCUPANCY TYPE A3, F2
PROPOSED ( BASEMENT+G+9) 10 STORIED 02 HAZARD GROUP LIGHT HAZARD- II
RESIDENTIAL CUM COMMERCIAL BUILDING 03 ROAD WIDTH ( FRONT) 22'-0" WIDE ROAD
PLAN FOR ADDUHA ALI GANG AT KO - 189, 04 TOTAL BUILDING HEIGHT 100'-0"
05 TYPE OF BUILDING RCC FRAME STRUCTURE
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. 06 CODE & STANDARD BNBC-2006,2020

CLIENT
BL: 02 NOV 2022

MRS. ADDUHA ALI GANG


CONSULTANT:

ASANTO LIMITED
P D L P
M D
ONE STOP MEP SOLUTION E

APPROVED BY:

DEPARTMENT OF FIRE SERVICE AND CIVIL DEFENCE


R A R
S D
BL : 02 NOV-2022

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, SUPPRESSION SYSTEM PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. INSTRUCTION Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-05
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
TRANSFORMER Discharge Nozzle Automatic Clean Agent
BL : 02 NOV-2022
1. VOLTAGE 11KV /0.415 KV Discharge Pipe
Fire Detector
Distribution System
2. PHASE 3 PHASE-4 WIRE Notification Appliances for substation, generator,
3. TYPE ( OIL / DRY) OIL Control Panel electromechanical room,
Automatic Clean
Agent (ACA) room size
EARTHING QNTY CONDUCTOR SIZE Cylinder
Approximately 1337 sft SYMBOL & LEGEND:
1. TRANSFORMER 1 4SWG
Symbol Item Description Qty.
Fire Alarm Control Panel
S 00
Smoke Detector 03
R/F
Heat Detector 00
F OM R/F
Multi Sensor Detector 00
EXIT FD

F Manual Pull Station 03


OM Control Module 03
Agent (ACA) Cylinder

Monitor Module 00
Horn-Strobe 03
Automatic Clean

four hour fire rated wall Hose Cabinet With 38mm Ø 30m long Fire Hose Real 00
and 63mm Landing valve
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 03
ELECTRO MECHANICAL ROOM Fire Extinguisher (5Kg CO2 Type) 03
22'-0"x18'-0" PA System Speaker 04
EXIT Exit Sign 03
SUBSTATION ROOM Emergency Light 03
1000 KVA Emergency Exit Light 03
Gas Discharge Nozzle (1" dia) 14
Early Streamer Emission 00
GENERATOR SPACE 00

four hour fire rated wall


S 2 hr Fire Rated Door

22'-0"x12'-0" S S
3 hr Fire Rated Door
4 hr Fire Rated Wall

02

02

Automatic Clean
02
EXIT EXIT Agent (ACA) Cylinder
F OM
F OM
Automatic Clean FD
S Automatic Clean FD
S
Agent (ACA) Cylinder Agent (ACA) Cylinder
2 hr Fire Rated Door 2 hr Fire Rated Door
(single Leaf) (single Leaf)

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, SUPPRESSION SYSTEM PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. GROUND FLOOR Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-06
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
1st FLOOR PLAN (COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, TOILET)
FLOOR AREA : 7050 SFT
21'-6"

Toilet
5'-0"X4'-0" 72'-2"
FIRE ESCAPE EL.ROOM SYMBOL & LEGEND:
8'-0"x22'-4"
5'-10"
Toilet
R1-∅100mm Stand Pipe(Riser)

5'-7"X4'-0"
R/F
A/C OUTER UNIT Symbol Item Description Qty.
LADIES R/F
R/F

Toilet
Fire Alarm Control Panel 00
5'-7"X4'-0"

5'-10"
Smoke Detector 10
Toilet
5'-7"X4'-0"
R/F
R/F
Heat Detector 04
UP GENTS

R/F
Multi Sensor Detector 00
F
EXIT

R/F
F Manual Pull Station 02
S

02
OM
FD
OM Control Module
Monitor Module 00
LOBBY

FIRE LIFT
8'-0"x7'-0"
Horn-Strobe 04
63'-11"

Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 06
COMMERCIAL SPACE
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 06


PA System Speaker 05
S

UP DN EXIT F OM
FD EXIT Exit Sign 02

R/F
Emergency Light 10
SAFETY LOBBY Emergency Exit Light 02
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT
Early Streamer Emission 00
S 2 hr Fire Rated Door
93'-6"
S S
3 hr Fire Rated Door
0 1' 2' 4' 10' 20' 4 hr Fire Rated Wall
1st FLOOR PLAN (COMMERCIAL)
SCALE (GRAPHIC SCALE)
SCALE: 1:100

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, 1ST FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-07
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
2nd FLOOR PLAN (COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, TOILET)
FLOOR AREA : 7050 SFT
21'-6"

Toilet
5'-0"X4'-0" 72'-2"
FIRE ESCAPE EL.ROOM SYMBOL & LEGEND:
8'-0"x22'-4"
5'-10"
Toilet
R1-∅100mm Stand Pipe(Riser)

5'-7"X4'-0"
R/F
A/C OUTER UNIT
Symbol Item Description Qty.
LADIES R/F
R/F

Toilet
Fire Alarm Control Panel 00
5'-7"X4'-0"

5'-10"
Smoke Detector 10
Toilet
5'-7"X4'-0"
R/F
R/F
Heat Detector 04
UP GENTS

R/F
Multi Sensor Detector 00
F
EXIT

R/F
F Manual Pull Station 02
S

02
OM
FD
OM Control Module
Monitor Module 00
LOBBY

FIRE LIFT
8'-0"x7'-0"
Horn-Strobe 04
63'-11"

Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 06
COMMERCIAL SPACE
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 06


PA System Speaker 05
S

UP DN EXIT F OM
FD EXIT Exit Sign 02

R/F
Emergency Light 10
SAFETY LOBBY Emergency Exit Light 02
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT
Early Streamer Emission 00
S 2 hr Fire Rated Door
93'-6"

0 1' 2' 4' 10' 20'


S S
3 hr Fire Rated Door
2nd FLOOR PLAN (COMMERCIAL)
SCALE (GRAPHIC SCALE) 4 hr Fire Rated Wall
SCALE: 1:100

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, 2ND FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-08
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
3rd-6th FLOOR PLAN (COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, TOILET)
FLOOR AREA : 7050 SFT
21'-6"

Toilet
5'-0"X4'-0" 72'-2"
FIRE ESCAPE EL.ROOM SYMBOL & LEGEND:
8'-0"x22'-4"
5'-10"
Toilet
R1-∅100mm Stand Pipe(Riser)

5'-7"X4'-0"
R/F
A/C OUTER UNIT
Symbol Item Description Qty.
LADIES R/F
R/F

Toilet
Fire Alarm Control Panel 00
5'-7"X4'-0"

5'-10"
Smoke Detector 10
Toilet
5'-7"X4'-0"
R/F
R/F
Heat Detector 04
UP GENTS

R/F
Multi Sensor Detector 00
F
EXIT

R/F
F Manual Pull Station 02
S

02
OM
FD
OM Control Module
Monitor Module 00
LOBBY

FIRE LIFT
8'-0"x7'-0"
Horn-Strobe 04
63'-11"

Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 06
COMMERCIAL SPACE
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 06


PA System Speaker 05
S

UP DN EXIT F OM
FD EXIT Exit Sign 02

R/F
Emergency Light 10
SAFETY LOBBY Emergency Exit Light 02
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT
Early Streamer Emission 00
S 2 hr Fire Rated Door
93'-6"
S S
3 hr Fire Rated Door
0 1' 2' 4' 10' 20'
3rd-6th FLOOR PLAN (COMMERCIAL) 4 hr Fire Rated Wall
SCALE (GRAPHIC SCALE)
SCALE: 1:100

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, 3TH-6TH FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-09
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
7th FLOOR PLAN (COMMERCIAL SPACE, SAFETY LOBBY, STAIR, LIFT, TOILET)
FLOOR AREA : 7050 SFT
21'-6"

Toilet
5'-0"X4'-0" 72'-2"
FIRE ESCAPE EL.ROOM SYMBOL & LEGEND:
8'-0"x22'-4"
5'-10"
Toilet
R1-∅100mm Stand Pipe(Riser)

5'-7"X4'-0"
R/F
A/C OUTER UNIT
Symbol Item Description Qty.
LADIES R/F
R/F

Toilet
Fire Alarm Control Panel 00
5'-7"X4'-0"

5'-10"
Smoke Detector 10
Toilet
5'-7"X4'-0"
R/F
R/F
Heat Detector 04
UP GENTS

R/F
Multi Sensor Detector 00
F
EXIT

R/F
F Manual Pull Station 02
S

02
OM
FD
OM Control Module
Monitor Module 00
LOBBY

FIRE LIFT
8'-0"x7'-0"
Horn-Strobe 04
63'-11"

Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 06
COMMERCIAL SPACE
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 06


PA System Speaker 05
S

UP DN EXIT F OM
FD EXIT Exit Sign 02

R/F
Emergency Light 10
SAFETY LOBBY Emergency Exit Light 02
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT
Early Streamer Emission 00
S 2 hr Fire Rated Door
93'-6"
S S
3 hr Fire Rated Door
0 1' 2' 4' 10' 20'
7th FLOOR PLAN (COMMERCIAL) 4 hr Fire Rated Wall
SCALE (GRAPHIC SCALE)
SCALE: 1:100

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, 7TH FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-10
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
8th-9th FLOOR PLAN (DRAWING & DINING, KITCHEN, BED ROOM, SAFETY LOBBY, STAIR, LIFT, TOILET)
FLOOR AREA : 7050 SFT
21'-6"

72'-2"
FIRE ESCAPE SYMBOL & LEGEND:
8'-0"x22'-4"
Toilet
R1-∅100mm Stand Pipe(Riser)

A/C OUTER UNIT


Symbol Item Description Qty.
R/F
R/F

Drawing & Dining Fire Alarm Control Panel 00


Smoke Detector 10
Kitchen Room
R/F
Heat Detector 04
UP

R/F
Multi Sensor Detector 00
F
Bed Room Bed Room
EXIT

R/F
F Manual Pull Station 02
S

02
OM
FD
OM Control Module

FIRE LIFT
Toilet Monitor Module 00
8'-0"x7'-0"
Horn-Strobe 04
LOBBY
63'-11"

Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR
Upright Sprinkler K-8.0 00
LOBBY

Drawing & Dining Fire Extinguisher(5kg ABC Type) 06


R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 06


Bed Room M. Bed Room PA System Speaker 05
S

UP DN EXIT F OM
FD EXIT Exit Sign 02

R/F
Emergency Light 10
Kitchen Room Toilet Toilet
SAFETY LOBBY Emergency Exit Light 02
Gas Discharge Nozzle (1" dia) 00
LIFT LIFT
Early Streamer Emission 00
S 2 hr Fire Rated Door
93'-6"

0 1' 2' 4' 10' 20'


S S
3 hr Fire Rated Door
8th-9th FLOOR PLAN (Residential)
PRESENTATION PLAN SCALE (GRAPHIC SCALE) 4 hr Fire Rated Wall

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, 8TH-9TH FLOOR PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-11
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022
ROOF FLOOR PLAN ( LIFT MACHINE ROOM, STAIR)
FLOOR AREA : 995 SFT
21'-6"

72'-2"
FIRE ESCAPE SLO SYMBOL & LEGEND:
8'-0"x22'-4" PE
1 :20
0
R1-∅100mm Stand Pipe(Riser)

Symbol Item Description Qty.


SL
OP
E1
0
:20 Fire Alarm Control Panel 00
Smoke Detector 00
R/F
Heat Detector 06
OM
FD
DN
F
R/F
Multi Sensor Detector 00
S

Manual Pull Station 04


EXIT

R/F F

OM Control Module 04
LIFT MACHINE ROOM
19'-10"x7'-10" Monitor Module 00
EXIT

R/F R/F
Horn-Strobe 04
S

OM F
63'-11"

FD
Hose Cabinet With 38mm Ø 30m long Fire Hose Real 02

54'-6"
and 63mm Landing valve
STAIR SLO
PE
1:2
00
Upright Sprinkler K-8.0 00
Fire Extinguisher(5kg ABC Type) 04
R2-∅100mm Stand Pipe(Riser)

Fire Extinguisher (5Kg CO2 Type) 04


PA System Speaker 04
OM

Exit Sign
FD

DN F EXIT 04
S
EXIT

Emergency Light 06
00
S E 1:2 P
SLO
00

R/F
E1:2

F
04
OM
OP

FD
EXIT Emergency Exit Light
SL

R/F
Gas Discharge Nozzle (1" dia) 00
LIFT MACHINE ROOM
R/F19'-10"x10'-10" Early Streamer Emission 20
S 2 hr Fire Rated Door
93'-6"
S S
3 hr Fire Rated Door
0 1' 2' 4' 10' 20'
ROOF PLAN 4 hr Fire Rated Wall
PRESENTATION PLAN SCALE (GRAPHIC SCALE)

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, ROOF TOP PLAN Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-12
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
PROPOSED POSITIVE SUCTION FIRE HYDRANT SCHEMATIC DIAGRAM BL : 02 NOV-2022
Ø100mm Ø100mm
Standpipe Riser Standpipe Riser
AIR RELIEF VALVE AIR RELIEF VALVE
BALL VALVE BALL VALVE
PRESSURE GAUGE PRESSURE GAUGE

BALL VALVE BALL VALVE


Class-I Hose Class-I Hose
Connection Connection
Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe
Roof Floor Level
Ø65mm Ø65mm
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose
Connection Connection
Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe
9th Floor Level
1½" Ø CONTROLLED
Ø65mm Ø65mm BALL VALVE PRESSURE HYDRNT
Branch Pipe Branch Pipe VALVE
Class-III Hose Class-III Hose FIRE HOSE CABINET
(2'-4"X10"X2'-8")
Connection Connection
WIRRED GLASS
Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe
8th Floor Level Ø65mm Ø65mm HOSE NOZZE
SPRING LOCK
Branch Pipe Branch Pipe HANDLE
Class-III Hose Class-III Hose

6" Ø STANDPIPE RISER


Connection Connection 2½" Ø M.S. PIPE

Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe
7th Floor Level Ø65mm Ø65mm 1½" Ø CANVASS HOSE
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose 2½" Ø LANDING VALVE
Connection Connection
Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe LEGEN
6th Floor Level Ø65mm Ø65mm SYMBOL SYMBOL NAME QTY
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose Cl ss II Hose Co ec io
Connection Connection ( mm Pressure H dr l e ih mm
C s Hose mm ri le No le mm L di
l e Co ec io i hi C i e)
Ø40mm Ø40mm
+10'-0" Branch Pipe Branch Pipe Cl ss I L di l e
5th Floor Level Ø65mm Ø65mm ( mm L di l e)
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose Pill r H dr
( mm mm)
Connection Connection
Ø40mm Ø40mm FDC
Fire ep r me Co ec io
+10'-0" Branch Pipe Branch Pipe ( mm mm)

4th Floor Level Ø65mm Ø65mm


Branch Pipe Branch Pipe
Class-III Hose Class-III Hose Proposed Fire Pump Schedule
Connection Connection
Pu
em
E
rP
(M
Fp
)i i S d B Fire Pump ( P) oc e Pump ( P)
Ø40mm Ø40mm Hori o l Spil C se Hori o l Spil C se er ic l Mul i s e
T pe o Pump
+10'-0" Branch Pipe Branch Pipe Ce i u l Ce i u l Ce i u l

3rd Floor Level Ø65mm Ø65mm T pe o ri er Elec ric l Mo or iesel E i e Elec ric l Mo or
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose R ed C p ci ( S GPM)
Connection Connection R ed He d (FT )
Ø40mm Ø40mm R ed Pressure ( r )
+10'-0" Branch Pipe Branch Pipe
Pump RPM
2nd Floor Level Ø65mm Ø65mm
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose
Connection Connection
Ø40mm Ø40mm
Branch Pipe Branch Pipe
+10'-0"
1st Floor Level Ø65mm Ø65mm Proposed Posi i e Suc io Fire Pump Schem ic
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose i r m d I s ll io e ili
Connection Connection
Ø40mm Ø40mm 02-Way Fire
+10'-0" Branch Pipe Branch Pipe Ø100mm Department Connection
Ground Floor Level Ø65mm Ø65mm Pillar Hydrant (2xØ65mm/Ø150mm)
Branch Pipe Branch Pipe
Class-III Hose Class-III Hose FDC

Ø100mm
Connection Connection
OS & Gate Valve

TS
Ø40mm Ø40mm
Branch Pipe Branch Pipe
Ø 65 ZCV Ø 65 ZCV

-10'-0"
Ø65mm Ø65mm
BASEMENT Floor Level Branch Pipe Branch Pipe
Class-III Hose Class-III Hose
Connection Connection
Ø40mm Ø40mm
Branch Pipe Branch Pipe
Ø50mm Drain Pipe Ø50mm Drain Pipe
To Nearest Drain Pit To Nearest Drain Pit
Ø150mm

WF
Ø150mm
WF

Standpipe Riser-01 Standpipe Riser-02

e TO DRAIN
Pip
der Ø200mm Delivery Pipe,
Hea 0" TS
F
Level (-) 3'-0"
mm l (-) 3'-
00
Ø2 Leve Ø150mm Test Header
Delivery Pipe , Ø 150 mm

Ø150mm Flow Meter Pipe, Pipe, Level (+) 0'-6"


Level (+) 0'-6"
Delivery Pipe , Ø 50 mm

Ø150mm Relief valve discharge Pipe, er Le el G u e


Level (+) 0'-6"
Le el ( )
Delivery Pipe , Ø 150 mm

Ø100mm Pipe mm Pipe rom eep Tu e ell


er Le el ( ) o Fill he der rou d
TS
er Reser ore
Le el ( )
U.G.W.R FOR FIRE FIGHTING
U.G.W.R FOR FIRE FIGHTING SIZE=27'-6"X18'-10"X12'-0"
Ø150mm Suction for Engine Driven Fire Pump, Level (-) 12'-0"
TS SIZE=27'-6"X18'-10"X12'-0" TOTAL CAPACITY=44,841 US GALLONS
TOTAL CAPACITY=44,841 US GALLONS REQUIRED FOR FIRE FIGHTING
Ø65 mm Suction for Motor Driven Jockey Pump, Level (-) 12'-0"
TS
REQUIRED FOR FIRE FIGHTING =37,500 US GALLONS(50MIN)
=37,500 US GALLONS(50MIN)
Ø150 mm Suction for Motor Driven Fire Pump, Level (-) 12'-0" Le el ( )

Proposed Posi i e Suc io Fire Pump Schem ic


i r m d I s ll io e ili

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, PUMP DETAILS & RISER DIAGRAM Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA. Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-13
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
PROPOSED SINGLE LINE DIAGRAM (SLD) BL : 02 NOV-2022

Desco Supply
11 KV LIGHTNING ARRESTER

EARTH PIT

11KV DROP OUT FUSE(100A)


1000 KVA Diesel Generator
12.7mm Dia Cu Conductor

12.7mm Dia Cu Conductor


(Body Earthing) M
(Body Earthing)
12.7mm Dia Cu Conductor
12.7mm Dia Cu Conductor G 12.7mm Dia Cu Conductor N
N (Neutal Earthing)
(Body Earthing)
EARTH PIT-1 Earth (Neutal Earthing)
Earth
Pit-06 Earth Pit-08
1000 KVA TRANSFORMER, OIL TYPE Pit-07 Earth
11KV / 415V, %Z=0.6 Pit-09

12.7mm Dia Cu Conductor 1CX4X2X240 SQMM NYY (TP+N)


12.7mm Dia Cu Conductor

N Automatic Transfer Switch


(Body Earthing) 12.7mm Dia Cu Conductor 12.7mm Dia Cu Conductor
400A Note:
(Neutal Earthing)
N 1.Fire Lift
Earth (Body Earthing)
(Neutal Earthing) Earth 2.Emergency Light
Pit-2
Pit-04 3.Mechanical Ventilation
Earth
Pit-3
Earth 4.Positive Air Pressure
Pit-05 5.Fire Control Room
1CX4X2X400 SQMM NYY (TP+N) 1CX4X2X240 SQMM NYY (TP+N) 6. Jokey Pump
All Power Supply are Backup From

400A TP MCCB SET-0.8


Generator.
360A TP MCCB SET-0.8

LT PANEL
Total Load=1785KW GN PANEL
Total Load=400KW

Bus Bar- 2480A (TP+N) & ECC- 1395A, 80mmX20mm (TP+N) CU BUS BAR +260mmX15mm ECC Bus Bar- 2480A (TP+N) & ECC- 1395A, 80mmX20mm (TP+N) CU BUS BAR +260mmX15mm ECC
CKT- 1

CKT- 2

CKT- 3

CKT- 4

CKT- 5

CKT-6

CKT- 7

CKT- 8

CKT- 9

CKT- 10

CKT- 1

CKT- 2

CKT- 3

CKT- 4

CKT- 5

CKT-6

CKT- 7

CKT- 8

CKT- 9
RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB

RYB
R

R
150A TP MCCB
100A TP MCCB

150A TP MCCB
32A TP MCCB
350A TP MCCB

100A TP MCCB
32A TP MCCB

16A TP MCCB
40A TP MCCB

32A TP MCCB
63A TP MCCB

32A TP MCCB

32A TP MCCB
40A TP MCCB

16A TP MCCB
63A TP MCCB

32A TP MCCB
32A DP MCB

32A DP MCB

Door ECC=1X4.0 rm
ENERGY METER

ENERGY METER
1CX4X16 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X10 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X4 Sqmm (TP+N) NYY

1CX2X10 Sqmm (SP+N) BYA

1CX4X16 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X10 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X4 Sqmm (TP+N) NYY

1CX2X6 Sqmm (SP+N) BYA


1CX4X300X2 Sqmm (TP+N) NYY

1CX4X25 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X50 Sqmm (TP+N) NYY

1CX4X25 Sqmm (TP+N) NYY

1CX4X6 Sqmm (TP+N) NYY

1CX4X50 Sqmm (TP+N) NYY


ECC 1CX1X16 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X10 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X4 Sqmm BYA

ECC 1CX1X10 Sqmm BYA

ECC 1CX1X16 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X10 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X4 Sqmm BYA

ECC 1CX1X6 Sqmm BYA


ECC 1CX1X300 Sqmm BYA

ECC 1CX1X16 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X25 Sqmm BYA

ECC 1CX1X16 Sqmm BYA

ECC 1CX1X6 Sqmm BYA

ECC 1CX1X25 Sqmm BYA


Door ECC=1X4.0 rm
Door ECC=1X4.0 rm

Load=10kw

Load=10kw
SDB-1 FIRE LIFT

SDB-1 FIRE LIFT


1X15000w,

1X15000w,
Load=15kw
Load=7.5kw

Load=7.5kw
Load=5kw

Load=10X6kw

Load=15kw

Load=5kw

Load=10X6kw
Submersible Pump 1Nos,

SDB-

Submersible Pump 1Nos,


SDB-1 JOCKEY PUMP

SDB-Lift

1X60000w,

SDB-1 JOCKEY PUMP

1X60000w,
Fire Pump 1Nos,

Fire Pump 1Nos,


SDB-1EMERGENCY LIGHT

Load=60kw

SDB-1EMERGENCY LIGHT

Load=60kw
Load=2kw

Load=2kw
Load=7kw

Load=7kw
SDB-1FIRE CONTROL PANEL

SDB-1FIRE CONTROL PANEL


SDB-1 POSITIVE AIR PRESSURIED

SDB-1 POSITIVE AIR PRESSURIED


Load=8kw

Load=8kw
DB-1 MECHANICAL VENTILATION

DB-1 MECHANICAL VENTILATION


PFI VAR

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA.
SINGLE LINE DIAGRAM (SLD)
Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-14
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***
BL : 02 NOV-2022

PROPOSED FIRE ALARM RISER DIAGRAM


LEGEND
SYMBOL SYMBOL NAME QTY.

Smoke Detector
EOL
Heat Detector

Horn With Light

F Manual call points

AIM Addressable Input Module


For Sensor & devices: AS PER
2X1.5 mm²(Soild) FR Cable DRAWING

For Fire Alarm (NAC): AS PER


2X2.5 MM² (Solid) FR Cable DRAWING

Addressable Fire Alarm


Control Panel
F F F F F F F F F EOL
EOLR

End of Line Resistor

F F F F F F F F F F F F
1.5 x 2.5rm Fire Detection cable

NAC -1 NAC -2

AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM

11 06

SUPPLY (NAC CIRCUIT)


AUX-ILIARY POWER
MAIN FIRE ALARM CONTROL PANEL, No-01
2 LOOPS
BATTERY CAPACITY = 10 AH
SECURITY ROOM (GF)

3 x 2.5rm wire from


primary power source
INTERFACE WITH PUBLIC ADDRESS
SOFTWARE INTERFACE WITH BMS SYSTEM

Project Details: CLIANT: Drawing Title: FIRE ENGINEER: Arc/Structural Seal & Signature: Fire Safety Consultant: Firm Owner Seal & Signature: Fire Professional: Submitted To: DATE : SHEET NO:
PROPOSED ( BASEMENT+G+9) 10 STORIED
02/11/2022
FIRE SAFETY PLAN LAYOUT- ASANTO LIMITED DEPARTMENT OF FIRE
RESIDENTIAL CUM COMMERCIAL BUILDING P D L P SERVICE AND CIVIL DEFENCE SCALE: 1:100
PLAN FOR ADDUHA ALI GANG AT KO - 189, Engr. Md.Harunur Rashid
JOMOJ ROAD, ZOAR SAHARA, BADDA, DHAKA.
RISER DIAGRAM
Design Engineer, Bsc in EEE
M D
ISSUED FOR: REV : 00
FDS-15
ONE STOP MEP SOLUTION E
MIAENG-311868 APPROVAL
***© This is a licensed copy for using by client and should not be duplicated or altered without permission for valid authorized person. ***