2. DESIGN SCHEDULE
A. BUILDING SIZE
WIDTH: 10'-0"
LENGTH: 16'-0"
SIDE WALL HEIGHT: 8'-9 3/4"
TOTAL HEIGHT: 10'-5"
B. BUILDING LOADS
ROOF LIVE LOAD: 40 PSF
ROOF DEAD LOAD: 10 PSF
C. DESIGN WIND
BASIC WIND SPEED: 105 MPH
WIND EXPOSURE: C
D. SEISMIC DESIGN CATEGORY: C
E. SITE CLASS: D
F. ROOF PITCH: 3/12
3. ROOFING SCHEDULE
A. ROOF SHEATHING SHALL BE APA RATED 7/16" THICK OSB WITH FOIL
BACKING, 24/16 RATED MIN., UNBLOCKED DIAPHRAGM. STAGGER LAYOUT
PER APA CONDITION 1. 6/21/2022
B. SHEATHING NAILING SHALL BE PER NAILING SCHEDULE.
WOOD LAP SIDING C. LIFETIME DIMENSIONAL ASPHALT SHINGLES (U.N.O.).
OVER HOUSE WRAP
ENGINEERING DEPARTMENT
TCAHALAN@TUFFSHED.COM
D. GAF FELTBUSTER.
3030 3030
8'-913 16"
ACCESSORY BUILDING
FCII = 2510 PSI, FC┴ = 750 PSI, E = 2.0 x 106 PSI, SG= 0.50
PO No. 11007
CLAYEY SILT (CL, ML, MH & CH). PRESCRIPTIVE ALLOWABLE SOIL BEARING
Site Address:
PRESSURE USED IN DESIGN IS 1500 PSF AT 12" DEEP. VALUES ARE PER
Description:
TABLE R401.4.1.
B. IN THE EVENT OF THE DISCOVERY OF EXPANSIVE SOILS, THE SERVICES OF
A SOILS ENGINEER MAY BE REQUIRED.
C. ALL FOOTINGS SHALL BE FOUNDED ON UNDISTURBED NATURAL SOIL.
D. IN THE EVENT EXCAVATIONS REVEAL UNFAVORABLE CONDITIONS, THE
SERVICES OF A SOILS ENGINEER MAY BE REQUIRED.
ENGINEER OF RECORD.
DRAWINGS ARE FOR A
7. GENERAL NOTES
A. INSTALLATION PROCEDURES SHALL CONFORM TO OSHA STANDARDS.
BUILDER SHALL PROTECT ALL ADJACENT PROPERTY, STRUCTURES, TREES,
UTILITIES, ETC.
B. BUILDER IS RESPONSIBLE FOR SAFETY OF BUILDING DURING
CONSTRUCTION. PROVIDE ALL SHORING OR BRACING AS REQUIRED AND
PER GOVERNING REGULATIONS.
C. ALL WOOD CONSTRUCTION CONNECTORS REFERENCED IN THIS DRAWING
SHALL BE SIMPSON 'STRONG-TIE' OR EQUIVALENT INSTALLED PER
MANUFACTURER'S SPECIFICATIONS.
D. GREEN VINYL SINKER NAILS DO NOT MEET THE NAILING REQUIREMENTS OF
COMMON NAILS.
STORE 310
CONTRACTOR'S LICENSE: TUFFSI*038RZ
8. MATERIAL EVALUATION REPORT IDENTIFICATION
(509) 535-8833
ICC-ES REPORT #ESR-1301.
C. HARDIE PANEL SIDING BY JAMES HARDIE BUILDING PRODUCTS PER
2'-0" 12
3
Drawn By: TB
1'-0" 1'-0" 1'-0" Date: 5/9/22
10'-5116"
TW TW TW TW TW TW TW TW TW TW TW
8'-913 16"
S1 Sheet 1 of 3
CALC. ALLOW. CALC. ALLOW.
SIMPSON USP EQUIVALENT
NAILING SCHEDULE SHEAR WALL SCHEDULE
SHEAR SHEAR
SHEAR WALL SCHEDULE
SHEAR SHEAR
LOAD LOAD LOAD LOAD H2.5A RT7A
(lb/ft) (lb/ft) (lb/ft) (lb/ft)
CHORD SPLICE NAILING: 8 - 16d NAILS EACH SIDE OF SPLICE. SSTB16-SSTB36 STB16-STB36
TRUSS BLOCKING: (4) - 16d (TOENAILED) 2X4 FRAMING. SHEATHE EXTERIOR WITH 7/16" HDU2-HDU5 PHD2A-PHD5A
2X4 FRAMING. SHEATHE EXTERIOR WITH 7/16"
OSB FOR WOOD LAP SIDING. HDU8 PHD8
FRAMING NAILING: OSB FOR WOOD LAP SIDING.
10'-0" LONG TOTAL. 10' USED FOR SHEAR. 54 167 - - LUS24-LUS210 JUS24-JUS210
STUD TO TOP PLATE, 2-16d END NAIL 16'-0" LONG TOTAL. 0' USED FOR SHEAR.
NAILING: LS30/LS50 MP3/MP5
STUD TO SILL PLATE, 2-16d END NAIL OR 4-8d TOENAIL A B NAILING:
EDGE: 8d COMMON @ 6" OC LSTA9-LSTA24 LSTA9-LSTA24
DBL. HEADER 16d @ 16" OC ALONG EACH EDGE EDGE: 8d COMMON @ 6" OC
FIELD: 8d COMMON @ 12" OC A24 TDL5
HEADER TO KING STUD 4-8d TOENAIL OR 4-16d END NAIL FIELD: 8d COMMON @ 12" OC H1 RT15
DOUBLE TOP PLATES, 16d @ 16" FACENAIL NO HOLD-DOWNS REQUIRED. NO HOLD-DOWNS REQUIRED. H3 RT3A
H6 LFTA6
H8 LTW12
UNLESS SPECIFIED HEREIN, ALL NAILING SHALL BE PER
H10 RT16A
TABLE R602.3(1).
PA51/PA68 TA51/TA71
UPLIFT TRANSFER: PROVIDE SIMPSON H2.5A AT EACH END OF ABA44/ABA66 PA44E/PA66E
TRUSSES. BC4/BC6 C44/C66
TOENAIL BLOCKING TO TOP PLATE: 3-8d/ BLOCK A311 TDL10
150
PROVIDE 2X4 SOLID BLOCKING ON ALL UNSUPPORTED EDGES OF HST2 KHST2
PLYWOOD ON SHEAR WALLS. 2X4 FRAMING. SHEATHE EXTERIOR WITH 7/16" 2X4 FRAMING. SHEATHE EXTERIOR WITH 7/16" SDS1/4X3 SCREW WS3
OSB FOR WOOD LAP SIDING. OSB FOR WOOD LAP SIDING. A34 MP34
CALC. ALLOW. 10'-0" LONG TOTAL. (3.5'+3.5') = 7' AND 2bs/h=0.79 77 133 16'-0" LONG TOTAL. 16' USED FOR SHEAR. 37 167 A35 MPA1 6/21/2022
UNBLOCKED ROOF DIAPHRAGM SHEAR SHEAR
ROOF SHEATHING NAILING: USED FOR SHEAR. D
NAILING: CS18/CS22 RS200/RS300
LOAD LOAD C
EDGE: 8d COMMON @ 6" OC
ENGINEERING DEPARTMENT
NAILING:
TCAHALAN@TUFFSHED.COM
BORDER: 8d COMMON @ 6" OC (lb/ft) (lb/ft) HTT4/HTT5 HTT16/HTT22
ENGINEER OF RECORD.
DRAWINGS ARE FOR A
STORE 310
CONTRACTOR'S LICENSE: TUFFSI*038RZ
Storage Buildings & Garages
TUFF SHED, INC.
415 N THIERMAN ROAD
SPOKANE, WA 99212
B D B D B D
10'-0" 10'-0"
(509) 535-8833
DOUBLE TOP PLATES
2X4 TREATED SILL INTERLOCK AT
PLATE TYPICAL ALL CORNERS
A A A
1'-0"
3'-3" HEADER
2 - 2X4 HF #2
3'-0"
16'-0"
3'x3'
6'-6"
LANDING @ 12" OC
Date: 6/3/22
Revised:
Revised:
2X4 WALL FRAMING STUDS 2 1 Title:
9"
@ 16" OC S3 S3 -
3'-3" HEADER
2 - 2X4 HF #2
3 6
PLANS
3'-0"
S3 S3
SHEAR WALL SCHED
NAILING SCHEDULE
1'-0"
-
C C C Scale: 1/4" = 1'-0"
3'-3" HEADER Sheet:
2 - 2X4 HF #2 2X6 LADDER FRAMING
3'-6" 3'-0" 3'-6"
@ 12" O.C.
STUDS
ENGINEERING DEPARTMENT
TCAHALAN@TUFFSHED.COM
TIMOTHY D. CAHALAN, P.E.
NAILING:
HEADER TO STUD - (4) 8d TOENAIL OR (4) 16d END NAIL
DOUBLED HEADER - 16d @ 16" STAGGERED FACE NAIL
HEADER DETAIL
ACCESSORY BUILDING
10' X 16' = 160 SQ FT
ENGINEER OF RECORD.
DRAWINGS ARE FOR A
UNHEATED GARAGE SPACE
STORE 310
CONTRACTOR'S LICENSE: TUFFSI*038RZ
P.T. SILL PLATE
3" PROJ.
TOP & BOTTOM
(509) 535-8833
13 4"
3" CLR.
TYP.
FINISH CONCRETE FLOOR
GRADE
4"
6"
ATTACH 7/16" OSB SHEATHING WITH FOIL
7"
BACKING TO TRUSSES PER NAILING
SCHEDULE. REFERENCE TABLE 2304.10.1.
MIN.
1'-0"
SLAB REINFORCEMENT
PER NOTES BELOW
12
NAIL SHEATHING TO WALL STUD 3 3" CLR. 3" CLR. THICKENED SLAB
PER SHEAR WALL SCHEDULE TYP. TYP. 1'-0"
MIN.
MONOLITHIC FOUNDATION Drawn By: TB
SHEAR TRANSFER NOTES: Date: 5/9/22
1. REFERENCE SHEAR WALL SCHEDULE FOR 2x6 RAFTERS @ 12" O.C.
NAILING AND HOLDOWN REQUIREMENTS. Checked By: JR
10'-5116"
5. REINFORCING STEEL: A615, GRADE 40 OR GRADE 60. ALL REINFORCING STEEL SHOWN
TO BE CONTINUOUS MAY BE LAPPED A MINIMUM OF 38 BAR DIAMETERS OR 24".
10'-0" 6. SEISMIC DESIGN CATEGORY: C
S3
A. ATTACH PRESSURE TREATED SILL PLATE TO THE FOOTING USING 1/2" DIA X 10"
LONG 'L' BOLTS WITH NUTS AND WASHERS.
B. ANCHOR BOLTS SHALL BE EMBEDDED AT LEAST 7" INTO THE CONCRETE AND SHALL
BE SPACED NOT MORE THAN 6' OC.
C. THERE SHALL BE A MINIMUM OF 2 BOLTS PER SILL PLATE PIECE WITH 1 BOLT
LOCATED NOT MORE THAN 12" NOR LESS THAN 7 BOLT DIAMETERS FROM EACH END
OF EACH PIECE.
SHEAR TRANSFER DETAIL BUILDING SECTION ATTACH EACH END OF EACH TRUSS TO TOP PLATES WITH H2.5A OR EQUIV CLIPS. FOUNDATION DETAIL
1 3/4" = 1' - 0" 2 3/8" = 1' - 0" WALL FRAMING TO BE 2X4 HF STUD GRADE @ 16" OC. 3 3/4" = 1'-0"