15. Click OK.

16. Wait until the red FLSH LED on the controller has turned off.
17. Reboot the controller using the power switch.

Use Totalizers
Totalizers are timers and counters that store data such as number of trips, number of
starts, number of fired hours and such. They are currently used in Mark VI or
EX2100 application code. The outputs of the timers and counters are then stored in
NOVRAM.

Note A special password is required to modify Totalizer values. To obtain a


password from the GE OnSite Center, click the Save button on the dialog box below
for instructions. No password is required to view the current value of the Totalizers.

! To view or modify the totalizers value


"# From the Device menu, select Download, and View/Set Totalizers. The
Totalizers dialog box displays.

Enter the
password in
Password
field.
Click Modify to
change the value
of the highlighted
item.

3-110 ! Chapter 3 Basic Configuration GEH-6403K Toolbox for a Mark VI Turbine Controller
! To request a totalizer password
1. From the Device menu, select Download, View/Set Totalizers. The
Totalizers dialog box displays an Identifier.
2. Click Save to save the identifier to the hard drive. The Totalizer_ID text
displays the procedure to follow to receive a Totalizer password. The password
sent is valid for 24 hours only.

Restore Application Code


The application code running in the controller's memory may be different from that
in permanent storage. If the code in memory becomes unstable, this command loads
into the controller's memory the uncorrupted code in permanent storage. All changes
to the code in memory will be lost.

Note Restoring from permanent storage cannot revert application code if the major
revisions between permanent storage and memory are not equal.

! To restore application code from permanent storage


"# From the Device menu, select Download, then Restore from Perm
Storage.

GEH-6403K Toolbox for a Mark VI Turbine Controller Chapter 3 Basic Configuration ! 3-111
Replicate Device
The Replicate command allows you to copy a configuration file from one device to
another. In the case of a multi-unit turbine system, each control unit typically has the
same configuration, such as hardware I/O, network I/O, or sequence code library.
However, each unit requires some unique device identifiers, which require manual
input; this command automates that process.
! To replicate a configuration file
1. From the Device menu, select Replicate. A copy of the configuration file
opens and the Mark VI Device Name dialog box displays.
2. Enter the new device name and click OK. The Translate Regions dialog box
displays.
Click this column to
enter the new region.
Select regions
to include in
replication.

Select to save the


new document in a
New Unit Folder.
Enter the new
folder location
or click the
Browse...
button.
Enter the
Sourcefile New
Unit Folder
location or click
the Browse...
button.

3. Verify the new regions to replace and select the desired options. Click OK.
The replication process
!" Replaces the selected regions
!" Replaces Sourcefile folder names, if desired
!" Creates a new folder, if desired
!" Sets the device number to zero
!" Deletes all system data
!" Deletes all external EGD pages and exchanges

3-112 ! Chapter 3 Basic Configuration GEH-6403K Toolbox for a Mark VI Turbine Controller