1. DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.

2. ALL FIRE ALARM SYSTEM EQUIPMENT MUST BE FIRE MARSHALL


APPROVED ONLY.

3. FACP BACKUP BATTERY SHALL BE NICKEL-METAL HYDRIDE (Ni-MH)


AND CAPABLE OF OPERATING THE SYSTEM UNDER THE FOLLOWING
CONDITIONS:
a) MINIMUM OF 24 HOURS UNDER NON-ALARM CONDITION.
b) MINIMUM OF 15 MINUTES AT MAXIMUM CONNECTED
LOAD UNDER EMERGENCY CONDITION.
4. FOR EXACT LOCATION OF AND DETECTORS REFER TO
ARCHITECTURAL REFLECTED CEILING PLAN.

5. MINIMUM SIZE OF CONDUIT SHALL BE 20mm DIAMETER UNLESS


OTHERWISE NOTED.

6. PVC INSULATED 1.5mm2 MINIMUM FIRE RETARDANT CABLES SHALL BE


USED FOR THE WIRING OF FIRE ALARM SYSTEM (SCREENED CABLES -
105°C HEAT RESISTANT).

7. FIRE ALARM SYSTEM SHALL BE IN MICC CABLE IN EXPOSED AREA AND


FIRE RATED CABLE IN CONDUIT IN CONCRETE SLAB.

8. A SMOKE DETECTOR UNDER A FLAT CEILING HAS A RADIUS OF 7.5


METERS.

9. THERE SHOULD BE A 500mm CLEAR SPACE BELOW AND AROUND THE


DETECTOR.

10. FIRE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW NOT


CLOSER THAN (1 METER) FROM AN AIR SUPPLY DIFFUSSER OR
RETURN AIR OPENING. THE DETECTION OF SMOKE IN THE DUCT
ASSOCIATED WITH A PARTICULAR AHU WILL CAUSE A SHUTDOWN IN
THAT UNIT ONLY AND WILL NOT AFFECT OTHER AIR HANDLING UNITS.

11. FIRE ALARM WALL MOUNTED BELLS/HORNS/STROBES SHALL BE


INSTALLED WITHIN 2100mm TO 2500mm FROM FINISH FLOOR LEVEL
UNLESS OTHERWISE INDICATED IN THE DRAWINGS.

12. THE BRANCH CIRCUIT BREAKER THAT SUPPLY POWER TO THE FIRE
ALARM CONTROL PANEL SHALL BE PROVIDED WITH A WARNING MARK,
"FIRE ALARM SYSTEM - DO NOT SWITCH OFF".

13. EACH DUCT SMOKE DETECTOR SHALL HAVE A REMOTE INDICATOR


LIGHT TO INDICATE ACTIVATION OF THE SMOKE DETECTOR. THIS
LIGHT SHALL BE MOUNTED ON THE WALL DIRECTLY BELOW THE
POSITION OF THE DETECTOR.

MICROPROCESSOR BASED ADDRESSABLE FIRE ALARM CONTROL


FACP PANEL WITH ALARM SUPERVISORY, TROUBLE AND MONITOR
OPERATION LED DISPLAY UNIT AND DIALER MODULE WITH SEALED
LEAD ACID BUILT-IN BATTERY BACKUP, WALL SURFACE MOUNTED

FGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL/DISPLAY

S ADDRESSABLE SMOKE DETECTOR, PHOTOELECTRIC TYPE.

ADDRESSABLE HEAT DETECTOR COMBINATION RATE OF RISE AND


H
FIXED TEMPERATURE.

ELECTRONIC SOUNDER (BELL) WITH STROBE LIGHT.

F
ADDRESSABLE MANUAL FIRE ALARM PULL STATION, SURFACE WALL
LOOP-2 (L02/D01 TO L02/D45) L01/D17 L01/D16 MOUNTED.
S S
LOOP-3 (L03/D01 TO L03/D41) Main LV 1.5mm² CU, SHIELDED AND TWISTED PAIR CABLE, FIRE RETARDANT,
LOOP-4 (L04/D01 TO L04/D45)
LOOP-5 (L05/D01 TO L05/D38) Electrical Room POWER LIMITED WITH 300V INSULATION, IN 20mm Ø PVC CONDUIT,
LOOP-6 (L06/D01 TO L06/D34) EMT FOR EXPOSED INSTALLATION ABOVE FALSE CEILING AND HEAVY
LOOP-7 (L07/D01 TO L07/D40)
(1585X650) GAUGE PVC FOR EMBEDDED INSTALLATION IN 50MM SAND CEMENT
SCREED/WALL FOR ALARM INITIATING CIRCUIT.

2.5mm² CU, SHIELDED AND TWISTED PAIR CABLE, FIRE RETARDANT,


ELECTRICAL / MECHANICAL
SHAFT 4970x1200mm SIZE Potable POWER LIMITED WITH 300V INSULATION, IN 20mm Ø PVC CONDUIT,
EMT FOR EXPOSED INSTALLATION ABOVE FALSE CEILING AND HEAVY
(TYPICAL ALL FLOOR) Water GAUGE PVC FOR EMBEDDED INSTALLATION IN CONCRETE SLAB FOR
Grey Firefighting ALARM INDICATING CIRCUIT.
LOOP-2 (L02/B01 TO L02/B20) Tank
LOOP-3 (L03/B01 TO L03/B20) Water Tank Water Tank
LOOP-4 (L04/B01 TO L04/B03) L01/D18
LOOP-5 (L05/B01 TO L05/B03) S L01/D15
LOOP-6 (L06/B01 TO L06/B02) H
LOOP-7 (L07/B01 TO L07/B06)

Pumps Room

FACP
L01/D01
F

L01/D02 L01/B01
S
Low Current /
Server Room
(635X865)
L01/D14 L01/D13 L01/D12
S S S

Furniture Storage
Storage

R E M A R K S
L01/D03
S

L01/D05 L01/D09
S S

L01/B02

L01/D10
S

Uniforms Storage Stationary Storage Stationary Storage S


L01/D11
L01/D04 L01/D06 L01/D07 L01/D08
S S S S

REV
No. DATE BY CHK'D CERT APP'D

PROPRIETARY NOTICE

This drawing and the information contained herein are the exclusive property of
SUHAIMI DESIGN and shall not be copied, reproduced or disclosed in any manner,
or used for any purpose whatsoever, except with the prior written authorization of
SUHAIMI DESIGN. This drawing, including any documentation, drawings, calculation
or other information prepared or derived from the information contained herein shall
be returned to SUHAIMI DESIGN upon request.
PROJECT TITLE :

ANJAL NATIONAL SCHOOLS

LOCATION : PROJ. MANAGER :


-
PROJ. ARCHITECT :
-
OWNER : STR. ENGINEER :
-
ELECT'L. ENGINEER :
-
TEL.: -
FAX.: - H.V.A.C. ENGINEER :
-
SHEET TITLE :
SANITARY ENGINEER :
BASEMENT FLOOR FIRE ALARM LAYOUT -
CAD BY : CHECKED BY : APPROVED BY : DRAWING NUMBER :
PM MNZ MN

CAD DATE : CHECKED DATE : APPROVED DATE : EE-111


18-02-2021 18-02-2021 18-02-2021

CONTRACT NO. PROJECT NO. FILENAME SHEET NO. TTL SHTS

- - - -
A BASEMENT FLOOR FIRE ALARM LAYOUT

LICENSE No. 369


DAMMAM 31451 P.O. BOX 2202,
PROTECOOLING Fax. +9663 834-1032 Tel. +9663 834-7660
E-mail : info@suhaimidesign.com Web Site : www.suhaimidesign.com