1. DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.

2. ALL FIRE ALARM SYSTEM EQUIPMENT MUST BE FIRE MARSHALL


APPROVED ONLY.
Middle & Secondary School Entry
3. FACP BACKUP BATTERY SHALL BE NICKEL-METAL HYDRIDE (Ni-MH)
L03/B10 AND CAPABLE OF OPERATING THE SYSTEM UNDER THE FOLLOWING
CONDITIONS:
a) MINIMUM OF 24 HOURS UNDER NON-ALARM CONDITION.
b) MINIMUM OF 15 MINUTES AT MAXIMUM CONNECTED
LOAD UNDER EMERGENCY CONDITION.
L03/B06 L03/B09 4. FOR EXACT LOCATION OF AND DETECTORS REFER TO
ARCHITECTURAL REFLECTED CEILING PLAN.
Men's Entry
L02/D25 L03/B07 5. MINIMUM SIZE OF CONDUIT SHALL BE 20mm DIAMETER UNLESS
S
OTHERWISE NOTED.

Security L03/B08
6. PVC INSULATED 1.5mm2 MINIMUM FIRE RETARDANT CABLES SHALL BE
USED FOR THE WIRING OF FIRE ALARM SYSTEM (SCREENED CABLES -
L03/B05 105°C HEAT RESISTANT).
L02/D26
40h F L02/B16 7. FIRE ALARM SYSTEM SHALL BE IN MICC CABLE IN EXPOSED AREA AND
F
KG 2 KG 2 KG 1 FIRE RATED CABLE IN CONDUIT IN CONCRETE SLAB.
L02/B20 L02/D18
20 Students 20 Students 20 Students 8. A SMOKE DETECTOR UNDER A FLAT CEILING HAS A RADIUS OF 7.5
METERS.
L02/D21

GB0000101
H
L02/D23 L02/D24 53h L02/D30 L02/D3153h L02/D3253h 9. THERE SHOULD BE A 500mm CLEAR SPACE BELOW AND AROUND THE
S S S S S DETECTOR.
L02/D22
S L02/D27
S
L02/D19 Human Nursery 1 Nursery 2 S
10. FIRE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIRFLOW NOT
CLOSER THAN (1 METER) FROM AN AIR SUPPLY DIFFUSSER OR

53h
L02/D20 Resources 20 Students 20 Students RETURN AIR OPENING. THE DETECTION OF SMOKE IN THE DUCT
L02/D17 S ASSOCIATED WITH A PARTICULAR AHU WILL CAUSE A SHUTDOWN IN
H
THAT UNIT ONLY AND WILL NOT AFFECT OTHER AIR HANDLING UNITS.
Middle School
Reception F L03/B11 11. FIRE ALARM WALL MOUNTED BELLS/HORNS/STROBES SHALL BE
L02/B15 L02/D29 INSTALLED WITHIN 2100mm TO 2500mm FROM FINISH FLOOR LEVEL
UNLESS OTHERWISE INDICATED IN THE DRAWINGS.
Register Training Hall L02/D43
H
L02/D40
L02/D28 S
L02/D36
S
L02/D33
S 12. THE BRANCH CIRCUIT BREAKER THAT SUPPLY POWER TO THE FIRE
S
L02/D16 Supervisor S
Kindergarten ALARM CONTROL PANEL SHALL BE PROVIDED WITH A WARNING MARK,
"FIRE ALARM SYSTEM - DO NOT SWITCH OFF".
L02/D07
13. EACH DUCT SMOKE DETECTOR SHALL HAVE A REMOTE INDICATOR
S
Nursery LIGHT TO INDICATE ACTIVATION OF THE SMOKE DETECTOR. THIS
KG 1 LIGHT SHALL BE MOUNTED ON THE WALL DIRECTLY BELOW THE
L02/D11 S
L02/D15
S L02/D44 20 Students POSITION OF THE DETECTOR.
L02/D39
S S
Purchasing Kids attractive
Manager Administration seating
S
L02/D37
53h h35 S
L02/D35
S
L02/D34
53h
Reception Nursery S
L02/D42
S
L02/D41

L02/D13
L02/D12 Reception MICROPROCESSOR BASED ADDRESSABLE FIRE ALARM CONTROL
S
H L02/D10
Principal Meeting
L02/D08 KG 1 KG 1 FACP PANEL WITH ALARM SUPERVISORY, TROUBLE AND MONITOR
S S
Lactation
Room L02/B17
Nap Room 20 Students 20 Students OPERATION LED DISPLAY UNIT AND DIALER MODULE WITH SEALED
S
S
L02/D09 L02/B19 F L02/D06
L02/D45 F Room LEAD ACID BUILT-IN BATTERY BACKUP, WALL SURFACE MOUNTED
L02/D14
Financial L02/D38 FGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL/DISPLAY

F
L02/B18
L02/B14
S ADDRESSABLE SMOKE DETECTOR, PHOTOELECTRIC TYPE.
L03/B04
L03/B03 Women's Nursery H
ADDRESSABLE HEAT DETECTOR COMBINATION RATE OF RISE AND
FIXED TEMPERATURE.
Entry Entry
ELECTRONIC SOUNDER (BELL) WITH STROBE LIGHT.
Primary School
F
ADDRESSABLE MANUAL FIRE ALARM PULL STATION, SURFACE WALL
Entry L03/D36
MOUNTED.
S
1.5mm² CU, SHIELDED AND TWISTED PAIR CABLE, FIRE RETARDANT,
POWER LIMITED WITH 300V INSULATION, IN 20mm Ø PVC CONDUIT,
L02/B12 EMT FOR EXPOSED INSTALLATION ABOVE FALSE CEILING AND HEAVY
GAUGE PVC FOR EMBEDDED INSTALLATION IN 50MM SAND CEMENT
L03/B02 SCREED/WALL FOR ALARM INITIATING CIRCUIT.
L03/D35
F S 2.5mm² CU, SHIELDED AND TWISTED PAIR CABLE, FIRE RETARDANT,
L02/B02 L02/D05
POWER LIMITED WITH 300V INSULATION, IN 20mm Ø PVC CONDUIT,
L02/B13 EMT FOR EXPOSED INSTALLATION ABOVE FALSE CEILING AND HEAVY
Kindergarten Yard GAUGE PVC FOR EMBEDDED INSTALLATION IN CONCRETE SLAB FOR
ALARM INDICATING CIRCUIT.
Primary School Educational
L02/D04 S Reception Equipments
S
L03/D34 Teachers
S
L03/D33 Supervisor
S
L03/D32

Middle School Yard


L02/D03
S

L03/D26 L03/B12
S
LOOP-2 (L02/D01 TO L02/D45) L02/B10
FROM FACP PANEL F L03/D27

FGAP
L02/B11
(BASEMENT FLOOR) Secondary School
LOOP-3 (L03/D01 TO L03/D41) Reception Storage L03/D29
FROM FACP PANEL H
(BASEMENT FLOOR) L02/B03
L02/D02 S
S
L03/D28
L03/D30
KG
S
L03/D31
LOOP-2 (L02/B01 TO L02/B20) H Principal
FROM FACP PANEL
(BASEMENT FLOOR)
LOOP-3 (L03/B01 TO L03/B20)
Secretary
FROM FACP PANEL
(BASEMENT FLOOR)

L02/D01 F L02/B01
R E M A R K S
L03/D25
S
High School
L03/B01
Entry ELECTRICAL / MECHANICAL
L03/D02
L03/D01 L02/B09
S
SHAFT 4970x1200mm SIZE
F

(TYPICAL ALL FLOOR)


L02/B04
L03/D03
L03/B20 S

L02/B05 F L03/D04

L03/B19

Aquarium KG 2 KG 2 KG 3
20 Students 20 Students 20 Students
L03/D05
S L03/D40 L03/D39 L03/D38 L03/D37
S S H S
L03/D2353h L03/D22 L03/D21
53h
S 53h S S

REV
No. DATE BY CHK'D CERT APP'D
Kindergarten
Waiting L02/B08 PROPRIETARY NOTICE
F
L03/D24 This drawing and the information contained herein are the exclusive property of
L03/D41 L03/D17 SUHAIMI DESIGN and shall not be copied, reproduced or disclosed in any manner,
S
Kindergarten Kindergarten S
S
L03/D20
or used for any purpose whatsoever, except with the prior written authorization of
Stage Reception SUHAIMI DESIGN. This drawing, including any documentation, drawings, calculation
L03/D13 L03/B13 or other information prepared or derived from the information contained herein shall
S
be returned to SUHAIMI DESIGN upon request.
Boys Primary PROJECT TITLE :
L03/D12
S
School
S
L03/D06
Reception L03/D14 ANJAL NATIONAL SCHOOLS
S
L03/D08 L03/D09 L03/D10 L03/D16 L03/D18 L03/D19
Sports Hall S S S h35 S S 53h S 53h
LOCATION : PROJ. MANAGER :
Clinic -
Backstage Sports KG 3 KG 3 KG 3
Instrutctor L03/D15 20 Students 20 Students 20 Students PROJ. ARCHITECT :
L03/B18 -
L02/B07 F
L03/D07 OWNER : STR. ENGINEER :
L02/B06 F L03/B16
-
ECB/Metering Room ELECT'L. ENGINEER :
Sec Inset/ Transformer Room -
TEL.: -
Security
S FAX.: - H.V.A.C. ENGINEER :
L03/D11 -
L03/B17 SHEET TITLE :
SANITARY ENGINEER :
L03/B15
GROUND FLOOR FIRE ALARM LAYOUT -
L03/B14 CAD BY : CHECKED BY : APPROVED BY : DRAWING NUMBER :
Boys Primary School & PM MNZ MN
Kindergarten Entry CAD DATE : CHECKED DATE : APPROVED DATE : EE-112
18-02-2021 18-02-2021 18-02-2021

CONTRACT NO. PROJECT NO. FILENAME SHEET NO. TTL SHTS

- - - -
A GROUND FLOOR FIRE ALARM LAYOUT

LICENSE No. 369


DAMMAM 31451 P.O. BOX 2202,
PROTECOOLING Fax. +9663 834-1032 Tel. +9663 834-7660
E-mail : info@suhaimidesign.com Web Site : www.suhaimidesign.com