Note:-

1- * WIRED AS SINGLE PHASE.

2- THE CONTRACTOR SHALL VERIFY THE FINAL LOADS IN COORDINATION WITH OTHER
TRADES. ACCORDINGLY FINAL SIZES OF CABLES AND CIRCUIT BREAKERS SHALL
BE ADJUSTED.
3- ALL CIRCUIT BREAKER RATINGS SHOWN ON DRAWING ARE PRESENTING THE THERMAL
CWP-01 CWP-02 CWP-03 FAHU-01 FAHU-02 TRIP SETTING AND FRAME SIZE. CIRCUIT BREAKERS RATED 100A AND ABOVE SHALL BE
EQUIPPED WITH ADJUSTABLE TRIP SETTING.
T.L. = 21.875 KVA T.L. = 21.875 KVA T.L. = 21.875 KVA T.L. = 6.875 KVA T.L. = 8.125 KVA
D.L. = 21.875 KVA D.L. = 21.875 KVA D.L. = 21.875 KVA D.L. = 6.875 KVA D.L. = 8.125 KVA 4- THE CONTRACTOR SHALL SUBMIT THE FOLLOWING CALCULATIONS AND STUDIES
FOR APPROVAL :
100A TP ISO. - LOAD SCHEDULES FOR ALL DISTRIBUTION BOARDS FOR RETAILS AND
100A TP ISO. 100A TP ISO. 40A TP ISO. 40A TP ISO. AND SERVICES (IF ANY CHANGES)
- CABLE SIZING AND VOLTAGE DROP CALCULATIONS (IF ANY CHANGES)
SMDB-FR.A - SHORT CIRCUIT CALCULATIONS AT EACH BUS (IF ANY CHANGES)
2 ACP1-SER ACP2-SER ACP3-SER ACP4-SER PP1-SER PP2-SER AT MAIN ELEC IN BAS. FL. - DISCRIMINATION STUDY & CIRCUIT BREAKERS SETTING VALUES
IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM T.C.L. = 80.625 KVA OBTAINED FROM THE MANUFACTURER.
FOR AC IN ELEC. RM FOR AC IN ELEC. RM S.POWER & AC S.POWER
T.C.L. = 16.892 KVA T.C.L. =12.2 KVA T.C.L. = 8.992 KVA T.C.L. = 28.211 KVA
T.DIV.L. = 72.562 KVA
T.C.L. = 63.440 KVA T.C.L. = 63.66 KVA
T.D.L. = 12.379 KVA T.D.L. = 9.838 KVA T.D.L. = 7.362 KVA T.D.L. = 22.686 KVA T.D.L. = 39.704 KVA T.D.L. = 39.876 KVA
2 SPARE

2 2
(4C-16mm ) CU/PVC/PVC
2
1C-16mm CU/PVC/ECC
2

SPARE
80A TP 80A TP 80A TP 40A TP 40A TP 40A TP 2
(4C-70mm ) CU/PVC/PVC
MCCB MCCB MCCB MCCB MCCB MCCB 2
1C-35mm CU/PVC/ECC
25 KA 25 KA 25 KA 25 KA 25 KA 25 KA
2
(4C-95mm ) AL/PVC/PVC
2
1C-50mm CU/PVC/ECC

160A TP
MCCB
25 KA

125A TP 125A TP 160A TP 40A TP


40A TP 40A TP 40A TP 40A TP MCCB MCCB MCCB
MCCB MCCB MCCB MCCB MCCB
30 KA 30 KA 30 KA
30 KA 30 KA 30 KA 30 KA

2 2
400A TP
MCCB
30 KA MDB-SER

2 2
2

For Tender

So a 2 O ICE BUILDING
MCC-PR ESMDB-LIFT EMDB-SER1 EMDB-SER2
DB-BS1 DB-BS2 DB-BS3 MCC1-BS3 MCC2-BS3 MCC1-BS2 MCC2-BS2 MCC1-BS1 MCC2-BS1 PRESSURIZATION FANS
LP1-SER LP2-SER AT MAIN ELEC IN BAS. FL.
FOR JOCKEY PUMP
IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM IN ELEC. RM & CORRIDOR SMOKE IN ELEC. RM IN ELEC. RM AT MAIN ELEC IN BAS. FL. AT MAIN ELEC IN BAS. FL.
IN ELEC. RM AT BASEMENT3 LIGHTING LIGHTING T.C.L. = 138.88 KVA
LIGHTING
T.C.L. = 50.26 KVA
LIGHTING LIGHTING
T.C.L. = 48.38 KVA
AT BASEMENT1
T.C.L. = 52.00 KVA
AT BASEMENT1
T.C.L. =64.00 KVA
AT BASEMENT2
T.C.L. = 52.00 KVA
AT BASEMENT2
T.C.L. =64.00 KVA T.C.L. = 54.00 KVA
AT BASEMENT3
T.C.L. = 62.00 KVA
AT ROOF
T.C.L. = 29.5 KVA T.C.L= 38.36 KVA T.C.L= 36.92 KVA
T.C.L. = 33.00 KVA T.C.L. =95.1025 KVA
T.DIV.L. = 111.48093 KVA T.L. = 6.5 KVA
T.D.L. = 39.786 KVA
T.C.L. = 49.76 KVA
T.D.L. = 40.206 KVA T.D.L. = 38.418 KVA T.D.L. = 52.00 KVA T.D.L. = 64.00 KVA T.D.L. = 52.00 KVA T.D.L. = 64.00 KVA T.D.L. = 54.00 KVA T.D.L. = 62.00 KVA T.D.L. = 29.5 KVA T.D.L. = 30.474 KVA T.D.L= 28.662 KVA
T.DIV.L. = 20.79 KVA T.DIV.L. =75.1845 KVA
D.L. = 6.5 KVA 24B. -
C/P C/P C/P C/P C/P C/P C/P

2
(4C-150mm ) AL/PVC/STA/PVC
2
1C-95mm CU/PVC/ECC
MOBIL :01024440717
(4C-16mm ) CU/PVC/PVC E-MAIL : m.amer@mod-eg.com
WEB SITE : WWW.mod-eg.com
1C-16mm CU/PVC/ECC
26 JULY CORRIDOR
2
(4C-35mm ) CU/PVC/PVC AVENUE MALL, SHEIKH ZAYED, GIZA, EGYPT
2
1C-16mm CU/PVC/ECC
2
(4C-25mm ) CU/PVC/STA/PVC
2
1C-16mm CU/PVC/ECC
2
4Cx95mm AL/PVC/PVC
2
1Cx50mm CU/PVC/ECC

2
4Cx185mm AL/PVC/PVC
2
1Cx95mm CU/PVC/ECC

80A TP 80A TP 80A TP 125A TP 125A TP 125A TP 125A TP 125A TP 125A TP 63A TP 80A TP 80A TP 80A TP 160A TP 250A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA 30 KA

1600A TP***
MCCB
36 KA EMDB-SER

2 2

---- ---- N.T.S @ A1

REV-01 SLD-09