Professional Documents
Culture Documents
Energy
journal homepage: www.elsevier.com/locate/energy
a r t i c l e i n f o a b s t r a c t
Article history: A graphical approach for the design of heat-integrated water systems has been proposed to improve
Received 22 August 2008 conceptual understanding for implications of heat recovery in water systems, as well as to provide
Received in revised form systematic design guidelines for selecting most appropriate integrated options in practice. The developed
26 February 2009
design method aims to fully exploit water reuse potentials between water-using operations, and
Accepted 19 March 2009
simultaneously to minimise any potential degradation of energy recovery resulted from water reuse.
Available online 5 May 2009
Graphical representations of heat-integrated water systems and their manipulation have been applied to
investigate systematically design interactions, impacts associated with stream merging and splitting, and
Keywords:
Water minimisation influences of non-isothermal mixing on heat recovery. Water Energy Balance Diagram has been devel-
Heat integration oped to improve energy recovery in water reuse network. Energy-efficient and cost-effective configu-
Water reuse ration for heat recovery has been identified, using improved Separate System Approach. The proposed
Heat recovery approach significantly reduces both water and energy requirements for single-contaminant water
systems.
Ó 2009 Elsevier Ltd. All rights reserved.
0360-5442/$ – see front matter Ó 2009 Elsevier Ltd. All rights reserved.
doi:10.1016/j.energy.2009.03.004
B. Leewongtanawit, J.-K. Kim / Energy 34 (2009) 880–893 881
contaminant level?
Operating temperature?
Operation 1
Water reuse
Freshwater Wastewater
Operation 2 Operation 3
Constraints
Energy
recovery
Operation N
Table 1 discharge temperatures. Minimum hot and cold utilities for Example
Operating data of Example 1 [21]. 1 are 3780 kW and 0 kW, respectively1. Both minimum freshwater
Operation Limiting Mass Load max
Cin max
Cout Temperature and energy requirements can be targeted ahead of design.
Flowrate (kg/s) (g/s) (ppm) (ppm) ( C) Two Dimensional Grid Diagram (Fig. 2) is then used to screen
Operation 1 20 2 0 100 40 design options for water reuse, subject to temperature constraints.
Operation 2 100 5 50 100 100 The diagram includes a concentration scale on the horizontal axis
Operation 3 40 30 50 800 75
and a temperature scale on the vertical axis, which captures both
Operation 4 10 4 400 800 50
concentration and temperature constraints of the operations. Three
design rules are applied to select most appropriate ways of reusing
system, as freshwater. Freshwater may undergo heating or cooling water between water streams, while degrading energy recovery is
when the temperature difference exists between temperature of intended to be minimal. As shown in Fig. 2, two non-isothermal
freshwater and the required water temperature for operations. mixing points for water reuse (one is at the inlet of Operation 3,
Water can be also reused between the operations. Reuse streams while the other at the inlet of Operation 4.) are selected among
may be heated up or cooled down, depending on the temperature possible reuse options. However, the resulting design achieves water
conditions of source and sink operations. Finally, water streams target (90 kg/s) but fails to achieve the energy targets, as additional
leave the system as wastewater. Wastewater may require cooling to 485 kW of hot and cold utilities is required (illustrated in Fig. 3). This
satisfy the discharge regulations for temperature. is because design rules for identifying reuse options within the
The design problem involves the combined water and energy intermediate water main at 100 ppm fails to consider fully the
minimisation. The synthesis of water reuse networks is a way to design consequence of water reuse selection on overall heat recovery.
all water-using operations in a holistic way, in which the freshwater Savulescu et al. [21,22] introduced a graphical design concept,
consumption and the wastewater generation can be systematically Separate System Approach, which is based on the idea of decom-
minimised by integrated allocation of water reuse according to the posing energy composite curves into ‘separate systems’ (i.e. enthalpy
quantity and quality of water required for water-using operation. On subsystems) as illustrated Fig. 3, to simplify the design of heat
the other hand, the synthesis of heat recovery systems maximises exchanger networks. A series of Separate Systems are generated by
potential recovery from waste heat, and identify the amount of energy fixing one of composite curves and modifying the other composite
to be exchanged between hot and cold water streams, and their curve to keep the same driving force for heat transfer (i.e. DTmin).
network configuration. Therefore, design tasks in the study of simul- From the data of water reuse network identified from Two
taneous water and energy minimisation are to identify targets for the Dimensional Grid Diagram, the energy composite curves are
design, namely, freshwater usage, energy consumption and waste- modified to create six blocks (i.e. separate systems) for Example 1,
water generation, as well as a network design to achieve the targets, and in this case the cold composite curve is modified both below
namely, water reuse network and heat exchanger network. and above pinch area. It should be noted that either hot or cold
An example from Savulescu et al. [21] is given in Table 1 for composite curves can be modified, and the modification chosen in
illustrating key design issues and drawbacks existed in their this design stage affects the network configuration and results in
method. The assumptions applied for their study are also employed potential penalty in energy target. As each separate system repre-
in the proposed study: sents a heat transfer unit, the simplified heat exchanger network
requires six heat transfer units (i.e. four heat exchangers, one heater
1) Single-contaminant is only considered for water use. and one cooler). The overall network is then configured from the
2) Water stream data are available for maximum inlet and outlet information on heat recovery from Separate System Approach and
concentrations, contaminant mass loads, and operating on water reuse from Two Dimension Grid Diagram.
temperatures. Therefore, the current study focuses on the development of
3) No heat loss or gain in the operation (i.e. fixed temperature a new conceptual method in order to provide a water reuse network
condition). without occurring any penalties on both water and energy targets,
4) No flowrate loss or flowrate gain in the operation as well as to facilitate a heat exchanger network with less number of
5) A single water source is available with 0 ppm and 20 C. heat transfer units and smaller heat exchanger areas. The under-
6) No discharge constraint of contaminant level for effluent. standing on simultaneous system interactions imposed by water
7) The discharge temperature is specified to be 30 C. system and energy system will be systematically investigated.
8) Design options associated with regeneration are not
considered. 3. New conceptual insights
9) Non-water-using operations are not included in the heat
recovery. To provide a better understanding, distinct features of water
10) An equal specific heat capacity for all the water streams streams (i.e. stream mixing and stream merging) are explored. The
(assumed to be 4.2 kJ/kg C). stream mixing enables the introduction of non-isothermal mixing
11) A minimum approach temperature (DTmin) is 10 C for energy in the design of water reuse networks, while the stream merging
recovery. allows the generation of separate systems in the design of heat
12) Continuous operation for water-using operations. exchanger networks.
T (°C)
100 50 kg/s
2
Point 1
11.667 kg/s
80
20 kg/s 3 40 kg/s
8.333 kg/s
60
0.952 kg/s
Point 2 5.714 kg/s
4
40 20 kg/s 4.762 kg/s
1
37.381 kg/s 6.905 kg/s
20
Water Water Water
Source Discharge Discharge
C (ppm) 0 ppm 100 ppm 800 ppm
allowed not only between streams with different concentration with Operation 4 in the Example 1. Effluent from Operations 1 and 2
levels, but also different temperature levels. This implies the heat could be reused in Operation 4. One option is to reuse water from
transfer can be made through heat exchangers (i.e. indirect heat Operation 1 to Operation 4, which requires heating for effluent
transfer) or mixing (i.e. direct heat transfer). This can be illustrated from Operation 1. On the other hand, if effluent from Operation 2 is
used for Operation 4, the reuse stream now requires cooling. These
two alternatives will have different impacts on overall heat
4265 recovery. Another possibility is to reuse water from both Operations
1 and 2, and then combine them, which involves direct heat
recovery by means of non-isothermal mixing without heat
100 exchanger unit required.
Hot composite curve
The introduction of non-isothermal mixing can replace indirect
heat recovery with direct heat recovery, which is able to contribute
Pinch
the reduction on the number of streams involving indirect heat
Temperature (°C)
75 TMIN transfer, as well as the heat duty for indirect heat transfer. This
could bring the potential reduction in the number and area of heat
65
exchangers. However, it might cause the bottleneck for indirect
heat recovery, and increase the demand of hot and cold utilities.
50 To explore the effects of non-isothermal mixing and its direct
Cold composite curve
heat recovery, six different cases are examined for evaluating non-
40
isothermal mixing in the water network design from Example 1.
30 Fig. 4 represents a water reuse network without any non-
isothermal mixing, which involves only the indirect transfer
20 scheme for heat recovery between hot and cold water streams.
3780 7560 15395 19320 23585
485 Enthalpy (kW) Fig. 5 presents the introduction of non-isothermal mixing (i.e.
direct heat recovery) at the inlet of Operation 4 between a hot reuse
Fig. 3. Separate System approach [19,22]. stream (RW2-4) and a cold reuse stream (RW1-4).
Figs. 6 and 7 show different schemes for non-isothermal mixing between the kinks on the hot composite curves originally consists of
at the inlet of Operation 3. The non-isothermal mixing in Fig. 6 is individual wastewater streams which belong to each temperature
between a hot reuse stream (RW2-3), a cold reuse stream (RW1-3) interval, and similarly each segment between the kinks on the cold
and a cold freshwater stream (FW3), while that in Fig. 7 is between composite curve consists of individual freshwater streams.
three streams: a hot reuse stream (RW2-3), a cold reuse stream If the energy composite curves are decomposed into blocks (i.e.
(RW1-3), and a cold freshwater stream (FW3). separate systems), for example, a block is defined as a region
Figs. 8 and 9 represent non-isothermal mixing occurred at the between two kinks of the hot composite curve at enthalpy 0 kW
inlet of Operations 3 and 4. The mixing at the inlet of Operation 4 is and 3780 kW. Four individual wastewater streams in this block can
one from Fig. 5. The mixing at the inlet of Operation 3 in Fig. 8 is one be merged to create one single stream on hot composite curve, and
from Fig. 6, while that in Fig. 9 is one from Fig. 7. three individual freshwater streams can be merged as a one single
Different non-isothermal mixings result in not only different stream on cold composite curve. The merged wastewater and
network configuration but also different energy implications. merged freshwater can then be matched for heat recovery to create
Table 2 summaries the results from six cases considered. The design a separate system (i.e. heat exchanger unit), in which correspond-
rules of Savulescu et al. [22] suggest only the introduction of non- ing heat exchange (3780 kW) is based on vertical heat transfer.
isothermal mixing between reuse streams. As illustrated above, the
introduction of non-isothermal mixing between hot (reuse) and 3.3. Generation of separate systems
cold (reuse and/or freshwater) streams is also possible to satisfy the
water and utility targets in the design of heat-integrated water The generation of Separate Systems could be beneficial not only
systems. for reducing the number of heat exchanger units, but also for
allowing the arrangement of vertical heat transfer. Since the
3.2. Stream merging problem involves water systems, all streams have similar film
coefficients. In this sense, the vertical heat transfer pattern is
In addition to stream mixing in the design of water reuse desirable for achieving minimum heat transfer area [25].
networks, stream merging is another feature to manipulate water Five different options for generating Separate Systems for Case 6
streams in the design of heat exchanger networks. Fig. 10 illustrates are presented in the heat exchanger network design. Fig. 11
the abilities of stream merging, based on energy composite curves demonstrates the generation of Separate Systems by following all
from the water network in Case 6. All streams on the hot composite kinks on both hot and cold composite curves. Each block is defined as
curve are wastewater streams, whereas all streams on the cold a region between two (hot or cold) kinks. As a result, seven Separate
composite curve are freshwater streams. Kink points are the Systems are created with maximum temperature driving forces.
consequences of the supply and target temperatures of all waste- Fig. 12 represents the generation of Separate Systems by
water and freshwater streams. The hot composite curve has five following the kinks and shape of the hot composite curve. Five
kinks and the cold composite curve has four kinks. Each segment Separate Systems are generated between individual kinks on the
hot composite curve with minimum approach temperature Different generations of Separate Systems result in different
(DTmin ¼ 10 C), and the modified cold composite curve terminates heat exchanger network configurations. Table 3 summaries the
at a higher temperature from 100 C to 116.4 C. Instead of results from those five different cases. If following the Separate
following the shape of hot composite curve, Fig. 13 presents the System Approach of Savulescu et al. [21,22], the number of Separate
generation of Separate Systems by following the kinks on the hot Systems is dependent on the number of kinks on the hot composite
composite curve while maximising the temperature driving forces curve above the pinch, plus that on the cold composite curve below
as much as possible. The number of Separate Systems is main- the pinch, and every Separate System has minimum temperature
tained, but the modified cold composite curve now terminates at driving force.
temperature 100 C. From the illustration above, various ways for the generation of
Fig. 14 shows the generation of Separate Systems by following Separate Systems is possible in the design of heat-integrated water
the kinks and the shape of cold composite curve. The number of systems, and their optimal selections should be made to achieve
Separate Systems can be further reduced from five to four, and the the minimum number of Separate Systems with maintaining
modified hot composite curve starts at a lower temperature (from maximum temperature driving forces as much as possible, rather
100 C to 92 C). In Fig. 15, the temperature driving forces are than having minimum driving force of DTmin. This is an important
maximised in each Separate System, and the modified hot observation which had been neglected in the previous methods,
composite curve now starts at temperature 100 C. because the exploitation of different arrangement for the
Table 2
Summary of the introduction of non-isothermal mixing.
Hot (kW) Cold (kW) Hot stream Cold stream Load (kW) Hot stream Cold stream Load (kW)
Case 1 3780 – 5 4 19560 – – –
Case 2 3780 – 5 3 19320 1 1 200
Case 3 4165 385 4 4 19175 1 1 1225
Case 4 3780 – 4 4 18720 1 2 1575
Case 5 4265 485 4 3 18835 2 2 1425
Case 6 3780 – 4 3 18480 2 3 1725
generation of Separate Systems allows better heat recovery (i.e. less A heat-integrated water system is subjected to the constraints of
heat exchanger area, less number of exchangers) with maintaining contaminant mass loads and concentration levels, as well as the
simpler configuration of networks. The new design method constraints of operating temperature levels. The design procedure
proposed in the paper will accommodate this improved conceptual for water reuse network in this paper is to guide a designer to
understanding into the design framework. identify a water reuse network with high water and energy effi-
ciency. Water Energy Balance Diagram is proposed for implementing
4. New design methodology new conceptual insights, which is an extension of Two Dimensional
Grid Diagram, and new design procedures for distributing water
4.1. Water energy balance diagram inside water mains are proposed with the aid of Water Energy
Balance Diagram.
Although minimum water and energy consumption can be Fig. 16 shows the water mains for the Example 1. Inside water
determined through targeting, different network configurations in mains, water can be distributed in different ways to satisfy the
the design stage can result in penalty on targets. Therefore, it is required flowrates and temperatures, and different water connec-
important to provide the guidance for the design of water reuse tions involve a variation in the energy consumption. Therefore, new
networks and heat exchanger networks in order to achieve the step involves a new representation of Water Energy Balance Diagram,
targets. to incorporate the energy evaluation in the design of water networks.
Wastewater streams
30° 40°
10.238 kg/s
34.048 kg/s
40.000 kg/s Individual
5.714 kg/s
30° 40°
0 kW 3780 kW
T (°C) T (°C)
3780 3780
100 100
WW1
WW2
WW 40°C - 30°C
WW3
WW4
40 40
FW1 1
30 30
FW2 FW 20°C - 30°C
20 FW3 20
0 3780 0 3780
Enthalpy (kW) Enthalpy (kW)
Freshwater streams
20° 30°
20.000 kg/s
50.000 kg/s Individual
20.000 kg/s
20° 30°
0 kW 3780 kW
T (°C)
3780
100
WW 100°C -75°C HU
(34.048 kg/s)
30 1 FW 20°C - 40°C
(90.000 kg/s)
20
3780 7130 7560 14905 14910 18480 22260
Q (kW)
One important development made in the new diagram is to shift of hot streams because wastewater is sent from the operations to
the temperature scale within the intermediate water main as the discharge with lower temperature. Following design rules of
shown in Fig. 16. This allows the minimum approach temperature Savulescu et al. [22], as the sinks (i.e. Operation 3 and Operation 4)
(10 C in this Example) between hot and cold streams. The first operate at intermediate temperatures of the sources (i.e. Operation
water main involves the distribution of cold streams, since fresh- 1 and Operation 2), the introduction of non-isothermal mixing at
water is supplied from the water source to the operations with the inlet of the Operations 3 and 4 is possible.
higher temperatures. The intermediate water main involves both Another important improvement is to incorporate heat cascade
hot and cold streams, as reuse streams can be either hot or cold diagram as shown in Fig. 17. This enables the evaluation of interval
streams depending on the temperature conditions. After the heat balances between hot and cold streams. Following the problem
temperature scale is shifted down by 10 C within the intermediate table algorithm in heat Integration [4], the heat cascade diagram
water main, the first half involves only the distribution of hot reuse represents heat flows and identifies minimum hot and cold utility
streams, while the second half involves only the distribution of cold requirements. The possibilities of non-isothermal mixing are not
reuse streams. Finally, the last water main involves the distribution only between hot and cold reuse streams, but also between hot reuse
T (°C)
3780
116.4
HU
T (°C)
3780
4
WW 75°C - 50°C
75 (74.048 kg/s)
WW 50°C - 40°C FW 65°C - 100°C
65 (50.000 kg/s)
(79.762 kg/s)
3 FW 38.9°C - 65°C
50 (70.000 kg/s)
WW 40°C
-30°C
(90 kg/s) 40 2 FW 30°C - 38.9°C
90.000 kg/s)
30 1
FW 20°C - 30°C
(90.000 kg/s)
20
3780 7130 14905 18480 22260
Q (kW)
and cold freshwater streams entering the same operation. It should streams, as the location of reuse fed to the operation has been
be noted that cooling or heating in the intermediate water main for moved to the inlet of the operation in order to achieve a uniform
reuse stream may or may not be necessary, subject to non- flowrate throughout the operation. One part of direct heat recovery
isothermal mixing patterns, however the implications for energy (735 kW) is between the hot reuse stream (15 kg/s, from Operation
recovery from this non-isothermal mixing is reflected in heat 2) and cold reuse stream (5 kg/s, from Operation 1), while the other
cascade diagram. In Fig. 17, the value in parenthesis represents the (840 kW) between the hot reuse stream (15 kg/s) and cold fresh-
enthalpy change for the water stream. water streams (20 kg/s) entering the same Operation 3. Therefore,
Fig. 17 illustrates the design and energy implication of a possible part of freshwater stream to Operation 3 gains the direct heat input
water reuse network. For non-isothermal mixing at the inlet of by means of the non-isothermal mixing. These streams associated
Operation 4, direct heat recovery (200 kW) occurs between the hot with non-isothermal mixing (i.e. streams with dashed arrow in
reuse stream (0.95 kg/s, from Operation 2) and cold reuse stream Fig. 17) will not be included in the energy recovery, and the
(4.76 kg/s, from Operation 1) entering the operation. At the inlet of remaining streams (i.e. three freshwater streams in the first water
Operation 3 there is a mixing between freshwater stream and reuse main, two wastewater streams from second water mains, and two
T (°C)
3780
100
WW 92°C - 75°C HU
(50.000 kg/s)
75 WW 75°C - 50°C
(70.000 kg/s)
FW 65°C - 100°C
65 (50.000 kg/s)
WW 50°C - 30°C
(90.000 kg/s) 2
FW 40°C - 65°C
50 (70.000 kg/s)
40
1
30 FW 20°C - 40°C
(90.000 kg/s)
20
7560 14910 18480 22260
Q (kW)
T (°C)
3780
100
WW 100°C - 75°C
(34.048 kg/s) HU
75 WW 75°C - 51°C
(74.048 kg/s)
FW 65°C - 100°C
65 (50.000 kg/s)
WW 50°C - 30°C
(90.000 kg/s) 2
FW 40°C - 65°C
50 (70.000 kg/s)
40
1
30 FW 20°C - 40°C
(90.000 kg/s)
20
7560 14910 18480 22260
Q (kW)
Table 3 recovery, with which the minimum hot utility (3780 kW) and
Summary of the generation of separate systems. minimum cold utility (0 kW) is identified. The streams involved in
Option Heat transfer unit (unit) Heat transfer areaa (m2) indirect heat recovery are also shown in Fig. 18.
Option 1 7 1380
The new tool, Water Energy Balance Diagram, allows the anal-
Option 2 5 1538 ysis of water reuse and energy recovery in the design of water
Option 3 5 1401 networks. The arrangements of direct and indirect heat transfer
Option 4 4 1517 between water streams are considered to determine the feasibility
Option 5 4 1412
of energy recovery. Therefore, the new design procedure enables
a
Based on the heat transfer coefficient of water stream ¼ 2.5 kW/m2 C, heat a designer to identify the water reuse network, which can achieve
transfer coefficient of steam ¼ 100 kW/m2 C (3 bar, 132 C)
the minimum freshwater and utility requirements.
The water reuse network in Fig. 17 not only satisfies the water
wastewater streams from third water mains) are now considered and energy targets, but also incorporates the features of non-
for heat recovery through indirect heat transfer. The problem table isothermal mixing. The non-isothermal mixing can partially
algorithm [3,4] is now applied to evaluate this indirect heat substitute indirect heat transfer with direct heat transfer. Such
T (°C)
90 kg/s 45.714 kg/s 0 kg/s
Limiting water 0 ppm 100 ppm 800 ppm
flowrate (kg/s)
50 kg/s
100° 2 2
100 kg/s 2 100°
20 kg/s
75° 3 3
40 kg/s 3 40 kg/s 3 75°
10 kg/s 50° 4
20 kg/s 4 5.714 kg/s 4 50°
40° 1 1
20 kg/s
1 40°
30°
20°
Water Water Water
Source Discharge Discharge
0 ppm 100 ppm 800 ppm
C (ppm)
0 kg/s 44.286 kg/s 45.714 kg/s
T (°C)
90 kg/s 45.714 kg/s 0 kg/s (a) (b)
0 ppm 100 ppm 800 ppm Hot utility Hot utility
0 3780
100° 2 2
2 100° H = -2100 -2100 H = -2100 1680
H = -1005 H = -1005
-3105 675
75° 3 3 H = -670 H = -670
3 3 75° -3735 5
15
H = +255 H = +255
-3520 260
50° 4 H = +170 H = -170
4 4 50° -3350 430
40° 1 5 4.762 1 0.952 H = -430 H= -430
1 40° -3780 0
30° H= 0 -3780 H= 0 0
20° 50 20 20 10.238 34.048 5.714 40 (kW) (kW)
Water Water Water
Source Discharge Discharge Cold utility Cold utility
100 ppm 800 ppm
C (ppm) 0 ppm 44.286 kg/s 45.714 kg/s
0 kg/s
Source operation Sink operation
Stream involving indirect heat transfer Stream involving direct heat transfer
substitution is a potential to reduce the number and area of heat required. Not all streams involve the indirect heat transfer through
exchangers in the design of heat exchanger networks. heat exchangers, as some streams are subject to the direct heat
transfer via the non-isothermal mixing. The thermal data of
freshwater and wastewater streams, which involve the design of
4.2. New separate system approach
heat exchanger network, are represented in Fig. 18(a). Energy
composite curves are generated based on such thermal stream data
As the synthesis of heat exchanger networks here involves only
of freshwater and wastewater streams with 10 C of minimum
water streams, the design of heat exchanger networks can be
approach temperature. Fig. 18(b) represents the initial energy
simplified with the generation of Separate Systems. A new
composite curves.
systematic design approach of Separate System Generation is
developed to design a heat exchanger network, which involves
4.2.2. Step 2: Maintain the utility consumption and minimise the
a small number of heat transfer units with the arrangement of
number of separate systems
vertical heat transfer. A description of the procedure is as follows.
In order to obtain the minimum utility consumption, the heat
recovery between hot and cold composite curves must remain at
4.2.1. Step 1: Set up the initial energy composite curves
the maximum value. The heat recovery zone defines the start and
To complete the heat exchanger network design, the extraction
end of Separate Systems between wastewater and freshwater
of thermal stream data from the water reuse network (Fig. 17) is
a b
30°C 10.238 kg/s 40°C T (°C)
WW 1 3780
WW2
30°C 34.048 kg/s 100°C 100
WW 2
WW2
30°C 40.000 kg/s 75°C WW3
WW 3
WW2
30°C 50°C 75
5.714 kg/s WW3 FW2
WW 4 WW4
65
WW1
WW2
WW3 50
FW2
WW4
20°C 20.000 kg/s 40°C FW3
FW 1 40
FW1
20°C 50.000 kg/s 100°C 30 FW2
FW 2 FW3
20
20°C 20.000 kg/s 75°C
FW 3 3780 7130 7560 14905 14910 18480 22260
Q (kW)
Thermal stream data of water network Initial energy composite curves
a T (°C)
3780
b T (°C)
3780
WW2 WW2
100 100
WW2 WW2
WW3 WW3
WW2 WW2
75 75
WW3 FW2 WW3 FW2
WW4 65 WW4
WW1 65 WW1
WW2 WW2
WW3 50 WW3 50
FW2 FW2
WW4 WW4
FW3 FW3
40 40
FW1 FW1
30 FW2 30 FW2
FW3 FW3
20 20
18480 22260 18480 22260
QRECOVERY QRECOVERY
Keep the maximum heat recovery Minimise the number of separate systems
streams, as shown in Fig. 19(a). In order to obtain the minimum temperature driving forces between hot and cold streams should be
number of Separate Systems, the fewest kinks should be selected. In maximised. The shaded area in Fig. 20 (a) represents the modifi-
this case, the kinks on the cold composite curve are selected, as cation of the hot composite curve, which is minimised for achieving
fewer kinks on the cold than the hot composite curve within the maximum temperature driving force in each Separate System. The
heat recovery zone. The boundaries of each Separate System are stream merging enables each segment of composite curves to be
created at the selected kink points as shown in Fig. 19(b). treated as a single stream in the generation of Separate Systems.
Fig. 20 (a) shows that individual wastewater streams are isother-
4.2.3. Step 3: Maximise the temperature driving force in each mally or non-isothermally merged within individual Separate
Separate System Systems, while freshwater distribution from Separate Systems does
Each Separate System represents a single heat transfer unit not change the profile or create the temperature degradation of the
between a single hot stream and a single cold stream, in which the cold composite curve.
However, two non-isothermal mixing areas identified from
Fig. 20(a) have not connected with each other. Such a disjunctive
a Temperature
and discontinuous creation for mixing areas leads to infeasible
[°C]
design, which requires adjustment for original design to regain
100
HU
feasibility. Fig. 20(b) shows the updated design of Separate Systems,
in which two non-isothermal mixing areas are linked after relaxing
3
75 maximum driving force of heat transfer in second heat recovery
New non-isothermal
stream mixing areas zone. This heat recovery with reduced driving force will increase
2 the overall heat exchanger area required than necessary.
50
10.206 kg/s
10.238 kg/s
5.714 kg/s
4.082 kg/s
40.000 kg/s
75.035°
34.048 kg/s
20.000 kg/s
Merged streams
Individual streams
10.206 kg/s
10.238 kg/s
5.714 kg/s
4.082 kg/s
40.000 kg/s
(i.e. fewer heat transfer units) and larger temperature driving forces water and energy (i.e. less hot and cold utilities) and enables the
(i.e. smaller heat transfer areas). effective structure for water reuse and heat exchanger networks
It should be noted that although the new approach is illustrated (i.e. fewer heat transfer units and smaller heat transfer areas).
with the threshold problem, it can also be applied to pinch prob-
lems. Finally, an overall network configuration is a combined result
of the water network design (Fig. 17) from Water Energy Balance
Table 4
Diagram and the heat exchanger network design (Fig. 21) from Overall design comparison (I).
Separate System Generation. The new overall network design is
Requirements Graphic-based New design Improvement (%)
presented in Fig. 22. The design can achieve both the water and method by
energy targets and accommodate the features of non-isothermal Savluescu et al. [22]
mixing and Separate Systems effectively and systematically. Freshwater (kg/s) 90 90 –
Tables 4 and 5 summarise the results for the new design of Hot utility (kW) 4265 3780 11
Fig. 22. The new conceptual design method is significantly Cold utility (kW) 485 0 100
improved (Table 4), compared to previous graphic-based design Heat exchanger unit (unit) 5 4 25
Heat exchanger area (m2) 1584 1390.7 11.2
method [22], because it provides the design with better use of
B. Leewongtanawit, J.-K. Kim / Energy 34 (2009) 880–893 893
Table 5 [2] Linnhoff B, Hindmarsh E. The pinch design method for heat exchanger
Overall design comparison (II). networks. Chemical Engineering Science 1983;38(5):745–63.
[3] Linnhoff B, Townsend D, Boland D, Hewitt G, Thomas B, Guy A, et al. User
Requirements Automated design New Improvement (%) guide on process integration for the efficient use of energy. Rugby: IChemE;
by Bogataj and design 1982.
Bagajewicz [24] [4] Smith R. Chemical process design and integration. UK: John Wiley; 2005.
[5] Varbanov P, Perry S, Klemeš J, Smith R. Synthesis of industrial utility systems:
Heat exchanger unit (unit) 4 4 –
cost-effective de-carbonisation. Applied Thermal Engineering
Heat exchanger area for 3498.4 3370.4 3.7
2005;25(7):985–1001.
water-to-water heat [6] Kemp I. Pinch analysis and process integration: a user guide on process
recovery (m2) integration for the efficient use of energy. 2nd ed. UK: IChemE; 2007.
Heat exchanger area for a 132.2 132.2 – [7] Klemeš J, Perry S. Process optimisation to minimise energy use in food pro-
heater (m2) cessing. In: Waldron K, editor. Handbook of waste management and co-
product recovery in food processing, vol. 1. UK: Woodhead Publising; 2007. p.
* Based on the heat transfer coefficient of water stream ¼ 1 kW/m2 C (15 C–20 C),
59–89.
heat transfer coefficient of steam ¼ 5 kW/m2 C (126 C).
[8] Floudas CA, Ciric AR. Strategies for overcoming uncertainties in heat
exchanger network synthesis. Computers and Chemical Engineering
1989;13(10):1133–52.
[9] Daichendt MM, Grossmann IE. Preliminary screening procedure for the MINLP
synthesis of process systems II: heat exchanger networks. Computers &
The result is also compared with the one from automated design Chemical Engineering 1994;18(8):679–709.
method by Bogataj and Bagajewicz [24] in Table 5, by applying the [10] El-Halwagi M. Pollution prevention through process integration: systematic
design tools. San Diego: Academic Press; 1997.
same design parameters. The methodological soundness and [11] Wang YP, Smith R. Wastewater minimisation. Chemical Engineering Science
coherence of the design method developed in this paper is clearly 1994;49(7):981–1006.
demonstrated, and the developed design method is able to produce [12] Kuo W, Smith R. Design of water-using systems involving regeneration.
Transactions of the Institution of Chemical Engineers 1998;76(B):94–114.
high quality solutions as much as mathematical optimisation [13] Wang YP, Smith R. Design of distributed effluent treatment systems. Chemical
methods can offer. Engineering Science 1994;49:3127–45.
[14] Kuo W, Smith R. Effluent treatment system design. Chemical Engineering
Science 1997;52:4273–90.
5. Summary [15] Galen B, Grossmann IE. Optimal design of distributed wastewater treatment
networks. Industrial & Engineering Chemistry Research 1998;37:4036–48.
New conceptual design method for heat-integrated water [16] Thevendiraraj S, Klemeš J, Paz D, Aso G, Cardenas G. Water and wastewater
minimisation study of a citrus plant. Resources, Conservation and Recycling
system design has been proposed. The new tool, Water Energy
2003;37:227–50.
Balance Diagram, allows the analysis of water reuse, as well as the [17] Gunaratnam M, Alva-Argáez A, Kokossis A, Kim J, Smith R. Automated design
analysis of direct and indirect heat recovery in the design of water of total water systems. Industrial & Engineering Chemistry Research
2005;44:588–99.
reuse networks. The new procedure, Separate System Generation,
[18] Foo DCY. 11th Conference on Process Integration, Modelling and Optimisation
enables the systematic modification of energy composite curves for for Energy Saving and Pollution Reduction (PRES 2008), Prague, Czech
simplifying the design of heat exchanger networks and minimising Republic, 24–28 August, 2008.
exchanger areas for heat recovery. The proposed method provides [19] Savulescu L, Alva-Argaez. Direct heat transfer considerations for improving
energy efficiency in pulp and paper Kraft mills. Energy 2008;33:1562–71.
an efficient design of heat-integrated water systems, because the [20] Bagajewicz M, Rodera H, Savelski M. Energy efficient water utilisation systems
introduction of non-isothermal mixing has been systematically in process plants. Computers and Chemical Engineering 2002;26:59–79.
incorporated in the targeting and design method, which allows [21] Savulescu L, Kim J, Smith R. Studies on simultaneous energy and water min-
imisation – Part I: systems with no water re-use. Chemical Engineering
achieving minimum water and energy consumptions, and cost- Science 2005;60:3279–90.
effective arrangement for heat recovery existed in the water reuse [22] Savulescu L, Kim J, Smith R. Studies on simultaneous energy and water min-
networks. Comparison has been made against previous design imisation – Part II: systems with maximum re-use. Chemical Engineering
Science 2005;60:3291–308.
methods using both graphical technique and mathematical opti- [23] Leewongtanawit B, Kim J. Synthesis and optimisation of heat-integrated
misation, which shows the applicability and robustness of design multiple-contaminant water systems. Chemical Engineering and Processing
method proposed in this paper. 2008;47:670–94.
[24] Bogataj M, Bagajewicz MJ. Synthesis of non-isothermal heat-integrated water
networks in chemical processes. Computers & Chemical Engineering 2008;.
References doi:10.1016/j.compchemeng.2008.05.006.
[25] Gundersen T, Grossmann IE. Improved optimization strategies for automated
[1] Linnhoff B, Mason DR, Wardle I. Understanding heat exchanger networks. heat exchanger network synthesis through physical insights. Computers &
Chemical Engineering Science 1979;3:295–302. Chemical Engineering 1990;14(9):925–44.