You are on page 1of 71

Cat Electronic Technician 2022A v1.

0
Product Status Report

05/09/2022 21:35

Product Status Report


Parameter Value
Product ID GFP01229
Equipment ID INDUS DYEING
Comments

G3520 EPG-Standard (GFP01229)


Parameter Value
Equipment ID INDUS DYEING
Engine Serial Number GFP01229
ECM Serial Number 03608476RE
Software Group Part Number 5936337-00
Software Group Release Date OCT2019
Software Group Description Rel: GAS_FUMI_LB_ALPHA_11pt1

Logged Diagnostic Codes [SHM: 10055.5] - G3520 EPG-Standard (GFP01229)


Code Description Occ. SHM First SHM Last
168- 4 Battery Potential / Power Input #1 : 32 4118:36:09 10055:21:01
Voltage Below Normal

Logged Event Codes [SHM: 10055.5] - G3520 EPG-Standard (GFP01229)


Code Description Occ. SHM First SHM Last
1143-15 Engine Exhaust Gas Port 7 8 9950:43:11 10042:50:45
Temperature : High - least severe
(1)
1148-15 Engine Exhaust Gas Port 12 4 9950:43:10 10042:47:17
Temperature : High - least severe
(1)
1144-15 Engine Exhaust Gas Port 8 30 9230:32:37 10041:58:52
Temperature : High - least severe
(1)
1137-15 Engine Exhaust Gas Port 1 17 8396:47:09 10038:50:22
Temperature : High - least severe
(1)
3607-31 Engine Emergency Shutdown 9 4886:07:29 9991:38:28
Indication
1138-15 Engine Exhaust Gas Port 2 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1139-15 Engine Exhaust Gas Port 3 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1140-15 Engine Exhaust Gas Port 4 1 9950:43:09 9950:43:09
Temperature : High - least severe
(1)
1141-15 Engine Exhaust Gas Port 5 1 9950:43:09 9950:43:09
Temperature : High - least severe
(1)
1142-15 Engine Exhaust Gas Port 6 4 7893:44:15 9950:43:10
Temperature : High - least severe
(1)
1145-15 Engine Exhaust Gas Port 9 3 7893:44:28 9950:43:12
Temperature : High - least severe
(1)
1146-15 Engine Exhaust Gas Port 10 1 9950:43:11 9950:43:11
Temperature : High - least severe
(1)
1147-15 Engine Exhaust Gas Port 11 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1149-15 Engine Exhaust Gas Port 13 1 9950:43:11 9950:43:11
Temperature : High - least severe
(1)
1150-15 Engine Exhaust Gas Port 14 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1151-15 Engine Exhaust Gas Port 15 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1152-15 Engine Exhaust Gas Port 16 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1153-15 Engine Exhaust Gas Port 17 1 9950:43:11 9950:43:11
Temperature : High - least severe
(1)
1154-15 Engine Exhaust Gas Port 18 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1155-15 Engine Exhaust Gas Port 19 1 9950:43:13 9950:43:13
Temperature : High - least severe
(1)
1156-15 Engine Exhaust Gas Port 20 1 9950:43:10 9950:43:10
Temperature : High - least severe
(1)
1180- 0 Engine Turbocharger #1 Turbine 1 9950:43:18 9950:43:18
Intake Temperature : High - most
severe (3)

Active Diagnostic Codes [SHM: 10055.5] - G3520 EPG-Standard (GFP01229)


Code Description Occ.
2988- 7 Engine Coolant Diverter Valve : Not Responding Properly 1
3216- 9 Engine Exhaust #1 NOx #1 : Abnormal Update Rate 1

Active Event Codes [SHM: 10055.5] - G3520 EPG-Standard (GFP01229)


Code Description Occ.
No Active
Events
Current Totals - G3520 EPG-Standard (GFP01229)
Description Value Unit
Total Operating Hours 10055.4 hours

Configuration - G3520 EPG-Standard (GFP01229)


Description Value Unit
Equipment ID INDUS DYEING
Engine Serial Number GFP01229
Rating Number Unavailable
First Desired Timing 24.0 Deg
Spark Plug Life Extension Feature Enable Unavailable
Status
Fuel Quality Input Type Configuration Configured Value
Fuel Quality 33.40 MJ/nm3
Fuel Quality Sensor LHV Lower Setpoint 25.0 MJ/nm3
Fuel Quality Sensor LHV Upper Setpoint 94.0 MJ/nm3
Gas Specific Gravity 0.632
Fuel Specific Heat Ratio 1.320
Emissions Feedback Mode Configuration NOx Feedback
Desired Engine Exhaust NOx Level Setting 180.0 ppm
Air/Fuel Ratio Proportional Gain Unavailable %
Percentage
Air/Fuel Ratio Integral Gain Percentage Unavailable %
Desired Speed Input Configuration 0-5 VDC Input
Secondary Desired Speed Input Not Installed
Configuration
Low Idle Speed 1000 rpm
Engine Acceleration Rate 150 rpm/s
Maximum Engine High Idle Speed 1550.0 rpm
Minimum Engine High Idle Speed 1460.0 rpm
Governor Type Setting Droop
Engine Speed Droop 1.0 %
Governor (Proportional) Gain Percentage 100.0 %
Governor (Integral) Stability Percentage 100.0 %
Engine State Control Input Configuration CAN Input
Starting System #1 Type Electrical
Crank Terminate RPM 250 rpm
Engine Purge Cycle Time 8 sec
Crank Duration 30 sec
Cycle Crank Time 210 sec
Engine Speed Drop Time 40.0 sec
Cooldown Duration 0 min
Engine Protection System Approaching Unavailable
Shutdown Indicator Installation Status
Specific Humidity Sensor Installation Status Unavailable
Gaseous Fuel Methane Number Unavailable
Configuration
Engine Intake Manifold Air Temperature Unavailable %
Control Proportional Gain Percentage
Engine Intake Manifold Air Temperature Unavailable %
Control Integral Gain Percentage
Minimum Desired Intake Manifold Air Unavailable Deg C
Temperature Configuration
Maximum Desired Separate Circuit Unavailable Deg C
Aftercooler Temperature Configuration
Separate Circuit Aftercooler Coolant Mixing Unavailable
Valve Installation Status
Crankcase Pressure Sensor Installation Unavailable
Status
Engine Pre-Lube Enabled
Engine Pre-Lube System Configuration Automatic
Engine Ready to Start Pre-Lube Duration 120 sec
Engine Continuous Pre-Lube Duration 2.00 min
Engine Continuous Pre-Lube Interval 120 min
Engine Post-Lube Duration 120 sec
Generator Output Power Primary Input CAN Input
Type Configuration
Generator Output Power Primary Input -50.000 kW
Minimum Data Range
Generator Output Power Primary Input 2586.000 kW
Maximum Data Range
Generator Output Power Secondary Input Not Installed
Type Configuration
Generator Output Power Secondary Input -50.000 kW
Minimum Data Range
Generator Output Power Secondary Input 2586.000 kW
Maximum Data Range
Engine Driven Accessory Load 0 kW
Configuration
Generator Efficiency Configuration 96.0 %
CAN Communication Protocol Write Unavailable
Security
CAN Communication Protocol Read Unavailable
Security
Total Tattletale 0
Desired IMAT Temperature 60 Deg C
Methane Number 90.0000
IMAT Control Proportional Gain % 100 %
IMAT Control Integral Gain % 100 %
Max. Desired SCAC Temperature 60 Deg C
SCAC Mixing Valve Inst. Status (16=inst., 16
17=not inst.)
Crank Case Pressure Sensor Inst. Status 16
(16=inst., 17=not inst.)
Humidity/Altitude Derate Enable 0=Derate 0
Disabled, 1=Derate Enabled
Engine Rating 1=HR (High Response), 1
2=HE (High Efficiency), 3=HFT (High
Humidity, Fuel Tolerant)

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Coolant
Temperature - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
Deg C
<88.0 122.30 463.15 1121.60 815.60 100.55 0.00 0.00 0.00 2623.20
88.0- 8.20 49.35 472.65 1503.60 1854.50 51.25 0.00 0.00 3939.55
89.9
90.0- 0.00 0.00 0.90 128.55 2455.70 226.30 0.10 0.00 2811.55
91.9
92.0- 0.00 0.00 0.00 4.50 555.00 112.80 0.85 0.00 673.15
93.9
94.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
95.9
96.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
97.9
98.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
100.0
>100.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 130.50 512.50 1595.15 2452.25 4965.75 390.35 0.95 0.00 10047.4
5

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Intake Manifold Air
Temperature - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
Deg C
<46.0 0.65 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.70
46.0- 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
46.9
47.0- 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
47.9
48.0- 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
48.9
49.0- 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
49.9
50.0- 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
50.9
51.0- 0.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20
51.9
52.0- 0.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20
52.9
53.0- 0.25 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.30
53.9
54.0- 0.25 0.20 0.05 0.00 0.00 0.00 0.00 0.00 0.50
54.9
55.0- 0.30 0.75 0.15 0.00 0.00 0.00 0.00 0.00 1.20
56.0
>56.0 117.85 511.35 1594.90 2452.25 4965.70 390.40 0.95 0.00 10033.4
0
Total 120.45 512.40 1595.10 2452.25 4965.70 390.40 0.95 0.00 10037.2
5
Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Aftertreatment #1
Intake #1 NOx - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
Aftertrea
tment #1
Intake
#1 NOx
<0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
19.99
20.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
39.99
40.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
44.99
45.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
49.99
50.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
54.99
55.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
59.99
60.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
69.99
70.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
79.99
80.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
89.99
90.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
99.99
100.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
109.99
110.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
114.99
115.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
119.99
120.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
124.99
125.00- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
129.99
130.00- 0.00 0.30 1.95 2.05 16.85 0.70 0.00 0.00 21.85
154.99
155.00- 0.10 189.60 806.80 1306.45 2519.60 161.50 0.45 0.00 4984.50
179.99
180.00- 3.95 296.00 768.15 1138.25 2404.10 222.90 0.50 0.00 4833.85
204.99
205.00- 54.20 22.25 5.35 1.95 24.75 5.30 0.00 0.00 113.80
229.99
230.00- 7.55 0.10 0.05 0.00 0.00 0.00 0.00 0.00 7.70
234.99
235.00- 6.10 0.05 0.00 0.00 0.00 0.00 0.00 0.00 6.15
239.99
240.00- 3.95 0.05 0.00 0.00 0.00 0.00 0.00 0.00 4.00
244.99
245.00- 2.65 0.05 0.00 0.00 0.00 0.00 0.00 0.00 2.70
249.99
250.00- 1.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.75
254.99
255.00- 1.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.15
259.99
260.00- 3.70 0.05 0.00 0.00 0.00 0.00 0.00 0.00 3.75
279.99
280.00- 3.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.45
299.99
300.00- 11.35 0.05 0.05 0.00 0.00 0.00 0.00 0.00 11.45
400.00
>400.00 15.70 0.05 0.05 0.00 0.00 0.00 0.00 0.00 15.80
Total 115.60 508.55 1582.40 2448.70 4965.30 390.40 0.95 0.00 10011.9
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Oil
Temperature - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
Deg C
<(-10.0) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
(-10.0)-(- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.1)
0.0-9.9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
19.9
20.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
29.9
30.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
39.9
40.0- 0.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
49.9
50.0- 1.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
59.9
60.0- 0.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65
64.9
65.0- 0.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.70
69.9
70.0- 0.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.70
74.9
75.0- 0.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.70
79.9
80.0- 1.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
84.9
85.0- 124.80 512.50 1595.10 2433.00 4105.65 274.95 0.95 0.00 9046.95
89.9
90.0- 0.00 0.00 0.00 19.20 860.15 115.40 0.00 0.00 994.75
94.9
95.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
99.9
100.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
104.9
105.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
110.0
>110.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 130.00 512.50 1595.10 2452.20 4965.80 390.35 0.95 0.00 10046.9
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Average
Exhaust Port Temperature - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
Deg C
<600.0 12.25 0.25 0.00 0.00 0.00 0.00 0.00 0.00 12.50
600.0- 88.15 30.90 0.20 0.00 21.55 49.15 0.45 0.00 190.40
609.9
610.0- 28.00 443.95 428.65 251.55 2278.75 307.55 0.50 0.00 3738.95
619.9
620.0- 0.70 37.30 878.85 1315.85 2588.90 33.70 0.00 0.00 4855.30
629.9
630.0- 0.35 0.10 286.15 881.40 76.55 0.00 0.00 0.00 1244.55
639.9
640.0- 0.35 0.00 1.30 3.40 0.00 0.00 0.00 0.00 5.05
649.9
650.0- 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
659.9
660.0- 0.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
669.9
670.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
680.0
>680.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 129.95 512.50 1595.15 2452.20 4965.75 390.40 0.95 0.00 10046.9
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Turbocharger
Compressor Bypass Valve Position - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
%
<10.0 10.70 0.20 0.00 0.00 0.00 0.00 0.00 0.00 10.90
10.0- 88.60 86.75 62.65 78.55 1820.85 362.45 0.95 0.00 2500.80
19.9
20.0- 30.00 425.55 1532.40 2373.65 3144.90 27.95 0.00 0.00 7534.45
29.9
30.0- 0.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
39.9
40.0- 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
50.0
>50.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 129.95 512.50 1595.05 2452.20 4965.75 390.40 0.95 0.00 10046.8
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Gas Fuel
Correction Factor - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
%
<85.0 120.40 512.50 1595.15 2452.25 4965.75 390.40 0.95 0.00 10037.4
0
85.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
87.9
88.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
90.9
91.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
93.9
94.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
96.9
97.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
99.9
100.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
102.9
103.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
105.9
106.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
108.9
109.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
111.9
112.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
115.0
>115.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 120.40 512.50 1595.15 2452.25 4965.75 390.40 0.95 0.00 10037.4
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Fuel Valve Position
- G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
%
<20.0 20.40 80.20 249.20 383.50 775.70 61.10 0.15 0.00 1570.25
20.0- 10.15 40.05 124.50 191.25 387.40 30.50 0.05 0.00 783.90
29.9
30.0- 10.20 40.05 124.50 191.55 388.65 30.45 0.10 0.00 785.50
39.9
40.0- 10.15 40.05 124.50 191.35 387.80 30.60 0.10 0.00 784.55
49.9
50.0- 10.10 40.15 124.70 191.55 387.80 30.55 0.10 0.00 784.95
59.9
60.0- 10.15 40.10 124.65 192.25 388.35 30.60 0.05 0.00 786.15
69.9
70.0- 10.10 40.00 124.70 191.70 388.00 30.45 0.05 0.00 785.00
80.0
>80.0 48.80 191.95 598.35 919.10 1862.10 146.15 0.35 0.00 3766.80
Total 130.05 512.55 1595.10 2452.25 4965.80 390.40 0.95 0.00 10047.1
0
Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine #1 Throttle
Position - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
%
<40.0 7.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.55
40.0- 2.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.50
44.9
45.0- 4.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.05
49.9
50.0- 45.65 0.60 0.05 0.00 0.00 0.00 0.00 0.00 46.30
54.9
55.0- 70.05 379.15 235.20 48.35 0.85 0.00 0.00 0.00 733.60
59.9
60.0- 0.10 132.70 1356.90 2337.70 3339.60 237.40 0.10 0.00 7404.50
64.9
65.0- 0.00 0.05 3.00 66.10 1625.30 152.95 0.80 0.00 1848.20
70.0
>70.0 0.10 0.00 0.05 0.05 0.00 0.00 0.05 0.00 0.25
Total 130.00 512.50 1595.20 2452.20 4965.75 390.35 0.95 0.00 10046.9
5

Job:Accumulated Time vs Engine Oil Temperature And Engine Coolant Temperature - G3520
EPG-Standard (GFP01229)
Deg C <(-10.0) (-10.0)-(- 0.0-9.9 10.0- 20.0- 30.0- 40.0- 50.0- 60.0-
0.1) 19.9 29.9 39.9 49.9 59.9 64.9
Deg C
<10.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
19.9
20.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
29.9
30.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
39.9
40.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.10 0.00 0.00
49.9
50.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.25 0.70 0.00
59.9
60.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30 0.65
69.9
70.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
79.9
80.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
89.9
90.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
99.9
100.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
110.0
>110.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 0.00 0.00 0.00 0.00 0.00 0.00 0.35 1.00 0.65
Job:Accumulated Time vs Engine Oil Temperature And Engine Coolant Temperature - G3520
EPG-Standard (GFP01229)
Deg C 65.0- 70.0- 75.0- 80.0- 85.0- 90.0- 95.0- 100.0- 105.0-
69.9 74.9 79.9 84.9 89.9 94.9 99.9 104.9 110.0
Deg C
<10.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
19.9
20.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
29.9
30.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
39.9
40.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
49.9
50.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
59.9
60.0- 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
69.9
70.0- 0.25 0.70 0.40 0.00 0.00 0.00 0.00 0.00 0.00
79.9
80.0- 0.00 0.00 0.30 1.05 6557.00 0.00 0.00 0.00 0.00
89.9
90.0- 0.00 0.00 0.00 0.00 2489.95 994.75 0.00 0.00 0.00
99.9
100.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
110.0
>110.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 0.70 0.70 0.70 1.05 9046.95 994.75 0.00 0.00 0.00

Job:Accumulated Time vs Engine Oil Temperature And Engine Coolant Temperature - G3520
EPG-Standard (GFP01229)
Deg C >110.0 Total
Deg C
<10.0 0.00 0.00
10.0-19.9 0.00 0.00
20.0-29.9 0.00 0.00
30.0-39.9 0.00 0.00
40.0-49.9 0.00 0.10
50.0-59.9 0.00 0.95
60.0-69.9 0.00 1.40
70.0-79.9 0.00 1.35
80.0-89.9 0.00 6558.35
90.0-99.9 0.00 3484.70
100.0-110.0 0.00 0.00
>110.0 0.00 0.00
Total 0.00 10046.85

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Throttle
Valve #1 Differential Pressure - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
kPa
<0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.0-4.9 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
5.0-9.9 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
10.0- 0.20 0.05 0.15 0.05 0.00 0.00 0.00 0.00 0.45
14.9
15.0- 66.80 396.45 1173.25 782.45 418.30 48.40 0.25 0.00 2885.90
19.9
20.0- 53.80 115.90 421.65 1669.45 4546.85 341.90 0.70 0.00 7150.25
24.9
25.0- 1.85 0.05 0.05 0.20 0.60 0.10 0.00 0.00 2.85
29.9
30.0- 0.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
34.9
35.0- 0.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
40.0
>40.0 6.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.40
Total 130.00 512.45 1595.10 2452.15 4965.75 390.40 0.95 0.00 10046.8
0

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Knock Level
- G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
%
<10.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
10.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
19.9
20.0- 0.05 0.05 0.25 0.00 0.00 0.00 0.00 0.00 0.35
29.9
30.0- 54.20 220.60 598.70 1055.35 1184.40 55.60 0.05 0.00 3168.90
39.9
40.0- 64.40 284.10 965.30 1348.65 3521.95 292.05 0.75 0.00 6477.20
49.9
50.0- 1.70 7.65 30.55 47.65 253.25 40.85 0.15 0.00 381.80
59.9
60.0- 0.05 0.10 0.35 0.55 6.05 1.85 0.00 0.00 8.95
69.9
70.0- 0.00 0.00 0.00 0.00 0.10 0.05 0.00 0.00 0.15
79.9
80.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
89.9
90.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
99.9
100.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
110.0
>110.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 120.40 512.50 1595.15 2452.20 4965.75 390.40 0.95 0.00 10037.3
5

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Intake Manifold
Pressure - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- 97.0- 99.0-
54.9 64.9 74.9 84.9 94.9 96.9 98.9 100.9
kPa
<200.0 66.30 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
200.0- 54.10 92.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
229.9
230.0- 0.00 403.05 57.35 0.00 0.00 0.00 0.00 0.00 0.00
259.9
260.0- 0.00 17.25 972.35 0.05 0.00 0.00 0.00 0.00 0.00
289.9
290.0- 0.00 0.00 565.45 1266.65 0.00 0.00 0.00 0.00 0.00
319.9
320.0- 0.00 0.00 0.05 1181.80 327.60 0.00 0.00 0.00 0.00
349.9
350.0- 0.00 0.00 0.00 3.70 3929.50 7.25 0.00 0.00 0.00
379.9
380.0- 0.00 0.00 0.00 0.00 708.65 383.00 0.00 0.00 0.00
409.9
410.0- 0.00 0.00 0.00 0.00 0.00 0.15 0.05 0.00 0.00
439.9
440.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25 0.60
469.9
470.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
500.0
>500.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 120.40 512.55 1595.20 2452.20 4965.75 390.40 0.05 0.25 0.60

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Intake Manifold
Pressure - G3520 EPG-Standard (GFP01229)
% 101.0-102.9 103.0-105.0 >105.0 Total
kPa
<200.0 0.00 0.00 0.00 66.35
200.0-229.9 0.00 0.00 0.00 146.30
230.0-259.9 0.00 0.00 0.00 460.40
260.0-289.9 0.00 0.00 0.00 989.65
290.0-319.9 0.00 0.00 0.00 1832.10
320.0-349.9 0.00 0.00 0.00 1509.45
350.0-379.9 0.00 0.00 0.00 3940.45
380.0-409.9 0.00 0.00 0.00 1091.65
410.0-439.9 0.00 0.00 0.00 0.20
440.0-469.9 0.10 0.00 0.00 0.95
470.0-500.0 0.00 0.00 0.00 0.00
>500.0 0.00 0.00 0.00 0.00
Total 0.10 0.00 0.00 10037.50

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed - G3520 EPG-Standard
(GFP01229)
Percent Engine Load at Current hours %
Engine Speed( % )
<45.0 130.55 1.30
45.0-54.9 512.50 5.10
55.0-64.9 1595.05 15.88
65.0-74.9 2452.10 24.41
75.0-84.9 4966.45 49.43
85.0-94.9 389.90 3.88
95.0-105.0 0.95 0.01
>105.0 0.00 0.00

Job:Accumulated Occurrences vs Engine Startup Period - G3520 EPG-Standard (GFP01229)


Engine Startup Period( sec ) Count %
<4.0 0 0.00
4.0-4.4 0 0.00
4.5-4.9 0 0.00
5.0-5.4 0 0.00
5.5-5.9 0 0.00
6.0-6.4 0 0.00
6.5-6.9 0 0.00
7.0-7.4 0 0.00
7.5-7.9 0 0.00
8.0-8.4 0 0.00
8.5-8.9 0 0.00
9.0-9.4 0 0.00
9.5-10.0 0 0.00
>10.0 86 100.00

Job:Accumulated Time vs Percent Engine Load at Current Engine Speed And Engine Oil Filter
Differential Pressure - G3520 EPG-Standard (GFP01229)
% <45.0 45.0- 55.0- 65.0- 75.0- 85.0- 95.0- >105.0 Total
54.9 64.9 74.9 84.9 94.9 105.0
kPa
<50.0 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.15
50.0- 1.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.15
59.9
60.0- 2.55 0.40 0.95 0.70 1.00 0.10 0.00 0.00 5.70
69.9
70.0- 37.20 118.20 248.70 253.30 347.00 17.50 0.00 0.00 1021.90
79.9
80.0- 87.95 386.95 1292.70 2022.10 3918.35 283.40 0.35 0.00 7991.80
89.9
90.0- 1.00 6.85 52.40 175.05 695.05 88.10 0.55 0.00 1019.00
99.9
100.0- 0.00 0.05 0.30 0.95 4.90 0.80 0.05 0.00 7.05
109.9
110.0- 0.00 0.00 0.00 0.00 0.15 0.05 0.00 0.00 0.20
119.9
120.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
129.9
130.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
139.9
140.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
149.9
150.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
159.9
160.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
179.9
180.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
579.9
580.0- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1000.0
>1000.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 130.00 512.45 1595.05 2452.10 4966.45 389.95 0.95 0.00 10046.9
5

Monitoring System - G3520 EPG-Standard (GFP01229)


Description State Trip Point Delay Time
Engine Overspeed
Least Severe (1) On 1700 rpm 2 sec
Most Severe (3) Always On 1875 rpm 0 sec
Exhaust Port
Temperature High
Deviation
Least Severe (1) On 50 Deg C 10 sec
Most Severe (3) Off 100 Deg C 10 sec
Exhaust Port
Temperature Low
Deviation
Least Severe (1) On 50 Deg C 5 sec
Most Severe (3) Always On 150 Deg C 20 sec
High Air Inlet #1
Differential Pressure
Least Severe (1) On 3.5 kPa 300 sec
High Circuit Coolant
Differential Air
Temperature
Least Severe (1) On 12 Deg C 20 sec
High Crankcase
Pressure
Least Severe (1) On 2.00 kPa 3 sec
Most Severe (3) Always On 3.00 kPa 3 sec
High Eng Oil to Eng
Coolant Differential
Temp
Least Severe (1) On 12 Deg C 20 sec
Most Severe (3) Always On 15 Deg C 20 sec
High Engine Coolant
Pressure
Least Severe (1) On 325 kPa 10 sec
Most Severe (3) Always On 379 kPa 10 sec
High Engine Coolant
Temperature
Least Severe (1) On 106 Deg C 20 sec
Most Severe (3) Always On 111 Deg C 20 sec
High Engine Ignition
Transformer Secondary
Output
Least Severe (1) On 97 % 600 sec
High Engine Oil
Temperature
Least Severe (1) On 102 Deg C 20 sec
Most Severe (3) Always On 104 Deg C 20 sec
High Exhaust
Temperature
Least Severe (1) On 650 Deg C 5 sec
Most Severe (3) Always On 700 Deg C 30 sec
High Fuel Temperature
Least Severe (1) On 60.0 Deg C 20 sec
High Gas Fuel
Differential Pressure
Least Severe (1) On 35.0 kPa 10 sec
Most Severe (3) Always On 50.0 kPa 5 sec
High Gas Fuel
Pressure
Least Severe (1) On 135 kPa 10 sec
High Gaseous Fuel
Quality Value
Least Severe (1) On 40 MJ/nm3 10 sec
High Inlet Air
Temperature at High
Engine Load
Least Severe (1) On 68.0 Deg C 20 sec
Most Severe (3) Always On 70.0 Deg C 20 sec
High Inlet Air
Temperature at Low
Engine Load
Least Severe (1) On 68.0 Deg C 20 sec
Most Severe (3) Always On 70.0 Deg C 20 sec
High Oil Filter
Differential Pressure
Least Severe (1) On 140 kPa 20 sec
Most Severe (3) Always On 240 kPa 10 sec
High System Voltage
Least Severe (1) On 30.0 Volts 20 sec
Most Severe (3) Always On 32.0 Volts 5 sec
High Turbo Turbine
Inlet Temp at Low
Engine Load
Least Severe (1) On 680 Deg C 10 sec
Most Severe (3) Always On 690 Deg C 5 sec
High Turbo Turbine
Inlet Temperature
Least Severe (1) On 680 Deg C 10 sec
Most Severe (3) Always On 690 Deg C 5 sec
High Turbo Turbine
Outlet Temperature
Least Severe (1) Off 660 Deg C 5 sec
Most Severe (3) Off 710 Deg C 30 sec
Low Crankcase
Pressure
Least Severe (1) On -2.0 kPa 3 sec
Most Severe (3) Always On -5.0 kPa 3 sec
Low Engine Coolant
Pressure
Least Severe (1) On None 10 sec
Most Severe (3) Always On None 10 sec
Low Engine Coolant
Temperature
Least Severe (1) On 60 Deg C 20 sec
Low Engine Oil
Pressure
Least Severe (1) On None 10 sec
Most Severe (3) Always On None 0 sec
Low Gas Fuel
Differential Pressure
Least Severe (1) On 7.0 kPa 10 sec
Most Severe (3) Always On 1.0 kPa 5 sec
Low Gas Fuel Pressure
Least Severe (1) On 105 kPa 10 sec
Low Gaseous Fuel
Quality Value
Least Severe (1) On 32 MJ/nm3 10 sec
Low Oil Filter
Differential Pressure
Least Severe (1) On 40 kPa 60 sec
Most Severe (3) Always On 20 kPa 10 sec
Low System Voltage
Least Severe (1) On 20 Volts 20 sec
Most Severe (3) Always On 18 Volts 10 sec

Engine Sensing #1
Parameter Value
ECM Part Number 3538089-04
ECM Serial Number 0340B113LY
Software Group Part Number 5663900-00
Software Group Release Date APR2018
Software Group Description Rel: GAS_ISM_PROD_9.2.2

EMCP 4.3
Parameter Value
ECM Part Number 5034406-00
ECM Serial Number 2499E067TW
Software Group Part Number 5707832-00
Software Group Release Date NOV2018
Software Group Description EMCP 4.3 English, v4.9H PROD, 12 November
2018

Logged Diagnostic Codes [SHM: 10063 RTC: 05/09/2037 22:58:33] - EMCP 4.3
Code Description Occ. SHM First SHM Last RTC First RTC Last
190- 5 Engine Speed : Current 1 8941:49:24 8941:49:24 28/06/2022 28/06/2022
Below Normal 07:55:36 07:55:36
639-11 J1939 Network #1 : Other 1 6096:22:07 6096:22:07 19/01/2022 19/01/2022
Failure Mode 11:55:20 11:55:20
1383-11 Engine was Shut Down 2 0:49:03 0:49:33 14/04/2021 14/04/2021
Hot : Other Failure Mode 13:08:35 13:10:10

Logged Event Codes [SHM: 10063 RTC: 05/09/2037 22:58:33] - EMCP 4.3
Code Description Occ. SHM First SHM Last RTC First RTC Last
4007-31 Generator Control not in 62 0:37:30 10063:04:3 13/04/2021 05/09/2022
Automatic 0 13:22:26 22:39:49
2456-15 Generator Total Reactive 14 1:35:19 10053:23:2 14/04/2021 05/09/2022
Power : High - least 0 20:08:39 06:10:49
severe (1)
190- 0 Engine Speed : High - 7 1:54:09 9999:15:33 15/04/2021 02/09/2022
most severe (3) 14:26:41 00:05:30
167-17 Charging System 15 0:00:00 9246:24:20 29/04/2020 30/07/2022
Potential : Low - least 19:49:17 14:09:24
severe (1)
168-17 Battery Potential / Power 3 8941:49:24 9246:24:20 09/07/2022 30/07/2022
Input #1 : Low - least 06:18:27 14:09:24
severe (1)
970-31 Engine Auxiliary Engine 6 0:38:30 8509:49:14 13/04/2021 08/06/2022
Shutdown Switch 18:14:12 23:39:03
2448-15 Generator Average AC 7 2462:15:17 7021:45:33 30/07/2021 23/03/2022
RMS Current : High - 06:51:54 15:43:25
least severe (1)
100- 1 Engine Oil Pressure : Low 1 1:57:31 1:57:31 15/04/2021 15/04/2021
- most severe (3) 14:34:43 14:34:43
110- 0 Engine Coolant 1 1:56:13 1:56:13 15/04/2021 15/04/2021
Temperature : High - 14:30:26 14:30:26
most severe (3)
2440- 0 Generator Average Line- 2 1:00:43 1:01:13 14/04/2021 14/04/2021
Line AC RMS Voltage : 18:29:37 18:34:07
High - most severe (3)

Active Diagnostic Codes [SHM: 10063 RTC: 05/09/2037 22:58:34] - EMCP 4.3
Code Description Occ.
No Active
Diagnostic
Codes

Active Event Codes [SHM: 10063 RTC: 05/09/2037 22:58:34] - EMCP 4.3
Code Description Occ.
No Active
Events

Current Totals - EMCP 4.3


Description Value Unit
Total Operating Hours 10063.2 hours
Generator Total kW Hours 18222095 KW-hr
Export
Generator Total kVAr Hours 6289266 kVAr-hr
Export
Generator Trip kW Hours 18222095 KW-hr
Export
Generator Trip kVAr Hours 6289266 kVAr-hr
Export

Configuration - EMCP 4.3


Description Value Unit
Genset Control Software Type Standard
Configuration
Voltage Regulator Control Source Genset Control
Configuration
Voltage Regulator Starting Time 5.0 sec
Voltage Regulator Starting Voltage Percent 10.0 %
Voltage Regulator Loop Gain Percentage 5.00 %
Voltage Regulation Proportional Gain 20.00 %
Percentage
Voltage Regulation Integral Gain 60.00 %
Percentage
Voltage Regulation Derivative Gain 3.00 %
Percentage
Voltage Regulator Noise Filter Time 0.00 sec
Constant
Voltage Regulator Corner (Knee) 49.8 Hz
Frequency
Voltage Regulator Deviation From Corner 5.0 Hz
(Knee) Frequency
Voltage Regulator Volts/Hz Slope 1 2.0 V/Hz
Voltage Regulator Volts/Hz Slope 2 2.0 V/Hz
Voltage Regulator Minimum Voltage 33.0 %
Setpoint Percentage
Voltage Regulator Minimum Frequency 20.0 Hz
Threshold
Voltage Regulator Load Compensation Off
Type Configuration
Voltage Regulator Voltage (IR) 0.0 %
Compensation Percentage
Voltage Regulator Maximum Droop 0.0 %
Percentage
Voltage Regulator Lockout Configuration Not Locked Out
Voltage Regulator Loss of Sensing 2.0 sec
Shutdown Event Notification Delay Time
Voltage Regulator Over Excitation 70 %
Shutdown Event Threshold Percentage
Voltage Regulator Over Excitation 10.0 sec
Shutdown Event Notification Delay Time
Voltage Regulator Excitation Enabled Enabled
During Shutdown Event Configuration
Transient Load Relief Enable Status Disabled
Analog Input #1 Signal Type Disabled
Analog Input #2 Signal Type Disabled
Analog Input #3 Signal Type Voltage
Analog Input #3 Supply Voltage Disabled
Analog Input #3 Signal Range -10 to +10 V
Analog Input #3 Data Identification Desired Generator Voltage Command
Analog Input #3 Minimum Data Range -10.000
Analog Input #3 Maximum Data Range 10.000
Custom Map #101 Number of Mapped 4
Points
Custom Map #101 Y-Axis Type Custom
Custom Map #101 Map Point X-Axis Value 5.0
#1
Custom Map #101 Map Point Y-Axis Value 0.0
#1
Custom Map #101 Map Point X-Axis Value 10.0
#2
Custom Map #101 Map Point Y-Axis Value 0.0
#2
Custom Map #101 Map Point X-Axis Value 190.0
#3
Custom Map #101 Map Point Y-Axis Value 100.0
#3
Custom Map #101 Map Point X-Axis Value 200.0
#4
Custom Map #101 Map Point Y-Axis Value 100.0
#4
Custom Map #102 Number of Mapped 4
Points
Custom Map #102 Y-Axis Type Custom
Custom Map #102 Map Point X-Axis Value 5.0
#1
Custom Map #102 Map Point Y-Axis Value 0.0
#1
Custom Map #102 Map Point X-Axis Value 10.0
#2
Custom Map #102 Map Point Y-Axis Value 0.0
#2
Custom Map #102 Map Point X-Axis Value 190.0
#3
Custom Map #102 Map Point Y-Axis Value 100.0
#3
Custom Map #102 Map Point X-Axis Value 200.0
#4
Custom Map #102 Map Point Y-Axis Value 100.0
#4
Custom Map #103 Number of Mapped 4
Points
Custom Map #103 Y-Axis Type Custom
Custom Map #103 Map Point X-Axis Value 5.0
#1
Custom Map #103 Map Point Y-Axis Value 0.0
#1
Custom Map #103 Map Point X-Axis Value 10.0
#2
Custom Map #103 Map Point Y-Axis Value 0.0
#2
Custom Map #103 Map Point X-Axis Value 190.0
#3
Custom Map #103 Map Point Y-Axis Value 100.0
#3
Custom Map #103 Map Point X-Axis Value 200.0
#4
Custom Map #103 Map Point Y-Axis Value 100.0
#4
Custom Map #104 Number of Mapped 4
Points
Custom Map #104 Y-Axis Type Custom
Custom Map #104 Map Point X-Axis Value 5.0
#1
Custom Map #104 Map Point Y-Axis Value 0.0
#1
Custom Map #104 Map Point X-Axis Value 10.0
#2
Custom Map #104 Map Point Y-Axis Value 0.0
#2
Custom Map #104 Map Point X-Axis Value 190.0
#3
Custom Map #104 Map Point Y-Axis Value 100.0
#3
Custom Map #104 Map Point X-Axis Value 200.0
#4
Custom Map #104 Map Point Y-Axis Value 100.0
#4
Analog Output #1 Output Type Disabled
Analog Output #2 Output Type Disabled
Analog Output #3 Output Type Disabled
PWM Output #1 Enable Status Enabled
PWM Output #1 Output Range 5 to 95%
PWM Output #1 Data Identification Generator Total Real Power
PWM Output #1 Minimum Data Range 0.000
PWM Output #1 Maximum Data Range 2514.000
Engine Start Fault Protection Activation 30 sec
Delay Time
Crank Duration 30 sec
Crank Cycle Rest Interval 10 sec
Engine Purge Cycle Time with Ignition 0.0 sec
Engine Purge Cycle Time without Ignition 0 sec
Engine Start Sequence Delay Time 0.0 sec
Maximum Number of Crank Cycles 5
Cooldown Duration 0 min
Start Aid Activation Time 0 sec
Crank Alert Activation Time 0 sec
Crank Terminate RPM 250 rpm
Engine Cooldown Speed Configuration Rated Speed
Engine Operating State Input Configuration CAN Input
Fuel Priming Feature Enable Status Disabled
Engine Forced Idle Feature Enable Status Enabled
Emergency Stop Switch Active State High
Configuration
Engine Control Data Link Configuration J1939
SCADA Data Link Remote Control Enable Disabled
Status
ECU Fault Reset Active Time 0.1 sec
Digital Input Electronic Control Unit Fault Disabled
Reset Enable Status
Engine Crank Delay Time 0.0 sec
Starter Pinion Engagement Detection Unavailable
System Enable Status
High Battery Voltage Warning Event 30.0 Volts
Threshold
High Battery Voltage Warning Event 10 sec
Notification Delay Time
High Battery Voltage Shutdown Event 32.0 Volts
Threshold
High Battery Voltage Shutdown Event 2 sec
Notification Delay Time
Low Battery Voltage Warning Event 23.0 Volts
Threshold
Low Battery Voltage Warning Event 30 sec
Notification Delay Time
Low Battery Charging System Voltage 24.0 Volts
Warning Event Threshold
Low Battery Charging System Voltage 30 sec
Warning Event Notification Delay Time
Low Cranking Voltage Warning Event 21.0 Volts
Threshold
Low Cranking Voltage Warning Event 10 sec
Notification Delay Time
Engine Cooling Fan Minimum Air Flow 101.0 Deg C
Coolant Temperature
Engine Cooling Fan Maximum Air Flow 103.0 Deg C
Coolant Temperature
Engine Cooling Fan Coolant Temperature 16.0 Deg C
Hysteresis
Engine Cooling Fan Minimum Air Flow 15.0 Deg C
Aftercooler Output Air Temperature
Engine Cooling Fan Aftercooler Output Air 20.0 Deg C
Temperature Hysteresis
Engine Cooling Fan Maximum Air Flow 50.0 Deg C
Aftercooler Output Air Temperature
Custom Screen #1 Line #1 Modbus 0
Register Number
Custom Screen #1 Line #2 Modbus 0
Register Number
Custom Screen #1 Line #3 Modbus 0
Register Number
Custom Screen #1 Line #4 Modbus 0
Register Number
Custom Screen #1 Line #5 Modbus 0
Register Number
Custom Screen #1 Line #6 Modbus 0
Register Number
Custom Screen #2 Line #1 Modbus 0
Register Number
Custom Screen #2 Line #2 Modbus 0
Register Number
Custom Screen #2 Line #3 Modbus 0
Register Number
Custom Screen #2 Line #4 Modbus 0
Register Number
Custom Screen #2 Line #5 Modbus 0
Register Number
Custom Screen #2 Line #6 Modbus 0
Register Number
Custom Screen #3 Line #1 Modbus 0
Register Number
Custom Screen #3 Line #2 Modbus 0
Register Number
Custom Screen #3 Line #3 Modbus 0
Register Number
Custom Screen #3 Line #4 Modbus 0
Register Number
Custom Screen #3 Line #5 Modbus 0
Register Number
Custom Screen #3 Line #6 Modbus 0
Register Number
Custom Screen #4 Line #1 Modbus 0
Register Number
Custom Screen #4 Line #2 Modbus 0
Register Number
Custom Screen #4 Line #3 Modbus 0
Register Number
Custom Screen #4 Line #4 Modbus 0
Register Number
Custom Screen #4 Line #5 Modbus 0
Register Number
Custom Screen #4 Line #6 Modbus 0
Register Number
Custom Screen #5 Line #1 Modbus 0
Register Number
Custom Screen #5 Line #2 Modbus 0
Register Number
Custom Screen #5 Line #3 Modbus 0
Register Number
Custom Screen #5 Line #4 Modbus 0
Register Number
Custom Screen #5 Line #5 Modbus 0
Register Number
Custom Screen #5 Line #6 Modbus 0
Register Number
Custom Screen #6 Line #1 Modbus 0
Register Number
Custom Screen #6 Line #2 Modbus 0
Register Number
Custom Screen #6 Line #3 Modbus 0
Register Number
Custom Screen #6 Line #4 Modbus 0
Register Number
Custom Screen #6 Line #5 Modbus 0
Register Number
Custom Screen #6 Line #6 Modbus 0
Register Number
Customer Password Security Level for Factory Default
Analog Input #1
Customer Password Security Level for Factory Default
Analog Input #2
Customer Password Security Level for Factory Default
Analog Input #3
Customer Password Security Level for Factory Default
Analog Outputs
Customer Password Security Level for Factory Default
Digital Inputs
Customer Password Security Level for Factory Default
Digital Outputs
Customer Password Security Level for Factory Default
Automatic Start/Stop
Customer Password Security Level for Fuel Factory Default
Transfer Feature
Customer Password Security Level for Factory Default
Load Shed Feature
Customer Password Security Level for Factory Default
Integrated Voltage Regulator
Customer Password Security Level for Factory Default
Programmable Cycle Timer Feature
Customer Password Security Level for Factory Default
Generator Rated Voltages
Customer Password Security Level for Factory Default
Generator Protection Monitoring
Customer Password Security Level for Factory Default
Engine Protection Monitoring
Customer Password Security Level for Factory Default
Custom Display Features
Customer Password Security Level to 3-Factory, Single Use
Reset Crank/Start Counters
SCADA Data Link Baud Rate 19200 baud
SCADA Data Link Parity None
SCADA Data Link Slave Address 1
SCADA Data Link Access Password 00000000
RS-485 Bias Resistor Enable Status Disabled
SCADA Port Enable Status Enabled
RS-485 Annunciator Port Enable Status Enabled
Internet Protocol (IPv4) Address 10.1.1.31
Internet Protocol (IPv4) Network Mask 255.0.0.0
Network Default Gateway Internet Protocol 0.0.0.0
(IPv4) Address
Digital Input #1 Usage Type Command/Status Parameter
Digital Input #1 Active State Configuration Low
Digital Input #1 Command/Status Engine Control Switch in Stop
Parameter Data Identification
Digital Input #2 Usage Type System Event
Digital Input #2 Active State Configuration Low
Event Input Function #2 Event Notification 0 sec
Delay Time
Event Input Function #2 Suspect Custom Event
Parameter Number
Event Input Function #2 Failure Mode Condition Exists
Identifier
Digital Input #3 Usage Type System Event
Digital Input #3 Active State Configuration Low
Event Input Function #3 Event Notification 0 sec
Delay Time
Event Input Function #3 Suspect Custom Event
Parameter Number
Event Input Function #3 Failure Mode Condition Exists
Identifier
Digital Input #4 Usage Type System Event
Digital Input #4 Active State Configuration Low
Event Input Function #4 Event Notification 0 sec
Delay Time
Event Input Function #4 Suspect Custom Event
Parameter Number
Event Input Function #4 Failure Mode Condition Exists
Identifier
Digital Input #5 Usage Type System Event
Digital Input #5 Active State Configuration Low
Event Input Function #5 Event Notification 0 sec
Delay Time
Event Input Function #5 Suspect Custom Event
Parameter Number
Event Input Function #5 Failure Mode Condition Exists
Identifier
Digital Input #6 Usage Type System Event
Digital Input #6 Active State Configuration Low
Event Input Function #6 Event Notification 0 sec
Delay Time
Event Input Function #6 Suspect Custom Event
Parameter Number
Event Input Function #6 Failure Mode Condition Exists
Identifier
Digital Input #7 Usage Type System Event
Digital Input #7 Active State Configuration Low
Event Input Function #7 Event Notification 0 sec
Delay Time
Event Input Function #7 Suspect Custom Event
Parameter Number
Event Input Function #7 Failure Mode Condition Exists
Identifier
Digital Input #8 Usage Type System Event
Digital Input #8 Active State Configuration Low
Event Input Function #8 Event Notification 0 sec
Delay Time
Event Input Function #8 Suspect Custom Event
Parameter Number
Event Input Function #8 Failure Mode Condition Exists
Identifier
Isolated Digital Input #1 Usage Type System Event
Isolated Digital Input #1 Active State Low
Configuration
Isolated Digital Input #1 Event Notification 0 sec
Delay Time
Isolated Digital Input #1 Suspect Parameter Isolated Digital Input #1 Custom Event
Number
Isolated Digital Input #1 Failure Mode Condition Exists
Identifier
Isolated Digital Input #2 Usage Type System Event
Isolated Digital Input #2 Active State Low
Configuration
Isolated Digital Input #2 Event Notification 0 sec
Delay Time
Isolated Digital Input #2 Suspect Parameter Isolated Digital Input #2 Custom Event
Number
Isolated Digital Input #2 Failure Mode Condition Exists
Identifier
Isolated Digital Input #3 Usage Type System Event
Isolated Digital Input #3 Active State Low
Configuration
Isolated Digital Input #3 Event Notification 0 sec
Delay Time
Isolated Digital Input #3 Suspect Parameter Isolated Digital Input #3 Custom Event
Number
Isolated Digital Input #3 Failure Mode Condition Exists
Identifier
Isolated Digital Input #4 Usage Type System Event
Isolated Digital Input #4 Active State Low
Configuration
Isolated Digital Input #4 Event Notification 0 sec
Delay Time
Isolated Digital Input #4 Suspect Parameter Isolated Digital Input #4 Custom Event
Number
Isolated Digital Input #4 Failure Mode Condition Exists
Identifier
Digital Output #1 Usage Type Disabled
Digital Output #2 Usage Type Disabled
Digital Output #3 Usage Type Disabled
Digital Output #4 Usage Type Disabled
Digital Output #5 Usage Type Disabled
Digital Output #6 Usage Type Disabled
Digital Output #7 Usage Type Disabled
Digital Output #8 Usage Type Disabled
Digital Output #9 Usage Type Disabled
Digital Output #10 Usage Type Disabled
Digital Output #11 Usage Type Disabled
Digital Output #12 Usage Type Disabled
Digital Output #13 Usage Type Command/Status Parameter
Digital Output #13 Command/Status Common Warning
Parameter Data Identification
Digital Output #14 Usage Type Command/Status Parameter
Digital Output #14 Command/Status Auto Mode
Parameter Data Identification
Digital Output #15 Usage Type Command/Status Parameter
Digital Output #15 Command/Status Disable Aux AC Supply
Parameter Data Identification
Digital Output #16 Usage Type Command/Status Parameter
Digital Output #16 Command/Status Common Shutdown
Parameter Data Identification
Engine Coolant Temperature Sensor Data Link
Configuration
High Engine Coolant Temperature Warning 99 Deg C
Event Threshold
High Engine Coolant Temperature Warning 10 sec
Event Notification Delay Time
High Engine Coolant Temperature 105 Deg C
Shutdown Event Threshold
High Engine Coolant Temperature 10 sec
Shutdown Event Notification Delay Time
Low Engine Coolant Temperature Warning 0 Deg C
Event Threshold
Low Engine Coolant Temperature Warning 10 sec
Event Notification Delay Time
Engine Oil Pressure Sensor Configuration Data Link
Low Engine Oil Pressure Warning Event 34 kPa
Threshold
Low Idle Low Engine Oil Pressure Warning 104 kPa
Event Threshold
Low Engine Oil Pressure Warning Event 10 sec
Notification Delay Time
Low Engine Oil Pressure Shutdown Event 35 kPa
Threshold
Low Idle Low Engine Oil Pressure 70 kPa
Shutdown Event Threshold
Low Engine Oil Pressure Shutdown Event 10 sec
Notification Delay Time
Low Engine Oil Pressure Step Speed 1200 rpm
Flywheel Teeth 183
Engine Overspeed Setpoint 1670 rpm
Engine Underspeed Warning Event 1275 rpm
Threshold
Engine Underspeed Warning Event 15.0 sec
Notification Delay Time
Engine Underspeed Shutdown Event 1200 rpm
Threshold
Engine Underspeed Shutdown Event 15.0 sec
Notification Delay Time
Engine Speed Sensor Configuration Sensor
Generator Drive Ratio 1.000 Ratio
Third Party Engine Low Idle Speed Enable Disabled
Status
Third Party Engine Low Idle Speed 1000 rpm
Engine Speed Based Generator Frequency Disabled
Calculation Enable
Genset Engine Speed Control Source Unavailable
Configuration
Engine Cylinder Temperature Sensor Installed
Installation Status
Number of Engine Cylinders 20
Engine Exhaust Temperature Differential Disabled
Monitor Enable Status
Generator Winding Temperature Sensor Installed
Installation Status
Generator Bearing Temperature Sensor Front & Rear
Installation Configuration
Accessory Data Link Diagnostic Response Activate Warning Condition
Configuration
Accessory Data Link Diagnostic Audible Yes
Alert
Accessory Data Link Diagnostic Breaker #1 No
Trip
Accessory Data Link Diagnostic Breaker #2 No
Trip
Engine Speed Sensor Diagnostic Activate Hard Shutdown Condition
Response Configuration
Engine Speed Sensor Diagnostic Audible Yes
Alert
Engine Speed Sensor Diagnostic Breaker No
#1 Trip
Engine Speed Sensor Diagnostic Breaker No
#2 Trip
Primary Data Link Diagnostic Response Activate Warning Condition
Configuration
Primary Data Link Diagnostic Audible Alert No
Primary Data Link Diagnostic Breaker #1 No
Trip
Primary Data Link Diagnostic Breaker #2 No
Trip
RS-485 SCADA Data Link Diagnostic Activate Warning Condition
Response Configuration
RS-485 SCADA Data Link Diagnostic No
Audible Alert
RS-485 SCADA Data Link Diagnostic No
Breaker #1 Trip
RS-485 SCADA Data Link Diagnostic No
Breaker #2 Trip
RS-485 SCADA Data Link Diagnostic Fault No
Protection Timer
TCP/IP SCADA Data Link Diagnostic Activate Warning Condition
Response Configuration
TCP/IP SCADA Data Link Diagnostic No
Audible Alert
TCP/IP SCADA Data Link Diagnostic No
Breaker #1 Trip
TCP/IP SCADA Data Link Diagnostic No
Breaker #2 Trip
TCP/IP SCADA Data Link Diagnostic Fault No
Protection Timer
RS-485 Annunciator Data Link Diagnostic Activate Warning Condition
Response Configuration
RS-485 Annunciator Data Link Diagnostic No
Audible Alert
RS-485 Annunciator Data Link Diagnostic No
Breaker #1 Trip
RS-485 Annunciator Data Link Diagnostic No
Breaker #2 Trip
RS-485 Annunciator Data Link Diagnostic No
Fault Protection Timer
Battery Charger Failure Diagnostic Activate Warning Condition
Response Configuration
Battery Charger Failure Diagnostic Audible Yes
Alert
Engine Controller Not Responding Disable Condition
Diagnostic Response Configuration
Engine Controller Not Responding No
Diagnostic Audible Alert
Engine Controller Not Responding No
Diagnostic Breaker #1 Trip
Engine Controller Not Responding No
Diagnostic Breaker #2 Trip
Analog Input #1 Diagnostic Response Activate Warning Condition
Configuration
Analog Input #1 Diagnostic Audible Alert No
Analog Input #1 Diagnostic Breaker #1 Trip No
Analog Input #1 Diagnostic Breaker #2 Trip No
Analog Input #2 Diagnostic Response Activate Warning Condition
Configuration
Analog Input #2 Diagnostic Audible Alert No
Analog Input #2 Diagnostic Breaker #1 Trip No
Analog Input #2 Diagnostic Breaker #2 Trip No
Analog Input #3 Diagnostic Response Activate Warning Condition
Configuration
Analog Input #3 Diagnostic Audible Alert No
Analog Input #3 Diagnostic Breaker #1 Trip No
Analog Input #3 Diagnostic Breaker #2 Trip No
Modbus Data Link Communication Failure Unavailable
Diagnostic Response Configuration
Modbus Data Link Communication Failure Unavailable
Diagnostic Audible Alert
Ethernet Network #1 Communication Unavailable
Failure Diagnostic Response Configuration
Ethernet Network #1 Communication Unavailable
Failure Diagnostic Audible Alert
Air Damper Closed Event Response Hard Shutdown & Active Only
Configuration Condition
Air Damper Closed Event Audible Alert Yes
Emergency Stop Activated Event Activate Hard Shutdown Condition
Response Configuration
Emergency Stop Activated Event Audible Yes
Alert
Emergency Stop Activated Event Breaker No
#1 Trip
Emergency Stop Activated Event Breaker No
#2 Trip
High Engine Coolant Level Warning Event Activate Warning Condition
Response Configuration
High Engine Coolant Level Warning Event Yes
Audible Alert
High Engine Coolant Level Warning Event No
Breaker #1 Trip
High Engine Coolant Level Warning Event No
Breaker #2 Trip
High Engine Coolant Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
High Engine Coolant Level Shutdown Yes
Event Audible Alert
High Engine Coolant Level Shutdown No
Event Breaker #1 Trip
High Engine Coolant Level Shutdown No
Event Breaker #2 Trip
Low Engine Coolant Level Warning Event Activate Warning Condition
Response Configuration
Low Engine Coolant Level Warning Event Yes
Audible Alert
Low Engine Coolant Level Warning Event No
Breaker #1 Trip
Low Engine Coolant Level Warning Event No
Breaker #2 Trip
Low Engine Coolant Level Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Low Engine Coolant Level Shutdown Event Yes
Audible Alert
Low Engine Coolant Level Shutdown Event No
Breaker #1 Trip
Low Engine Coolant Level Shutdown Event No
Breaker #2 Trip
High Engine Coolant Temperature Warning Activate Warning Condition
Event Response Configuration
High Engine Coolant Temperature Warning Yes
Event Audible Alert
High Engine Coolant Temperature Warning No
Event Breaker #1 Trip
High Engine Coolant Temperature Warning No
Event Breaker #2 Trip
High Engine Coolant Temperature Warning Yes
Event Fault Protection Timer
High Engine Coolant Temperature Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Engine Coolant Temperature Yes
Shutdown Event Audible Alert
High Engine Coolant Temperature No
Shutdown Event Breaker #1 Trip
High Engine Coolant Temperature No
Shutdown Event Breaker #2 Trip
High Engine Coolant Temperature Yes
Shutdown Event Fault Protection Timer
Low Engine Coolant Temperature Warning Activate Warning Condition
Event Response Configuration
Low Engine Coolant Temperature Warning Yes
Event Audible Alert
Low Engine Coolant Temperature Warning No
Event Breaker #1 Trip
Low Engine Coolant Temperature Warning No
Event Breaker #2 Trip
Low Engine Coolant Temperature Warning No
Event Fault Protection Timer
Engine Failure To Start Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Engine Failure To Start Shutdown Event Yes
Audible Alert
Engine Failure To Start Shutdown Event No
Breaker #1 Trip
Engine Failure To Start Shutdown Event No
Breaker #2 Trip
High Engine Oil Level Warning Event Activate Warning Condition
Response Configuration
High Engine Oil Level Warning Event Yes
Audible Alert
High Engine Oil Level Warning Event No
Breaker #1 Trip
High Engine Oil Level Warning Event No
Breaker #2 Trip
High Engine Oil Level Shutdown Event Activate Hard Shutdown Condition
Response Configuration
High Engine Oil Level Shutdown Event Yes
Audible Alert
High Engine Oil Level Shutdown Event No
Breaker #1 Trip
High Engine Oil Level Shutdown Event No
Breaker #2 Trip
Low Engine Oil Level Warning Event Activate Warning Condition
Response Configuration
Low Engine Oil Level Warning Event Yes
Audible Alert
Low Engine Oil Level Warning Event No
Breaker #1 Trip
Low Engine Oil Level Warning Event No
Breaker #2 Trip
Low Engine Oil Level Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Low Engine Oil Level Shutdown Event Yes
Audible Alert
Low Engine Oil Level Shutdown Event No
Breaker #1 Trip
Low Engine Oil Level Shutdown Event No
Breaker #2 Trip
Low Engine Oil Pressure Warning Event Activate Warning Condition
Response Configuration
Low Engine Oil Pressure Warning Event Yes
Audible Alert
Low Engine Oil Pressure Warning Event No
Breaker #1 Trip
Low Engine Oil Pressure Warning Event No
Breaker #2 Trip
Low Engine Oil Pressure Warning Event Yes
Fault Protection Timer
Low Engine Oil Pressure Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Low Engine Oil Pressure Shutdown Event Yes
Audible Alert
Low Engine Oil Pressure Shutdown Event No
Breaker #1 Trip
Low Engine Oil Pressure Shutdown Event No
Breaker #2 Trip
Low Engine Oil Pressure Shutdown Event Yes
Fault Protection Timer
High Engine Oil Temperature Warning Activate Warning Condition
Event Response Configuration
High Engine Oil Temperature Warning Yes
Event Audible Alert
High Engine Oil Temperature Warning No
Event Breaker #1 Trip
High Engine Oil Temperature Warning No
Event Breaker #2 Trip
High Engine Oil Temperature Warning No
Event Fault Protection Timer
High Engine Oil Temperature Shutdown Activate Hard Shutdown Condition
Event Response Configuration
High Engine Oil Temperature Shutdown Yes
Event Audible Alert
High Engine Oil Temperature Shutdown No
Event Breaker #1 Trip
High Engine Oil Temperature Shutdown No
Event Breaker #2 Trip
High Engine Oil Temperature Shutdown No
Event Fault Protection Timer
Low Engine Oil Temperature Warning Activate Warning Condition
Event Response Configuration
Low Engine Oil Temperature Warning Yes
Event Audible Alert
Low Engine Oil Temperature Warning No
Event Breaker #1 Trip
Low Engine Oil Temperature Warning No
Event Breaker #2 Trip
Low Engine Oil Temperature Warning Yes
Event Fault Protection Timer
Low Engine Oil Temperature Shutdown Disable Condition
Event Response Configuration
Low Engine Oil Temperature Shutdown No
Event Audible Alert
Low Engine Oil Temperature Shutdown No
Event Breaker #1 Trip
Low Engine Oil Temperature Shutdown No
Event Breaker #2 Trip
Low Engine Oil Temperature Shutdown No
Event Fault Protection Timer
Unexpected Engine Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Unexpected Engine Shutdown Event Yes
Audible Alert
Unexpected Engine Shutdown Event No
Breaker #1 Trip
Unexpected Engine Shutdown Event No
Breaker #2 Trip
Engine Overspeed Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Engine Overspeed Shutdown Event Yes
Audible Alert
Engine Overspeed Shutdown Event No
Breaker #1 Trip
Engine Overspeed Shutdown Event No
Breaker #2 Trip
Engine Underspeed Warning Event Activate Warning Condition
Response Configuration
Engine Underspeed Warning Event Audible Yes
Alert
Engine Underspeed Warning Event No
Breaker #1 Trip
Engine Underspeed Warning Event No
Breaker #2 Trip
Engine Underspeed Warning Event Fault Yes
Protection Timer
Engine Underspeed Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Engine Underspeed Shutdown Event Yes
Audible Alert
Engine Underspeed Shutdown Event No
Breaker #1 Trip
Engine Underspeed Shutdown Event No
Breaker #2 Trip
Engine Underspeed Shutdown Event Fault Yes
Protection Timer
High Exhaust Temperature Warning Event Activate Warning Condition
Response Configuration
High Exhaust Temperature Warning Event Yes
Audible Alert
High Exhaust Temperature Warning Event No
Breaker #1 Trip
High Exhaust Temperature Warning Event No
Breaker #2 Trip
High Exhaust Temperature Warning Event No
Fault Protection Timer
High Exhaust Temperature Shutdown Activate Hard Shutdown Condition
Event Response Configuration
High Exhaust Temperature Shutdown Yes
Event Audible Alert
High Exhaust Temperature Shutdown No
Event Breaker #1 Trip
High Exhaust Temperature Shutdown No
Event Breaker #2 Trip
High Exhaust Temperature Shutdown No
Event Fault Protection Timer
Low Exhaust Temperature Warning Event Activate Warning Condition
Response Configuration
Low Exhaust Temperature Warning Event Yes
Audible Alert
Low Exhaust Temperature Warning Event No
Breaker #1 Trip
Low Exhaust Temperature Warning Event No
Breaker #2 Trip
Low Exhaust Temperature Warning Event Yes
Fault Protection Timer
Low Exhaust Temperature Shutdown Event Disable Condition
Response Configuration
Low Exhaust Temperature Shutdown Event No
Audible Alert
Low Exhaust Temperature Shutdown Event No
Breaker #1 Trip
Low Exhaust Temperature Shutdown Event No
Breaker #2 Trip
Low Exhaust Temperature Shutdown Event No
Fault Protection Timer
High Fuel Level Warning Event Response Activate Warning Condition
Configuration
High Fuel Level Warning Event Audible Yes
Alert
High Fuel Level Warning Event Breaker #1 No
Trip
High Fuel Level Warning Event Breaker #2 No
Trip
High Fuel Level Shutdown Event Response Activate Hard Shutdown Condition
Configuration
High Fuel Level Shutdown Event Audible Yes
Alert
High Fuel Level Shutdown Event Breaker No
#1 Trip
High Fuel Level Shutdown Event Breaker No
#2 Trip
Low Fuel Level Warning Event Response Activate Warning Condition
Configuration
Low Fuel Level Warning Event Audible Yes
Alert
Low Fuel Level Warning Event Breaker #1 No
Trip
Low Fuel Level Warning Event Breaker #2 No
Trip
Low Fuel Level Shutdown Event Response Activate Hard Shutdown Condition
Configuration
Low Fuel Level Shutdown Event Audible Yes
Alert
Low Fuel Level Shutdown Event Breaker No
#1 Trip
Low Fuel Level Shutdown Event Breaker No
#2 Trip
External Tank High Fuel Level Warning Activate Warning Condition
Event Response Configuration
External Tank High Fuel Level Warning Yes
Event Audible Alert
External Tank High Fuel Level Warning No
Event Breaker #1 Trip
External Tank High Fuel Level Warning No
Event Breaker #2 Trip
External Tank High Fuel Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
External Tank High Fuel Level Shutdown Yes
Event Audible Alert
External Tank High Fuel Level Shutdown No
Event Breaker #1 Trip
External Tank High Fuel Level Shutdown No
Event Breaker #2 Trip
External Tank Low Fuel Level Warning Activate Warning Condition
Event Response Configuration
External Tank Low Fuel Level Warning Yes
Event Audible Alert
External Tank Low Fuel Level Warning No
Event Breaker #1 Trip
External Tank Low Fuel Level Warning No
Event Breaker #2 Trip
External Tank Low Fuel Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
External Tank Low Fuel Level Shutdown Yes
Event Audible Alert
External Tank Low Fuel Level Shutdown No
Event Breaker #1 Trip
External Tank Low Fuel Level Shutdown No
Event Breaker #2 Trip
Fuel Leak Event Response Configuration Activate Warning Condition
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 Trip No
Fuel Leak Event Breaker #2 Trip No
Service Maintenance Interval Warning Disable Condition
Event Response Configuration
Service Maintenance Interval Warning No
Event Audible Alert
High Gas Pressure Warning Event Activate Warning Condition
Response Configuration
High Gas Pressure Warning Event Audible Yes
Alert
High Gas Pressure Warning Event Breaker No
#1 Trip
High Gas Pressure Warning Event Breaker No
#2 Trip
High Gas Pressure Shutdown Event Activate Hard Shutdown Condition
Response Configuration
High Gas Pressure Shutdown Event Yes
Audible Alert
High Gas Pressure Shutdown Event No
Breaker #1 Trip
High Gas Pressure Shutdown Event No
Breaker #2 Trip
Low Gas Pressure Warning Event Activate Warning Condition
Response Configuration
Low Gas Pressure Warning Event Audible Yes
Alert
Low Gas Pressure Warning Event Breaker No
#1 Trip
Low Gas Pressure Warning Event Breaker No
#2 Trip
Low Gas Pressure Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Low Gas Pressure Shutdown Event Yes
Audible Alert
Low Gas Pressure Shutdown Event No
Breaker #1 Trip
Low Gas Pressure Shutdown Event No
Breaker #2 Trip
Engine Intake Manifold Charge Activate Hard Shutdown Condition
Combustion Event Response Configuration
Engine Intake Manifold Charge Yes
Combustion Event Audible Alert
Engine Intake Manifold Charge No
Combustion Event Breaker #1 Trip
Engine Intake Manifold Charge No
Combustion Event Breaker #2 Trip
Engine Intake Manifold Charge No
Combustion Event Fault Protection Timer
Remote Emergency Stop Activated Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Remote Emergency Stop Activated Yes
Shutdown Event Audible Alert
Remote Emergency Stop Activated Yes
Shutdown Event Breaker #1 Trip
Remote Emergency Stop Activated Yes
Shutdown Event Breaker #2 Trip
High Aftercooler Coolant Level Warning Activate Warning Condition
Event Response Configuration
High Aftercooler Coolant Level Warning Yes
Event Audible Alert
High Aftercooler Coolant Level Warning No
Event Breaker #1 Trip
High Aftercooler Coolant Level Warning No
Event Breaker #2 Trip
High Aftercooler Coolant Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
High Aftercooler Coolant Level Shutdown Yes
Event Audible Alert
High Aftercooler Coolant Level Shutdown No
Event Breaker #1 Trip
High Aftercooler Coolant Level Shutdown No
Event Breaker #2 Trip
Low Aftercooler Coolant Level Warning Activate Warning Condition
Event Response Configuration
Low Aftercooler Coolant Level Warning Yes
Event Audible Alert
Low Aftercooler Coolant Level Warning No
Event Breaker #1 Trip
Low Aftercooler Coolant Level Warning No
Event Breaker #2 Trip
Low Aftercooler Coolant Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
Low Aftercooler Coolant Level Shutdown Yes
Event Audible Alert
Low Aftercooler Coolant Level Shutdown No
Event Breaker #1 Trip
Low Aftercooler Coolant Level Shutdown No
Event Breaker #2 Trip
High Engine Coolant Temperature #2 Activate Warning Condition
Warning Event Response Configuration
High Engine Coolant Temperature #2 Yes
Warning Event Audible Alert
High Engine Coolant Temperature #2 No
Warning Event Breaker #1 Trip
High Engine Coolant Temperature #2 No
Warning Event Breaker #2 Trip
High Engine Coolant Temperature #2 Yes
Warning Event Fault Protection Timer
High Engine Coolant Temperature #2 Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Engine Coolant Temperature #2 Yes
Shutdown Event Audible Alert
High Engine Coolant Temperature #2 No
Shutdown Event Breaker #1 Trip
High Engine Coolant Temperature #2 No
Shutdown Event Breaker #2 Trip
High Engine Coolant Temperature #2 Yes
Shutdown Event Fault Protection Timer
Low Engine Coolant Temperature #2 Activate Warning Condition
Warning Event Response Configuration
Low Engine Coolant Temperature #2 Yes
Warning Event Audible Alert
Low Engine Coolant Temperature #2 No
Warning Event Breaker #1 Trip
Low Engine Coolant Temperature #2 No
Warning Event Breaker #2 Trip
Low Engine Coolant Temperature #2 No
Warning Event Fault Protection Timer
Low Engine Coolant Temperature #2 Disable Condition
Shutdown Event Response Configuration
Low Engine Coolant Temperature #2 No
Shutdown Event Audible Alert
Low Engine Coolant Temperature #2 No
Shutdown Event Breaker #1 Trip
Low Engine Coolant Temperature #2 No
Shutdown Event Breaker #2 Trip
Low Engine Coolant Temperature #2 No
Shutdown Event Fault Protection Timer
High Engine Coolant Temperature #3 Activate Warning Condition
Warning Event Response Configuration
High Engine Coolant Temperature #3 Yes
Warning Event Audible Alert
High Engine Coolant Temperature #3 No
Warning Event Breaker #1 Trip
High Engine Coolant Temperature #3 No
Warning Event Breaker #2 Trip
High Engine Coolant Temperature #3 Yes
Warning Event Fault Protection Timer
High Engine Coolant Temperature #3 Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Engine Coolant Temperature #3 Yes
Shutdown Event Audible Alert
High Engine Coolant Temperature #3 No
Shutdown Event Breaker #1 Trip
High Engine Coolant Temperature #3 No
Shutdown Event Breaker #2 Trip
High Engine Coolant Temperature #3 Yes
Shutdown Event Fault Protection Timer
Low Engine Coolant Temperature #3 Activate Warning Condition
Warning Event Response Configuration
Low Engine Coolant Temperature #3 Yes
Warning Event Audible Alert
Low Engine Coolant Temperature #3 No
Warning Event Breaker #1 Trip
Low Engine Coolant Temperature #3 No
Warning Event Breaker #2 Trip
Low Engine Coolant Temperature #3 No
Warning Event Fault Protection Timer
Low Engine Coolant Temperature #3 Disable Condition
Shutdown Event Response Configuration
Low Engine Coolant Temperature #3 No
Shutdown Event Audible Alert
Low Engine Coolant Temperature #3 No
Shutdown Event Breaker #1 Trip
Low Engine Coolant Temperature #3 No
Shutdown Event Breaker #2 Trip
Low Engine Coolant Temperature #3 No
Shutdown Event Fault Protection Timer
High Engine Fluid Bund Level Warning Activate Warning Condition
Event Response Configuration
High Engine Fluid Bund Level Warning Yes
Event Audible Alert
High Engine Fluid Bund Level Warning No
Event Breaker #1 Trip
High Engine Fluid Bund Level Warning No
Event Breaker #2 Trip
High Engine Fluid Bund Level Shutdown Activate Hard Shutdown Condition
Event Response Configuration
High Engine Fluid Bund Level Shutdown Yes
Event Audible Alert
High Engine Fluid Bund Level Shutdown No
Event Breaker #1 Trip
High Engine Fluid Bund Level Shutdown No
Event Breaker #2 Trip
Engine Derate Event Response Activate Warning Condition
Configuration
Engine Derate Event Audible Alert Yes
High Generator Bearing #1 Temperature Activate Warning Condition
Warning Event Response Configuration
High Generator Bearing #1 Temperature Yes
Warning Event Audible Alert
High Generator Bearing #1 Temperature No
Warning Event Breaker #1 Trip
High Generator Bearing #1 Temperature No
Warning Event Breaker #2 Trip
High Generator Bearing #1 Temperature No
Warning Event Fault Protection Timer
High Generator Bearing #1 Temperature Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Generator Bearing #1 Temperature Yes
Shutdown Event Audible Alert
High Generator Bearing #1 Temperature No
Shutdown Event Breaker #1 Trip
High Generator Bearing #1 Temperature No
Shutdown Event Breaker #2 Trip
High Generator Bearing #1 Temperature No
Shutdown Event Fault Protection Timer
Low Generator Bearing #1 Temperature Activate Warning Condition
Warning Event Response Configuration
Low Generator Bearing #1 Temperature Yes
Warning Event Audible Alert
Low Generator Bearing #1 Temperature No
Warning Event Breaker #1 Trip
Low Generator Bearing #1 Temperature No
Warning Event Breaker #2 Trip
Low Generator Bearing #1 Temperature Yes
Warning Event Fault Protection Timer
Low Generator Bearing #1 Temperature Disable Condition
Shutdown Event Response Configuration
Low Generator Bearing #1 Temperature No
Shutdown Event Audible Alert
Low Generator Bearing #1 Temperature No
Shutdown Event Breaker #1 Trip
Low Generator Bearing #1 Temperature No
Shutdown Event Breaker #2 Trip
Low Generator Bearing #1 Temperature No
Shutdown Event Fault Protection Timer
Generator Overcurrent Warning Event Activate Warning Condition
Response Configuration
Generator Overcurrent Warning Event Yes
Audible Alert
Generator Overcurrent Warning Event No
Breaker #1 Trip
Generator Overcurrent Warning Event No
Breaker #2 Trip
Generator Overcurrent Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Generator Overcurrent Shutdown Event Yes
Audible Alert
Generator Overcurrent Shutdown Event No
Breaker #1 Trip
Generator Overcurrent Shutdown Event No
Breaker #2 Trip
Generator Over Frequency Warning Event Activate Warning Condition
Response Configuration
Generator Over Frequency Warning Event Yes
Audible Alert
Generator Over Frequency Warning Event No
Breaker #1 Trip
Generator Over Frequency Warning Event No
Breaker #2 Trip
Generator Over Frequency Shutdown Activate Hard Shutdown Condition
Event Response Configuration
Generator Over Frequency Shutdown Yes
Event Audible Alert
Generator Over Frequency Shutdown No
Event Breaker #1 Trip
Generator Over Frequency Shutdown No
Event Breaker #2 Trip
Generator Under Frequency Warning Activate Warning Condition
Event Response Configuration
Generator Under Frequency Warning Yes
Event Audible Alert
Generator Under Frequency Warning No
Event Breaker #1 Trip
Generator Under Frequency Warning No
Event Breaker #2 Trip
Generator Under Frequency Warning Yes
Event Fault Protection Timer
Generator Under Frequency Shutdown Activate Hard Shutdown Condition
Event Response Configuration
Generator Under Frequency Shutdown Yes
Event Audible Alert
Generator Under Frequency Shutdown No
Event Breaker #1 Trip
Generator Under Frequency Shutdown No
Event Breaker #2 Trip
Generator Under Frequency Shutdown Yes
Event Fault Protection Timer
Generator Reverse Power Warning Event Activate Warning Condition
Response Configuration
Generator Reverse Power Warning Event Yes
Audible Alert
Generator Reverse Power Warning Event No
Breaker #1 Trip
Generator Reverse Power Warning Event No
Breaker #2 Trip
Generator Reverse Power Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Generator Reverse Power Shutdown Event Yes
Audible Alert
Generator Reverse Power Shutdown Event No
Breaker #1 Trip
Generator Reverse Power Shutdown Event No
Breaker #2 Trip
Generator Over Voltage Warning Event Activate Warning Condition
Response Configuration
Generator Over Voltage Warning Event Yes
Audible Alert
Generator Over Voltage Warning Event No
Breaker #1 Trip
Generator Over Voltage Warning Event No
Breaker #2 Trip
Generator Over Voltage Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Generator Over Voltage Shutdown Event Yes
Audible Alert
Generator Over Voltage Shutdown Event No
Breaker #1 Trip
Generator Over Voltage Shutdown Event No
Breaker #2 Trip
Generator Under Voltage Warning Event Activate Warning Condition
Response Configuration
Generator Under Voltage Warning Event Yes
Audible Alert
Generator Under Voltage Warning Event No
Breaker #1 Trip
Generator Under Voltage Warning Event No
Breaker #2 Trip
Generator Under Voltage Warning Event Yes
Fault Protection Timer
Generator Under Voltage Shutdown Event Activate Hard Shutdown Condition
Response Configuration
Generator Under Voltage Shutdown Event Yes
Audible Alert
Generator Under Voltage Shutdown Event No
Breaker #1 Trip
Generator Under Voltage Shutdown Event No
Breaker #2 Trip
Generator Under Voltage Shutdown Event Yes
Fault Protection Timer
Earth Fault Event Response Configuration Activate Hard Shutdown Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 Trip No
Earth Fault Event Breaker #2 Trip No
Generator Winding #1 High Temperature Activate Warning Condition
Warning Event Response Configuration
Generator Winding #1 High Temperature Yes
Warning Event Audible Alert
Generator Winding #1 High Temperature No
Warning Event Breaker #1 Trip
Generator Winding #1 High Temperature No
Warning Event Breaker #2 Trip
Generator Winding #1 High Temperature No
Warning Event Fault Protection Timer
Generator Winding #1 High Temperature Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Generator Winding #1 High Temperature Yes
Shutdown Event Audible Alert
Generator Winding #1 High Temperature No
Shutdown Event Breaker #1 Trip
Generator Winding #1 High Temperature No
Shutdown Event Breaker #2 Trip
Generator Winding #1 High Temperature No
Shutdown Event Fault Protection Timer
Generator High Power Warning Event Activate Warning Condition
Response Configuration
Generator High Power Warning Event Yes
Audible Alert
Generator High Power Warning Event No
Breaker #1 Trip
Generator High Power Warning Event No
Breaker #2 Trip
Generator Current Imbalance Warning Activate Warning Condition
Event Response Configuration
Generator Current Imbalance Warning Yes
Event Audible Alert
Generator Current Imbalance Warning No
Event Breaker #1 Trip
Generator Current Imbalance Warning No
Event Breaker #2 Trip
Generator Current Imbalance Warning No
Event Fault Protection Timer
Generator Current Imbalance Shutdown Activate Soft Shutdown Condition
Event Response Configuration
Generator Current Imbalance Shutdown Yes
Event Audible Alert
Generator Current Imbalance Shutdown No
Event Breaker #1 Trip
Generator Current Imbalance Shutdown No
Event Breaker #2 Trip
Generator Current Imbalance Shutdown No
Event Fault Protection
Generator Reverse Reactive Power Activate Warning Condition
Warning Event Response Configuration
Generator Reverse Reactive Power Yes
Warning Event Audible Alert
Generator Reverse Reactive Power No
Warning Event Breaker #1 Trip
Generator Reverse Reactive Power No
Warning Event Breaker #2 Trip
Generator Reverse Reactive Power Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Generator Reverse Reactive Power Yes
Shutdown Event Audible Alert
Generator Reverse Reactive Power No
Shutdown Event Breaker #1 Trip
Generator Reverse Reactive Power No
Shutdown Event Breaker #2 Trip
Programmable Trip Point #1 Condition Disable Condition
Exists Event Response Configuration
Programmable Trip Point #1 Condition No
Exists Event Audible Alert
Programmable Trip Point #1 Condition No
Exists Event Breaker #1 Trip
Programmable Trip Point #1 Condition No
Exists Event Breaker #2 Trip
Programmable Trip Point #1 Condition No
Exists Event Fault Protection Timer
Programmable Trip Point #2 Condition Disable Condition
Exists Event Response Configuration
Programmable Trip Point #2 Condition No
Exists Event Audible Alert
Programmable Trip Point #2 Condition No
Exists Event Breaker #1 Trip
Programmable Trip Point #2 Condition No
Exists Event Breaker #2 Trip
Programmable Trip Point #2 Condition No
Exists Event Fault Protection Timer
Generator Output Sensing System Disable Condition
Diagnostic Response Configuration
Generator Output Sensing System No
Diagnostic Audible Alert
Generator Output Sensing System No
Diagnostic Breaker #1 Trip
Generator Output Sensing System No
Diagnostic Breaker #2 Trip
Generator Output Sensing System No
Diagnostic Fault Protection Timer
Programmable Trip Point #3 Condition Disable Condition
Exists Event Response Configuration
Programmable Trip Point #3 Condition No
Exists Event Audible Alert
Programmable Trip Point #3 Condition No
Exists Event Breaker #1 Trip
Programmable Trip Point #3 Condition No
Exists Event Breaker #2 Trip
Programmable Trip Point #3 Condition No
Exists Event Fault Protection Timer
High Battery Voltage Warning Event Activate Warning Condition
Response Configuration
High Battery Voltage Warning Event Yes
Audible Alert
High Battery Voltage Warning Event No
Breaker #1 Trip
High Battery Voltage Warning Event No
Breaker #2 Trip
High Battery Voltage Shutdown Event Activate Soft Shutdown Condition
Response Configuration
High Battery Voltage Shutdown Event Yes
Audible Alert
High Battery Voltage Shutdown Event No
Breaker #1 Trip
High Battery Voltage Shutdown Event No
Breaker #2 Trip
Low Battery Voltage Warning Event Activate Warning Condition
Response Configuration
Low Battery Voltage Warning Event Yes
Audible Alert
Low Battery Voltage Warning Event No
Breaker #1 Trip
Low Battery Voltage Warning Event No
Breaker #2 Trip
Low Battery Voltage Warning Event Fault No
Protection Timer
Low Battery Charging System Voltage Activate Warning Condition
Warning Event Response Configuration
Low Battery Charging System Voltage Yes
Warning Event Audible Alert
Low Battery Charging System Voltage No
Warning Event Breaker #1 Trip
Low Battery Charging System Voltage No
Warning Event Breaker #2 Trip
Low Battery Charging System Voltage No
Warning Event Fault Protection Timer
Generator Breaker Open Event Response Active Only Condition
Configuration
Generator Breaker Open Event Audible No
Alert
Generator Breaker Closed Event Response Active Only Condition
Configuration
Generator Breaker Closed Event Audible No
Alert
Engine In Cooldown Event Response Active Only Condition
Configuration
Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Activate Warning Condition
Mismatch Warning Event Response Config
Engine Speed-Generator Output Freq Yes
Mismatch Warning Event Audible Alert
Engine Speed-Generator Output Freq No
Mismatch Warning Event Breaker #1 Trip
Engine Speed-Generator Output Freq No
Mismatch Warning Event Breaker #2 Trip
Generator Control Not in Automatic Activate Warning Condition
Warning Event Response Configuration
Generator Control Not in Automatic Yes
Warning Event Audible Alert
Earth Leakage Event Response Activate Hard Shutdown Condition
Configuration
Earth Leakage Event Audible Alert Yes
Earth Leakage Event Breaker #1 Trip No
Earth Leakage Event Breaker #2 Trip No
Emergency Power System Supplying Load Warning & Active Only Condition
Event Response Configuration
Emergency Power System Supplying Load No
Event Audible Alert
Low Cranking Voltage Warning Event Disable Condition
Response Configuration
Low Cranking Voltage Warning Event No
Audible Alert
Low Cranking Voltage Warning Event No
Breaker #1 Trip
Low Cranking Voltage Warning Event No
Breaker #2 Trip
Analog Input #1 Custom Parameter High Activate Warning Condition
Warning Event Response Configuration
Analog Input #1 Custom Parameter High Yes
Warning Event Audible Alert
Analog Input #1 Custom Parameter High No
Warning Event Breaker #1 Trip
Analog Input #1 Custom Parameter High No
Warning Event Breaker #2 Trip
Analog Input #1 Custom Parameter High No
Warning Event Fault Protection Timer
Analog Input #1 Custom Parameter High Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #1 Custom Parameter High Yes
Shutdown Event Audible Alert
Analog Input #1 Custom Parameter High No
Shutdown Event Breaker #1 Trip
Analog Input #1 Custom Parameter High No
Shutdown Event Breaker #2 Trip
Analog Input #1 Custom Parameter High No
Shutdown Event Fault Protection Timer
Analog Input #1 Custom Parameter Low Activate Warning Condition
Warning Event Response Configuration
Analog Input #1 Custom Parameter Low Yes
Warning Event Audible Alert
Analog Input #1 Custom Parameter Low No
Warning Event Breaker #1 Trip
Analog Input #1 Custom Parameter Low No
Warning Event Breaker #2 Trip
Analog Input #1 Custom Parameter Low No
Warning Event Fault Protection Timer
Analog Input #1 Custom Parameter Low Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #1 Custom Parameter Low Yes
Shutdown Event Audible Alert
Analog Input #1 Custom Parameter Low No
Shutdown Event Breaker #1 Trip
Analog Input #1 Custom Parameter Low No
Shutdown Event Breaker #2 Trip
Analog Input #1 Custom Parameter Low No
Shutdown Event Fault Protection Timer
Analog Input #2 Custom Parameter High Activate Warning Condition
Warning Event Response Configuration
Analog Input #2 Custom Parameter High Yes
Warning Event Audible Alert
Analog Input #2 Custom Parameter High No
Warning Event Breaker #1 Trip
Analog Input #2 Custom Parameter High No
Warning Event Breaker #2 Trip
Analog Input #2 Custom Parameter High No
Warning Event Fault Protection Timer
Analog Input #2 Custom Parameter High Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #2 Custom Parameter High Yes
Shutdown Event Audible Alert
Analog Input #2 Custom Parameter High No
Shutdown Event Breaker #1 Trip
Analog Input #2 Custom Parameter High No
Shutdown Event Breaker #2 Trip
Analog Input #2 Custom Parameter High No
Shutdown Event Fault Protection Timer
Analog Input #2 Custom Parameter Low Activate Warning Condition
Warning Event Response Configuration
Analog Input #2 Custom Parameter Low Yes
Warning Event Audible Alert
Analog Input #2 Custom Parameter Low No
Warning Event Breaker #1 Trip
Analog Input #2 Custom Parameter Low No
Warning Event Breaker #2 Trip
Analog Input #2 Custom Parameter Low No
Warning Event Fault Protection Timer
Analog Input #2 Custom Parameter Low Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #2 Custom Parameter Low Yes
Shutdown Event Audible Alert
Analog Input #2 Custom Parameter Low No
Shutdown Event Breaker #1 Trip
Analog Input #2 Custom Parameter Low No
Shutdown Event Breaker #2 Trip
Analog Input #2 Custom Parameter Low No
Shutdown Event Fault Protection Timer
Analog Input #3 Custom Parameter High Activate Warning Condition
Warning Event Response Configuration
Analog Input #3 Custom Parameter High Yes
Warning Event Audible Alert
Analog Input #3 Custom Parameter High No
Warning Event Breaker #1 Trip
Analog Input #3 Custom Parameter High No
Warning Event Breaker #2 Trip
Analog Input #3 Custom Parameter High No
Warning Event Fault Protection Timer
Analog Input #3 Custom Parameter High Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #3 Custom Parameter High Yes
Shutdown Event Audible Alert
Analog Input #3 Custom Parameter High No
Shutdown Event Breaker #1 Trip
Analog Input #3 Custom Parameter High No
Shutdown Event Breaker #2 Trip
Analog Input #3 Custom Parameter High No
Shutdown Event Fault Protection Timer
Analog Input #3 Custom Parameter Low Activate Warning Condition
Warning Event Response Configuration
Analog Input #3 Custom Parameter Low Yes
Warning Event Audible Alert
Analog Input #3 Custom Parameter Low No
Warning Event Breaker #1 Trip
Analog Input #3 Custom Parameter Low No
Warning Event Breaker #2 Trip
Analog Input #3 Custom Parameter Low No
Warning Event Fault Protection Timer
Analog Input #3 Custom Parameter Low Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Analog Input #3 Custom Parameter Low Yes
Shutdown Event Audible Alert
Analog Input #3 Custom Parameter Low No
Shutdown Event Breaker #1 Trip
Analog Input #3 Custom Parameter Low No
Shutdown Event Breaker #2 Trip
Analog Input #3 Custom Parameter Low No
Shutdown Event Fault Protection Timer
Utility Breaker Failure To Open Event Activate Hard Shutdown Condition
Response Configuration
Utility Breaker Failure To Open Event Yes
Audible Alert
Utility Breaker Failure To Open Event No
Breaker #1 Trip
Utility Breaker Failure To Open Event No
Breaker #2 Trip
Utility Breaker Failure To Close Event Activate Warning Condition
Response Configuration
Utility Breaker Failure To Close Event Yes
Audible Alert
Utility Breaker Failure To Close Event No
Breaker #1 Trip
Utility Breaker Failure To Close Event No
Breaker #2 Trip
Utility Breaker Failure To Close Event Loss Yes
of Utility
Loss of Utility Event Response Warning & Active Only Condition
Configuration
Loss of Utility Event Audible Alert Yes
Loss of Utility Event Breaker #1 Trip No
Loss of Utility Event Breaker #2 Trip No
Loss of Utility Event Loss of Utility Yes
Utility to Generator Transfer Failure Disable Condition
Warning Event Response Configuration
Utility to Generator Transfer Failure No
Warning Event Audible Alert
Utility to Generator Transfer Failure No
Warning Event Breaker #1 Trip
Utility to Generator Transfer Failure No
Warning Event Breaker #2 Trip
Utility to Generator Transfer Failure Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Utility to Generator Transfer Failure Yes
Shutdown Event Audible Alert
Utility to Generator Transfer Failure Yes
Shutdown Event Breaker #1 Trip
Utility to Generator Transfer Failure No
Shutdown Event Breaker #2 Trip
Generator to Utility Transfer Failure Activate Warning Condition
Warning Event Response Configuration
Generator to Utility Transfer Failure Yes
Warning Event Audible Alert
Generator to Utility Transfer Failure No
Warning Event Breaker #1 Trip
Generator to Utility Transfer Failure No
Warning Event Breaker #2 Trip
Generator to Utility Transfer Failure Yes
Warning Event Loss of Utility
Utility Breaker System Fault Event Activate Warning Condition
Response Configuration
Utility Breaker System Fault Event Audible Yes
Alert
Utility Breaker System Fault Event Breaker No
#1 Trip
Utility Breaker System Fault Event Breaker No
#2 Trip
Utility Breaker System Fault Event Loss of Yes
Utility
Custom Event #1 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #1 Condition Exists Event No
Audible Alert
Custom Event #1 Condition Exists Event No
Breaker #1 Trip
Custom Event #1 Condition Exists Event No
Breaker #2 Trip
Custom Event #1 Condition Exists Event No
Fault Protection Timer
Custom Event #2 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #2 Condition Exists Event No
Audible Alert
Custom Event #2 Condition Exists Event No
Breaker #1 Trip
Custom Event #2 Condition Exists Event No
Breaker #2 Trip
Custom Event #2 Condition Exists Event No
Fault Protection Timer
Custom Event #3 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #3 Condition Exists Event No
Audible Alert
Custom Event #3 Condition Exists Event No
Breaker #1 Trip
Custom Event #3 Condition Exists Event No
Breaker #2 Trip
Custom Event #3 Condition Exists Event No
Fault Protection Timer
Custom Event #4 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #4 Condition Exists Event No
Audible Alert
Custom Event #4 Condition Exists Event No
Breaker #1 Trip
Custom Event #4 Condition Exists Event No
Breaker #2 Trip
Custom Event #4 Condition Exists Event No
Fault Protection Timer
Custom Event #5 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #5 Condition Exists Event No
Audible Alert
Custom Event #5 Condition Exists Event No
Breaker #1 Trip
Custom Event #5 Condition Exists Event No
Breaker #2 Trip
Custom Event #5 Condition Exists Event No
Fault Protection Timer
Custom Event #6 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #6 Condition Exists Event No
Audible Alert
Custom Event #6 Condition Exists Event No
Breaker #1 Trip
Custom Event #6 Condition Exists Event No
Breaker #2 Trip
Custom Event #6 Condition Exists Event No
Fault Protection Timer
Custom Event #7 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #7 Condition Exists Event No
Audible Alert
Custom Event #7 Condition Exists Event No
Breaker #1 Trip
Custom Event #7 Condition Exists Event No
Breaker #2 Trip
Custom Event #7 Condition Exists Event No
Fault Protection Timer
Custom Event #8 Condition Exists Event Active Only Condition
Response Configuration
Custom Event #8 Condition Exists Event No
Audible Alert
Custom Event #8 Condition Exists Event No
Breaker #1 Trip
Custom Event #8 Condition Exists Event No
Breaker #2 Trip
Custom Event #8 Condition Exists Event No
Fault Protection Timer
Isolated Digital Input #1 Custom Event Active Only Condition
Response Configuration
Isolated Digital Input #1 Custom Event No
Audible Alert
Isolated Digital Input #1 Custom Event No
Breaker #1 Trip
Isolated Digital Input #1 Custom Event No
Breaker #2 Trip
Isolated Digital Input #1 Custom Event No
Fault Protection Timer
Isolated Digital Input #2 Custom Event Active Only Condition
Response Configuration
Isolated Digital Input #2 Custom Event No
Audible Alert
Isolated Digital Input #2 Custom Event No
Breaker #1 Trip
Isolated Digital Input #2 Custom Event No
Breaker #2 Trip
Isolated Digital Input #2 Custom Event No
Fault Protection Timer
Isolated Digital Input #3 Custom Event Active Only Condition
Response Configuration
Isolated Digital Input #3 Custom Event No
Audible Alert
Isolated Digital Input #3 Custom Event No
Breaker #1 Trip
Isolated Digital Input #3 Custom Event No
Breaker #2 Trip
Isolated Digital Input #3 Custom Event No
Fault Protection Timer
Isolated Digital Input #4 Custom Event Active Only Condition
Response Configuration
Isolated Digital Input #4 Custom Event No
Audible Alert
Isolated Digital Input #4 Custom Event No
Breaker #1 Trip
Isolated Digital Input #4 Custom Event No
Breaker #2 Trip
Isolated Digital Input #4 Custom Event No
Fault Protection Timer
Engine Running Conditions - Custom Event Activate
Digital Input
Engine Running Conditions - Engine Do Not Activate
Running
Engine Running Conditions - Volts/Hertz Do Not Activate
within Limits
Engine Running Conditions - Engine Do Not Activate
Running at Rated Speed
Fuel Fill/Drain Feature Enable Status Disabled
Fuel Fill Activation Tank Level Percentage 0.0 %
Threshold
Fuel Fill Deactivation Tank Level 100.0 %
Percentage Threshold
Generator Connection Configuration Wye (or Star) Connection
Generator Potential Transformer Primary 400 Volts
Winding Rating
Generator Potential Transformer 400 Volts
Secondary Winding Rating
Generator Current Transformer Primary 5000 Amps
Winding Rating
Generator Current Transformer Secondary 5 Amps
Winding Rating
Number of Generator Poles 4 Poles
Generator Rated Frequency 50 Hz
Generator Rated Voltage 410 Volts
Generator Rated Power 2500 kW
Generator Rated Apparent Power 3125 kVA
Maximum Generator Voltage Output Bias 15 %
Percentage
Customer Password Security Level to 3-Factory, Single Use
Reset Generator Energy Meters
Generator Definite Time Overcurrent 105 %
Warning Event Percentage Threshold
Generator Inverse Time Overcurrent 0.27 sec
Shutdown Event Time Multiplier
Generator Definite Time Overcurrent 110 %
Shutdown Event Percentage Threshold
Generator Definite Time Overcurrent 10.0 sec
Shutdown Event Notification Delay Time
Generator Inverse Time Over Current 110 %
Shutdown Event Threshold
Generator Inverse Definite Minimum Time Normal Inverse Curve
Curve Type Configuration
Generator Rated Current Multiplier 1.00
Maintenance Mode Definite Time Over 150 %
Current Shutdown Event Percentage
Generator Stator Current Limiter Enable Disabled
Status
Generator Stator Current Limiter Setpoint 250 %
Generator Stator Current Limiter 50.0 %
Proportional Gain Percentage
Generator Stator Current Limiter Integral 50.0 %
Gain Percentage
Generator Current Imbalance Warning 25.0 %
Event Percentage Threshold
Generator Current Imbalance Warning 5 sec
Event Notification Delay Time
Generator Current Imbalance Shutdown 35.0 %
Event Percentage Threshold
Generator Current Imbalance Shutdown 30 sec
Event Notification Delay Time
Generator Over Frequency Warning Event 108.0 %
Percentage Threshold
Generator Over Frequency Warning Event 10 sec
Notification Delay Time
Generator Over Frequency Shutdown 112.0 %
Event Percentage Threshold
Generator Over Frequency Shutdown 10 sec
Event Notification Delay Time
Generator Under Frequency Warning 90.0 %
Event Percentage Threshold
Generator Under Frequency Warning 20 sec
Event Notification Delay Time
Generator Under Frequency Shutdown 85.0 %
Event Percentage Threshold
Generator Under Frequency Shutdown 10 sec
Event Notification Delay Time
Generator Over Voltage Warning Event 110 %
Percentage Threshold
Generator Over Voltage Warning Event 10 sec
Notification Delay Time
Generator Over Voltage Shutdown Event 118 %
Percentage Threshold
Generator Over Voltage Shutdown Event 5 sec
Notification Delay Time
Generator Under Voltage Warning Event 90 %
Percentage Threshold
Generator Under Voltage Warning Event 20 sec
Notification Delay Time
Generator Under Voltage Shutdown Event 85 %
Percentage Threshold
Generator Under Voltage Shutdown Event 20 sec
Notification Delay Time
Generator Reactive Load Control 1.0 %
Proportional Gain Percentage
Generator Reactive Load Control Integral 1.0 %
Gain Percentage
Generator Reactive Load Control Power 1.00
Factor Level Configuration
Generator Load Control Protective Droop Unavailable
Enable Status
Generator Real Load Control Protective Unavailable %
Droop High Power Threshold
Generator Real Load Control Protective Unavailable Hz/%
Droop High Power Slope
Generator Real Load Control Protective Unavailable %
Droop Low Power Threshold
Generator Real Load Control Protective Unavailable Hz/%
Droop Low Power Slope
Generator Reactive Load Control Unavailable %
Protective Droop High Power Threshold
Generator Reactive Load Control Unavailable V/%
Protective Droop High Power Slope
Generator Reactive Load Control Unavailable %
Protective Droop Low Power Threshold
Generator Reactive Load Control Unavailable
Protective Droop Low Power Slope
Generator Reverse Power Warning Event 5 %
Percentage Threshold
Generator Reverse Power Warning Event 8 sec
Notification Delay Time
Generator Reverse Power Shutdown Event 10 %
Percentage Threshold
Generator Reverse Power Shutdown Event 5 sec
Notification Delay Time
Generator Reverse Reactive Power 10.00 %
Warning Event Percentage Threshold
Generator Reverse Reactive Power 5 sec
Warning Event Notification Delay Time
Generator Reverse Reactive Power 15.00 %
Shutdown Event Percentage Threshold
Generator Reverse Reactive Power 20 sec
Shutdown Event Notification Delay Time
Load Shed Activation Conditions - Do Not Activate
Generator Breaker Open
Load Shed Activation Conditions - Do Not Activate
Underfrequency Warning Event Active
Load Shed Activation Conditions - Do Not Activate
Undervoltage Warning Event Active
Load Shed Activation Conditions - Do Not Activate
Programmable kW Relay Trip #1 Active
Load Shed Activation Conditions - Do Not Activate
Programmable kW Relay Trip #2 Active
Load Shed Activation Conditions - Do Not Activate
Programmable kW Relay Trip #3 Active
Programmable Cycle Timer #1 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #1 Activation Deactivate
Day - Monday
Programmable Cycle Timer #1 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #1 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #1 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #1 Activation Deactivate
Day - Friday
Programmable Cycle Timer #1 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #1 Activation 0 min
Start Time
Programmable Cycle Timer #1 Active Time 1 min
Programmable Cycle Timer #1 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #1 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #2 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #2 Activation Deactivate
Day - Monday
Programmable Cycle Timer #2 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #2 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #2 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #2 Activation Deactivate
Day - Friday
Programmable Cycle Timer #2 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #2 Activation 0 min
Start Time
Programmable Cycle Timer #2 Active Time 1 min
Programmable Cycle Timer #2 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #2 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #3 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #3 Activation Deactivate
Day - Monday
Programmable Cycle Timer #3 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #3 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #3 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #3 Activation Deactivate
Day - Friday
Programmable Cycle Timer #3 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #3 Activation 0 min
Start Time
Programmable Cycle Timer #3 Active Time 1 min
Programmable Cycle Timer #3 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #3 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #4 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #4 Activation Deactivate
Day - Monday
Programmable Cycle Timer #4 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #4 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #4 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #4 Activation Deactivate
Day - Friday
Programmable Cycle Timer #4 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #4 Activation 0 min
Start Time
Programmable Cycle Timer #4 Active Time 1 min
Programmable Cycle Timer #4 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #4 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #5 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #5 Activation Deactivate
Day - Monday
Programmable Cycle Timer #5 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #5 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #5 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #5 Activation Deactivate
Day - Friday
Programmable Cycle Timer #5 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #5 Activation 0 min
Start Time
Programmable Cycle Timer #5 Active Time 1 min
Programmable Cycle Timer #5 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #5 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #6 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #6 Activation Deactivate
Day - Monday
Programmable Cycle Timer #6 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #6 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #6 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #6 Activation Deactivate
Day - Friday
Programmable Cycle Timer #6 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #6 Activation 0 min
Start Time
Programmable Cycle Timer #6 Active Time 1 min
Programmable Cycle Timer #6 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #6 Output #2 Inactive
Activation Configuration
Programmable Cycle Timer #7 Activation Deactivate
Day - Sunday
Programmable Cycle Timer #7 Activation Deactivate
Day - Monday
Programmable Cycle Timer #7 Activation Deactivate
Day - Tuesday
Programmable Cycle Timer #7 Activation Deactivate
Day - Wednesday
Programmable Cycle Timer #7 Activation Deactivate
Day - Thursday
Programmable Cycle Timer #7 Activation Deactivate
Day - Friday
Programmable Cycle Timer #7 Activation Deactivate
Day - Saturday
Programmable Cycle Timer #7 Activation 0 min
Start Time
Programmable Cycle Timer #7 Active Time 1 min
Programmable Cycle Timer #7 Output #1 Inactive
Activation Configuration
Programmable Cycle Timer #7 Output #2 Inactive
Activation Configuration
Electronic Control Module Reduced Power Disabled
Mode Enable Status
Electronic Control Module Reduced Power 30 min
Mode Delay Time
Maintenance Level 1 Cycle Interval Hours 2000 hours
Maintenance Level 1 Cycle Interval Days 180
Customer Password Security Level to 0-No Security
Reset Service Maintenance Interval
Programmable Trip Point Function #1 Disabled
Trigger Condition
Programmable Trip Point Function #1 0 %
Percentage Threshold
Programmable Trip Point Function #1 0 %
Hysteresis Percentage
Programmable Trip Point Function #1 Trip 0 sec
Activation Delay Time
Programmable Trip Point Function #1 Trip 0 sec
Deactivation Delay Time
Programmable Trip Point Function #2 Disabled
Trigger Condition
Programmable Trip Point Function #2 0 %
Percentage Threshold
Programmable Trip Point Function #2 0 %
Hysteresis Percentage
Programmable Trip Point Function #2 Trip 0 sec
Activation Delay Time
Programmable Trip Point Function #2 Trip 0 sec
Deactivation Delay Time
Programmable Trip Point Function #3 Disabled
Trigger Condition
Programmable Trip Point Function #3 0 %
Percentage Threshold
Programmable Trip Point Function #3 0 %
Hysteresis Percentage
Programmable Trip Point Function #3 Trip 0 sec
Activation Delay Time
Programmable Trip Point Function #3 Trip 0 sec
Deactivation Delay Time
Overview Screen Enable Status Disabled
Overview Screen Keypad Inactivity Delay 60.0 sec
Time
Generator/Utility Automatic Transfer Disabled
Enable Status
Loss of Utility Event Notification Delay 10.0 sec
Time
Generator to Utility Transfer Delay Time 3 min
Generator to Utility Fast Transfer Delay 10 sec
Time
Utility to Generator Transfer Failure 60 sec
Warning Event Threshold
Utility to Generator Transfer Failure 90 sec
Shutdown Event Threshold
Generator to Utility Transfer Failure 60 sec
Warning Event Threshold
Generator/Utility Automatic Transfer 0.0 sec
Unpowered Load Time
Generator Ready to Load Threshold 90.0 %
Percentage
Generator Ready to Load Delay Time 0.0 sec
Generator to Utility Transfer Mode Manual
Utility Breaker Maximum Closing Time 30 sec
Utility Breaker Maximum Opening Time 3 sec
Programmable Logic Feature Enable Disabled
Status
Programmable Logic Function File Name
Programmable Logic Function File Login
User Name
Programmable Logic Function File 01/01/1999 00:00:00
Download Time/Date
Programmable Logic Function File Modified 01/01/1999 00:00:00
Time/Date
Engine Serial Number GFP01229
Display Pressure Units Configuration kPa
Display Temperature Units Configuration Degrees Centigrade (Celsius)
Display Volume Units Configuration liters

Lifetime:Total Operating Hours vs Generator Real Load Percentage - EMCP 4.3


Generator Real Load hours %
Percentage( % )
0.0-29.9 15.67 93.41
30.0-89.9 0.00 0.00
90.0-99.9 0.97 5.81
100.0-110.0 0.13 0.79
>110.0 0.00 0.00

Status Event History - EMCP 4.3


Description Value Unit
Time of Download for Status 05/09/2022 22:57:25
Event Log

Event Description Date/Time


Remote Initiate contact removed 05/09/2022 22:53:44
Acceptable Voltage and Frequency Reached 05/09/2022 22:46:49
(VFSR)
Crank Terminate Reached 05/09/2022 22:46:44
Remote Initiate contact received 05/09/2022 22:44:19
Package in Auto 05/09/2022 22:40:50
Engine Control Switch (ECS) in Auto Position 05/09/2022 22:40:50
Reset All Events Command Issued 05/09/2022 22:40:46
EMCP 4 Power Up Cycle Complete 05/09/2022 22:39:51
Package Not in Auto 05/09/2022 22:39:50
Programmable Logic Feature (PLC) Disabled 05/09/2022 22:39:50
Engine Not in Auto 05/09/2022 22:39:50
Reset All Events Command Issued 05/09/2022 22:36:52
Package Not in Auto 05/09/2022 22:36:48
Engine Control Switch (ECS) in Stop Position 05/09/2022 22:36:48
Engine Not in Auto 05/09/2022 22:36:48
Engine Control Switch (ECS) in Auto Position 05/09/2022 22:36:24
Package in Auto 05/09/2022 22:36:24
Reset All Events Command Issued 05/09/2022 22:36:05
EMCP 4 Power Up Cycle Complete 05/09/2022 22:35:34
Engine Not in Auto 05/09/2022 22:35:33
Programmable Logic Feature (PLC) Disabled 05/09/2022 22:35:33
Package Not in Auto 05/09/2022 22:35:33
Remote Initiate contact removed 05/09/2022 22:34:31
Acceptable Voltage and Frequency Reached 05/09/2022 12:55:33
(VFSR)
Crank Terminate Reached 05/09/2022 12:55:27
Remote Initiate contact received 05/09/2022 12:53:02
Acceptable Voltage and Frequency Reached 05/09/2022 06:10:58
(VFSR)
Remote Initiate contact removed 05/09/2022 06:10:57
Acceptable Voltage and Frequency Reached 04/09/2022 22:34:40
(VFSR)
Crank Terminate Reached 04/09/2022 22:34:35
Remote Initiate contact received 04/09/2022 22:32:09
Remote Initiate contact removed 03/09/2022 23:04:31
Acceptable Voltage and Frequency Reached 02/09/2022 00:36:47
(VFSR)
Crank Terminate Reached 02/09/2022 00:36:42
Remote Initiate contact received 02/09/2022 00:34:21
Remote Initiate contact removed 02/09/2022 00:31:37
Acceptable Voltage and Frequency Reached 02/09/2022 00:30:09
(VFSR)
Crank Terminate Reached 02/09/2022 00:30:04
Remote Initiate contact received 02/09/2022 00:27:43
Remote Initiate contact removed 02/09/2022 00:27:33
Remote Initiate contact received 02/09/2022 00:26:53
Engine Control Switch (ECS) in Auto Position 02/09/2022 00:26:24
Package in Auto 02/09/2022 00:26:24
Reset All Events Command Issued 02/09/2022 00:25:59
Engine Not in Auto 02/09/2022 00:25:56
Engine Control Switch (ECS) in Stop Position 02/09/2022 00:25:56
Acceptable Voltage and Frequency Reached 02/09/2022 00:05:31
(VFSR)
Crank Terminate Reached 02/09/2022 00:05:31
Package Not in Auto 02/09/2022 00:05:30
Remote Initiate contact removed 02/09/2022 00:05:30
Acceptable Voltage and Frequency Reached 31/08/2022 07:08:48
(VFSR)
Crank Terminate Reached 31/08/2022 07:08:42
Remote Initiate contact received 31/08/2022 07:06:19
Engine Control Switch (ECS) in Auto Position 31/08/2022 07:05:20
Package in Auto 31/08/2022 07:05:20
Reset All Events Command Issued 31/08/2022 07:05:03
Engine Not in Auto 31/08/2022 07:05:01
Engine Control Switch (ECS) in Stop Position 31/08/2022 07:05:01
Remote Initiate contact removed 31/08/2022 06:42:01
Package Not in Auto 31/08/2022 06:41:40
Acceptable Voltage and Frequency Reached 31/08/2022 06:41:15
(VFSR)
Acceptable Voltage and Frequency Reached 30/08/2022 00:06:48
(VFSR)
Crank Terminate Reached 30/08/2022 00:06:43
Remote Initiate contact received 30/08/2022 00:04:15
Remote Initiate contact removed 27/08/2022 23:24:00
Acceptable Voltage and Frequency Reached 30/07/2022 14:15:46
(VFSR)
Crank Terminate Reached 30/07/2022 14:15:39
Remote Initiate contact received 30/07/2022 14:12:57
Engine Control Switch (ECS) in Auto Position 30/07/2022 14:11:33
Package in Auto 30/07/2022 14:11:33
Reset All Events Command Issued 30/07/2022 14:11:14
Engine Not in Auto 30/07/2022 14:11:12
Engine Control Switch (ECS) in Stop Position 30/07/2022 14:11:12
Package Not in Auto 30/07/2022 14:11:12
Remote Initiate contact removed 30/07/2022 14:10:04
Remote Initiate contact received 30/07/2022 14:06:38
Remote Initiate contact removed 27/07/2022 19:34:44
Acceptable Voltage and Frequency Reached 27/07/2022 10:17:33
(VFSR)
Crank Terminate Reached 27/07/2022 10:17:28
Remote Initiate contact received 27/07/2022 10:14:59
Remote Initiate contact removed 22/07/2022 02:51:34
Acceptable Voltage and Frequency Reached 10/07/2022 05:10:43
(VFSR)
Crank Terminate Reached 10/07/2022 05:10:38
Remote Initiate contact received 10/07/2022 05:08:16
Remote Initiate contact removed 10/07/2022 05:07:38
Remote Initiate contact received 10/07/2022 05:07:28
Package in Auto 10/07/2022 05:07:02
Engine Control Switch (ECS) in Auto Position 10/07/2022 05:07:02
Reset All Events Command Issued 10/07/2022 05:06:47
Engine Not in Auto 10/07/2022 05:06:43
Engine Control Switch (ECS) in Stop Position 10/07/2022 05:06:43
Acceptable Voltage and Frequency Reached 10/07/2022 04:22:45
(VFSR)
Crank Terminate Reached 10/07/2022 04:22:45
Package Not in Auto 10/07/2022 04:22:44
Remote Initiate contact removed 10/07/2022 04:22:43
Acceptable Voltage and Frequency Reached 09/07/2022 18:51:48
(VFSR)
Crank Terminate Reached 09/07/2022 18:51:42
Remote Initiate contact received 09/07/2022 18:49:04
Remote Initiate contact removed 09/07/2022 06:20:14
Remote Initiate contact received 09/07/2022 06:15:40
Engine Control Switch (ECS) in Auto Position 28/06/2022 11:41:41
Package in Auto 28/06/2022 11:41:41
Reset All Events Command Issued 28/06/2022 11:41:40
Engine Not in Auto 28/06/2022 11:41:35
Engine Control Switch (ECS) in Stop Position 28/06/2022 11:41:35
Package Not in Auto 28/06/2022 07:55:36
Remote Initiate contact removed 27/06/2022 17:15:23
Acceptable Voltage and Frequency Reached 27/06/2022 17:01:34
(VFSR)
Crank Terminate Reached 27/06/2022 17:01:28
Remote Initiate contact received 27/06/2022 16:59:02
Remote Initiate contact removed 27/06/2022 00:07:20
Acceptable Voltage and Frequency Reached 15/06/2022 14:02:56
(VFSR)
Crank Terminate Reached 15/06/2022 14:02:51
Remote Initiate contact received 15/06/2022 14:00:28
Remote Initiate contact removed 15/06/2022 13:23:47
Acceptable Voltage and Frequency Reached 08/06/2022 23:49:30
(VFSR)
Crank Terminate Reached 08/06/2022 23:49:25
Remote Initiate contact received 08/06/2022 23:47:04
Remote Initiate contact removed 08/06/2022 23:46:19
Remote Initiate contact received 08/06/2022 23:45:48
Remote Initiate contact removed 08/06/2022 23:45:34
Remote Initiate contact received 08/06/2022 23:45:25
Engine Control Switch (ECS) in Auto Position 08/06/2022 23:40:10
Package in Auto 08/06/2022 23:40:10
Reset All Events Command Issued 08/06/2022 23:40:07
Engine Control Switch (ECS) in Stop Position 08/06/2022 23:40:03
Engine Not in Auto 08/06/2022 23:40:03
Emergency Stop Received 08/06/2022 23:39:03
Package Not in Auto 08/06/2022 23:39:03
Package in Auto 08/06/2022 23:38:53
Engine Control Switch (ECS) in Auto Position 08/06/2022 23:38:53
Reset All Events Command Issued 08/06/2022 23:38:50
Engine Not in Auto 08/06/2022 23:38:47
Engine Control Switch (ECS) in Stop Position 08/06/2022 23:38:47
Emergency Stop Received 08/06/2022 23:35:48
Remote Initiate contact removed 08/06/2022 23:35:48
Acceptable Voltage and Frequency Reached 08/06/2022 23:35:47
(VFSR)
Crank Terminate Reached 08/06/2022 23:35:47
Package Not in Auto 08/06/2022 23:35:46
Acceptable Voltage and Frequency Reached 08/06/2022 23:35:44
(VFSR)
Remote Initiate contact received 08/06/2022 23:35:41
Remote Initiate contact removed 08/06/2022 23:35:34
Acceptable Voltage and Frequency Reached 08/06/2022 23:34:33
(VFSR)
Crank Terminate Reached 08/06/2022 23:34:28
Remote Initiate contact received 08/06/2022 23:32:07
Engine Control Switch (ECS) in Auto Position 08/06/2022 23:31:15
Package in Auto 08/06/2022 23:31:15
Reset All Events Command Issued 08/06/2022 23:31:10
Engine Not in Auto 08/06/2022 23:31:01
Engine Control Switch (ECS) in Stop Position 08/06/2022 23:31:01
Engine Control Switch (ECS) in Auto Position 08/06/2022 23:30:20
Engine Not in Auto 08/06/2022 23:30:06
Engine Control Switch (ECS) in Stop Position 08/06/2022 23:30:06
Emergency Stop Received 08/06/2022 23:15:05
Package Not in Auto 08/06/2022 23:15:05
Remote Initiate contact removed 08/06/2022 23:15:05
Acceptable Voltage and Frequency Reached 08/06/2022 23:15:04
(VFSR)
Acceptable Voltage and Frequency Reached 08/06/2022 22:59:50
(VFSR)
Crank Terminate Reached 08/06/2022 22:59:40
Remote Initiate contact received 08/06/2022 22:57:13
Engine Control Switch (ECS) in Auto Position 08/06/2022 22:55:10
Package in Auto 08/06/2022 22:55:10
Engine Not in Auto 08/06/2022 22:55:03
Engine Control Switch (ECS) in Stop Position 08/06/2022 22:55:03
Package Not in Auto 08/06/2022 22:55:03
Remote Initiate contact removed 01/06/2022 03:07:03
Acceptable Voltage and Frequency Reached 10/05/2022 23:01:05
(VFSR)
Crank Terminate Reached 10/05/2022 23:01:00
Remote Initiate contact received 10/05/2022 22:58:36
Remote Initiate contact removed 10/05/2022 05:25:18
Acceptable Voltage and Frequency Reached 10/05/2022 05:24:01
(VFSR)
Crank Terminate Reached 10/05/2022 05:23:56
Remote Initiate contact received 10/05/2022 05:21:36
Engine Control Switch (ECS) in Auto Position 10/05/2022 05:21:27
Package in Auto 10/05/2022 05:21:27
Reset All Events Command Issued 10/05/2022 05:21:14
Engine Control Switch (ECS) in Stop Position 10/05/2022 05:21:11
Engine Not in Auto 10/05/2022 05:21:11
Remote Initiate contact removed 10/05/2022 05:12:11
Package Not in Auto 10/05/2022 05:11:45
Acceptable Voltage and Frequency Reached 10/05/2022 05:10:58
(VFSR)
Crank Terminate Reached 10/05/2022 05:10:53
Remote Initiate contact received 10/05/2022 05:08:33
Package in Auto 10/05/2022 05:08:02
Engine Control Switch (ECS) in Auto Position 10/05/2022 05:08:02
Reset All Events Command Issued 10/05/2022 05:07:45
Engine Not in Auto 10/05/2022 05:07:42
Engine Control Switch (ECS) in Stop Position 10/05/2022 05:07:42
Remote Initiate contact removed 10/05/2022 05:01:14
Package Not in Auto 10/05/2022 05:00:48
Acceptable Voltage and Frequency Reached 10/05/2022 05:00:29
(VFSR)
Crank Terminate Reached 10/05/2022 05:00:24
Remote Initiate contact received 10/05/2022 04:58:01
Remote Initiate contact removed 10/05/2022 04:52:04
Acceptable Voltage and Frequency Reached 10/05/2022 04:47:35
(VFSR)
Crank Terminate Reached 10/05/2022 04:47:30
Remote Initiate contact received 10/05/2022 04:45:10
Engine Control Switch (ECS) in Auto Position 10/05/2022 04:44:40
Package in Auto 10/05/2022 04:44:40
Reset All Events Command Issued 10/05/2022 04:44:28
Engine Control Switch (ECS) in Stop Position 10/05/2022 04:44:23
Engine Not in Auto 10/05/2022 04:44:23
Acceptable Voltage and Frequency Reached 10/05/2022 04:22:24
(VFSR)
Crank Terminate Reached 10/05/2022 04:22:24
Package Not in Auto 10/05/2022 04:22:23
Remote Initiate contact removed 10/05/2022 04:22:22
Acceptable Voltage and Frequency Reached 09/05/2022 22:45:20
(VFSR)
Crank Terminate Reached 09/05/2022 22:45:15
Remote Initiate contact received 09/05/2022 22:42:48
Remote Initiate contact removed 06/05/2022 17:40:13
Acceptable Voltage and Frequency Reached 06/05/2022 02:24:18
(VFSR)
Crank Terminate Reached 06/05/2022 02:24:13
Remote Initiate contact received 06/05/2022 02:21:47
Remote Initiate contact removed 05/05/2022 09:30:40
Acceptable Voltage and Frequency Reached 05/05/2022 09:27:31
(VFSR)
Crank Terminate Reached 05/05/2022 09:27:25
Remote Initiate contact received 05/05/2022 09:24:59
Remote Initiate contact removed 04/05/2022 19:53:42
Acceptable Voltage and Frequency Reached 04/05/2022 10:08:56
(VFSR)
Crank Terminate Reached 04/05/2022 10:08:51
Remote Initiate contact received 04/05/2022 10:06:30
Remote Initiate contact removed 04/05/2022 09:57:33
Acceptable Voltage and Frequency Reached 04/05/2022 09:56:30
(VFSR)
Crank Terminate Reached 04/05/2022 09:56:25
Remote Initiate contact received 04/05/2022 09:54:03
Remote Initiate contact removed 04/05/2022 09:53:48
Remote Initiate contact received 04/05/2022 09:53:35
Package in Auto 04/05/2022 09:34:50
Engine Control Switch (ECS) in Auto Position 04/05/2022 09:34:50
Reset All Events Command Issued 04/05/2022 09:34:30
Engine Control Switch (ECS) in Stop Position 04/05/2022 09:34:24
Engine Not in Auto 04/05/2022 09:34:24
Package Not in Auto 04/05/2022 09:34:24
Remote Initiate contact removed 04/05/2022 09:29:21
Acceptable Voltage and Frequency Reached 04/05/2022 09:29:21
(VFSR)
Acceptable Voltage and Frequency Reached 04/05/2022 09:13:39
(VFSR)
Crank Terminate Reached 04/05/2022 09:13:34
Remote Initiate contact received 04/05/2022 09:11:08
Remote Initiate contact removed 03/05/2022 17:54:52
Acceptable Voltage and Frequency Reached 03/05/2022 09:12:40
(VFSR)
Crank Terminate Reached 03/05/2022 09:12:35
Remote Initiate contact received 03/05/2022 09:10:09
Remote Initiate contact removed 02/05/2022 17:26:47
Acceptable Voltage and Frequency Reached 02/05/2022 04:15:13
(VFSR)
Crank Terminate Reached 02/05/2022 04:15:08
Remote Initiate contact received 02/05/2022 04:12:44
Engine Control Switch (ECS) in Auto Position 02/05/2022 04:11:36
Package in Auto 02/05/2022 04:11:36
Reset All Events Command Issued 02/05/2022 04:11:19
Engine Not in Auto 02/05/2022 04:11:16
Engine Control Switch (ECS) in Stop Position 02/05/2022 04:11:16
Remote Initiate contact removed 02/05/2022 04:08:02
Package Not in Auto 02/05/2022 04:07:39
Acceptable Voltage and Frequency Reached 02/05/2022 04:07:29
(VFSR)
Crank Terminate Reached 02/05/2022 04:07:24
Remote Initiate contact received 02/05/2022 04:04:58
Remote Initiate contact removed 01/05/2022 13:10:46
Acceptable Voltage and Frequency Reached 01/05/2022 05:59:58
(VFSR)
Crank Terminate Reached 01/05/2022 05:59:53
Remote Initiate contact received 01/05/2022 05:57:28
Remote Initiate contact removed 30/04/2022 23:00:10
Acceptable Voltage and Frequency Reached 30/04/2022 23:00:10
(VFSR)
Acceptable Voltage and Frequency Reached 28/03/2022 15:40:22
(VFSR)
Crank Terminate Reached 28/03/2022 15:40:17
Remote Initiate contact received 28/03/2022 15:37:53
Remote Initiate contact removed 28/03/2022 15:25:41
Acceptable Voltage and Frequency Reached 22/03/2022 14:39:42
(VFSR)
Crank Terminate Reached 22/03/2022 14:39:36
Remote Initiate contact received 22/03/2022 14:37:12
Remote Initiate contact removed 22/03/2022 14:14:15
Acceptable Voltage and Frequency Reached 14/03/2022 15:54:43
(VFSR)
Crank Terminate Reached 14/03/2022 15:54:38
Remote Initiate contact received 14/03/2022 15:52:12
Remote Initiate contact removed 11/03/2022 20:13:44
Acceptable Voltage and Frequency Reached 09/03/2022 20:12:32
(VFSR)
Crank Terminate Reached 09/03/2022 20:12:27
Remote Initiate contact received 09/03/2022 20:10:01
Remote Initiate contact removed 09/03/2022 20:09:28
Remote Initiate contact received 09/03/2022 20:09:10
Remote Initiate contact removed 08/03/2022 15:39:03
Acceptable Voltage and Frequency Reached 08/03/2022 15:34:21
(VFSR)
Crank Terminate Reached 08/03/2022 15:34:15
Remote Initiate contact received 08/03/2022 15:31:46
Remote Initiate contact removed 08/03/2022 15:31:12
Remote Initiate contact received 08/03/2022 15:31:06
Engine Control Switch (ECS) in Auto Position 08/03/2022 14:53:04
Package in Auto 08/03/2022 14:53:04
Reset All Events Command Issued 08/03/2022 14:52:58
Engine Not in Auto 08/03/2022 14:52:56
Package Not in Auto 08/03/2022 14:52:56
Engine Control Switch (ECS) in Stop Position 08/03/2022 14:52:56
Engine Control Switch (ECS) in Auto Position 08/03/2022 14:52:45
Package in Auto 08/03/2022 14:52:45
Engine Control Switch (ECS) in Stop Position 08/03/2022 12:53:48
Engine Control Switch (ECS) in Run Position 08/03/2022 12:51:30
Engine Control Switch (ECS) in Stop Position 08/03/2022 12:50:08
Engine Not in Auto 08/03/2022 12:47:49
Package Not in Auto 08/03/2022 12:47:49
Engine Control Switch (ECS) in Run Position 08/03/2022 12:47:49
Remote Initiate contact removed 08/03/2022 12:21:00
Acceptable Voltage and Frequency Reached 08/03/2022 12:13:59
(VFSR)
Crank Terminate Reached 08/03/2022 12:13:54
Remote Initiate contact received 08/03/2022 12:11:26
Remote Initiate contact removed 04/03/2022 18:42:37
Acceptable Voltage and Frequency Reached 26/02/2022 13:10:21
(VFSR)
Crank Terminate Reached 26/02/2022 13:10:16
Remote Initiate contact received 26/02/2022 13:07:50
Remote Initiate contact removed 26/02/2022 02:15:32
Acceptable Voltage and Frequency Reached 26/02/2022 01:10:25
(VFSR)
Crank Terminate Reached 26/02/2022 01:10:19
Remote Initiate contact received 26/02/2022 01:07:55
Engine Control Switch (ECS) in Auto Position 25/02/2022 22:13:57
Package in Auto 25/02/2022 22:13:57
Reset All Events Command Issued 25/02/2022 22:13:53
Engine Not in Auto 25/02/2022 22:13:49
Engine Control Switch (ECS) in Stop Position 25/02/2022 22:13:49
Package Not in Auto 25/02/2022 21:27:00
Crank Terminate Reached 25/02/2022 21:27:00
Acceptable Voltage and Frequency Reached 25/02/2022 21:27:00
(VFSR)
Acceptable Voltage and Frequency Reached 25/02/2022 21:26:59
(VFSR)
Remote Initiate contact removed 25/02/2022 21:26:59
Acceptable Voltage and Frequency Reached 10/02/2022 11:33:10
(VFSR)
Crank Terminate Reached 10/02/2022 11:33:05
Remote Initiate contact received 10/02/2022 11:30:38
Remote Initiate contact removed 05/02/2022 15:01:38
Acceptable Voltage and Frequency Reached 02/02/2022 16:03:16
(VFSR)
Crank Terminate Reached 02/02/2022 16:03:11
Remote Initiate contact received 02/02/2022 16:00:43
Remote Initiate contact removed 27/01/2022 17:21:37
Acceptable Voltage and Frequency Reached 24/01/2022 19:32:45
(VFSR)
Crank Terminate Reached 24/01/2022 19:32:40
Remote Initiate contact received 24/01/2022 19:30:12
Remote Initiate contact removed 19/01/2022 16:26:58
Acceptable Voltage and Frequency Reached 19/01/2022 16:15:41
(VFSR)
Crank Terminate Reached 19/01/2022 16:15:36
Remote Initiate contact received 19/01/2022 16:13:10
Engine Control Switch (ECS) in Auto Position 19/01/2022 16:12:33
Package in Auto 19/01/2022 16:12:33
Reset All Events Command Issued 19/01/2022 16:12:21
Engine Control Switch (ECS) in Stop Position 19/01/2022 16:12:17
Engine Not in Auto 19/01/2022 16:12:17
Remote Initiate contact removed 19/01/2022 09:04:42
Package Not in Auto 19/01/2022 09:04:17
Acceptable Voltage and Frequency Reached 11/01/2022 14:12:17
(VFSR)
Crank Terminate Reached 11/01/2022 14:12:11
Remote Initiate contact received 11/01/2022 14:09:46
Remote Initiate contact removed 11/01/2022 07:30:47
Acceptable Voltage and Frequency Reached 11/01/2022 01:15:14
(VFSR)
Crank Terminate Reached 11/01/2022 01:15:09
Remote Initiate contact received 11/01/2022 01:12:42
Remote Initiate contact removed 08/01/2022 12:43:45
Acceptable Voltage and Frequency Reached 03/01/2022 14:09:43
(VFSR)
Crank Terminate Reached 03/01/2022 14:09:37
Remote Initiate contact received 03/01/2022 14:07:10
Remote Initiate contact removed 01/01/2022 02:20:24
Acceptable Voltage and Frequency Reached 31/12/2021 18:49:56
(VFSR)
Crank Terminate Reached 31/12/2021 18:49:51
Remote Initiate contact received 31/12/2021 18:47:21
Remote Initiate contact removed 16/12/2021 00:16:16
Acceptable Voltage and Frequency Reached 11/12/2021 07:37:29
(VFSR)
Crank Terminate Reached 11/12/2021 07:37:24
Remote Initiate contact received 11/12/2021 07:35:02
Engine Control Switch (ECS) in Auto Position 11/12/2021 07:32:57
Package in Auto 11/12/2021 07:32:57
Reset All Events Command Issued 11/12/2021 07:32:41
Engine Not in Auto 11/12/2021 07:32:35
Engine Control Switch (ECS) in Stop Position 11/12/2021 07:32:35
Remote Initiate contact removed 11/12/2021 07:15:46
Package Not in Auto 11/12/2021 07:15:21
Acceptable Voltage and Frequency Reached 26/11/2021 18:29:07
(VFSR)
Crank Terminate Reached 26/11/2021 18:29:02
Remote Initiate contact received 26/11/2021 18:26:37
Remote Initiate contact removed 26/11/2021 18:25:39
Remote Initiate contact received 26/11/2021 18:24:37
Remote Initiate contact removed 26/11/2021 17:01:28
Acceptable Voltage and Frequency Reached 13/11/2021 13:21:33
(VFSR)
Crank Terminate Reached 13/11/2021 13:21:28
Remote Initiate contact received 13/11/2021 13:19:04
Remote Initiate contact removed 13/11/2021 13:06:41
Acceptable Voltage and Frequency Reached 08/11/2021 22:10:34
(VFSR)
Crank Terminate Reached 08/11/2021 22:10:29
Remote Initiate contact received 08/11/2021 22:08:09
Engine Control Switch (ECS) in Auto Position 08/11/2021 22:07:36
Package in Auto 08/11/2021 22:07:36
Reset All Events Command Issued 08/11/2021 22:07:32
Engine Not in Auto 08/11/2021 22:07:27
Engine Control Switch (ECS) in Stop Position 08/11/2021 22:07:27
Engine Control Switch (ECS) in Auto Position 08/11/2021 22:06:42
Engine Not in Auto 08/11/2021 22:06:39
Engine Control Switch (ECS) in Stop Position 08/11/2021 22:06:39
Acceptable Voltage and Frequency Reached 08/11/2021 21:21:26
(VFSR)
Crank Terminate Reached 08/11/2021 21:21:26
Remote Initiate contact removed 08/11/2021 21:21:25
Package Not in Auto 08/11/2021 21:21:25
Acceptable Voltage and Frequency Reached 02/11/2021 16:29:36
(VFSR)
Crank Terminate Reached 02/11/2021 16:29:30
Remote Initiate contact received 02/11/2021 16:27:03
Remote Initiate contact removed 02/11/2021 16:19:56
Remote Initiate contact received 02/11/2021 16:17:39
Remote Initiate contact removed 02/11/2021 11:25:04
Acceptable Voltage and Frequency Reached 07/10/2021 16:15:40
(VFSR)
Crank Terminate Reached 07/10/2021 16:15:35
Remote Initiate contact received 07/10/2021 16:13:13
Remote Initiate contact removed 07/10/2021 16:08:28
Acceptable Voltage and Frequency Reached 07/10/2021 16:07:18
(VFSR)
Crank Terminate Reached 07/10/2021 16:07:13
Remote Initiate contact received 07/10/2021 16:06:56
Remote Initiate contact removed 07/10/2021 16:06:38
Remote Initiate contact received 07/10/2021 16:06:25
Remote Initiate contact removed 07/10/2021 16:06:16
Remote Initiate contact received 07/10/2021 16:06:09
Remote Initiate contact removed 07/10/2021 15:59:28
Acceptable Voltage and Frequency Reached 07/10/2021 15:57:23
(VFSR)
Crank Terminate Reached 07/10/2021 15:57:18
Remote Initiate contact received 07/10/2021 15:54:53
Remote Initiate contact removed 07/10/2021 15:30:56
Acceptable Voltage and Frequency Reached 24/08/2021 13:54:57
(VFSR)
Crank Terminate Reached 24/08/2021 13:54:52
Remote Initiate contact received 24/08/2021 13:52:28
Remote Initiate contact removed 24/08/2021 12:44:10
Acceptable Voltage and Frequency Reached 02/08/2021 18:40:26
(VFSR)
Crank Terminate Reached 02/08/2021 18:40:21
Remote Initiate contact received 02/08/2021 18:37:57
Remote Initiate contact removed 02/08/2021 18:05:04
Acceptable Voltage and Frequency Reached 02/08/2021 18:04:53
(VFSR)
Crank Terminate Reached 02/08/2021 18:04:47
Remote Initiate contact received 02/08/2021 18:02:23
Engine Control Switch (ECS) in Auto Position 02/08/2021 17:56:28
Package in Auto 02/08/2021 17:56:28
Engine Not in Auto 02/08/2021 17:44:16
Engine Control Switch (ECS) in Stop Position 02/08/2021 17:44:16
Package Not in Auto 02/08/2021 17:44:16
Remote Initiate contact removed 02/08/2021 17:43:11
Acceptable Voltage and Frequency Reached 02/08/2021 17:42:58
(VFSR)
Crank Terminate Reached 02/08/2021 17:42:53
Remote Initiate contact received 02/08/2021 17:40:28
Engine Control Switch (ECS) in Auto Position 02/08/2021 17:38:34
Package in Auto 02/08/2021 17:38:34
EMCP 4 Power Up Cycle Complete 02/08/2021 17:38:22
Engine Not in Auto 02/08/2021 17:38:21
Programmable Logic Feature (PLC) Disabled 02/08/2021 17:38:21
Package Not in Auto 02/08/2021 17:38:21
Engine Not in Auto 02/08/2021 17:37:30
Engine Control Switch (ECS) in Stop Position 02/08/2021 17:37:30
Package Not in Auto 02/08/2021 17:37:30
Remote Initiate contact removed 02/08/2021 16:25:39
Acceptable Voltage and Frequency Reached 02/08/2021 16:20:46
(VFSR)
Crank Terminate Reached 02/08/2021 16:20:41
Remote Initiate contact received 02/08/2021 16:18:17
Remote Initiate contact removed 02/08/2021 16:17:38
Remote Initiate contact received 02/08/2021 16:17:30
Engine Control Switch (ECS) in Auto Position 02/08/2021 16:16:39
Package in Auto 02/08/2021 16:16:39
Reset All Events Command Issued 02/08/2021 16:16:38
Engine Not in Auto 02/08/2021 16:16:37
Engine Control Switch (ECS) in Stop Position 02/08/2021 16:16:37
Remote Initiate contact removed 02/08/2021 15:53:56
Package Not in Auto 02/08/2021 15:53:30
Acceptable Voltage and Frequency Reached 02/08/2021 15:46:21
(VFSR)
Crank Terminate Reached 02/08/2021 15:46:16
Remote Initiate contact received 02/08/2021 15:43:55
Remote Initiate contact removed 02/08/2021 15:43:41
Remote Initiate contact received 02/08/2021 15:43:19
Engine Control Switch (ECS) in Auto Position 02/08/2021 15:42:25
Package in Auto 02/08/2021 15:42:25
Reset All Events Command Issued 02/08/2021 15:42:24
Engine Not in Auto 02/08/2021 15:42:22
Engine Control Switch (ECS) in Stop Position 02/08/2021 15:42:22
Remote Initiate contact removed 02/08/2021 15:37:13
Package Not in Auto 02/08/2021 15:36:45
Acceptable Voltage and Frequency Reached 02/08/2021 14:39:51
(VFSR)
Crank Terminate Reached 02/08/2021 14:39:46
Remote Initiate contact received 02/08/2021 14:37:21
Remote Initiate contact removed 02/08/2021 14:36:20
Remote Initiate contact received 02/08/2021 14:36:06
Engine Control Switch (ECS) in Auto Position 02/08/2021 14:22:47
Package in Auto 02/08/2021 14:22:47
Engine Not in Auto 02/08/2021 12:42:47
Engine Control Switch (ECS) in Stop Position 02/08/2021 12:42:47
Package Not in Auto 02/08/2021 12:42:47
Remote Initiate contact removed 02/08/2021 11:53:42
Acceptable Voltage and Frequency Reached 25/06/2021 14:10:55
(VFSR)
Crank Terminate Reached 25/06/2021 14:10:49
Remote Initiate contact received 25/06/2021 14:08:26
Remote Initiate contact removed 25/06/2021 14:07:47
Remote Initiate contact received 25/06/2021 14:07:43
Remote Initiate contact removed 25/06/2021 13:10:40
Acceptable Voltage and Frequency Reached 14/06/2021 12:30:05
(VFSR)
Crank Terminate Reached 14/06/2021 12:30:00
Remote Initiate contact received 14/06/2021 12:27:38
Remote Initiate contact removed 14/06/2021 12:11:26
Remote Initiate contact received 14/06/2021 12:11:16
Remote Initiate contact removed 14/06/2021 11:53:58
Acceptable Voltage and Frequency Reached 14/06/2021 11:38:14
(VFSR)
Crank Terminate Reached 14/06/2021 11:38:09
Remote Initiate contact received 14/06/2021 11:35:47
Remote Initiate contact removed 14/06/2021 11:15:24
Acceptable Voltage and Frequency Reached 14/06/2021 10:52:08
(VFSR)
Crank Terminate Reached 14/06/2021 10:52:03
Remote Initiate contact received 14/06/2021 10:49:35
Product Link Elite (GFP01229)
Parameter Value
Product ID GFP01229
Machine Serial Number
Equipment ID
ECM Part Number 4590786-04
ECM Serial Number 3199F508TR
Software Group Part Number 5697534-00
Software Group Release Date Nov2018
Software Group Description VIMS_TELEMATICS_2018_11_01
Application Software Part Number
Cellular Device ECM Serial Number 2839S110YN
Cellular Device ECM Hardware Part Number 5555510-03
Cellular Radio Module Software Part Number 5811997-00
Satellite Device ECM Serial Number NA
Satellite Device ECM Hardware Part Number NA
Satellite Radio Module Software Part Number NA

Logged Diagnostic Codes [Total Operating Hours = 10063 hours] - Product Link Elite (GFP01229)
Code Description Occ. First Last
1888- 3 Local GPS Antenna : Voltage Above Normal 1 2 2
4682- 3 Cellular Antenna : Voltage Above Normal 1 2 2

Logged Event Codes [Total Operating Hours = 10063 hours] - Product Link Elite (GFP01229)
Code Description Occ. First Last
No Logged
Event Codes

Active Diagnostic Codes - Product Link Elite (GFP01229)


Code Description
No Active
Diagnostic
Codes

Active Event Codes - Product Link Elite (GFP01229)


Code Description
No Active
Events

Current Totals - Product Link Elite (GFP01229)


Description Value Unit
Total Operating Hours 10063.2 hours
Total Distance 54.10 km

Configuration - Product Link Elite (GFP01229)


Description Value Unit
Product ID GFP01229
Equipment ID
External Service Lamp Installation Installed
Configuration
External Service Lamp Display Mode No Snapshot Notice
Setting
Telemetry Feature Installation Status Not Installed
Tire Monitoring System Installation Status Unavailable
CAT Data Link Module Identifier Gateway #1
Configuration
Machine Serial Number
Mining Aftermarket System Installation Unavailable
Status
Maintenance Mode Off
Machine Payload Control System Not Installed
Installation Status
Road Analysis System Installation Status Not Installed
Tire Analysis System Installation Status Not Installed
Tire Analysis System Temporary Not Installed
Installation Status
Tire Analysis System Temporary 15000 min
Installation Time Remaining
Security System Tamper Resistant Not Installed
Configuration

You might also like