Bulletin Numbers 500, 500F, 505, 509, 520
Selection Guide
NEMA Open Type Contactors and Starters Selection Guide
What’s Inside
Topic Page
2
Product Overview 3
Bulletin 500 Top-Wired Contactor 5
Bulletin 500F Feed-Through Contactor 9
Bulletin 509 Non-Reversing Starter 13
Bulletin 505 Reversing Starter 17
Bulletin 520 Multi-Speed Starter 19
Accessories and Renewal Parts 23
Specifications 27
Typical Wiring Diagrams 31
Approximate Dimensions 33
What’s New
Topic Page
Added Bulletin 505 and 520 starters. 17
Updated document for E100 overload relays. —
Added typical wiring diagrams. 31
Updated approximate dimension drawings. 33
Ordering Options
Depending on the type of open style contactor or starter that choose, you can decide which ordering method suits your needs best.
• Individual Components: You select individual catalog numbers of each component and accessory, to build up a contactor or starter.
• Modular Kits: You select one catalog number. This catalog number will include your selected accessories which are all shipped
together (unassembled), along with the base contactor or starter. This method saves lead time.
• Factory Assembled: You select one catalog string and the factory assembles your selected options and accessories to the contactor
or starter, before it gets shipped.
Product Comparison
Bulletin 500 top-wired contactors can be ordered as modular kits or individual components, as follows:
• Modular kit (sizes 0…4) (single catalog number, pre-stocked modular components shipped in one carton to reduce lead time)
• User assembled (sizes 0…4) (list of kitted components)
• Factory assembled (sizes 00 and 5) (single catalog number)
500 - B O D 930 - 17
a b c d e f
a c e
Bulletin Number Enclosure Type Number of Poles
Code Description Code Description Code Description
500 Top-wired contactor O No enclosure 930 Three power poles and one N.O. auxiliary contact
Top-wired contactor with
500DC 940 Four power poles and one N.O. auxiliary contact
DC coil voltage selected
d 950 Five power poles and one N.O. auxiliary contact
Nominal Coil Voltage
b Code Voltage Frequency f
220V 50 Hz
A
NEMA Size 240V 60 Hz Options
440V 50 Hz
B
Code Description 480V 60 Hz Code Description
550V 50 Hz
T 00 C 17 Surge suppressor for 120 or 240V AC coil
600V 60 Hz
110V 50 Hz
A 0 D 120V 60 Hz 90(2) One N.O. auxiliary contact
(1) DC coil voltages are only available for NEMA sizes 0…3. When ordering a DC coil voltage, add “DC” to the catalog number.
Example: 500DC-BOVL-930.
(2) Up to six combinations of auxiliary contacts can be selected. For example, Code 90011 indicates two N.O. contacts and two N.C. contacts.
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
DC(1) VL — — VG — — — VG — — — — — — —
(1) DC coil voltages are only available for NEMA sizes 0…3.When ordering a DC coil voltage, add “DC” to the catalog number.
Example: 500DC-BOVL-930.
Example: Catalog Number 500-COD930-17-90 includes a NEMA size 2, 3-pole contactor with a 120V AC coil, a surge suppressor, and one N.O. auxiliary contact.
Auxiliary Contact —
Base Contactor Coil Surge Suppressor Power Pole Top Wire Kit Load-side Terminal Shield
Contactor
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
DC(1) VL — — VG — — — VG — — — — — — —
(1) DC coil voltages are only available for NEMA sizes 0…3.When ordering a DC coil voltage, add “DC” to the catalog number.
Example: 500DC-FOVL-930.
Bulletin 500F feed-through contactors can be ordered as modular kits or individual components, as follows:
• Modular kit (sizes 0…4) (single catalog number, pre-stocked modular components shipped in one carton to reduce lead time)
• User assembled (sizes 0…4) (list of kitted components)
• Factory assembled (size 5) (single catalog number)
500F - B O D 930 - 17
a b c d e f
a c e
Bulletin Number Enclosure Type Number of Poles
Code Description Code Description Code Description
500F Feed-through contactor O No enclosure 930 Three power poles and one N.O. auxiliary contact
Feed-through contactor
500FC with DC voltage coil
d f
Nominal Coil Voltage Options
b Code Voltage Frequency Code Description
220V 50 Hz
NEMA Size A 17 Surge suppressor for 120 or 240V AC coil
240V 60 Hz
440V 50 Hz
Code Description B 480V 60 Hz 90(2) One N.O. auxiliary contact
550V 50 Hz
A 0 C 600V 60 Hz 91(2) One N.C. auxiliary contact
110V 50 Hz
B 1 D 120V 60 Hz
C 2 F 277V 60 Hz
D 3 H 208V 60 Hz
E 4 I 415V 50 Hz
F 5 J 24V 50/60 Hz
N 380V 50 Hz
VL(1) 24V DC —
VG(1) 125…250V DC —
(1) DC coil voltages are only available for NEMA sizes 0…3. When ordering a DC coil voltage, add “C” to the catalog number.
Example: 500FC-BOVL-930.
(2) Up to six combinations of auxiliary contacts can be selected. For example, Code 90011 indicates two N.O. contacts and two N.C. contacts.
(1) Includes a 120V AC coil and one N.O. auxiliary contact, as standard.
(2) The cat. nos. as listed are incomplete. Select a value from the Voltage Code table to complete each cat. no.
Example: To select a 120V AC coil voltage, Cat. No. 500F-AO930 becomes Cat. No. 500F-AOD930.
(3) See NEMA Size 5 on page 12 for NEMA size 5 contactors.
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
DC(1) VL — — VG — — — VG — — — — — — —
(1) DC coil voltages are only available for NEMA sizes 0…3.When ordering a DC coil voltage, add “C” to the catalog number.
Example: 500FC-BOVL-930.
Example: Catalog Number 500F-COD930-17-90 includes a NEMA size 2, 3-pole contactor with a 120V AC coil, a surge suppressor, and one N.O. auxiliary contact.
2 45 3 7.5 10 15 25 25 (3)
3 90 7.5 15 25 30 50 50 (3)
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
Bulletin 509 non-reversing starters can be ordered as modular kits or individual components, as follows:
• Modular kit (sizes 0…4) (single catalog number, pre-stocked modular components shipped in one carton to reduce lead time)
• Factory assembled (sizes 00 and 5) (single catalog number)
509 - B O D - A2E - 17
a b c d e f
a c e
Bulletin Number Enclosure Type Eutectic Overload Relay
Code Description Code Description Code Description
509 Non-reversing starter O No enclosure blank Eutectic alloy(3)
509DC Non-reversing starter with
DC coil voltage selected E100 Solid-state Overload Relay
d Code NEMA Size Full Load Current Adjustment Range [A]
Nominal Coil Voltage A2C 0, 1 0.2…1.0
b Code Voltage Frequency A2E 0, 1 1.0…5.0
220V 50 Hz
NEMA Size A A2F 0, 1 3.2…16
240V 60 Hz
440V 50 Hz
B A2G 0, 1, 2 5.4…27
Code Description 480V 60 Hz
550V 50 Hz
T 00 C A2J 1, 2 11…55
600V 60 Hz
110V 50 Hz
A 0 D A2L 3 20…100
120V 60 Hz
B 1 F 277V 60 Hz A2M 4 30…150
C 2 H 208V 60 Hz A2N 5 60…300
D 3 I 415V 50 Hz
E 4 J 24V 50/60 Hz f
F 5 N 380V 50 Hz Options
VG(1) 125…250V DC — Code Description
VL(1) 24V DC — 9 One N.O. auxiliary contact for use on Eutectic overload relay
9A One N.C. auxiliary contact for use on Eutectic overload relay
17 Surge suppressor for 120 or 240V AC coil
90(2) One N.O. auxiliary contact for use on starter
91(2) One N.C. auxiliary contact for use on starter
(1) DC coil voltages are only available for NEMA sizes 0…3. When ordering a DC coil voltage, add “DC” to the catalog number.
Example: 509DC-BOVL-A2E.
(2) Up to six combinations of auxiliary contacts can be selected. For example, Code 90011 indicates two N.O. contacts and two N.C. contacts.
(3) Starters with eutectic alloy overload relays require three heater elements. See Heater Elements Specifications Technical Data, publication 592-TD010, for heater element selection.
0 18 1 2 3 3 5 5 509-AO-✪
1 27 2 3 7.5 7.5 10 10 509-BO-✪
2 45 3 7.5 10 15 25 25 509-CO-✪
3 90 7.5 15 25 30 50 50 509-DO-✪
4 135 — — 40 50 75 100 509-EO-✪
5 270 — — 75 100 150 200 (4)
(1) The starters include a 120V AC coil and one N.O. auxiliary contact, as standard.
(2) NEMA sizes 0…3 can be wired for 3-phase or 1-phase applications, but 1-phase coil codes are no longer valid.
(3) The cat. nos. as listed are incomplete. Select a value from the Voltage Code table and a value from the Overload Relay Code table, to complete each cat. no.
Example: To select a 240V AC coil voltage with a E100 overload relay (1…5 A), Cat. No. 509-AO-✪ becomes Cat. No. 509-AOA-A2E.
(4) See NEMA Size 00 and 5 for NEMA size 00 and 5 starter product selection.
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
DC(1) VL — — VG — — — VG — — — — — — —
(1) DC coil voltages are only available for NEMA sizes 0…3.When ordering a DC coil voltage, add “DC” to the catalog number. Example: 509DC-BOVL.
Surge Suppressor
NEMA Size Description Cat. No.
12…120V AC 599-K04
0…5
240…264V AC Varistor 599-KA04
2 45 3 7.5 10 15 25 25 (3)
3 90 7.5 15 25 30 50 50 (3)
Voltage Code
Note: The base starter includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
Options
Code Description
9 One N.O. auxiliary contact for use on Eutectic overload relay
9A One N.C. auxiliary contact for use on Eutectic overload relay
17 Surge suppressor for 120 or 240V AC coil
90(1) One N.O. auxiliary contact
91(1) One N.C. auxiliary contact
(1) Up to six combinations of auxiliary contacts can be selected. For example, Code 90011 indicates two N.O. contacts and two N.C. contacts.
Example: Catalog Number 509-FOD-A2N-17-90 includes a NEMA size 5 starter with a 120V AC coil, E100 overload relay, a surge suppressor, and one N.O. auxiliary contact.
a c e
Bulletin Number Enclosure Type Overload Relay
Code Description Code Description Code Description
505 Reversing starter O No enclosure blank Eutectic alloy
Vertically-arranged
505V 23 no overload relay
reversing starter(1)
d E100 Plus Solid-state Overload Relay (3-phase)
b Nominal Coil Voltage Code NEMA Size Full Load Current Adjustment Range [A]
NEMA Size Code Voltage Frequency A2A 00 0.1…0.5
220V 50 Hz
Code Description A A2C 00, 0, 1 0.2…1.0
240V 60 Hz
440V 50 Hz
T 00 B A2E 00, 0, 1 1.0…50
480V 60 Hz
550V 50 Hz
A 0 C A2F 00, 0, 1 3.2…16
600V 60 Hz
110V 50 Hz
B 1 D A2G 0, 1, 2 5.4…27
120V 60 Hz
C 2 F 277V 60 Hz A2J 1, 2 11…55
D 3 H 208V 60 Hz A2L 3 20…100
E 4 I 415V 50 Hz A2M 4 30…150
F 5 J 24V 50/60 Hz A2N 5 60…300
N 380V 50 Hz
f
Options
Code Description
17 Surge suppressor for 120 or 240V AC coil
87A On-delay timer
87B Off-delay timer
90(2) One N.O. auxiliary contact for use on contactor
91(2) One N.C. auxiliary contact for use on contactor
97(3) One N.C.L.B. auxiliary contact for use on contactor
(1) Only available for NEMA sizes 0…5.
(2) Up to six combinations of auxiliary contacts can be selected. For example, Code 90011 indicates two N.O. contacts and two N.C. contacts.
(3) Up to three combinations of auxiliary contacts can be selected. For example, Code 977 indicates two N.C.L.B. contacts.
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
a c e
Bulletin Number Enclosure Type Overload Relay
Code Description Code Description Code Description
520G 2-speed constant horsepower starter O No enclosure blank Eutectic alloy
520F 2-speed constant/variable torque starter 23 no overload relay
520E 2-speed separate winding starter d E100 Solid-state Overload Relay
520V_(1) Vertically-arranged starter(2) Nominal Coil Voltage Code NEMA Size Full Load Current Adjustment Range [A]
Code Voltage Frequency A2C 0, 1 0.2…1.0
220V 50 Hz
b A 240V 60 Hz A2E 0, 1 1.0…5.0
Voltage Code
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24(1) 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
(1) When using 24V coils on sizes 4 or 5, an interposing relay may be required. For coil VA values, see AC Operating Coils on page 26.
Note: The base contactor includes a 120V AC coil as standard. For all other
Voltage Code voltages, an alternate coil will be included in the modular kit for field installation.
[V] 24(1) 110 120 125 208 220 240 250 277 380 415 440 480 550 600
AC, 50 Hz J D — — — — — — — —
AC, 60 Hz J — D — H — A — F — — — B — C
(1) When using 24V coils on sizes 4 or 5, an interposing relay may be required. For coil VA values, see AC Operating Coils on page 26.
Select two overload relay codes to complete the cat. no. The first code is for the
✪ Overload Relay Code high-speed overload relay and the second code is for the low-speed overload relay.
Notes:
Contactor Accessories
E100 Solid-State Overload Relay Mounting Bracket Terminal and Lug Covers
Description Cat. No. NEMA
Type Cat. No.
Size
0…1 599-TC01N
E100 overload relay mounting bracket kit 592-1EIKIT1 2 599-TC2N
Line-side terminal covers 3 599-TC3N
4 599-TC4N
5 599-TC5N
Coils(1) Line-side terminal covers
(reversing) 0…1 599-TC01R
(1) For a full list of available coils, see AC Operating Coils on page 26. 520F, 520G 599-PC01-5(1)
500, 500F, 505 599-PC2
Surge Suppressor 505, 509, 520E (2) 2 599-PS2(1)
520F, 520G 599-PC2-5(1)
Surge suppressors are made to be mounted directly across the coil
terminals of contactors and starters with 120V or 240V AC coils. The 500, 500F, 505 599-PC3
purpose of the suppressor is to limit voltage transients for 505, 509, 520E (2) 3 599-PS3(1)
applications requiring interface with solid-state components. 520F, 520G 599-PC3-5(1)
One suppressor is required per coil.
500, 500F, 505 599-PC4
NEMA
Type Voltage Range Size Cat. No. 505, 509, 520E (2) 4 599-PS4(1)
24…48V AC, 520F, 520G 599-PC4-5(1)
100-FSC48
50/60 Hz 500, 500F 599-PC5
110…280V AC, 5
RC module(1) 50/60 Hz 00 100-FSC280 509 599-PS5(1)
380…480V AC, (1) Eutectic alloy or solid-state overload relay.
100-FSC480
50/60 Hz
12…55V AC/
12…77V DC 100-FSV55
56…136V AC/ 100-FSV136
Varistor module 78…180V DC 00
137…277V AC/ 100-FSV277
181…350V DC
278…575V AC 100-FSV575
Surge suppressor 12…120V AC 599-K04
0…5
Varistor 240…264V AC 599-KA04
(1) For starters only.
A pneumatic timer attachment may be field installed in the space of The one N.O. and one N.C. power poles may be field added to all size
two adjacent auxiliary contact blocks. Timing units are available for 0…4 Bulletin 500 line contactors and starters. 2- and 3-pole
either ON-Delay or OFF-Delay operation with a timed set of one N.O. contactors will accept a maximum of two adder poles and 4-pole
and one N.C. snap-action contacts that are electrically isolated. devices will accept one adder pole. Each adder pole kit includes a
mechanical load balancer to be used when only one power pole is
Repetitive accuracy within the timer range is approximately ±10% added.
provided a minimum reset time of 75 ms is allowed.
When power poles are added to Size 2, 3, or 4 (2- or 3-pole devices)
Notes: the operating coil must be changed. Refer to the listing for the size
• Size 00: Timers can be mounted to the front of the contactor. of your contactor or starter. Order the operating coil listed for a
• Sizes 0…5: Timers can be added to the left- or right-hand 4-…5-pole device. (Coils can also be factory installed.)
side of the contactor body. Description NEMA Size Cat. No.
• Size 0, 1 and 2: Timers cannot be used on the same side as One N.O. 0…1 599-P01A
power pole adders. One N.O. 2 599-P2A
• Size 2: The operating coil must be changed. See AC Operating One N.O. 3 599-P3A
Coils on page 26 and refer to the size 2 operating coil listing. One N.O. 599-P4A
Order the coil listed for a 4-…5-pole device. (Coils can also be 4
factory installed.) One N.C. 599-P4B
Overload Accessories
Auxiliary Contact
Renewal Parts
AC Operating Coils
For use on size 00 (Series B) For use on size 00 (Series D) For use on sizes 0…5
Manual Reset (Eutectic Alloy) Overload Relay Single Pole Contact Kit — Sizes 00…5
Includes front and rear stationary contact, movable contact, and contact spring.
3-phase or 1-phase (3 elements) Size Part No.
Size Cat. No.
0(1) 40410-331-51
00 (Series B and D) 592-JOV16
0, 1 592-EUTB 1(1) 40410-331-52
4 599-P4A
Electrical Ratings
Service Maximum Transformer Primary Transformer Primary Maximum
Maximum
Continuous Limit Hp Rating Switching kVa Rating Switching kVa Rating Capacitor Circuit
Load Hp Rating Switching Closing Inrush
NEMA Voltage Current Current (Non-plugging and (Plugging and (Inrush Current (Inrush Current
Size Rating ≤ 20 times = 20 to 40 times kVAR (3) Current [A] Peak
Rating (1) non-jogging duty) jogging duty) (2) Continuous Current) Continuous Current) Including Offset
[V] [A] [A] 1 3 1 3 1 3 1 3 3 3
115 1/3 — 1/4 — — — — — —
200 — 1-1/2 — 1 — — — — —
230 1 1-1/2 1/2 1 — — — — —
00 9 11 87
380 — 1-1/2 — 1 — — — — —
460 — 2 — 1-1/2 — — — — —
575 — 2 — 1-1/2 — — — — —
115 1 — 1/2 — 0.6 — 0.3 — —
200 — 3 — 1-1/2 — 1.8 — 0.9 —
230 2 3 1 1-1/2 1.2 2.1 0.6 1 —
0 18 21 140
380 — 5 — 1-1/2 — — — — —
460 — 5 — 2 2.4 4.2 1.2 2.1 —
575 — 5 — 2 3 5.2 1.5 2.6 —
115 2 — 1 — 1.2 — 0.6 — —
200 — 7-1/2 — 3 — 3.6 — 1.8 —
230 3 7-1/2 2 3 2.4 4.3 1.2 2.1 6
1 27 32 288
380 — 10 — 5 — — — — —
460 — 10 — 5 4.9 8.5 2.5 4.3 13.5
575 — 10 — 5 6.2 11 3.1 5.3 17
115 3 — 1-1/2 — — — — — — —
1P 36 42
230 5 — 3 — — — — — — —
115 3 — 2 — 2.1 — 1 — —
200 — 10 — 7-1/2 — 6.3 — 3.1 —
230 7-1/2 15 5 10 4.1 7.2 2.1 3.6 12
2 45 52 483
380 — 25 — 15 — — — — —
460 — 25 — 15 8.3 14 4.2 7.2 25
575 — 25 — 15 10 18 5.2 8.9 31
115 7-1/2 — 7-1/2 — 4.1 — 2 — —
200 — 25 — 15 — 12 — 6.1 —
230 15 30 15 20 8.1 14 4.1 7.0 27
3 90 104 947
380 — 50 — 30 — — — — —
460 — 50 — 30 16 28 8.1 14 53
575 — 50 — 30 20 35 10 18 67
115 — — — — 6.8 — 3.4 — —
200 — 40 — 25 — 20 — 10 —
230 — 50 — 30 14 23 6.8 12 40
4 135 156 1581
380 — 75 — 50 — — — — —
460 — 100 — 60 27 47 14 23 80
575 — 100 — 60 34 59 17 29 100
115 — — — — 14 — 6.8 — —
200 — 75 — 60 — 41 — 20 —
230 — 100 — 75 27 47 14 24 80
5 270 311 3163
380 — 150 — 125 — — — — —
460 — 200 — 150 54 94 27 47 160
575 — 200 — 150 68 117 34 59 200
(1) Service-Limit Current Ratings — The service-limit current ratings that are shown represent the maximum rms current, in amperes, which the controller shall be permitted to carry for
protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its continuous current
rating. The current rating of overload relays or the trip current of other motor protective devices that are used shall not exceed the service-limit current rating of the controller.
(2) Plugging or Jogging Service — The listed horsepower ratings are recommended for those applications requiring repeated interruption of stalled motor current that is encountered in rapid
motor reversal in excess of five openings or closings per minute and shall not be more than ten in a ten minute period.
(3) If maximum available current (at capacitor terminals) is greater than 3000 A, contact your local Rockwell Automation sales office, Allen-Bradley distributor, or NEMA ICS-2 Standard.
Mechanical Ratings
NEMA Mechanical Life Maximum Number of Operating Time [ms]
Size (Millions of Operations) Auxiliary Contacts Pick-up (Average) Drop-out (Average)
00 10 5 20 16
0 10 8 21 16
1 10 8 22 14
2 10 8 27 13
3 5 8 37 20
4 5 8 27 20
5 5 8 25 18
Construction
Required Torque on Contact Material
NEMA Wire Size for Power Terminal Wire Type of Power Requirements for
Size Power Terminals Clamps and Pressure Terminal Power Contacts Auxiliary Contacts Sizing of Wire
Connectors or Lugs
00 #16…10 AWG 9 lb•in Pressure terminals
0 #14…10 AWG 20 lb•in
Saddle or wire clamps All wire rated 167 °F
1 #14…8 AWG 20 lb•in
(75 °C) or higher must
2 #14…4 AWG 45 lb•in Silver alloy Silver be sized per the local
3 #8…1/0 AWG 150 lb•in Electrical Code for
Pressure terminals
4 #6…4/0 AWG 275 lb•in 167 °F (75 °C) wire.
5 #4 AWG…500 MCM 375 lb•in
Environmental
NEMA Operating Operating Corrosion-
Altitude
Size Position Temperature Range Resistance
00 Horizontal Starters with eutectic alloy
0 Overload relay
1 –13…+149 °F (–25…+65 °C)
All metal parts are treated for
2 10 000 feet before derating
Vertical Starters with SMP™ Overload relay corrosion-resistance
3 –13…+131 °F (–25…+55 °C)
4
5 (provided condensation is prevented)
AC Coil Data
Operating Volt Amperes Burden [VA]
NEMA Size 60 Hz Coils Heat Dissipation [W] Coil Operating Limits
Inrush Sealed
00 70 8 2.7
0 192 29 5.9
1 & 1P 192 29 5.9
2 (2…3 poles) 240 29 5.9
2 (4…5 poles) 315 38 5.9
85…110%
3 (2…3 poles) 660 45 10
3 (4…5 poles) 840 58 10
4 (2…3 poles) 1225 69 14.8
4 (4…5 poles) 1490 96 14.8
5 (Series L) 1490 96 19.8
Load-life Curves
Bulletin 500 Line contactors and starters are designed to provide high performance in various applications. These load-life curves are based
on Rockwell Automation tests according to the requirements defined in IEC 947-4. Actual contact life may vary based on the application, duty
cycle, and environmental conditions from that indicated by the curves.
To find the contactor’s estimated electrical life, follow these guidelines:
• Choose the appropriate graph that most closely approximates the utilization category of the application.
• Locate the intersection of the life-load curve of the appropriate contactor with the application’s operational current (Ie) found on the
horizontal axis.
• Read the estimated contact life in millions of operations along the vertical axis.
In many applications, the utilization category cannot be defined as either purely AC3 or AC4. In those applications, the electrical life of the
contactor can be estimated from the following equation:
L AC3
L mixed =
(
L
1 + PAC4 AC3 – 1
L AC4 )
Where:
L mixed= Approximate contact life for a mixed AC3/AC4 utilization category application
L AC3= Approximate contact life in operations for AC3 utilization category (from AC3 life-load curves below)
L AC4= Approximate contact life in operations for AC4 utilization category (from AC4 life-load curves below)
P AC4= Percentage of AC4 operations
Utilization Categories
10M
10M
8M
AC3
8M
AC4
6M
6M
4M
4M
2M
2M
1M 1M
800K 800K
OPERATING CYCLES
OPERATING CYCLES
600K 600K
400K 400K
200K 200K
100K 100K
80K 80K
60K 60K
40K 40K
20K 20K
10K 10K
Bulletin 505 Reversing Starter with Eutectic Bulletin 505 Reversing Starter without
Alloy or Solid-state Overload Relay Overload Relay
L1 L2 L3
Control
Circuit B
A
Fuses
(When Used)
Forward
Reverse D 7 3
Stop F
5 2
3-Wire Control REV FOR
6
5
R
4 3 E
R F
Limit Switches
(When Used)
B L1 L2 L3
Control B
Circuit A
A
Control Fuses
Circuit (When Used)
Fuses Start
(When Used)
1 3
5 6 3-Wire Control
REV (Momentary Contact)
X 4 3 2
Stop
O.L.
T1 T2 T3
7 3
5 2
Motor
FOR
Separate Control Circuit — When the controller coils are to operate
on a voltage other than line voltage, check coil rating for
O.L. compatibility and change coils if necessary. Disconnect wires A and
B from lines L1 and L2. Connect wires A and B to the separate
T1 T2 T3 control source. Refer to local Electrical Code for control circuit
disconnection requirements
L1 L2 L3 L1 L2 L3
A
B
Control Control
Circuit Circuit
Fuses Fuses
(When Used) (When Used)
3 4
HIGH L LOW
3 4 6 5
HIGH L LOW 2
5
2 6 5 H
Bulletin 520E
2-Speed 5 Bulletin 520F 3 7
Separate Winding H 2-Speed
Consequent Pole OL OL OL OL OL OL
3 7
T6 T4 T5 T1 T2 T3
OL OL OL OL OL OL
T11 T12 T13 T1 T2 T3
T4 T4
Motor Terminal Markings T1 T1
T3 T3
T12 T2
T5 T2 T6 T5 T2 T6
Constant Torque Variable Torque
T11 T13 T1 T3
HIGH LOW
L1 L2 L3
Control
Circuit
Fuses
(When Used)
7 3
LOW H HIGH
5 2
5 Motor Terminal Markings
6
L T4 Constant
4 3
Horsepower
T3 T1
Bulletin 520G OL OL OL OL OL OL
2-Speed T5 T6
T2
Consequent Pole T1 T2 T3 T6 T4 T5
D
B
E
A C
Size 00
Sizes 5…9
B
D
E 5/16 Reset
(7.9) Travel
11/64 (4.4) Dia.
Mtg. Holes EE
Size 00 with Eutectic Alloy Overload Relay
B
D
11 Reset
32 Travel
(8.7)
E C
Sizes 0…5
Bulletin 509 Non-reversing Starters with E100 Solid-state Overload Relay — NEMA Size 2
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 509 Non-reversing Starters with E100 Solid-state Overload Relay — NEMA Size 3
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 509 Non-reversing Starters with E100 Solid-state Overload Relay — NEMA Size 4
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
[165.1]
[47.6]
[23.0] [54.8] [198.4]
[250.0]
[275.4]
[380.2]
[419.1] [401.6]
[37.3]
[8.7]
[81.0] [81.0]
[44.4] [199.2]
[160.3]
[187.3]
Bulletin 509 Non-reversing Starters with E100 Solid-state Overload Relay — NEMA Size 5
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
[165.1]
[47.6]
[54.8]
[23.0] [194.5]
[275.4] [250.0]
[380.2] [401.6]
[429.4]
[37.3]
[8.7]
[81.0] [81.0]
[44.4] [204.8]
[160.3]
[187.3]
Bulletin 505 Reversing Starters with and without Eutectic Overload Relay
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.
F G
A
B
D
11/32
(8.70) Reset
Travel
E C
Bulletin 505 Reversing Starters with E100 Solid-state Overload Relay — NEMA Sizes 0…1
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 505 Reversing Starters with E100 Solid-state Overload Relay — NEMA Size 2
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 505 Reversing Starters with E100 Solid-state Overload Relay — NEMA Size 3
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 505 Reversing Starters with E100 Solid-state Overload Relay — NEMA Size 4
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 505 Reversing Starters with E100 Solid-state Overload Relay — NEMA Size 5
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
H 8.70
J E
(11/32)
Travel
Bulletin 520E Multi-speed Starters with E100 Solid-state Overload Relay — NEMA Size 1
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 520E Multi-speed Starters with E100 Solid-state Overload Relay — NEMA Size 2
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 520E Multi-speed Starters with E100 Solid-state Overload Relay — NEMA Size 3
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 520E Multi-speed Starters with E100 Solid-state Overload Relay — NEMA Size 4
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Bulletin 520E Multi-speed Starters with E100 Solid-state Overload Relay — NEMA Size 5
Approximate dimensions are shown in inches [millimeters]. Dimensions are not intended for manufacturing purposes.
Notes:
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation. You can view or download
publications at rok.auto/literature.
Resource Description
Pump Panel Specifications, publication 1232-TD001 Provides specifications for Bulletin 1232 and 1233 pump panels.
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, ENET-UM006 network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
UL Standards Listing for Industrial Control Products, Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure
publication CMPNTS-SR002 that they conform to the requirements of Underwriters Laboratories.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
Allen-Bradley, expanding human possibility, ProposalWorks, Rockwell Automation, and SMP are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur