You are on page 1of 162

CL 600 x1

Project: New Project

Submitted by:

Phone Mobile/Office:
E-mail:
Date: 14/02/2022

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 2

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Media Interface
2 Part list
2.1 Channels
2.2 Base Connectors
2.3 System Connectors
2.4 Accessories
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 3

1 Geometry and Application

Modular Support Spacing


Main Support Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used?

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 4

1.1 Supports

Support No. Orientation Thickness [mm] Concrete grade


1 - - C20/25
2 - - C20/25

Support No. Orientation Profile Steel grade Rotation


-

1.2 Nodes

Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
3 -700.00 0.00 0.00 Base 1 HST3 M10x90 30/10 HST3 M10 (C)
4 -300.00 0.00 0.00 Base 2 HST3 M10x90 30/10 HST3 M10 (C)

1.3 Members

Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2268498 MT-30 1 2 - - 90.00

1.4 Media Interface

No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 5

2 Part list

2.1 Channels

Quantity Description Item No. Weight [kg] Length [mm] Member No.
1 I.-Channel MT-30 2268498 1.04 700.00 1

2.2 Base Connectors

Quantity Description Item No. Weight [kg] Node


2 HST3 M10x90 30/10 2105712 - 3,4

2.3 System Connectors

Quantity Description Item No. Weight [kg] Node

2.4 Accessories

Quantity Description Item No. Weight [kg] Length [mm]


2 Safety stud anchor HST3 M10x90 30/10 2105712 0.00 0.00
2 Washer 12 13x24x2,5 Zn ISO7089 200HV 2184512 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 6

3 Load Types

3. Loads

3.1 Loading objects

Allowable Intermediate Actual


No. Description Size [mm] Waterfilled Insulation
spacing [mm] Supports Spacing [mm]
1 Custom Point load - - - - - -
2 Custom Point load - - - - - -

3.2 Point Loads

No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
2 Design 1 50.00 0.00 0.00 -1.25 0.00 0.00 0.00
3 Design 1 650.00 0.00 0.00 -1.25 0.00 0.00 0.00
4 Self Weight Support 1 150.00 0.00 0.00 -0.00 0.00 0.00 0.00
5 Self Weight Support 1 550.00 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
6 Self Weight Support 1 0.00 700.00 0.00 0.00 -0.01 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 7

4 Load Combinations

Design base: Eurocode 1993

Load combination design base: Eurocode 1990

4.1 Ultimate Limit State

Design base: Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 8

5 Results
5.1 Calculation summary

5.1.1 Members

No Members ULS SLS Status


1 MT-30 48.35% - OK

5.1.2 Base Connectors

No Base ULS Status


3 HST3 M10x90 30/10 0.00% - OK
4 HST3 M10x90 30/10 0.00% - OK

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 9

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-30 Members: 1
5.2.1.1.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 180.00 1.49 12099.27 -1004.46 51923.41
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
162.57 81.28 -1004.46 -2443.33 1104.21 2443.24

5.2.1.1.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
S250GD 1.0242 290.00 210000.00 80769.00 1.10 1.10 1.10

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Member No. Type Load Combination: σ[N/mm²] τ[N/mm²]σeqv[N/mm²]σ[N/mm²]limitτ[N/mm²]limitUtilization


1 MT-30 1.35 * LC1 + 1.00 * LC7 51.25 -69.79 121.14 263.64 152.21 45.95%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 10

5.2.2.2.2 Governing Member Loading

Beam No. 1

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 50.00(-) kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 50.00(+) kN/kNm 0.00 1.25 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 140.00 kN/kNm 0.00 1.25 0.00 0.00 0.00 -0.11
1.35 * LC1 + 1.00 * LC7 150.00(-) kN/kNm 0.00 1.25 0.00 0.00 0.00 -0.13
1.35 * LC1 + 1.00 * LC7 150.00(+) kN/kNm 0.00 -0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 280.00 kN/kNm 0.00 -0.00 0.00 0.00 0.00 0.00
1.35 * LC1 + 1.00 * LC7 420.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 0.00
1.35 * LC1 + 1.00 * LC7 550.00(-) kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 550.00(+) kN/kNm 0.00 -1.25 0.00 0.00 0.00 -0.13
1.35 * LC1 + 1.00 * LC7 560.00 kN/kNm 0.00 -1.25 0.00 0.00 0.00 -0.11
1.35 * LC1 + 1.00 * LC7 650.00(-) kN/kNm 0.00 -1.25 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 650.00(+) kN/kNm 0.00 -0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 700.00 kN/kNm 0.00 -0.00 0.00 0.00 0.00 -0.00

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 11

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 12

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 13

Moment around Z

5.2.3 Stability Analysis

Buckling ratio

Max. lateral torsional


Set Max. buckling under
Length [mm] Buckling Length [mm] Buckling ratio buckling under Max. interaction
No. compression
bending
1 700.00 1400.00 2.00 48.35% 0.00% 48.35%

5.2.4 Deflection Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 14

The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.

Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview

Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 700.00 L/200 -0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 15

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 16

5.3 System Connectors


5.3 Connectors

5.3.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 17

5.4 Base Connectors


5.4 Bases

5.4.1Overview

Base 3 - HST3 M10x90 30/10 Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]
Local Forces: 0.00 -0.00 -0.00 0.00 0.00 -0.00
Resistance: 0.00 0.00 0.00 0.00 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: -5000000000000000.00 % OK

Governing Load
1.00 * LC1
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 600 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 18

6 Remarks, Your Cooperation Duties

Warning messages for manual adjustment of sets of members


The reference length and/or buckling ratio for the stability evaluation in this project was manually adjusted by the user.

Warning messages for manual adjustment of sets of members


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by the user.

General design note


Buckling and LTB checks must always be controlled separately by the responsible designer engineer.
Channel design computation is carried out by the calculation engine from the RSTAB 8.04.0131.84645 framework software by Dlubal, analogous to the
elastic-elastic method inconformance with EC/DIN 18800 for Europe, AISIS100 for the US and SP 16. 13330 for Russia. The connector design method is
based on a combination of serval calculation models following:
for Europe the principles of either DIN 18800 or EC3 and tests carried out by an independent institute (HTL Rankweil, Austria)
for US the principles of AISC360 13th Edition and tests carried out an independent institute (HTL Rankweil, Austria)
for Russia the principles of SP16. 13330 and tests carried out an independent institute (HTL Rankweil, Austria)
XBT threaded bolts and pipe fittings must be calculated separately according to the manual.
Local stress and deformation of members at places where load is manually entered is not considered.
Relative deflection evaluation and stability checks: For the relative deflection evaluation and stability checks PROFIS Installation uses a reference length
based on a set of members. A member is a connection form one node to the next on a beam. Members can be connected to a set of members if the
nodes in between do not reduce the reference length. Tis connection of members to a set of members is done automatically based on the assumption
that a node with very low global displacement is eithera support or can be regarded as a support. The global displacement limit to define a node as a
support is 0.1 mm for relative deflection evaluation and 0.005 for stability checks. The connection of members to a set of members can also be done by
the user. The user can also decide manually if a set of members is a single-/multispan beam or a cantilever. The buckling ratio can also be manually
changed. The user can finally also decide to exclude a set of members from the relative deflection evaluation. In case of any manual adjustment you will
find a remark in the report.
The static analysis performed on the basis of a stationary system. 2nd - Order analysis due to possible eccentricities or deflections in the design
(deformation according to DIN 18800 or EC 3 for Europe, ASCE7-05 for the US and SP 20. 13330 for Russia) must be considered separately by the
appropriate personnel.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 18
CL 900 x1

Project: New Project

Submitted by:

Phone Mobile/Office:
E-mail:
Date: 14/02/2022

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 2

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Media Interface
2 Part list
2.1 Channels
2.2 Base Connectors
2.3 System Connectors
2.4 Accessories
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 3

1 Geometry and Application

Modular Support Spacing


Main Support Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used?

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 4

1.1 Supports

Support No. Orientation Thickness [mm] Concrete grade


1 - - C20/25
2 - - C20/25

Support No. Orientation Profile Steel grade Rotation


-

1.2 Nodes

Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
3 -800.00 0.00 0.00 Base 1 HST3 M10x90 30/10 HST3 M10 (C)
4 -200.00 0.00 0.00 Base 2 HST3 M10x90 30/10 HST3 M10 (C)

1.3 Members

Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2268498 MT-30 1 2 - - 90.00

1.4 Media Interface

No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 5

2 Part list

2.1 Channels

Quantity Description Item No. Weight [kg] Length [mm] Member No.
1 I.-Channel MT-30 2268498 1.49 1000.00 1

2.2 Base Connectors

Quantity Description Item No. Weight [kg] Node


2 HST3 M10x90 30/10 2105712 - 3,4

2.3 System Connectors

Quantity Description Item No. Weight [kg] Node

2.4 Accessories

Quantity Description Item No. Weight [kg] Length [mm]


2 Safety stud anchor HST3 M10x90 30/10 2105712 0.00 0.00
2 Washer 12 13x24x2,5 Zn ISO7089 200HV 2184512 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 6

3 Load Types

3. Loads

3.1 Loading objects

Allowable Intermediate Actual


No. Description Size [mm] Waterfilled Insulation
spacing [mm] Supports Spacing [mm]
1 Custom Point load - - - - - -
2 Custom Point load - - - - - -

3.2 Point Loads

No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 1 950.00 0.00 0.00 -1.78 0.00 0.00 0.00
2 Design 1 50.00 0.00 0.00 -1.78 0.00 0.00 0.00
3 Self Weight Support 1 200.00 0.00 0.00 -0.00 0.00 0.00 0.00
4 Self Weight Support 1 800.00 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
5 Self Weight Support 1 0.00 1000.00 0.00 0.00 -0.01 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 7

4 Load Combinations

Design base: Eurocode 1993

Load combination design base: Eurocode 1990

4.1 Ultimate Limit State

Design base: Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 8

5 Results
5.1 Calculation summary

5.1.1 Members

No Members ULS SLS Status


1 MT-30 68.84% - OK

5.1.2 Base Connectors

No Base ULS Status


3 HST3 M10x90 30/10 0.00% - OK
4 HST3 M10x90 30/10 0.00% - OK

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 9

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-30 Members: 1
5.2.1.1.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 180.00 1.49 12099.27 -1004.46 51923.41
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
162.57 81.28 -1004.46 -2443.33 1104.21 2443.24

5.2.1.1.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
S250GD 1.0242 290.00 210000.00 80769.00 1.10 1.10 1.10

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Member No. Type Load Combination: σ[N/mm²] τ[N/mm²]σeqv[N/mm²]σ[N/mm²]limitτ[N/mm²]limitUtilization


1 MT-30 1.35 * LC1 + 1.00 * LC7 109.45 -99.36 175.95 263.64 152.21 66.74%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 10

5.2.2.2.2 Governing Member Loading

Beam No. 1

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 50.00(-) kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 50.00(+) kN/kNm 0.00 1.78 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 200.00 kN/kNm 0.00 1.78 0.00 0.00 0.00 -0.27
1.35 * LC1 + 1.00 * LC7 200.00(+) kN/kNm 0.00 -0.01 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 400.00 kN/kNm 0.00 -0.00 0.00 0.00 0.00 0.00
1.35 * LC1 + 1.00 * LC7 600.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 0.00
1.35 * LC1 + 1.00 * LC7 800.00 kN/kNm 0.00 0.01 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 800.00(+) kN/kNm 0.00 -1.78 0.00 0.00 0.00 -0.27
1.35 * LC1 + 1.00 * LC7 1000.00 kN/kNm 0.00 -0.00 0.00 0.00 0.00 -0.00

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 11

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 12

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 13

5.2.3 Stability Analysis

Buckling ratio

Max. lateral torsional


Set Max. buckling under
Length [mm] Buckling Length [mm] Buckling ratio buckling under Max. interaction
No. compression
bending
1 1000.00 2000.00 2.00 68.84% 0.00% 68.84%

5.2.4 Deflection Analysis


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.

Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 14

Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 1000.00 L/200 0.00 0.00

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 15

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 16

5.3 System Connectors


5.3 Connectors

5.3.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 17

5.4 Base Connectors


5.4 Bases

5.4.1Overview

Base 3 - HST3 M10x90 30/10 Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]
Local Forces: 0.00 -0.01 -0.00 0.00 0.00 -0.00
Resistance: 0.00 0.00 0.00 0.00 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: -8000000000000000.00 % OK

Governing Load
1.00 * LC1
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 18
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 x1
Phone Mobile/Office: Date: 14/02/2022
E-mail: Page: 18

6 Remarks, Your Cooperation Duties

Warning messages for manual adjustment of sets of members


The reference length and/or buckling ratio for the stability evaluation in this project was manually adjusted by the user.

Warning messages for manual adjustment of sets of members


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by the user.
General design note
Buckling and LTB checks must always be controlled separately by the responsible designer engineer.
Channel design computation is carried out by the calculation engine from the RSTAB 8.04.0131.84645 framework software by Dlubal, analogous to the
elastic-elastic method inconformance with EC/DIN 18800 for Europe, AISIS100 for the US and SP 16. 13330 for Russia. The connector design method is
based on a combination of serval calculation models following:
for Europe the principles of either DIN 18800 or EC3 and tests carried out by an independent institute (HTL Rankweil, Austria)
for US the principles of AISC360 13th Edition and tests carried out an independent institute (HTL Rankweil, Austria)
for Russia the principles of SP16. 13330 and tests carried out an independent institute (HTL Rankweil, Austria)
XBT threaded bolts and pipe fittings must be calculated separately according to the manual.
Local stress and deformation of members at places where load is manually entered is not considered.
Relative deflection evaluation and stability checks: For the relative deflection evaluation and stability checks PROFIS Installation uses a reference length
based on a set of members. A member is a connection form one node to the next on a beam. Members can be connected to a set of members if the
nodes in between do not reduce the reference length. Tis connection of members to a set of members is done automatically based on the assumption
that a node with very low global displacement is eithera support or can be regarded as a support. The global displacement limit to define a node as a
support is 0.1 mm for relative deflection evaluation and 0.005 for stability checks. The connection of members to a set of members can also be done by
the user. The user can also decide manually if a set of members is a single-/multispan beam or a cantilever. The buckling ratio can also be manually
changed. The user can finally also decide to exclude a set of members from the relative deflection evaluation. In case of any manual adjustment you will
find a remark in the report.
The static analysis performed on the basis of a stationary system. 2nd - Order analysis due to possible eccentricities or deflections in the design
(deformation according to DIN 18800 or EC 3 for Europe, ASCE7-05 for the US and SP 20. 13330 for Russia) must be considered separately by the
appropriate personnel.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 18
double on concrete 900

Project: solimasn alhabib hospital CL


shaft

Submitted by:

Phone Mobile/Office:
E-mail:
Date: 10/03/2022

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 2

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Media Interface
2 Part list
2.1 Channels
2.2 Base Connectors
2.3 System Connectors
2.4 Accessories
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 3

1 Geometry and Application

Modular Support Spacing


Main Support Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used?

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 4

1.1 Supports

Support No. Orientation Thickness [mm] Concrete grade


1 Vertical 300.00 C20/25
2 Vertical 300.00 C20/25

Support No. Orientation Profile Steel grade Rotation


-

1.2 Nodes

Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
1 -2700.00 0.00 2750.00 Base 1 MT-BR-40 450 OC MT-BR-40 450 OC (C)
3 -2700.00 1100.00 2750.00 Base 2 MT-BR-40 450 OC MT-BR-40 450 OC (C)
5 -2400.00 0.00 2750.00 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
6 -2400.00 1100.00 2750.00 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)

1.3 Members

Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2271445 MT-40 1 2 - - 0.00
2 2271445 MT-40 3 4 - - 0.00
3 2268508 MT-40 5 6 1 2 90.00

1.4 Media Interface

No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 5

2 Part list

2.1 Channels

Quantity Description Item No. Weight [kg] Length [mm] Member No.
2 Bracket MT-BR-40 450 OC 2271445 2.69 400.00 1, 2
1 I.-Channel MT-40 OC 2268508 2.36 1157.50 3

2.2 Base Connectors

Quantity Description Item No. Weight [kg] Node


2 MT-BR-40 450 OC 2271445 - 1,3

2.3 System Connectors

Quantity Description Item No. Weight [kg] Node


2 Connector MT-CC-40/50 OC 2322391 - 5,6

2.4 Accessories

Quantity Description Item No. Weight [kg] Length [mm]


4 Safety stud anchor HST3-R M12x115 40/20 2105870 0.00 0.00
6 Hexagon Bolt MT-TLB OC 2273256 0.00 0.00
6 Twist-Lock MT-TL M10 OC 2272082 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 6

3 Load Types

3. Loads

3.1 Loading objects

Allowable Intermediate Actual


No. Description Size [mm] Waterfilled Insulation
spacing [mm] Supports Spacing [mm]
1 Custom Point load - - - - - -
2 Custom Point load - - - - - -

3.2 Point Loads

No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 3 100.00 0.00 0.00 -1.62 0.00 0.00 0.00
2 Design 3 1000.00 0.00 0.00 -1.62 0.00 0.00 0.00
3 Self Weight Support 1 300.00 0.00 0.00 -0.00 0.00 0.00 0.00
4 Self Weight Support 2 300.00 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
5 Self Weight Support 1 0.00 400.00 0.00 0.00 -0.04 0.00 0.00 0.00
6 Self Weight Support 2 0.00 400.00 0.00 0.00 -0.04 0.00 0.00 0.00
7 Self Weight Support 3 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 7

4 Load Combinations

Design base: Eurocode 1993

Load combination design base: Eurocode 1990

4.1 Ultimate Limit State

Design base: Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 8

5 Results
5.1 Calculation summary

5.1.1 Members

No Members ULS SLS Status


1 MT-40 72.46% - OK

5.1.2 Base Connectors

No Base ULS Status


1 MT-BR-40 450 OC 75.12% - OK
3 MT-BR-40 450 OC 75.12% - OK

5.1.3 System Connectors

No System Connectors ULS Status


5 MT-CC-40/50 OC 21.80% - OK
6 MT-CC-40/50 OC 21.80% - OK

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 9

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 2
5.2.1.1.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 214.00 6.74 57717.48 -2652.65 65876.44
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
259.85 129.92 -2652.65 -3099.95 2782.31 3099.77

5.2.1.1.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
Steel Q235 A | GB/T
284.10 210000.00 80769.00 1.10 1.10 1.10
700-2006

5.2.1.2 MT-40 Members: 3


5.2.1.2.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 214.00 2.04 57717.48 -2652.65 65876.44
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
259.85 129.92 -2652.65 -3099.95 2782.31 3099.77

5.2.1.2.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
Steel S 280 GD 305.00 210000.00 80769.00 1.10 1.10 1.10

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 10

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Member No. Type Load Combination: σ[N/mm²] τ[N/mm²]σeqv[N/mm²]σ[N/mm²]limitτ[N/mm²]limitUtilization


1 MT-40 1.35 * LC1 + 1.00 * LC7 186.89 12.12 187.13 258.27 149.11 72.46%
2 MT-40 1.35 * LC1 + 1.00 * LC7 186.89 12.12 187.13 258.27 149.11 72.46%
3 MT-40 1.35 * LC1 + 1.00 * LC7 -53.60 88.53 153.34 277.27 160.08 55.30%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 11

5.2.2.2.2 Governing Member Loading

Beam No. 1

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.00 -0.00 -1.66 -0.00 0.50 -0.00
1.35 * LC1 + 1.00 * LC7 80.00 kN/kNm 0.00 -0.00 -1.65 -0.00 0.36 -0.00
1.35 * LC1 + 1.00 * LC7 160.00 kN/kNm 0.00 -0.00 -1.65 -0.00 0.23 -0.00
1.35 * LC1 + 1.00 * LC7 240.00 kN/kNm 0.00 -0.00 -1.65 -0.00 0.10 -0.00
1.35 * LC1 + 1.00 * LC7 300.00(-) kN/kNm 0.00 -0.00 -1.64 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 300.00(+) kN/kNm 0.00 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 320.00 kN/kNm 0.00 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 400.00 kN/kNm 0.00 0.00 -0.00 0.00 -0.00 -0.00

Beam No. 2

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.00 0.00 -1.66 0.00 0.50 0.00
1.35 * LC1 + 1.00 * LC7 80.00 kN/kNm 0.00 0.00 -1.65 0.00 0.36 0.00
1.35 * LC1 + 1.00 * LC7 160.00 kN/kNm 0.00 0.00 -1.65 0.00 0.23 0.00
1.35 * LC1 + 1.00 * LC7 240.00 kN/kNm 0.00 0.00 -1.65 0.00 0.10 0.00
1.35 * LC1 + 1.00 * LC7 300.00(-) kN/kNm 0.00 0.00 -1.64 0.00 0.00 0.00
1.35 * LC1 + 1.00 * LC7 300.00(+) kN/kNm 0.00 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 320.00 kN/kNm 0.00 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 400.00 kN/kNm 0.00 0.00 -0.00 0.00 0.00 -0.00

Beam No. 3

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm -0.00 -1.64 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 100.00(-) kN/kNm -0.00 -1.63 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 100.00(+) kN/kNm -0.00 -0.01 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 220.00 kN/kNm -0.00 -0.01 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 440.00 kN/kNm -0.00 -0.00 0.00 0.00 0.00 0.17
1.35 * LC1 + 1.00 * LC7 660.00 kN/kNm -0.00 0.00 0.00 0.00 0.00 0.17
1.35 * LC1 + 1.00 * LC7 880.00 kN/kNm -0.00 0.01 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 1000.00(-) kN/kNm -0.00 0.01 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 1000.00(+) kN/kNm -0.00 1.63 0.00 0.00 0.00 0.16
1.35 * LC1 + 1.00 * LC7 1100.00 kN/kNm -0.00 1.64 0.00 0.00 0.00 -0.00

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 12

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 13

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 14

Moment around Z

5.2.3 Stability Analysis

Buckling ratio

Max. lateral torsional


Set Max. buckling under
Length [mm] Buckling Length [mm] Buckling ratio buckling under Max. interaction
No. compression
bending
1 400.00 800.00 2.00 0.00% 0.00% 0.00%
2 400.00 800.00 2.00 0.00% 0.00% 0.00%
3 1100.00 2200.00 2.00 59.04% 0.00% 59.04%

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 15

5.2.4 Deflection Analysis


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.

Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview

Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 400.00 L/200 0.00 0.00
2 1.00 * LC1 Relative (Beam) 400.00 L/200 0.00 0.00
3 1.00 * LC1 Relative (Beam) 1100.00 L/200 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 16

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 17

5.3 System Connectors


5.3 Connectors

5.3.1 Overview

Connector 5 - MT-CC-40/50 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: -0.00 -0.00 1.64 0.00 -0.00 -0.00
Resistance: 3.50 8.00 7.50 0.04 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: 21.80 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 18

5.4 Base Connectors


5.4 Bases

5.4.1Overview

Base 1 - MT-BR-40 450 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: -0.00 0.00 1.66 -0.00 -0.50 0.00
Resistance: 74.50 7.00 8.50 0.41 0.89 0.79
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: 75.12 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 19
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: double on concrete 900
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 19

6 Remarks, Your Cooperation Duties

Warning messages for manual adjustment of sets of members


The reference length and/or buckling ratio for the stability evaluation in this project was manually adjusted by the user.

Warning messages for manual adjustment of sets of members


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by the user.
General design note
Buckling and LTB checks must always be controlled separately by the responsible designer engineer.
Channel design computation is carried out by the calculation engine from the RSTAB 8.04.0131.84645 framework software by Dlubal, analogous to the
elastic-elastic method inconformance with EC/DIN 18800 for Europe, AISIS100 for the US and SP 16. 13330 for Russia. The connector design method
is based on a combination of serval calculation models following:
for Europe the principles of either DIN 18800 or EC3 and tests carried out by an independent institute (HTL Rankweil, Austria)
for US the principles of AISC360 13th Edition and tests carried out an independent institute (HTL Rankweil, Austria)
for Russia the principles of SP16. 13330 and tests carried out an independent institute (HTL Rankweil, Austria)
XBT threaded bolts and pipe fittings must be calculated separately according to the manual.
Local stress and deformation of members at places where load is manually entered is not considered.
Relative deflection evaluation and stability checks: For the relative deflection evaluation and stability checks PROFIS Installation uses a reference
length based on a set of members. A member is a connection form one node to the next on a beam. Members can be connected to a set of members if
the nodes in between do not reduce the reference length. Tis connection of members to a set of members is done automatically based on the
assumption that a node with very low global displacement is eithera support or can be regarded as a support. The global displacement limit to define a
node as a support is 0.1 mm for relative deflection evaluation and 0.005 for stability checks. The connection of members to a set of members can also
be done by the user. The user can also decide manually if a set of members is a single-/multispan beam or a cantilever. The buckling ratio can also be
manually changed. The user can finally also decide to exclude a set of members from the relative deflection evaluation. In case of any manual
adjustment you will find a remark in the report.
The static analysis performed on the basis of a stationary system. 2nd - Order analysis due to possible eccentricities or deflections in the design
(deformation according to DIN 18800 or EC 3 for Europe, ASCE7-05 for the US and SP 20. 13330 for Russia) must be considered separately by the
appropriate personnel.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 19 / 19
CL 900 Dx2 on block

Project: solimasn alhabib hospital CL


shaft

Submitted by:

Phone Mobile/Office:
E-mail:
Date: 10/03/2022

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 2

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Media Interface
2 Part list
2.1 Channels
2.2 Base Connectors
2.3 System Connectors
2.4 Accessories
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 3

1 Geometry and Application

Modular Support Spacing


Main Support Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used?

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 4

1.1 Supports

Support No. Orientation Thickness [mm] Concrete grade


1 Vertical 300.00 C20/25
2 Vertical 300.00 C20/25
3 Vertical 300.00 C20/25
4 Vertical 300.00 C20/25

Support No. Orientation Profile Steel grade Rotation


-

1.2 Nodes

Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
1 -2700.00 0.00 3064.39 Base 1 MT-BR-40 450 OC MT-BR-40 450 OC (C)
3 -2450.00 0.00 3064.39 System - MT-AB-L 45 OC MT-AB-L 45 OC (C)
4 -2700.00 0.00 2814.39 Base 2 MT-AB-L 45 OC MT-AB-L 45 OC (C)
5 -2450.00 1100.00 3064.39 System - MT-AB-L 45 OC MT-AB-L 45 OC (C)
6 -2700.00 1100.00 2814.39 Base 3 MT-AB-L 45 OC MT-AB-L 45 OC (C)
7 -2700.00 1100.00 3064.39 Base 4 MT-BR-40 450 OC MT-BR-40 450 OC (C)
9 -2600.00 1100.00 3064.39 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
10 -2600.00 0.00 3064.39 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)

1.3 Members

Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2271445 MT-40 1 2 - - 180.00
2 2268508 MT-40 3 4 1 2 180.00
3 2268508 MT-40 5 6 3 4 180.00
4 2271445 MT-40 7 8 - - 180.00
5 2268508 MT-40 9 10 5 6 270.00
6 2268508 MT-40 11 12 - - 270.00

1.4 Media Interface

No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 5

2 Part list

2.1 Channels

Quantity Description Item No. Weight [kg] Length [mm] Member No.
2 Bracket MT-BR-40 450 OC 2271445 2.86 450.00 1, 4
2 I.-Channel MT-40 OC 2268508 1.49 365.79 2, 3
1 I.-Channel MT-40 OC 2268508 2.36 1157.50 5
1 I.-Channel MT-40 OC 2268508 2.24 1100.00 6

2.2 Base Connectors

Quantity Description Item No. Weight [kg] Node


2 MT-BR-40 450 OC 2271445 - 1,7
4 Angle Brace MT-AB-L 45 OC 2272114 - 4,6

2.3 System Connectors

Quantity Description Item No. Weight [kg] Node


4 Angle Brace MT-AB-L 45 OC 2272114 - 3,5
2 Connector MT-CC-40/50 OC 2322391 - 9,10

2.4 Accessories

Quantity Description Item No. Weight [kg] Length [mm]


6 Safety stud anchor HST3-R M12x115 40/20 2105870 0.00 0.00
16 Hexagon Bolt MT-TLB OC 2273256 0.00 0.00
16 Twist-Lock MT-TL M10 OC 2272082 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 6

3 Load Types

3. Loads

3.1 Loading objects

Allowable Intermediate Actual


No. Description Size [mm] Waterfilled Insulation
spacing [mm] Supports Spacing [mm]
1 Custom Point load - - - - - -
2 Custom Point load - - - - - -
3 Custom Point load - - - - - -
4 Custom Point load - - - - - -

3.2 Point Loads

No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 5 1000.00 0.00 0.00 -1.78 0.00 0.00 0.00
2 Design 5 100.00 0.00 0.00 -1.78 0.00 0.00 0.00
3 Design 6 1000.00 0.00 0.00 -1.78 0.00 0.00 0.00
4 Design 6 100.00 0.00 0.00 -1.78 0.00 0.00 0.00
5 Self Weight Support 1 250.00 0.00 0.00 -0.00 0.00 0.00 0.00
6 Self Weight Support 2 353.55 0.00 0.00 -0.00 0.00 0.00 0.00
7 Self Weight Support 3 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
8 Self Weight Support 3 353.55 0.00 0.00 -0.00 0.00 0.00 0.00
9 Self Weight Support 4 100.00 0.00 0.00 -0.00 0.00 0.00 0.00
10 Self Weight Support 1 100.00 0.00 0.00 -0.00 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 7

3.3 Distributed loads

Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
11 Self Weight Support 1 0.00 450.00 0.00 0.00 -0.03 0.00 0.00 0.00
12 Self Weight Support 2 0.00 353.55 0.00 0.00 -0.02 0.00 0.00 0.00
13 Self Weight Support 3 0.00 353.55 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 4 0.00 450.00 0.00 0.00 -0.03 0.00 0.00 0.00
15 Self Weight Support 5 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00
16 Self Weight Support 6 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 8

4 Load Combinations

Design base: Eurocode 1993

Load combination design base: Eurocode 1990

4.1 Ultimate Limit State

Design base: Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 9

5 Results
5.1 Calculation summary

5.1.1 Members

No Members ULS SLS Status


6 MT-40 68.08% 27.48% OK

5.1.2 Base Connectors

No Base ULS Status


1 MT-BR-40 450 OC 23.00% - OK
4 MT-AB-L 45 OC 51.77% - OK
6 MT-AB-L 45 OC 51.77% - OK
7 MT-BR-40 450 OC 23.00% - OK

5.1.3 System Connectors

No System Connectors ULS Status


3 MT-AB-L 45 OC 70.90% - OK
5 MT-AB-L 45 OC 70.90% - OK
9 MT-CC-40/50 OC 24.05% - OK
10 MT-CC-40/50 OC 24.05% - OK

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 10

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 4
5.2.1.1.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 214.00 6.36 57717.48 -2652.65 65876.44
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
259.85 129.92 -2652.65 -3099.95 2782.31 3099.77

5.2.1.1.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
Steel Q235 A | GB/T
284.10 210000.00 80769.00 1.10 1.10 1.10
700-2006

5.2.1.2 MT-40 Members: 2, 3, 5, 6


5.2.1.2.1 Section properties
t[mm] A[mm²] G[kg/m] Iy[mm^4] Wy[mm³] Iz[mm^4]
2.00 214.00 4.08 57717.48 -2652.65 65876.44
It[mm^4] Wt[mm³] Wymin[mm³] Wzmin[mm³] Wymax[mm³] Wzmax[mm³]
259.85 129.92 -2652.65 -3099.95 2782.31 3099.77

5.2.1.2.2 Material properties


Steel grade fu[N/mm²] E[N/mm²] G[N/mm²] γM0 γM1 γM2
Steel S 280 GD 305.00 210000.00 80769.00 1.10 1.10 1.10

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 11

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Member No. Type Load Combination: σ[N/mm²] τ[N/mm²]σeqv[N/mm²]σ[N/mm²]limitτ[N/mm²]limitUtilization


1 MT-40 1.35 * LC1 + 1.00 * LC7 117.61 16.96 119.25 258.27 149.11 46.17%
2 MT-40 1.35 * LC1 + 1.00 * LC7 -23.78 0.83 23.82 277.27 160.08 8.59%
3 MT-40 1.35 * LC1 + 1.00 * LC7 -23.78 -0.83 23.82 277.27 160.08 8.59%
4 MT-40 1.35 * LC1 + 1.00 * LC7 117.61 16.96 119.25 258.27 149.11 46.17%
5 MT-40 1.35 * LC1 + 1.00 * LC7 58.79 -97.20 168.35 277.27 160.08 60.72%
6 MT-40 1.35 * LC1 + 1.00 * LC7 61.35 -97.20 168.80 277.27 160.08 60.88%

5.2.2.2.2 Governing Member Loading

Beam No. 1

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 3.58 -0.20 0.04 -0.00 -0.01 -0.06
1.35 * LC1 + 1.00 * LC7 90.00 kN/kNm 3.58 -0.20 0.04 -0.00 -0.01 -0.05
1.35 * LC1 + 1.00 * LC7 100.00(-) kN/kNm 3.58 -0.20 0.04 -0.00 -0.01 -0.04
1.35 * LC1 + 1.00 * LC7 100.00(+) kN/kNm 3.58 -0.20 -1.76 -0.00 -0.01 -0.04
1.35 * LC1 + 1.00 * LC7 180.00 kN/kNm 3.58 -0.20 -1.76 -0.00 -0.15 -0.03
1.35 * LC1 + 1.00 * LC7 250.00(-) kN/kNm 3.58 -0.20 -1.77 -0.00 -0.27 -0.01
1.35 * LC1 + 1.00 * LC7 250.00(+) kN/kNm 0.00 -0.20 1.80 -0.00 -0.27 -0.01
1.35 * LC1 + 1.00 * LC7 270.00 kN/kNm 0.00 -0.20 1.80 -0.00 -0.23 -0.01
1.35 * LC1 + 1.00 * LC7 360.00 kN/kNm 0.00 -0.20 1.80 -0.00 -0.07 0.01
1.35 * LC1 + 1.00 * LC7 400.00(-) kN/kNm 0.00 -0.20 1.80 -0.00 -0.00 0.02
1.35 * LC1 + 1.00 * LC7 400.00(+) kN/kNm 0.00 0.00 0.00 0.00 -0.00 -0.00
1.35 * LC1 + 1.00 * LC7 450.00 kN/kNm 0.00 0.00 0.00 0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 12

Beam No. 2

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm -5.06 0.00 0.00 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 70.71 kN/kNm -5.06 0.00 0.00 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 141.42 kN/kNm -5.06 0.00 0.00 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 212.13 kN/kNm -5.07 0.00 -0.00 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 282.84 kN/kNm -5.07 0.00 -0.00 -0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 353.55 kN/kNm -5.07 0.00 -0.00 -0.00 -0.00 -0.00

Beam No. 3

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm -5.06 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 70.71 kN/kNm -5.06 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 141.42 kN/kNm -5.06 0.00 0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 212.13 kN/kNm -5.07 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 282.84 kN/kNm -5.07 0.00 -0.00 0.00 0.00 -0.00
1.35 * LC1 + 1.00 * LC7 353.55 kN/kNm -5.07 0.00 -0.00 0.00 -0.00 -0.00

Beam No. 4

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 3.58 0.20 0.04 0.00 -0.01 0.06
1.35 * LC1 + 1.00 * LC7 90.00 kN/kNm 3.58 0.20 0.04 0.00 -0.01 0.05
1.35 * LC1 + 1.00 * LC7 100.00(-) kN/kNm 3.58 0.20 0.04 0.00 -0.01 0.04
1.35 * LC1 + 1.00 * LC7 100.00(+) kN/kNm 3.58 0.20 -1.76 0.00 -0.01 0.04
1.35 * LC1 + 1.00 * LC7 180.00 kN/kNm 3.58 0.20 -1.76 0.00 -0.15 0.03
1.35 * LC1 + 1.00 * LC7 250.00(-) kN/kNm 3.58 0.20 -1.77 0.00 -0.27 0.01
1.35 * LC1 + 1.00 * LC7 250.00(+) kN/kNm 0.00 0.20 1.80 0.00 -0.27 0.01
1.35 * LC1 + 1.00 * LC7 270.00 kN/kNm 0.00 0.20 1.80 0.00 -0.23 0.01
1.35 * LC1 + 1.00 * LC7 360.00 kN/kNm 0.00 0.20 1.80 0.00 -0.07 -0.01
1.35 * LC1 + 1.00 * LC7 400.00(-) kN/kNm 0.00 0.20 1.80 0.00 -0.00 -0.02
1.35 * LC1 + 1.00 * LC7 400.00(+) kN/kNm 0.00 0.00 0.00 0.00 -0.00 -0.00
1.35 * LC1 + 1.00 * LC7 450.00 kN/kNm 0.00 0.00 0.00 0.00 -0.00 -0.00

Beam No. 5

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.00 1.80 -0.00 0.00 -0.00 0.00
1.35 * LC1 + 1.00 * LC7 100.00(-) kN/kNm 0.00 1.79 -0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 100.00(+) kN/kNm 0.00 0.01 -0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 220.00 kN/kNm 0.00 0.01 0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 440.00 kN/kNm 0.00 0.00 0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 660.00 kN/kNm 0.00 -0.00 0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 880.00 kN/kNm 0.00 -0.01 -0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 1000.00(-) kN/kNm 0.00 -0.01 0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 1000.00(+) kN/kNm 0.00 -1.79 0.00 0.00 -0.00 -0.18
1.35 * LC1 + 1.00 * LC7 1100.00 kN/kNm 0.00 -1.80 0.00 0.00 -0.00 0.00

Beam No. 6

Load Combination: Position[mm] Unit N Q2 Q3 T M2 M3


1.35 * LC1 + 1.00 * LC7 0.00 kN/kNm 0.20 1.80 -0.00 0.00 -0.02 0.01
1.35 * LC1 + 1.00 * LC7 100.00(-) kN/kNm 0.20 1.79 -0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 100.00(+) kN/kNm 0.20 0.01 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 220.00 kN/kNm 0.20 0.01 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 440.00 kN/kNm 0.20 0.00 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 660.00 kN/kNm 0.20 -0.00 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 880.00 kN/kNm 0.20 -0.01 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 1000.00(-) kN/kNm 0.20 -0.01 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 1000.00(+) kN/kNm 0.20 -1.79 0.00 0.00 -0.02 -0.17
1.35 * LC1 + 1.00 * LC7 1100.00 kN/kNm 0.20 -1.80 0.00 0.00 -0.02 0.01
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 13

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 14

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 15

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 16

5.2.3 Stability Analysis

Buckling ratio

Max. lateral torsional


Set Max. buckling under
Length [mm] Buckling Length [mm] Buckling ratio buckling under Max. interaction
No. compression
bending
1 450.00 900.00 2.00 53.04% 0.00% 53.04%
2 353.55 707.11 2.00 0.00% 17.75% 17.75%
3 353.55 707.11 2.00 0.00% 17.75% 17.75%
4 450.00 900.00 2.00 53.04% 0.00% 53.04%
5 1100.00 2200.00 2.00 64.81% 0.00% 64.81%
6 1100.00 2200.00 2.00 68.08% 0.00% 68.08%

5.2.4 Deflection Analysis


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.

Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 17

Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 450.00 L/200 0.00 0.00
2 1.00 * LC1 Relative (Beam) 353.55 L/200 -0.00 0.00
3 1.00 * LC1 Relative (Beam) 353.55 L/200 -0.00 0.00
4 1.00 * LC1 Relative (Beam) 450.00 L/200 0.00 0.00
5 1.00 * LC1 + 0.70 * LC7 Relative (Beam) 1100.00 L/200 1.59 28.84
6 1.00 * LC1 + 0.70 * LC7 Relative (Beam) 1100.00 L/200 1.51 27.48

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 18

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 19

5.3 System Connectors


5.3 Connectors

5.3.1 Overview

Connector 3 - MT-AB-L 45 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: -5.06 0.00 -0.00 -0.00 0.00 0.00
Resistance: 7.14 0.10 0.10 0.10 0.00 0.00
Equation: Fx.ed/Fx.rd;Fy.ed/Fy.rd;Fz.ed/Fz.rd;Mx.ed/Mx.rd;My.ed/My.rd;Mz.ed/Mz.rd
Utilization: 70.90 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Connector 9 - MT-CC-40/50 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: 0.00 0.00 -1.80 0.00 0.00 0.00
Resistance: 3.50 8.00 7.50 0.04 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: 24.05 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 19 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 20

5.4 Base Connectors


5.4 Bases

5.4.1Overview

Base 1 - MT-BR-40 450 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: 3.58 0.20 -0.04 -0.00 0.01 0.06
Resistance: 34.00 7.00 9.50 0.41 0.89 0.79
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: 23.00 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Base 4 - MT-AB-L 45 OC Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]


Local Forces: -5.07 -0.00 -0.01 -0.00 0.00 0.00
Resistance: 9.80 0.10 0.10 0.10 0.00 0.00
Equation: Fx.ed/Fx.rd;Fy.ed/Fy.rd;Fz.ed/Fz.rd;Mx.ed/Mx.rd;My.ed/My.rd;Mz.ed/Mz.rd
Utilization: 51.77 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 20 / 21
Version: 1.8.1

Cu.no./ Company: Contact:


Address: , Solution: CL 900 Dx2 on block
Phone Mobile/Office: Date: 10/03/2022
E-mail: Page: 21

6 Remarks, Your Cooperation Duties

Warning messages for manual adjustment of sets of members


The reference length and/or buckling ratio for the stability evaluation in this project was manually adjusted by the user.

Warning messages for manual adjustment of sets of members


The reference length and/or limits for the deflection evaluation in this project was manually adjusted by the user.
General design note
Buckling and LTB checks must always be controlled separately by the responsible designer engineer.
Channel design computation is carried out by the calculation engine from the RSTAB 8.04.0131.84645 framework software by Dlubal, analogous to the
elastic-elastic method inconformance with EC/DIN 18800 for Europe, AISIS100 for the US and SP 16. 13330 for Russia. The connector design method
is based on a combination of serval calculation models following:
for Europe the principles of either DIN 18800 or EC3 and tests carried out by an independent institute (HTL Rankweil, Austria)
for US the principles of AISC360 13th Edition and tests carried out an independent institute (HTL Rankweil, Austria)
for Russia the principles of SP16. 13330 and tests carried out an independent institute (HTL Rankweil, Austria)
XBT threaded bolts and pipe fittings must be calculated separately according to the manual.
Local stress and deformation of members at places where load is manually entered is not considered.
Relative deflection evaluation and stability checks: For the relative deflection evaluation and stability checks PROFIS Installation uses a reference
length based on a set of members. A member is a connection form one node to the next on a beam. Members can be connected to a set of members if
the nodes in between do not reduce the reference length. Tis connection of members to a set of members is done automatically based on the
assumption that a node with very low global displacement is eithera support or can be regarded as a support. The global displacement limit to define a
node as a support is 0.1 mm for relative deflection evaluation and 0.005 for stability checks. The connection of members to a set of members can also
be done by the user. The user can also decide manually if a set of members is a single-/multispan beam or a cantilever. The buckling ratio can also be
manually changed. The user can finally also decide to exclude a set of members from the relative deflection evaluation. In case of any manual
adjustment you will find a remark in the report.
The static analysis performed on the basis of a stationary system. 2nd - Order analysis due to possible eccentricities or deflections in the design
(deformation according to DIN 18800 or EC 3 for Europe, ASCE7-05 for the US and SP 20. 13330 for Russia) must be considered separately by the
appropriate personnel.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 21 / 21
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HSA-F M12 hnom1
Return period (service life in years): 50
Item number: 2004173 HSA-F M12x100 20/5/-
Effective embedment depth: hef = 50.0 mm, hnom = 64.0 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 10/22/2020 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm

Anchor plate :
R lx x ly x t = 148.0 mm x 60.0 mm x 8.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
uncracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 0.000; Vx = 1.600; Vy = 0.000; no no 35
Mx = 0.000; My = 0.500; Mz = 0.000;

2 Load case/Resulting anchor forces

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
y
Anchor Tension force Shear force Shear force x Shear force y
1 4.499 0.800 0.800 0.000
2 0.000 0.800 0.800 0.000 1 x 2
Tension Compression
max. concrete compressive strain: 0.14 [‰]
max. concrete compressive stress: 4.21 [N/mm ]
2

resulting tension force in (x/y)=(-49.0/0.0): 4.499 [kN]


resulting compression force in (x/y)=(62.1/0.0): 4.499 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 4.499 28.857 16 OK
Pullout Strength* 4.499 12.969 35 OK
Concrete Breakout Failure** 4.499 12.964 35 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


40.400 1.400 28.857 4.499

3.2 Pullout Strength

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NEd [kN]


17.400 1.118 1.500 12.969 4.499

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
22,500 22,500 75.0 150.0 25.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
111.1 1.000 11.000 19.445 1.500 12.964 4.499

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 0.800 23.600 4 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1.600 42.866 4 OK
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
29.500 1.000 29.500 1.250 23.600 0.800

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
37,200 22,500 75.0 150.0 2.000 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 19.445 1.500 42.866 1.600

Group anchor ID
1, 2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.156 0.034 2.000 3 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.347 0.037 1.500 22 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 3.333 [kN] dN = 0.1176 [mm]


VSk = 0.593 [kN] dV = 0.0745 [mm]
dNV = 0.1392 [mm]
Long term loading:

NSk = 3.333 [kN] dN = 0.2745 [mm]


VSk = 0.593 [kN] dV = 0.1136 [mm]
dNV = 0.2970 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HSA-F M12 hnom1
Profile: no profile Item number: 2004173 HSA-F M12x100 20/5/-
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 50 Nm
Plate thickness (input): 8.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 72.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.

Hilti HSA stud anchor with 64 mm embedment, M12 hnom1, Hot dip galvanized, installationwith torque control bar per ETA 11/0374

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Hilti SIW 6AT-A22 + SI AT-A22
• Properly sized drill bit • Hilti SFC 22-A drill driver
• Installation torque control bar with suitable
screw driver or torque wrench
• Hammer

y
74.0 74.0

30.0

30.0

1 2
-0.0

x
30.0

30.0

25.0 98.0 25.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -49.0 0.0 - - - -
2 49.0 -0.0 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x85
Item number: 2223853 HAS-U 5.8 M8x110 (element) / 2092828 HIT-HY
270 (adhesive) / 375982 HIT-SC 16x85 (sieve sleeve)
Effective embedment depth: hef,act = 80.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm

Anchor plate :
R lx x ly x t = 60.0 mm x 148.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M10 - M20; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

Geometry [mm] & Loading [kN, kNm]

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Load case: Design loads N = 0.000; Vx = 0.000; Vy = -2.000; no no 67
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces y

2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.000 0.000 -1.000
2 0.000 1.000 0.000 -1.000 x

max. compressive strain: - [‰]


max. compressive stress: - [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

3 Tension load (ETAG 029 Annex C, Section C.5.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Brick breakout** N/A N/A N/A N/A
Pullout of one brick** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

4 Shear load (ETAG 029 Annex C, Section C.5.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.000 7.360 14 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Local brick failure* - - 67 OK
Brick edge failure in direction x-** - - 67 OK
Pushing out of one brick in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

VRk,s [kN] gM,s VRd,s [kN] VSd [kN] A-ID


9.200 1.250 7.360 1.000 2

4.2 Local brick failure

A1-ID A2-ID s [mm] c [mm]


1 2 98.0 500.0

sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
50.0 200.0 7.500 1.000 0.0 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000

gM,m
2.500

VRk,b,|| [kN] VRd,b,|| [kN] Vsd,|| [kN] b||


7.500 3.000 2.000 0.667

VRk,b,^ [kN] VRd,b,^ [kN] Vsd,^ [kN] b^


0.000 0.000 0.000 -

b||+^
0.667

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

4.3 Brick edge failure in direction x-

A1-ID A2-ID s [mm] c [mm]


2 1 98.0 500.0

sETA,|| [mm] cETA,|| [mm] VRk,c,ETA,|| [kN] ag,V,|| aj,||


50.0 200.0 7.500 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -

gM,m
2.500

VRk,c,|| [kN] VRd,c,|| [kN] Vsd,|| [kN] b||


7.500 3.000 2.000 0.667

VRk,c,^ [kN] VRd,c,^ [kN] Vsd,^ [kN] b^


- - - -

b||+^
0.667

5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x85
Profile: no profile Item number: 2223853 HAS-U 5.8 M8x110 (element) /
2092828 HIT-HY 270 (adhesive) / 375982 HIT-SC 16x85
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 95.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 115.0 mm
Cleaning: compressed air
Fastening option: Pre fastening

Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x85 sieve sleeve(s) with 80 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160

y
30.0 30.0
25.0

2
74.0
98.0

x
74.0

1
25.0

30.0 30.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0.0 -49.0 500.0 500.0 951.0 1,049.0
2 0.0 49.0 500.0 500.0 1,049.0 951.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HSA-F M8 hnom1
Return period (service life in years): 50
Item number: 2004113 HSA-F M8x55 5/-/-
Effective embedment depth: hef = 30.0 mm, hnom = 39.0 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 10/22/2020 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm

Anchor plate :
R lx x ly x t = 1,000.0 mm x 42.5 mm x 3.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
uncracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 0.000; Vx = 0.000; Vy = -3.560; no no 30
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.780 0.000 -1.780
2 0.000 1.780 0.000 -1.780 2 y x1

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.780 8.480 21 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1.780 6.025 30 OK
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
10.600 1.000 10.600 1.250 8.480 1.780

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
8,100 8,100 45.0 90.0 1.000 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 9.037 1.500 6.025 1.780

Group anchor ID
2

5 Displacements (highest loaded anchor)


Short term loading:

NSk = 0.000 [kN] dN = 0.0000 [mm]


VSk = 1.319 [kN] dV = 0.4107 [mm]
dNV = 0.4107 [mm]
Long term loading:

NSk = 0.000 [kN] dN = 0.0000 [mm]


VSk = 1.319 [kN] dV = 0.6268 [mm]
dNV = 0.6268 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

7 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HSA-F M8 hnom1
Profile: no profile Item number: 2004113 HSA-F M8x55 5/-/-
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 15 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 8.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 44.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.

Hilti HSA stud anchor with 39 mm embedment, M8 hnom1, Hot dip galvanized, installationwith torque control bar per ETA 11/0374

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Hilti SIW 6AT-A22 + SI AT-A22
• Properly sized drill bit • Hilti SFC 22-A drill driver
• Installation torque control bar with suitable
screw driver or torque wrench
• Hammer

y
500.0 500.0

21.2

21.2
2 1
21.2

21.2 x
200.0 600.0 200.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 300.0 0.0 - - - -
2 -300.0 0.0 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x50
Item number: 2223852 HAS-U 5.8 M8x80 (element) / 2092828 HIT-HY
270 (adhesive) / 375981 HIT-SC 16x50 (sieve sleeve)
Effective embedment depth: hef,act = 50.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm

Anchor plate :
R lx x ly x t = 900.0 mm x 42.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M10 - M20; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

Geometry [mm] & Loading [kN, kNm]

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Load case: Design loads N = 0.000; Vx = 0.000; Vy = -3.560; no no 69
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.780 0.000 -1.780
2 0.000 1.780 0.000 -1.780 2 y 1x

max. compressive strain: - [‰]


max. compressive stress: - [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

3 Tension load (ETAG 029 Annex C, Section C.5.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Brick breakout** N/A N/A N/A N/A
Pullout of one brick** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

4 Shear load (ETAG 029 Annex C, Section C.5.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.780 7.360 25 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Local brick failure* - - 69 OK
Brick edge failure in direction x-** - - 69 OK
Pushing out of one brick in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

VRk,s [kN] gM,s VRd,s [kN] VSd [kN] A-ID


9.200 1.250 7.360 1.780 2

4.2 Local brick failure

A1-ID A2-ID s [mm] c [mm]


1 2 500.0 250.0

sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
200.0 200.0 6.500 2.000 0.0 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000

gM,m
2.500

VRk,b,|| [kN] VRd,b,|| [kN] Vsd,|| [kN] b||


13.000 5.200 3.560 0.685

VRk,b,^ [kN] VRd,b,^ [kN] Vsd,^ [kN] b^


0.000 0.000 0.000 -

b||+^
0.685

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

4.3 Brick edge failure in direction x-

A1-ID A2-ID s [mm] c [mm]


2 - - 250.0

sETA,|| [mm] cETA,|| [mm] VRk,c,ETA,|| [kN] ag,V,|| aj,||


- 200.0 6.500 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -

gM,m
2.500

VRk,c,|| [kN] VRd,c,|| [kN] Vsd,|| [kN] b||


6.500 2.600 1.780 0.685

VRk,c,^ [kN] VRd,c,^ [kN] Vsd,^ [kN] b^


- - - -

b||+^
0.685

5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x50
Profile: no profile Item number: 2223852 HAS-U 5.8 M8x80 (element) /
2092828 HIT-HY 270 (adhesive) / 375981 HIT-SC 16x50
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 60.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 80.0 mm
Cleaning: compressed air
Fastening option: Pre fastening

Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x50 sieve sleeve(s) with 50 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160

y
450.0 450.0

21.0

21.0
2 1 21.0

21.0
x
200.0 500.0 200.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 250.0 0.0 750.0 250.0 1,000.0 1,000.0
2 -250.0 0.0 250.0 750.0 1,000.0 1,000.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x85
Item number: 2223853 HAS-U 5.8 M8x110 (element) / 2092828 HIT-HY
270 (adhesive) / 375982 HIT-SC 16x85 (sieve sleeve)
Effective embedment depth: hef,act = 80.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm

Anchor plate :
R lx x ly x t = 700.0 mm x 42.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M2,5 - M9; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

Geometry [mm] & Loading [kN, kNm]

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Load case: Design loads N = 0.000; Vx = 0.000; Vy = -2.500; no no 42
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.250 0.000 -1.250
2 0.000 1.250 0.000 -1.250 2 y 1x

max. compressive strain: - [‰]


max. compressive stress: - [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

3 Tension load (ETAG 029 Annex C, Section C.5.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Brick breakout** N/A N/A N/A N/A
Pullout of one brick** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

4 Shear load (ETAG 029 Annex C, Section C.5.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.250 7.360 17 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Local brick failure* - - 42 OK
Brick edge failure in direction x-** - - 42 OK
Pushing out of one brick in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

VRk,s [kN] gM,s VRd,s [kN] VSd [kN] A-ID


9.200 1.250 7.360 1.250 2

4.2 Local brick failure

A1-ID A2-ID s [mm] c [mm]


1 2 400.0 300.0

sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
200.0 200.0 7.500 2.000 0.0 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000

gM,m
2.500

VRk,b,|| [kN] VRd,b,|| [kN] Vsd,|| [kN] b||


15.000 6.000 2.500 0.417

VRk,b,^ [kN] VRd,b,^ [kN] Vsd,^ [kN] b^


0.000 0.000 0.000 -

b||+^
0.417

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

4.3 Brick edge failure in direction x-

A1-ID A2-ID s [mm] c [mm]


2 - - 300.0

sETA,|| [mm] cETA,|| [mm] VRk,c,ETA,|| [kN] ag,V,|| aj,||


- 200.0 7.500 1.000 1.000

sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -

gM,m
2.500

VRk,c,|| [kN] VRd,c,|| [kN] Vsd,|| [kN] b||


7.500 3.000 1.250 0.417

VRk,c,^ [kN] VRd,c,^ [kN] Vsd,^ [kN] b^


- - - -

b||+^
0.417

5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x85
Profile: no profile Item number: 2223853 HAS-U 5.8 M8x110 (element) /
2092828 HIT-HY 270 (adhesive) / 375982 HIT-SC 16x85
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 95.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 115.0 mm
Cleaning: compressed air
Fastening option: Pre fastening

Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x85 sieve sleeve(s) with 80 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160

y
350.0 350.0

21.0

21.021.0
2 1 21.0
x

150.0 400.0 150.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 200.0 0.0 700.0 300.0 1,000.0 1,000.0
2 -200.0 0.0 300.0 700.0 1,000.0 1,000.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.76

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
MT SYSTEM
Modular Support System
Catalogue

上海市浦东新区耀元路58号上海环球都会广场2号楼8
免费服务热线: 800-820-2585 更多资讯:
www.hilti.group
Channels Girder
Technical data Technical data

S250GD EN 10346 MT-30


Material composition S350GD EN 10346
Material composition
S280GD EN 10346 MT-10/MT-15/MT-20/MT-40/MT-50/MT-60/MT-40D

ZM310 ZM, ZM310- EN 10346


Pre-galvanized Z275-for EN 10346 Surface finish for C3 outdoor use ASTM A1046
C1 indoor use
Surface finish
ZM, ZM310-for C3 EN 10346
outdoor use
ASTM A1046

Item Description Material thickness Height × Width Weight Sales pack Item number

MT-70 OC 2.75 50 × 50 3909 6 2268365


MT-80 OC 3.0 100 × 50 6058 6 2268367
MT-90 OC 3.0 100 × 100 8973 6 2268369
MT-100 OC 4.0 150 × 100 15096 6 2268491

50
50
50
3
50
2.75
23x23
50 100
∅11
∅9
∅9

MT-70 OC MT-80 OC

50
50 100
100
4
3

100 150

∅9
∅9

MT-90 OC MT-100 OC

1 2
TECHNICAL DATA MT CHANNEL SYSTEM

Technical data for channel profile MT (pregalvanized & zinc magnesium)

Definition of axes

) )

H H
\
H H
]
$ %

MT-15/ MT-20/ MT-30/ MT-40 T/ MT-40 MT-40D/ MT-50/ MT-60/


MT-10 MT-70 OC MT-80 OC MT-90 OC MT-100 OC
MT-15 OC MT-20 OC MT-30 OC MT-40 T OC MT-40 OC MT-40D OC MT-50 OC MT-60 OC

Channel wall thickness t [mm] 1.2 1.5 1.75 2.0 1.75 2.0 2.0 2.75 2.75 2.75 3,0 3.0 4,0

Cross-sectional area A [mm2] 48.43 85.2 148.65 180 175.59 214 429.52 276.05 500.1 428.78 592.66 976.08 1555.34

Channel weight [kg/m] 0.3888 0.6784 1.267 1.486 1.69 2.039 4.299 2.744 4.017 3.909 6.058 8.973 15.096

Delivered length [m] 2 2 2 3/6 6 3/6 3/6 3/6 3/6 3/6 3/6 3/6 3/6

Material

Steel grade S280GD S280GD S280GD S250GD S280GD S280GD S280GD S280GD S280GD S350GD S350GD S350GD S350GD

Permissible stress δperm [N/mm ] 2


207.8 206.7 205.8 188.3 200.5 202.2 202.2 207.8 202.3 227.3 233.3 233.3 233.3

E-Modul [N/mm2] 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000

Surface

pregalvanized
• • • • • • • • •
(DIN EN ISO 10346)

zinc magnesium
• • • • • • • • • • • •
(EN 10346 & ASTM A1046)

Cross-section values Y-axis

Axis of gravity A 1) e1 [mm] 9.25 11.90 21.25 12.04 23.05 21.76 42.50 22.04 36.62 25.00 50.00 50.00 75.00

Axis of gravity B e2 [mm] 16.75 23.10 21.25 10.96 19.45 20.74 42.50 20.46 35.38 25.00 50.00 50.00 75.00

Moment of inertia Iy [cm ]


4
0.40 1.27 3.65 1.21 4.84 5.77 29.96 7.04 28.67 15.87 87.97 150.85 487.36

Permtion modulus A Wy1 [cm3] 0.25 0.57 1.73 1.00 2.10 2.65 7.05 3.19 7.83 6.35 17.59 30.17 64.98

Permtion modulus B Wy2 [cm3] 0.41 1.00 1.73 1.10 2.48 2.78 7.05 3.44 8.10 6.35 17.59 30.17 64.98

Radius of gyration iy [cm] 0.91 1.22 1.57 0.82 1.66 1.64 2.64 1.60 2.39 1.92 3.85 3.93 5.60

Permissible moment 2)
My [Nm] 52 180 355 189 421 536 1425 663 1584 1443 4105 7040 15162

Z-axis

Moment of inertia Iz [cm4] 0.23 0.72 1.85 5.19 5.71 6.59 13.18 8.27 17.11 15.87 24.50 150.85 260.98

Permtion modulus Wz [cm ]


3
0.15 0.36 1.07 2.44 2.69 3.10 6.20 3.89 8.05 6.35 9.80 30.17 52.20

Radius of gyration iz [cm] 0.69 0.92 1.12 1.70 1.80 1.76 1.75 1.73 1.85 1.92 2.03 3.93 4.10

Design resistance
• MT-10 to MT-70: The permissible stress σD / γG/Q where y = 1,4. σD results from the higher yield strength (point) resulting from cold forming as per EN
1993-1-3: 2010: σD = fyk / γM where γM = 1,1.
• MT-80 to MT-100: The permissible stress σD / γG/Q where y = 1,5“
1) For the arithmetical bending dimensioning is the smaller value (Wy1, Wy2) decisive to (Wy1 = Iy / e1 bzw. Wy2 = Iy / e2).
2) My = δperm x min. (Wy1, Wy2)

3 4
POINT LOAD IN THE MIDDLE OF SPAN

Technical data for channel profiles MT (max. span width/deflection - point Load in the middle of span)

Max. span width L [cm] / deflection f [mm] - Result

MT-40 T/ MT-40D/
MT-15/ MT-20/ MT-30/ MT-40/ MT-50/ MT-60/
MT-10 MT-40 T MT-40D MT-70 OC MT-80 OC MT-90 OC MT-100 OC
MT-15 OC MT-20 OC MT-30 OC MT-40 OC MT-50 OC MT-60 OC
OC OC

load F [kN] L f L f L f L f L f L f L f L f L f L f L f L f L f

0,25 83 0.4 157 7.8 260 12.9 152 7.6 294 14.7 317 15.8 600 29.4 339 16.9 600 29.9 469 23.4 600 11.6 600 8.3 600 3.6

0,50 42 0.1 93 3.2 188 9.3 109 5.5 215 10.7 234 11.7 489 24.4 254 12.6 482 24.1 368 18.4 600 17.7 600 11.9 600 4.7

0,75 28 0.0 62 1.4 155 7.7 90 4.5 178 8.9 194 9.6 418 20.9 212 10.6 411 20.5 311 15.5 600 23.8 600 15.4 600 5.8

1,00 21 0.0 47 0.8 134 6.6 75 3.5 154 7.6 169 8.4 371 18.5 185 9.3 363 18.1 274 13.6 600 29.9 600 19.0 600 6.9

1,25 17 0.0 37 0.5 113 5.0 60 2.3 134 6.2 151 7.6 336 16.8 167 8.3 329 16.4 247 12.3 551 27.5 600 22.5 600 8.0

1,50 14 0.0 31 0.4 94 3.4 50 1.6 112 4.3 138 6.9 309 15.4 152 7.6 302 15.0 227 11.3 512 25.6 600 26.1 600 9.1

1,75 12 0.0 27 0.3 81 2.5 43 1.2 96 3.2 122 5.5 287 14.4 141 7.0 281 14.0 211 10.5 479 23.9 600 29.6 600 10.2

2,00 10 0.0 23 0.2 71 1.9 38 0.9 84 2.4 107 4.2 270 13.5 132 6.5 264 13.2 198 9.9 452 22.6 572 28.6 600 11.3

2,25 9 0.0 21 0.2 63 1.5 34 0.7 75 1.9 95 3.3 248 11.6 117 5.1 249 12.4 187 9.3 429 21.4 545 27.2 600 12.4

2,50 8 0.0 19 0.1 57 1.2 30 0.6 67 1.6 86 2.7 224 9.5 106 4.2 237 11.8 177 8.8 409 20.4 522 26.0 600 13.5

2,75 8 0.0 17 0.1 52 1.0 27 0.5 61 1.3 78 2.2 204 7.9 96 3.5 227 11.3 169 8.4 391 19.5 501 25.0 600 14.6

3,00 7 0.0 16 0.1 47 0.9 25 0.4 56 1.1 71 1.9 188 6.7 88 2.9 208 9.6 162 8.1 376 18.8 482 24.1 600 15.7

3,50 6 0.0 13 0.1 41 0.6 22 0.3 48 0.8 61 1.4 161 4.9 76 2.1 179 7.1 150 7.5 349 17.4 450 22.5 600 17.9

4,00 5 0.0 12 0.1 36 0.5 19 0.2 42 0.6 54 1.1 141 3.8 66 1.6 157 5.4 141 7.0 328 16.3 424 21.2 600 20.1

4,50 5 0.0 10 0.0 32 0.4 17 0.2 37 0.5 48 0.8 126 3.0 59 1.3 140 4.3 128 5.9 310 15.5 401 20.0 600 22.3

5,00 4 0.0 9 0.0 28 0.3 15 0.1 34 0.4 43 0.7 113 2.4 53 1.1 126 3.5 115 4.8 295 14.7 382 19.0 600 24.5

6,00 3 0.0 8 0.0 24 0.2 13 0.1 28 0.3 36 0.5 95 1.7 44 0.7 105 2.4 96 3.3 270 13.5 350 17.5 600 28.9

7,00 3 0.0 7 0.0 20 0.2 11 0.1 24 0.2 31 0.3 81 1.2 38 0.5 90 1.8 82 2.4 232 10.0 325 16.2 571 28.5

8,00 3 0.0 6 0.0 18 0.1 9 0.1 21 0.2 27 0.3 71 1.0 33 0.4 79 1.4 72 1.9 204 7.7 305 15.2 537 26.8

Design resistance
Selection example:
• 1,0 kN (≈ 100 kg) should be carried by a channel with a channel span width L = 100cm (single span sinply supported).
Solution:
• Select the line with the load, F = 1,0 kN.
• The channels MT-20, MT-40 T up to MT-100 can be used because the permissible span width (table value) is larger or equal to the required span
width of L = 100cm.
Load tables are based on stress and deflection calculations, lateral torsional buckling is not considered.
POINT LOAD IN THE MIDDLE OF SPAN

Technical data for channel profiles MT (max. span width/deflection - point Load in the middle of span)

Max. span width L [cm] / deflection f [mm] - Result

MT-40 T/
MT-15/ MT-20/ MT-30/ MT-40/ MT-40D/ MT-50/ MT-60/
MT-10 MT-40 T MT-70 OC MT-80 OC MT-90 OC MT-100 OC
MT-15 OC MT-20 OC MT-30 OC MT-40 OC MT-40D OC MT-50 OC MT-60 OC
OC

span width L [cm] F f F f F f F f F f F f F f F f F f F f F f F f F f

25 0.83 0.0 1.87 0.2 5.69 0.2 3.02 0.4 6.74 0.2 8.58 0.2 22.80 0.1 10.61 0.2 25.35 0.1 23.08 0.2 65.68 0.1 106.17 0.1 222.70 0.1

50 0.42 0.1 0.94 0.9 2.84 1.0 1.51 1.6 3.36 0.9 4.29 0.9 11.39 0.5 5.30 0.9 12.67 0.5 11.53 0.9 32.83 0.5 56.29 0.5 121.26 0.3

75 0.28 0.3 0.62 2.1 1.89 2.2 1.00 3.5 2.24 1.9 2.85 2.1 7.59 1.1 3.53 2.1 8.44 1.2 7.68 2.0 21.87 1.0 37.51 1.0 80.81 0.7

100 0.21 0.5 0.46 3.7 1.42 3.9 0.60 5.0 1.68 3.5 2.14 3.7 5.68 1.9 2.64 3.7 6.32 2.2 5.75 3.6 16.39 1.9 28.11 1.9 60.57 1.2

125 0.16 0.8 0.37 5.7 1.13 6.1 0.38 6.2 1.34 5.4 1.70 5.8 4.53 3.0 2.11 5.9 5.05 3.4 4.59 5.6 13.10 2.9 22.47 2.9 48.43 1.9

150 0.14 1.2 0.28 7.5 0.80 7.5 0.26 7.5 1.07 7.5 1.27 7.5 3.77 4.3 1.55 7.5 4.20 4.9 3.52 7.5 10.90 4.2 18.70 4.2 40.32 2.8

175 0.12 1.6 0.20 8.7 0.59 8.7 0.18 8.7 0.78 8.7 0.93 8.7 3.22 5.8 1.13 8.7 3.59 6.7 2.57 8.7 9.33 5.7 16.01 5.7 34.52 3.8

200 0.10 2.1 0.15 9.9 0.44 10.0 0.13 9.9 0.59 10.0 0.70 10.0 2.81 7.6 0.85 10.0 3.13 8.8 1.95 10.0 8.15 7.4 13.99 7.4 30.17 4.9

225 0.09 2.6 0.12 11.2 0.34 11.2 0.10 11.0 0.46 11.2 0.54 11.2 2.49 9.6 0.66 11.2 2.77 11.1 1.52 11.2 7.23 9.4 12.41 9.4 26.79 6.3

250 0.08 3.2 0.09 12.4 0.27 12.4 0.07 12.2 0.36 12.4 0.43 12.4 2.23 11.9 0.52 12.4 2.24 12.5 1.21 12.4 6.49 11.6 11.15 11.6 24.07 7.7

275 0.07 3.9 0.07 13.6 0.22 13.6 0.05 13.3 0.29 13.6 0.35 13.6 1.91 13.7 0.42 13.6 1.83 13.7 0.98 13.7 5.75 13.7 9.88 13.7 21.85 9.4

300 0.06 4.7 0.06 14.7 0.18 14.8 0.04 14.4 0.24 14.8 0.28 14.8 1.59 14.9 0.34 14.8 1.52 14.9 0.81 14.9 4.80 15.0 8.26 15.0 19.99 11.1

325 0.06 5.5 0.05 15.9 0.15 16.0 0.02 15.4 0.19 16.0 0.23 16.0 1.33 16.1 0.27 16.0 1.28 16.1 0.67 16.1 4.06 16.2 7.00 16.2 18.42 13.1

350 0.05 6.4 0.04 17.0 0.12 17.2 0.01 16.3 0.16 17.2 0.19 17.2 1.13 17.4 0.22 17.1 1.08 17.4 0.56 17.3 3.47 17.4 5.99 17.4 17.06 15.2

375 0.05 7.4 0.03 18.1 0.10 18.3 0.13 18.3 0.15 18.3 0.96 18.6 0.18 18.3 0.92 18.6 0.47 18.4 3.00 18.7 5.17 18.7 15.89 17.4

400 0.04 8.5 0.02 19.1 0.08 19.4 0.11 19.4 0.13 19.4 0.83 19.8 0.15 19.4 0.79 19.8 0.39 19.6 2.60 19.9 4.50 19.9 14.86 19.9

425 0.04 9.6 0.02 20.1 0.06 20.5 0.09 20.5 0.10 20.5 0.71 20.9 0.12 20.4 0.68 21.0 0.33 20.7 2.28 21.1 3.95 21.1 13.16 21.2

450 0.04 10.8 0.01 21.1 0.05 21.6 0.07 21.6 0.08 21.6 0.61 22.1 0.09 21.5 0.59 22.1 0.27 21.9 2.00 22.3 3.48 22.3 11.66 22.4

475 0.03 12.1 0.01 22.0 0.04 22.6 0.05 22.6 0.06 22.6 0.53 23.3 0.07 22.5 0.51 23.3 0.23 22.9 1.77 23.5 308 23.6 10.39 23.6

500 0.03 13.5 0.03 23.6 0.04 23.6 0.05 23.6 0.46 24.4 0.05 23.4 0.44 24.4 0.19 24.0 1.56 24.7 2.73 24.8 9.30 24.9

Design resistance
Load tables are based on stress and deflection calculations, lateral torsional buckling is not considered.
BUCKLING

Permissible buckling load for channel profile MT

MT-10 MT-15 / MT-15 OC MT-20 / MT-20 OC MT-30 / MT-30 OC MT-40 T / MT-40 T OC MT-40 / MT-40 OC MT-40D / MT-40D OC MT-50 / MT-50 OC MT-60 / MT-60 OC MT-70 OC MT-80 OC MT-90 OC MT-100 OC
Buckling length
permissible buckling load permissible buckling load permissible buckling load permissible buckling load permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling
Sk [cm]
[kN] [kN] [kN] [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN]

25 29.40 30.51 34.41 42.22 87.97 55.68 68.93 99.01 128.31 219.78 350.41

50 24.86 22.72 29.93 36.62 80.21 47.92 52.16 90.61 118.07 210.74 336.93

75 19.67 15.10 24.91 30.33 72.00 39.23 36.33 81.79 107.42 202.00 323.55

100 14.70 10.03 19.75 23.90 62.95 30.58 25.80 72.10 95.79 193.28 310.24

125 10.86 7.02 15.34 18.45 53.45 23.51 19.47 61.82 83.33 184.34 296.65

150 8.19 5.16 12.00 14.38 44.43 18.32 15.55 51.88 70.94 175.02 282.54
N/A N/A
175 6.33 3.96 9.58 11.44 36.66 14.62 12.97 43.12 59.66 165.24 267.77

200 5.03 3.13 7.82 9.31 30.34 11.94 11.18 35.87 50.05 155.00 252.31

225 4.08 2.54 6.51 7.73 25.32 9.97 9.86 30.04 42.18 144.40 236.27

250 3.37 2.11 5.52 6.54 21.35 8.46 8.86 25.40 35.81 133.67 219.89

275 2.83 1.78 4.75 5.62 18.20 7.29 8.06 21.68 30.67 123.05 203.52

300 2.41 1.52 4.14 4.89 15.67 6.36 7.41 18.70 26.51 112.80 187.54

Flexural buckling:
Rod length l (cm) / euler factor
β/Sk (cm) effective length
=l۰β 2,0 (l) 1,0 (l) 0,7 (l) 0,5 (l)

Fall 1 Fall 2 Fall 3 Fall 4

Design resistance

• MT-10 to MT-70: γG/Q = 1,4 → FD* = permissible buckling load x 1,4


• MT-80 to MT-100: γG/Q = 1,5 → FD* = permissible buckling load x 1,5
• Bend table is only valid for centric buckling loads. The values in this table aren‘t allowed for offset torque/oblique position/lateral-torsional
buckling and must be engineered.

*(design value)
Twist Lock (MT-TL) Thread Forming Bolt (MT-TFB)
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
Fastening of any component, media to Maximum connection reliability, no Fastening of any component, media to One bolt for all girder connections
MT open C-channels with MT-TLB reliance on friction, no restriction of MT girders
positioning steps For use with MT-TLB Fast installation easy to release
Fastening of any component, media to
One handed installation - No need for
MT open C-channels with MT-TLB
bolts or complex fixation elements
Guaranteed performance & productivity
缺清晰图 setting with SIW-AT module
Guaranteed performance &
productivity setting with SIW-AT
module

Releasing, re-positioning, and


Technical data
subsequent re-torquing fully enabled
Pre-galvanized 12μm-for C1 indoor use
Item Description Thread - M Surface Finish Weight Sales pack Item number
Surface finish HDG+ZiNi topcoat 20μm - for C3 outdoor use MT-TFB OC M10 HDG+ 28 50 2272084
1A

Item Description Thread - M Weight Sales pack Item number

MT-TL M8 M8 32 50 2273630
MT-TL M8 OC M8 32 50 2273631 Item Description For Girder Types Tightening torque - Nm Pull out Load - kN Shear Load - kN
* MT-TL M10 is the primary size for
MT-TL M10 M10 35 50 2272080 MT-TFB OC MT-70,MT-80 60 11 17
MT-TL M10 OC M10 35 50 2272082 connections within the system
MT-TFB OC MT-90 60 11 20
MT-TL M12 M12 38 50 2273632 * (with connectors & baseplates)
MT-TFB OC MT-100 60 17 20
MT-TL M12 OC M12 38 50 2273633
MT-TL M16 M16 37 50 2273634 > 10 mm
MT-TL M16 OC M16 37 50
60 Nm
2273635 (44 ft-lb)

1 2 3

Item Description Tightening torque - Nm Shear Load - kN

MT-TL M10 30 8 7.2 17


TX50
MT-TL M10 OC 40 8 7.2
SI-AT-A22
60°

Channel/Girder End Caps (MT-EC)


Twist-Lock Bolt (MT-TLB) APPLICATIONS

APPLICATIONS Protection of channel/girder cut ends


Fastening of any component, media to
MT open C-channels with MT-TL

For use with Twist-Lock MT-TL Technical data

Material composition Polypropylene (PP)

Colour Red - RAL 3000

Item Description Thread - M Thread length Wrench size Weight Sales pack Item number

MT-TLB M10 24 17 25 50 2273254 Item Description For channel/girder types Weight Sales pack Item number
MT-TLB OC M10 24 17 25 50 2273256 MT-EC-30 MT-30 3.7 20 2273642
MT-TLB 30 M10 30 17 31 50 2282190 MT-EC-40/50 MT-40,50,40D 5.8 20 2273643
MT-TLB 30 OC M10 30 17 31 50 2282191 MT-EC-60 MT-60 9.1 20 2273644
MT-EC-70 MT-70 8.4 20 2273697
* MT-TLB is the primary size for connections within the system (with connectors & baseplates)
MT-EC-80 MT-80 15.4 20 2273698
MT-EC-90 MT-90 31.0 20 2273699
MT-TLB 30 is used only with brackets (MT-BR’s) for fixation to open channels with TL’s MT-EC-100 MT-100 45.5 20 2273700

6
5
Open C-Channel Baseplates Open C-Channel Connectors
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
For fastening of MT channels to Reliable and easy to use Assembly of frames and other Universal few parts for all applications
base material Connection of channels to any structures using MT channels Simplified connectors for multi purpose
base material Simplest form of connectors, for usage
Simplest and most cost effective Easy to use
building standard L junctions
solution Three-dimensional, thus high strength

Technical data Technical data


Direct fastening to girders possible (w/ TFB)
for MT-C-L1/2

Q235B GB/T 1591-2018 Q355B GB/T 1591-2018


Material composition Material composition

Pre-galvanized galvanized ISO 2081 Pre-galvanized galvanized ISO 2081


12μm-for C1 indoor use 12μm-for C1 indoor use
Surface finish Surface finish
HDG, 56μm-for C3 outdoor ASTM A153M HDG, 56μm-for C3 outdoor ASTM A153M
use use

Item Description Plate thickness For Channel types Weight Sales pack Item number 90° Angle connector
MT-B-L 4.0 MT-30,MT-40,MT-50,MT-60 119 20 2272086
Angle Material thickness For Channel types
MT-B-L OC 4.0 MT-30,MT-40,MT-50,MT-60 119 20 2272088 Item Description Weight Sales pack Item number

MT-B-T 4.0 MT-30,MT-40,MT-50,MT-60 565 20 2272090 MT-C-L1 90° 6.0 MT-30,MT-40 199 20 2271514
MT-B-T OC 4.0 MT-30,MT-40,MT-50,MT-60 565 20 2272092 MT-C-L1 OC 90° 6.0 MT-50,MT-60 199 20 2271516
MT-B-O2 4.0 MT-30,MT-40,MT-50,MT-60 1027 12 2272094 MT-C-L2 90° 6.0 MT-30~MT-100 257 20 2271518
MT-B-O2 OC 4.0 MT-30,MT-40,MT-50,MT-60 1027 12 2272096 MT-C-L2 OC 90° 6.0 MT-30~MT-100 257 20 2271519
MT-B-O2B 8.0 MT-40D 2072 6 2282212 MT-C-LL1 90° 4.0 MT-30,MT-40 334 10 2272047
MT-B-O2B OC 8.0 MT-40D 2072 6 2282213 MT-C-LL1 OC 90° 4.0 MT-50,MT-60 334 10 2272049
MT-B-O4 8.0 MT-40D 3315 4 2272098 MT-C-LL2 90° 4.0 MT-30,MT-40 592 10 2272051
MT-B-O4 OC 8.0 MT-40D 3315 4 2272099 MT-C-LL2 OC 90° 4.0 MT-50,MT-60 592 10 2272053
* MT-C-L2/MT-C-L2 OC

Z Z Z Z
-FZ Design Load kN +FZ Design Load kN -F Design Load kN +FZ Design Load
Item Description Twist-Lock Qty.(pc) kN Item Description Twist-Lock Qty. Z

MT-B-L 1 7.0 2.9 MT-C-L1 2 5.6 4.6


MT-B-T 2 12.6 8.4 MT-C-L2 3 7.0 7.0
MT-B-O2 2 14.0 12.6 MT-C-LL1 2 5.2 7.0
MT-B-O2B 2 17.6 18.4 MT-C-LL2 4 6.5 5.8
MT-B-O4 2 17.6 18.4

168.7 ∅11
∅11 112 ∅11
14x19
105
14x19 52
57
4 ∅11

52 108 57
42 42 42 41
4 6 6

MT-B-L / MT-B-L OC MT-B-T / MT-B-T OC MT-C-L1 / MT-C-L1 OC MT-C-L2 / MT-C-L2 OC

∅11 ∅11
106 ∅11 106 105
105 ∅11 55
∅11 ∅14.7
4 8 8
14x20 14x20

135 150 140


185 200
83.5 200 200
100
4 4

MT-B-O2 / MT-B-O2 OC MT-B-O2B / MT-B-O2B OC MT-B-O4 / MT-B-O4 OC MT-C-LL1 / MT-C-LL1 OC MT-C-LL2 / MT-C-LL2 OC

7 8
Angle Brace Connectors Transverse Connectors - 2D
APPLICATIONS ADVANTAGES Item Description Material Material thickness Weight Sales pack Item number
$QJOHEUDFLQJZLWK07FKDQQHOV Wide range of channel compatibility MT-C-T/1 Q235B 6.0 435 20 2272040
MT-C-T/1 OC Q235B 6.0 435 20 2272042
Possibility to be used as baseplate (MT-AB A and MT-AB L MT-C-T/2
45) Q355B 4.0 782 15 2272054
MT-C-T/2 OC Q355B 4.0 782 15 2272055
MT-C-T A Q355B 4.0 323 20 2272056
MT-C-T A OC Q355B 4.0 323 20 2272057
Technical data
∅11 A B C

6
Q235B GB/T 700-2006
Material composition

Pre-galvanized galvanized ISO 2081 44.7 44.7


12μm-for C1 indoor use
Surface finish MT-C-T/1 / MT-C-T/1 OC
HDG, 56μm-for C3 outdoor ASTM A153M
use A
168

45°Angle connector 112

重量(g) 包装数量(pcs) 品号 ∅11


Item Description Angle Material thickness For Channel types Weight Sales pack Item number

MT-AB A Adjustable 4.0 MT-40,MT-50 441 12 2272111


MT-AB A OC Adjustable 4.0 MT-40,MT-50 441 12 2272112
MT-AB L 45 45° 4.0 MT-40,MT-50 427 10 2272113 MT-C-T/2 / MT-C-T/2 OC
MT-AB L 45 OC 45° 4.0 MT-40,MT-50 427 10 2272114 ∅12 A B

MT-AB LL2 45° 4.0 MT-40,MT-50 553 10 2272115


MT-AB LL2 OC 45° 4.0 MT-60,MT-40D 553 10 2273585
125
∅11

51.5
4
∅11.5 ∅11
59 114 MT-C-T A / MT-C-T A OC
135°
45° Z
∅11 114 +FZ Design Load kN
Item Description Twist-Lock Qty.(pc)
14x20 ∅14
MT-C-T/1 2 4.3 5.5
MT-C-T/2 4 11.9 11.3
51.5 40.5 46 4
114 MT-C-T A 2 14 8.8

MT-AB A / MT-AB A OC MT-AB- L 45 / MT-AB-L 45 OC MT-AB-LL2 / MT-AB-LL2 OC

Splice Connectors Transverse Connectors - 3D


Item Description Material Material thickness Weight Sales pack Item number
Material thickness For Channel types
Item Description Weight Sales pack Item number MT-C-T 3D/2 Q235B 6.0 418 10 2272058
MT-ES-40 4.0 MT-30,MT-40,MT-50, 805 12 2272062 MT-C-T 3D/2 OC Q235B 6.0 418 10 2272059
MT-ES-40 OC 4.0 MT-60,MT-40D 805 12 2272063 MT-C-T 3D/3 Q235B 6.0 629 10 2272060
MT-C-T 3D/3 OC Q235B 6.0 629 10 2272061

∅11
2

∅11
∅7 46
6
6
∅11 MT-TL M10

43.2 43.2 43.2 43.2


200
0 mm

4 MT-C-T 3D/2 / MT-C-T 3D/2 OC MT-C-T 3D/3 / MT-C-T 3D/3 OC

MT-ES-40 / MT-ES-40 OC

9 10
Girder Baseplates Girder Baseplates
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
For fastening of MT channels to base Connection of girders to both For fastening of MT channels to Connection of girders to I-beam
material (concrete) concrete and steel for MT-B-GS base material(steel) with sandwich plates
connectors

Technical data Technical data

Material composition Q355B GB/T 1591-2018 Q355B GB/T 1591-2018


Material composition
HDG, 56μm-for C3
HDG, 56μm-for C3 outdoor ASTM A153M outdoor use ASTM A153M
Surface finish Surface finish
use

Item Description Plate thickness I-beam width (mm) Weight Sales pack Item number

MT-B-GXL S1 OC 15.0 75-165 9401 2 2272106


MT-B-GXL S2 OC 15.0 165-235 9365 2 2272107
MT-B-GXL S3 OC 15.0 235-305 10816 2 2272108
Plate thickness For Girder Types
Item Description Weight Sales pack Item number MT-P-GXL S1 OC 15.0 75-165 6902 2 2272110
MT-B-GS T OC 8.0 MT-70,MT-80 2166 2 2272100
MT-B-GS O4U OC 12.0 MT-70,MT-80 4730 4 2272101 * MT-B-GXL S1/2/3 OC A B

MT-B-GL O4 OC 12.0 MT-90 14910 1 2272103


MT-B-GXL O4 OC 12.0 MT-100 17031 1 2272104 17x64

165 11x14 ∅14.7

17x64 ∅14.7 12
11x14
165.4 165.4 140 12
∅11 ∅11 ∅11 MI-SGC-M16
∅14.7
∅18 ∅18
144
12 12 70
144
70 215
12 280
215 185
280
280

400 290 350 290 150


200
350 350
200 MT-P-GXL S1 OC
MT-B-GXL S1 OC C
MT-B-
D

GXL S1

MT-B-GXL O4 OC MT-B-GL O4 OC MT-B-GS O4U OC


MT-B-
GXL S1
11x14

140 Z
+FZ Design Load kN 11x14 165 11x14
165
Item Description ±FZ Design Load kN
∅14.7 12
8 MT-B-GS T OC 33.4 25.9 17x64 12 17x64
∅11
MT-B-GS O4U OC 27.0 90.1
MT-B-GL O4 OC 82.8 183.6
294
50
175 MT-B-GXL O4 OC 140.1 218.6 214 420
215 155
350
155
90 220 220 * MT-B-GXL S1 OC
MT-P-GXL-S1 OC
* MT-B-GXL S2 OC, MT-B-GXL S3 OC
MT-B-GS T OC MT-B-GXL S3 OC
MT-B-GXL S2 OC

A B Item Description Plate thickness For Girder Types Weight Sales pack Item number

MT-70,MT-80
MT-90 MT-B-G WS OC 6.0 4345 4 2272109
MT-100 MT-90,MT-100
1 3 4 6

11x14

1
MT-70
226 226
MT-80

*MT-B-GS T OC MT-B-G WS OC

11 12
Girder Connectors Girder Connectors
APPLICATIONS ADVANTAGES Item Description Material thickness Surface finish Weight Sales pack Item number
Simplest form of connectors, for Possibility to be used as baseplate. MT-C-GSP L OC 4.0 HDG 424 10 2272073
building standard L junctions with MT MT-C-GSP T OC 4.0 HDG 455 10 2272074
girders Designed to provide extra adjustability MT-C-GLP T OC 4.0 HDG 884 8 2272075
4 ੋ11
ੋ11 45
4 90
ੋ11 45 4

145
140
Technical data 210
140
265
215

Q355B GB/T 1591-2018


Material composition
MT-C-GSP L OC MT-C-GSP T OC MT-C-GLP T OC
ASTM A153M
T-Post Coonector (U-shaped)
Surface finish HDG, 56μm-for C3 outdoor
use

Item Description Material thickness Surface finish Weight Sales pack Item number

MT-U-GL1 OC 4.0 HDG 8827 2 2272070


90°Angle connector
A
121
Item Description Angle Material thickness For Girder Types adjustment Weight Sales pack Item number

MT-C-GS OC 90° 3.0 MT-70,MT-80 25 400 10 2272064 1100

MT-C-GL OC 90° 4.0 MT-90,MT-100 25 1161 10 2272066


MT-C-GS A OC 90° 3.0 MT-70,MT-80 5 390 10 2272068 13.5x63
MT-C-GL A OC 90° 4.0 MT-90,MT-100 5 1145 10 2272069 ∅11
∅11.5
4

MT-U-GL1 OC MT-U-GL OC
A B

∅14.7
4
Splice Connectors
∅14.7

122.5 Item Description Material thickness Surface finish Weight Sales pack For Girder Types Item number
150
∅11 MT-ES-70 OC 5.0 HDG 1831 8 MT-70,MT-80 2272078
∅11
MT-ES-90 OC 6.0 HDG 4429 4 MT-90,MT-100 2272076
122.5 100 150
50 53
ੋ11 ੋ11
106
MT-C-GS OC MT-C-GL OC * MT-C-GS OC/ MT-C-GL OC
11x13 11x13

320
A B 320
MT-70 / 5 6
3 4 MT-80 /
MT-90/
MT-100

∅8 MT-ES-70 OC MT-ES-90 OC
11x25

122.5
11x25
150 Angle bracing connector
∅7
MT-70 /

122.5 MT-80
Item Description Angle Material thickness Surface finish Weight Sales pack Item number
50 100 150
MT-AB-G T OC 30°~60° 4.0 HDG 348 4 2272116

MT-C-GS A OC MT-C-GL A OC * MT-C-GS A OC / MT-C-GL A OC A B

108
ੋ11 4

30°

60°

241

MT-AB-G T OC * MT-AB-G T Angle 30°~60°

13 14
Hilti. Outperform. Outlast.

HILTI MC Galvanized Channel

Hilti Saudi Arabia


TECHNICAL ADVISORY SERVICE
SA.TSO@HILTI.COM

Quality Management System Certification

Standard: ISO 9001:2008


Issued by: The Swiss Association for Quality and Management Systems SQS.
Registration No: 12455 (The current certificate can be downloaded from www.hilti.sa)
Field of activity: Market Organization.
Note: The certificate of Hilti Saudi Arabia is a sub-certificate to the master certificate of Hilti
Aktiengesellschaft,FL-9494 Schaan with the field of activity: Research, Development, Manufacturing, Sales
and Service.

www.hilti.sa
sa.tso@hilti.com
Hilti Saudi Arabia
21454 Jeddah, Saudi Arabia
Kilo 14 | King Fahd Street | P. O. Box 15930
Free Toll Number: 800 1200 013
Fax Number: 800 2445 554
Hilti. Outperform. Outlast.

Product Data Sheet

www.hilti.sa
sa.tso@hilti.com
Hilti Saudi Arabia
21454 Jeddah, Saudi Arabia
Kilo 14 | King Fahd Street | P. O. Box 15930
Free Toll Number: 800 1200 013
Fax Number: 800 2445 554
MC Installation system

Installation channel MC-3D-41

Technical Data
Material Structural steel with minimum yield strength
280 N/mm2
Coating Sendzimir galvanized

Material
Height Length weight Designation Article number
thickness

41 mm 3m 1,6 mm 1713 g/m MC-3D-41 3m 2063295

41 mm 6m 1,6 mm 1713 g/m MC-3D-41 6m 2063294

Installation channel MC-72

Technical Data
Material Structural steel with minimum yield strength
250 N/mm2
Coating Sendzimir galvanized

Material
Height Length weight Designation Article number
thickness

72 mm 6m 2,75 mm 4108 g/m MC-72 6m 2063298

MC Installation System ¦ Catalogue data ¦ September 2013 ¦ NMtd 1


MC Installation system

Technical data for MC and relevant MQ channels

MC channel permissible stress calculated according EN 1993-1-3

Channel selection table


Max. span width L [cm] / deflection f [mm], max. L/200

MC Installation System ¦ Catalogue data ¦ September 2013 ¦ NMtd 2


HIT-HY 170 injection mortar
Anchor design (ETAG 029) / Rods&Sleeves / Masonry
Injection mortar system Benefits
- Chemical injection fastening for
Hilti HIT-HY 170 the most common types of base
materials:
500 ml foil pack - Hollow and solid clay bricks,
(also available as calcium silicate bricks, normal
330 ml foil pack) and light weight concrete blocks
- Two-component hybrid mortar
Anchor rod: - Versatile and convenient
HIT-V handling with HDE dispenser
HIT-V-F - Mortar filing control wit HIT-SC
HIT-V-R
sleeves
HIT-V-HCR
(M8-M12)
Internally
threaded sleeve:
HIT-IC
(M8-M12)

HIT-SC
sieve sleeve
(16-22)

Base material Load conditions

Solid brick Hollow brick Static/


quasi-static
Installation conditions Other information

Hammer Small edge Variable European CE Corrosion High PROFIS


drilled holes embedment embedment Technical conformity resistance corrosion Anchor
depth depth Assessment resistance design
software

Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical Approval a) DIBt, Berlin, Germany ETA-15/0197 / 2015-12-09
c) All data given in this section according to ETA-15/0197, issue 2015-12-09.

13 Updated: Sep-19
Brick types and properties

Instruction to this technical data


 Identify/choose your brick (or brick type) and its geometrical/physical properties on the following
tables.Information about edge and spacing criteria for every brick is available on page 4.
 The pages reffered on the last column of the table below contain the design resistance loads for pull-out failure
of the anchor, brick breakout failure and local brick failure for each respective brick. Notice that the data
displayed on these tables is only valid for single anchors with distance to edge equal to or greater than ccr – for
other cases not covered, use PROFIS Anchor software, consult ETA-15/0197 or contact Hilti Engineering
Team.
 The resistance loads provided by this technical data manual are valid only for exact same masonry unit (hollow
bricks) or for units made of the same base material with equal or higher size and compressive strength (solid
bricks). For other cases, on-site tests must be performed-please consult page 8.

Interior dimensions
Exterior brick dimensions
of the majority of the holes

Generic bricks

Brick types and properties


Brick Size tO tI a fb ρ
Data Brick name Image Page
code [mm] [mm] [mm] [mm] [N/mm2] [kg/dm3]
Solid Clay
l: ≥ 240
Solid clay brick Mz,
SC ETA b: ≥ 115 - - - 12 2,0 17
2DF
h: ≥ 113
Hollow Clay
l: 300
Hollow clay brick Hlz, tO1:12 tI1:11 a1: 10
HC ETA b: 240 12/20 1,4 17
10DF tO2:15 tI2:15 a2: 25
h: 238
Solid Calcium Silicate
l: ≥ 240
Solid silica brick KS,
SCS ETA b: ≥ 115 - - - 12/28 2,0 17
2DF
h: ≥ 113
Hollow Calcium Silicate
l: 248
Hollow silica brick tO1:34 tI1:12 a1: 50
HCS ETA b: 240 12/20 1,4 17
KSL, 8DF tO2:21 tI2:30 a2: 50
h: 238
Hollow lightweight concrete
l: 495
Hollow lightweight tO1:45 tI1:35 a1:196
HLWC ETA b: 240 2/6 0,8 18
concrete brick tO2:51 tI2:36 a2: 52
h: 238
Hollow normal weight concrete
l: 500
Hollow normal weight tO1:30 tI1:15 a1:133
HNWC ETA b: 200 4/10 1,0 18
concrete brick tO2:15 tI2:15 a2: 75
h: 200

Updated: Sep-19 14
Anchor installation parameters

Brick position: Spacing and edge distance:

 Header (H): The longest dimension of the


 c - Distance to the edge
brick represents the width of the wall
 Stretcher (S): The longest dimension of the
 s ║ - Spacing parallel to the horizontal joint
brick represents the length of the wall  s ┴ - Spacing perpendicular to the horizontal joint

Minimum and characteristic spacing and edge distance parameters

 cmin – Minimum edge distance  smin ║ - Min. spacing distance  smin ┴ - Min. spacing distance
parallel to the bed joint perpendicular to the bed joint
 ccr – Characteristic edge  scr ║ - Characteristic spacing  scr ┴ - Characteristic spacing
distance distance parallel to the bed joint distance perpendicular to the
bed joint

Allowed anchor positions:

c ≥ ccr = cmin c ≥ ccr = cmin

sII ≥ scr II = smin II

s┴ ≥ scr ┴ = smin ┴

 This FTM includes the load data for single


anchors in masonry with a distance to edge equal
to or greater than the characteristic edge distance. sII ≥ scr II = smin II

s┴ ≥ scr ┴ = smin ┴

15 Updated: Sep-19
Edge and spacing distances per brick
cmin= ccr sminII= scrII smin┴ = scr┴
Brick code
[mm] [mm] [mm]
SC 115 240 115
HC 150 300 240
SCS 115 240 115
HCS 125 248 240
HLC 250 240 240
HNC 200 200 200

Anchor dimensions
Anchor size M8 M10 M12
Embedment depth HIT-V-(R, HCR) hef [mm] 80
Embedment depth HIT-IT hef [mm] 80

Design

 Anchorages are designed under the responsibility of an engineer experienced in anchorages and masonry work.
 Verifiable calculation notes and drawings are prepared taking account of the loads to be anchored. The position
of the anchor is indicated on the design drawings (e.g. position of the anchor relative to supports, etc.).
 Anchorages under static or quasi-static loading are designed in accordance with: ETAG 029, Annex C, Design
method A.

Basic loading data (for a single anchor)


The load tables provide the design resistance load for a single loaded anchor.

All data in this section applies to:


 Edge distance c ≥ ccr = cmin.
 Correct anchor setting (see instruction for use, setting details)

Anchorages subject to: Hilti HIT-HY 170 with HIT-V or HIT-IC


Masonry in solid bricks in hollow bricks
Hole drilling hammer mode rotary mode
Category d/d - Installation and use in structures subject to dry internal
conditions.
Use category: dry or wet Category w/d - Installation in dry or wet substrate and use in structures subject
structure to dry, internal conditions.
Category w/w - Installation and use in structures subject to dry or wet
environmental conditions.
Installation direction horizontal
Use category b (solid masonry) c (hollow or perforated masonry)
Temperature in the base
+5° C to +40° C -5° C to +40° C
material at installation
Temperature (max. long term temperature +24°C and
-40 °C to +40°C
In-service range Ta: max. short term temperature +40 °C)
temperature Temperature (max. long term temperature +50°C and
-40 °C to +80°C
range Tb: max. short term temperature +80 °C)

Updated: Sep-19 16
Tension loading
The design tensile resistance is the lower value of
- Steel resistance: NRd,s
- Pull-out of the anchor: NRd,p
- Brick breakout failure: NRd,b
- Pull out of one brick NRd,pb

Shear loading
The design shear resistance is the lower value of
- Steel resistance: VRd,s
- Local brick failure: VRd,b
- Pushing out of one brick: VRd,pb

Design tension and shear resistances – Steel failure for HIT-V


Anchor size M8 M10 M12
HIT-V 5.8(F) 12,2 19,3 28,1
HIT-V 8.8(F) 19,5 30,9 44,9
Tension NRd,s [kN]
HIT-V-R 13,7 21,7 31,6
HIT-V-HCR 19,5 30,9 44,9
HIT-V 5.8(F) 7,4 11,6 16,9
HIT-V 8.8(F) 11,7 18,6 27,0
Shear VRd,s [kN]
HIT-V-R 8,2 13,0 18,9
HIT-V-HCR 11,7 18,6 27,0
HIT-V 5.8(F) 15,0 29,9 52,4
HIT-V 8.8(F) 24,0 47,8 83,8
M0Rd,s [Nm]
HIT-V-R 16,9 33,6 59,0
HIT-V-HCR 24,0 47,8 83,8

Design tension and shear resistances – Steel failure for internally threaded sleeves HIT-IC
Anchor size M8 M10 M12
Tension NRd,s HIT-IC [kN] 3,9 4,8 9,1
HIT-IC 7,4 11,6 16,9
Shear VRd,s [kN]
Screw 8.8 11,7 18,6 27,0
HIT-IC 15,0 29,9 52,4
M0Rd,s [Nm]
Screw 8.8 24,0 47,8 83,8

17 Updated: Sep-19
Design tension and shear resistances – Pull-out failure of the anchor, brick breakout
failure and local brick failure at characteristic edge distance (c ≥ ccr = cmin) for single anchor
applications
w/w and w/d d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
SC - Solid clay brick
Mz, 2DF
HIT-V M8, M10, M12 1,2 1,0 1,2 1,0
HIT-IC M8 1,2 1,0 1,2 1,0
NRd,p = NRd,b
HIT-IC M10, M12 80 12 1,6 1,4 1,6 1,4
(ccr = cmin = 115mm)
HIT-V + HIT-SC M8, M10, M12 1,6 1,4 1,6 1,4
HIT-IC + HIT-SC M8, M10, M12 1,6 1,4 1,6 1,4
HIT-V M8, M10, M12
VRd,b HIT-V + HIT-SC M8, M10, M12
80 12 1,4
(ccr = cmin = 115mm) HIT-IC M8, M10, M12
HIT-IC + HIT-SC M8, M10, M12
HC - Hollow clay brick
Hlz, 10DF

NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 12 1,2 1,0 1,2 1,0
80
(ccr = cmin = 150 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,4 1,2 1,4 1,2
VRd,b HIT-V + HIT-SC M8, M10, M12 12 0,8
80
(ccr = cmin = 150 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,2
SCS - Solid silica brick
KS, 2DF

HIT-V M8, M10, M12 12 2,2 2,0 2,4 2,0


NRd,p = NRd,b HIT-IC M8, M10, M12 28 3,4 3,0 3,4 3,0
80
(ccr = cmin = 115 mm) HIT-V + HIT-SC M8, M10, M12 12 1,6 1,4 2,2 2,0
HIT-IC + HIT-SC M8, M10, M12 28 2,4 2,2 3,2 3,0
HIT-V M8, M10, M12
12 1,6
VRd,b HIT-V + HIT-SC M8, M10, M12
80
(ccr = cmin = 115 mm) HIT-IC M8, M10, M12
28 2,4
HIT-IC + HIT-SC M8, M10, M12
HCS - Hollow silica brick
KSL, 8DF

NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 12 1,2 1,0 1,4 1,2
80
(ccr = cmin = 125 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,6 1,4 2,0 1,8
VRd,b HIT-V + HIT-SC M8, M10, M12 12 3,4
80
(ccr = cmin = 125 mm) HIT-IC + HIT-SC M8, M10, M12 20 4,8

Updated: Sep-19 18
w/w and w/d d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
HLWC – Hollow lightweight concrete brick
HBL, 16DF

NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 2 0,5 0,4 0,6 0,5
80
(ccr = cmin = 250 mm) HIT-IC + HIT-SC M8, M10, M12 6 0,8 0,6 1,0 0,8
VRd,b HIT-V + HIT-SC M8, M10, M12 2 1,0
80
(ccr = cmin = 250 mm) HIT-IC + HIT-SC M8, M10, M12 6 1,6
HNWC – Hollow normal weight concrete brick
Parpaing creux

NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 4 0,4


80
(ccr = cmin = 200 mm) HIT-IC + HIT-SC M8, M10, M12 10 0,5 0,6
VRd,b HIT-V + HIT-SC M8, M10, M12 4 1,0
80
(ccr = cmin = 200 mm) HIT-IC + HIT-SC M8, M10, M12 10 1,6

Design tension and shear resistances – Pull out and pushing out of one brick failures

Pull out of one brick (tension):


NRd,pb = 2 ∙ l ∙ b ∙ (0,5 ∙ fvko + 0,4 ∙ σd) / (2,5 ∙ 1000) [kN]

NRd,pb* = (2 ∙ l ∙ b ∙ (0,5 ∙ fvko + 0,4 ∙ σd) + b ∙ h ∙ fvko) / (2,5 ∙ 1000) [kN]


* this equation is applicable if the vertical joints are filled

Pushing out of one brick (shear):


VRd,pb = 2 ∙ l ∙ b ∙ (0,5 ∙ fvko + 0,4 ∙ σd) / (2,5 ∙ 1000) [kN]

σd = design compressive stress perpendicular to the shear (N/mm 2)


fvko = initial shear strength according to EN 1996-1-1, Table 3.4
Brick type Mortar strength fvko [N/mm2]
Clay brick M2,5 to M9 0,20
M10 to M20 0,30
All other types M2,5 to M9 0,15
M10 to M20 0,20

19 Updated: Sep-19
On-site test

For other bricks in solid or hollow masonry, not covered by the Hilti HIT-HY 170 ETA or this technical data manual,
the characteristic resistance may be determined by on-site tension tests (pull-out tests or proof-load tests), according
to ETAG029, Annex B.

For the evaluation of test results, the characteristic resistance shall be obtained taking into account the factor, which
considers the different influences of the product.

The factor for the brick types covered by the Hilti HIT-HY 170 ETA is provided in the following table:

Use categories w/w and w/d d/d


Temperature range Ta* Tb* Ta* Tb*
Base material Elements
HIT-V or HIT-IC
Solid clay brick HIT-V + HIT-SC 0,97 0,83 0,97 0,83
HIT-IC + HIT-SC
HIT-V or HIT-IC 0,96 0,84 0,97 0,84
Solid calcium silicate brick HIT-V + HIT-SC
0,69 0,62 0,91 0,82
HIT-IC + HIT-SC
HIT-V + HIT-SC
Hollow clay brick 0,97 0,83 0,97 0,83
HIT-IC + HIT-SC
HIT-V + HIT-SC
Hollow calcium silicate brick 0,69 0,62 0,91 0,82
HIT-IC + HIT-SC
HIT-V + HIT-SC
Hollow lightweight concrete brick 0,89 0,81 0,97 0,86
HIT-IC + HIT-SC
HIT-V + HIT-SC
Hollow normal weight concrete brick 0,97 0,80 0,97 0,80
HIT-IC + HIT-SC
*Ta / Tb, w/w and d/d anchorage parameters, as defined on Tables pages 8-9
Applying the factor from the table above, the characteristic tension resistance N Rk can be obtained. Characteristic
shear resistance VRk can also be directly derived from NRk. For detailed procedure consult ETAG 029, Annex B.

Updated: Sep-19 20
Materials

Material quality
Part Material
Threaded rod Strength class 5.8, A5 > 8% ductile
HIT-V 5.8 (F) Steel galvanized  5m; (F) Hot dip galvanized ≥ 45 m
Threaded rod Strength class 8.8, A5 > 8% ductile
HIT-V 8.8 (F) Steel galvanized  5m; (F) Hot dip galvanized ≥ 45 m
Threaded rod Strength class 70 for ≤ M24 and class 50 for > M24, A5 > 8% ductile
HIT-V-R Stainless steel 1.4401; 1.4404; 1.4578; 1.4571; 1.4439; 1.4362
Threaded rod A5 > 8% ductile
HIT-V-HCR High corrosion resistant steel 1.4528, 1.4565
A5 > 8% ductile
Internally threaded sleeve HIT-IC
Electroplated zinc coated  5m
Steel galvanized
Washer Stainless steel 1.4401; 1.4404; 1.4578; 1.4571; 1.4439; 1.4362
High corrosion resistant steel 1.4529, 1.4565 EN 10088
Strength class 8
Electroplated zinc coated  5m
Hot dip galvanized  45m
Hexagon nut
Strength class 70
Stainless steel grade A4 1.4401;1.4404;1.4578;1.4571;1.4439; 1.4362
Strength class 70, high corrosion resistant steel,1.4529; 1.4565
A5 > 8% ductile
Internally threaded sleeve HIT-IC
Electroplated zinc coated  5 m
Frame: Polyfort FPP 20T
Sieve sleeve HIT-SC
Sieve: PA6.6 N500/200

Base materials:
 Solid brick masonry. The characteristic resistances are also valid for larger brick sizes and larger compressive
strengths of the masonry unit.
 Hollow brick masonry
 Mortar strength class of the masonry: M2,5 at minimum according to EN 998-2: 2010.
 For other bricks in solid masonry and in hollow or perforated masonry, the characteristic resistance of the anchor
may be determined by on-site tests according to ETAG 029, Annex B under consideration of the β-factor
according to Table page 9.

Setting information

Installation temperature range:


-5°C to +40°C

In service temperature range


Hilti HIT-HY 170 injection mortar may be applied in the temperature ranges given below. An elevated base material
temperature may lead to a reduction of the design bond resistance.

Base material Max. long term base Max. short term base
Temperature range
temperature material temperature material temperature
Temperature range I -40 °C to + 40 °C + 24 °C + 40 °C
Temperature range II -40 °C to + 80 °C + 50 °C + 80 °C

21 Updated: Sep-19
Max. short term base material temperature
Short term elevated base material temperatures are those that occur over brief intervals, e.g. as a result of diurnal
cycling.
Max. long term base material temperature
Long term elevated base material temperatures are roughly constant over significant periods of time.

Working time and curing time


Temperature of the Maximum working time Minimum curing time
base material twork tcure
-5 °C ≤ TBM ≤ 0 °C a) 10 min 12 h
0 °C ≤ TBM ≤ 5 °C a) 10 min 5h
5 °C ≤ TBM ≤ 10 °C 8 min 2,5 h
10°C ≤ TBM ≤ 20 °C 5 min 1,5 h
20 °C ≤ TBM ≤ 30 °C 3 min 45 min
30 °C ≤ TBM ≤ 40 °C 2 min 30 min
The curing time data are valid for dry base material only. In wet base material the curing times must be doubled.
a) Data valid for hollow bricks only

Insallation Paramenters

Single sieve sleeve, 50mm > hef > 80mm

Installation parameters of HIT-V with sieve sleeve HIT-SC in hollow and solid brick
Threaded rods and HIT-V M8 M10 M12
with HIT-SC 16x85 18x85
Nominal diameter of drill bit d0 [mm] 16 16 18
Drill hole depth h0 [mm] 95 95 95
Effective embedment depth hef [mm] 80 80 80
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 16 16 18
Number of strokes HDM 6 6 8
Number of strokes HDE 500- 5 5 6
A
Maximum torque moment for
all brick types except Tmax [Nm] 3 4 6
“parpaing creux”
Maximum torque moment for
Tmax [Nm] 2 2 3
“parpaing creux”

Updated: Sep-19 22
Installation parameters of HIT-IC with HIT-SC in hollow and solid brick
HIT-IC M8 M10 M12
with HIT-SC 16x85 18x85 22x85
Nominal diameter of drill bit d0 [mm] 16 18 22
Drill hole depth h0 [mm] 95 95 95
Effective embedment depth hef [mm] 80 80 80
Thread engagement length hs [mm] 8…75 10…75 12…75
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 16 18 22
Number of strokes HDM 6 8 10
Number of strokes HDE-500 5 6 8
Maximum torque moment Tmax [Nm] 3 4 6

Solid bricks without sieve sleeves a)

Installation parameters of HIT-V in solid bricks


Threaded rods and HIT-V M8 M10 M12
Nominal diameter of drill bit d0 [mm] 10 12 14
Drill hole depth =
h0= hef [mm] 50…300 50…300 50…300
Effective embedment depth
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] h0+30 h0+30 h0+30
Brush HIT-RB 10 12 14
Maximum torque moment Tmax [Nm] 5 8 10
a) Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks
when it is guaranteed that it has not any hole or void.

23 Updated: Sep-19
Installation parameters of HIT-IC in solid bricks
HIT-IC M8x80 M10x80 M12x80
Nominal diameter of drill bit d0 [mm] 14 16 18
Drill hole depth =
h0= hef [mm] 80 80 80
Effective embedment depth
Thread engagement length hs [mm] 8…75 10…75 12…75
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 14 16 18
Maximum torque moment Tmax [Nm] 5 8 10
a) Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks
when it is guaranteed that it has not any hole or void.

Installation equipment
Anchor size M8 M10 M12
Rotary hammer TE2(A) – TE30(A)
compressed air gun or blow out pump, set of cleaning brushes,
Other tools
dispenser

Drilling and cleaning parameters


Brush Piston plug
HIT-V HIT-IC + Hammer drill
HIT-V a) HIT-IC a) HIT-RB HIT-SZ
+ sieve sleeve sieve sleeve
d0 [mm] size [mm]

M8 - - - 10 10 -
M10 - - - 12 12 12
M12 - M8 - 14 14 14
- M8 - - 16 16 16
- M10 M10 M8 16 16 16
- M12 M12 M10 18 18 18
- - - M12 22 22 22
a) Installation without the sieve sleeve HIT-SC can be used only in case of solid bricks.

Updated: Sep-19 24
Setting instructions

*For detailed information on installation see instruction for use given with the package of the product.
Safety regulations.
Review the Material Safety Data Sheet (MSDS) before use for proper and safe
handling! Wear well-fitting protective goggles and protective gloves when working
with Hilti HIT-HY 170.
Drilling

In hollow bricks: rotary mode

In solid bricks: hammer mode

Cleaning

Manual cleaning (MC)

Compressed air cleaning (CAC)

Instructions for solid bricks without sieve sleeve


Injection system

Injection system preparation.

Injection method for drill hole

25 Updated: Sep-19
Setting the element

Presetting element, observe working


time “twork”,

Loading the anchor: After required


curing time tcure the anchor can be
loaded.

Instructions for hollow and solid bricks with sieve sleeve


Praparation of the sieve sleeve

Close lid and insert sieve sleeve


manually

Injection system

Injection system preparation.

Injection system: hollow bricks

Installation with sieve sleeve HIT-SC

Setting the element

Presetting element, observe working


time “twork”,

Loading the anchor: After required


curing time tcure the anchor can be
loaded.

Updated: Sep-19 26
Hilti HSA
EXPANSION ANCHOR
Technical Datasheet
Update: May-19
Standard stud anchor HSA

BASE MATERIALS Approvals


● Concrete (uncracked) ETA
ETA 11/0374 for HSA stud anchor (ETAG 001-02,
Option 7)
Approvals and test reports may apply to selected products only. Please refer
APPLICATIONS to the documents for details.
● Wide range of fastening applications in concrete
Watch Video
● Fastening facade brackets
● Fastening columns and beams
● Fastening brackets and channels

ADVANTAGES
● ETA-approved torquing using SIW 14-A or 22-A impact wrench
and S-TB
● Fast and easy anchor setting with HS-SC and S-TB
● Excellent edge and spacing distances
● 3 embedment depths offering maximum flexibility
● Suitable for presetting and through-fastening in uncracked
concrete
These are abbreviated instructions which may vary according to the application.

Recommended load (kN), non-cracked concrete at 25N/mm², safety factor(γ)=3

Technical data Model Size M6 M8 M10 M12 M16 M20

Material composition (Galvanized) Steel, zinc-plated (min. HSA Tensile Load, Nrec 2.5 4.2 5.9 8.8 12.0 16.8
5 μm); (standard
(Hot-dip galvanized) Steel, hot-dip embedment) Shear Load, Vrec 2.1 3.5 6.3 9.8 17.0 28.6
galvanized (min. 5 μm); HSA-R/R2 Tensile Load, Nrec 2.5 4.2 5.9 8.8 12.0 16.8
(Stainless steel) Steel, A4(SS316), (standard
A2(SS304) embedment) Shear Load, Vrec 2.4 4.1 7.5 9.7 18.8 30.6
Head configuration Externally threaded Remarks:
Type of fastening Pre-fastening, Through-fastening 1) All the data applies to no edge distance, spacing and other influences
2) For detail design method and cracked concrete information, please refer to Fastening
Approvals / test reports ETA, Fire Technology Manual

Hilti online: www.hilti.com.hk


289
ANCHORING SYSTEMS 8
HSA (Galvanized min. 5μm)

Order Now

Ordering designation Anchor  Anchor  Drill bit  Drill. hole  Drill. hole  Drill. hole  Fastening  Fastening  Fastening  Base  Required  Sales  Item number
size length diameter depth at  depth at  depth at  thick- thick- thick- plate  tight- pack 
embed.1 embed.2 embed.3 ness at  ness at  ness at  clear- ening  quantity
embed.1 embed.2 embed.3 ance  torque
hole
HSA M6x50 5/-/-  M6 50 mm 6 mm 42 mm - - 5 mm - - 7 mm 5 Nm 200 pc 2036084
HSA M6x65 20/10/-  M6 65 mm 6 mm 42 mm 52 mm - 20 mm 10 mm - 7 mm 5 Nm 200 pc 2036085
HSA M6x85 40/30/10  M6 85 mm 6 mm 42 mm 52 mm 72 mm 40 mm 30 mm 10 mm 7 mm 5 Nm 100 pc 2036086
HSA M6x100 55/45/25  M6 100 mm 6 mm 42 mm 52 mm 72 mm 55 mm 45 mm 25 mm 7 mm 5 Nm 100 pc 2036087
HSA M8x55 5/-/-  M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004122
HSA M8x70 20/10/-  M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004123
HSA M8x85 35/25/-  M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004124
HSA M8x105 55/45/15  M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 2004125
HSA M8x130 80/70/40 M8 129.5 mm 8 mm 44 mm 54 mm 84 mm 80 mm 70 mm 40 mm 9 mm 15 Nm 50 pc 20041261)
HSA M10X68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 2004127
HSA M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004128
HSA M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 2004129
HSA M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004150
HSA M10x133 70/60/30 M10 133 mm 10 mm 55 mm 65 mm 95 mm 70 mm 60 mm 30 mm 12 mm 25 Nm 25 pc 20041511)
HSA M10x153 90/80/50 M10 153 mm 10 mm 55 mm 65 mm 95 mm 90 mm 80 mm 50 mm 12 mm 25 Nm 25 pc 2004152
HSA M10x168 105/95/65 M10 168 mm 10 mm 55 mm 65 mm 95 mm 105 mm 95 mm 65 mm 12 mm 25 Nm 25 pc 20041531)
HSA M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004154
HSA M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004155
HSA M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004156
HSA M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 2004157
HSA M12x175 95/80/45 M12 174.5 mm 12 mm 72 mm 87 mm 122 mm 95 mm 80 mm 45 mm 14 mm 50 Nm 25 pc 2004158
HSA M12x205 25/110/75 M12 204.5 mm 12 mm 72 mm 87 mm 122 mm 125 mm 110 mm 75 mm 14 mm 50 Nm 25 pc 20041591)
HSA M12x225 45/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20041601)
HSA M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 2004161
HSA M16x117 20/5/- M16 116.5 mm 16 mm 85 mm 100 mm - 20 mm 25 mm - 18 mm 80 Nm 16 pc 2004162
HSA M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004163
HSA M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004164
HSA M16x232 35/120/80 M16 231.5 mm 16 mm 85 mm 100 mm 140 mm 135 mm 120 mm 80 mm 18 mm 80 Nm 16 pc 2004165 8
HSA M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 2036088
HSA M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 2036089
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products

Customer Hotline: Hong Kong 8228 8118, Macau 00800 8228 8118 Email: hksales@hilti.com
290
HSA-F (Hot-dip galvanized min. 35μm)

Order Now

Ordering designation Anchor Anchor Drill bit Drilling Drilling Drilling Fastening Fastening Fastening Base Required Sales Item
size length diameter Hole Hole Hole thickness thickness thickness plate tightening pack number
Depth at Depth at Depth at at at at clearance torque quantity
embed. 1 embed. 2 embed. 3 embed.1 embed.2 embed.3 hole
HSA-F M8x55 5/-/- M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004113
HSA-F M8x70 20/10/- M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004114
HSA-F M8x85 35/25/- M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004115
HSA-F M8x105 55/45/15 M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 20041161)
HSA-F M8x130 80/70/40 M8 129.5 mm 8 mm 44 mm 54 mm 84 mm 80 mm 70 mm 40 mm 9 mm 15 Nm 50 pc 20041171)
HSA-F M10x68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 20041181)
HSA-F M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004119
HSA-F M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 20041701)
HSA-F M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004171
HSA-F M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004172
HSA-F M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004173
HSA-F M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004174
HSA-F M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 2004175
HSA-F M12x225 145/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20041761)
HSA-F M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 20041771)
HSA-F M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004178
HSA-F M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004179
HSA-F M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 20363121)
HSA-F M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 2036313
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products

Hilti online: www.hilti.com.hk


291
ANCHORING SYSTEMS 8
HSA-R (Stainless steel A4)

Order Now

Ordering designation Anchor Anchor Drill bit Drilling Drilling Drilling Fastening Fastening Fastening Base Required Sales Item
size length diameter Hole Hole Hole thickness thickness thickness plate tightening pack number
Depth at Depth at Depth at at at at clearance torque quantity
embed. 1 embed. 2 embed. 3 embed.1 embed.2 embed.3 hole
HSA-R M6x50 5/-/- M6 50 mm 6 mm 42 mm - - 5 mm - - 7 mm 5 Nm 200 pc 2036314
HSA-R M6x65 20/10/- M6 65 mm 6 mm 42 mm 52 mm - 20 mm 10 mm - 7 mm 5 Nm 200 pc 2036315
HSA-R M6x85 40/30/10 M6 85 mm 6 mm 42 mm 52 mm 72 mm 40 mm 30 mm 10 mm 7 mm 5 Nm 100 pc 2036316
HSA-R M8x55 5/-/- M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004197
HSA-R M8x70 20/10/- M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004198
HSA-R M8x85 35/25/- M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004199
HSA-R M8x105 55/45/15 M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 2004200
HSA-R M10x68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 2004201
HSA-R M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004202
HSA-R M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 2004203
HSA-R M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004204
HSA-R M10x133 70/60/30 M10 133 mm 10 mm 55 mm 65 mm 95 mm 70 mm 60 mm 30 mm 12 mm 25 Nm 25 pc 20042051)
HSA-R M10x153 90/80/50 M10 153 mm 10 mm 55 mm 65 mm 95 mm 90 mm 80 mm 50 mm 12 mm 25 Nm 25 pc 20042061)
HSA-R M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004207
HSA-R M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004208
HSA-R M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004209
HSA-R M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 20042101)
HSA-R M12x175 95/80/45 M12 174.5 mm 12 mm 72 mm 87 mm 122 mm 95 mm 80 mm 45 mm 14 mm 50 Nm 25 pc 20042111)
HSA-R M12x205 125/110/75 M12 204.5 mm 12 mm 72 mm 87 mm 122 mm 125 mm 110 mm 75 mm 14 mm 50 Nm 25 pc 20042121)
HSA-R M12x225 145/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20042131)
HSA-R M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 2004214
HSA-R M16x117 20/5/- M16 116.5 mm 16 mm 85 mm 100 mm - 20 mm 25 mm - 18 mm 80 Nm 16 pc 20042151)
HSA-R M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004216
HSA-R M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004217
HSA-R M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 20363171)
HSA-R M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 20363181)
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products
8

HSA-R2 (Stainless steel A2)

Order Now

Ordering designation Anchor size Drill bit diameter Fastening Base plate Required Sales pack Item number
thickness clearance tightening quantity
at embed.2 hole torque

HSA-R2 M8x70 20/10/- M8 8 mm 10 mm 9 mm 15 Nm 100 pc 2004218


HSA-R2 M10x83 20/10/- M10 10 mm 10 mm 12 mm 25 Nm 50 pc 2004219
HSA-R2 M12x100 20/5/- M12 12 mm 5 mm 14 mm 50 Nm 25 pc 2004220
HSA-R2 M12x115 35/20/- M12 12 mm 20 mm 14 mm 50 Nm 25 pc 20042211)
HSA-R2 M16x137 40/25/- M16 16 mm 40 mm 18 mm 80 Nm 16 pc 2004222
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products

Customer Hotline: Hong Kong 8228 8118, Macau 00800 8228 8118 Email: hksales@hilti.com
292
Torque bar S-TB

APPLICATIONS Technical data


● For setting HSA stud anchors with maximum accuracy and Base material Concrete (uncracked)
productivity Connection end size 12.7 mm
Drive connection 1/2 in square, female

Ordering  Drive connection Drive head Material coating/ Material  Tool type Base material Connection end  Sales  Item number
designation plating/finish composition size pack 
quantity
S-TB HSA M8  1/2 in square,  1/2 in, square,  Black Impact-grade  Impact tools,  Concrete  12.7 mm 1 pc 423774
female male chrome  SIW (uncracked)
molybdenum 
steel
S-TB HSA M10  1/2 in square,  1/2 in, square,  Black Impact-grade  Impact tools,  Concrete  12.7 mm 1 pc 423775
female male chrome  SIW (uncracked)
molybdenum 
steel
S-TB HSA M12  1/2 in square,  1/2 in, square,  Black Impact-grade  Impact tools,  Concrete  12.7 mm 1 pc 423776
female male chrome  SIW (uncracked)
molybdenum 
steel
S-TB HSA M16  1/2 in square,  1/2 in, square,  Black Impact-grade  Impact tools,  Concrete  12.7 mm 1 pc 423777
female male chrome  SIW (uncracked)
molybdenum 
steel

Please visit Hilti website for the latest item numbers and related products

Setting tool and torque bar

① ②

Order designation Description Outside diameter Length Package  Item no.


SIW 14-A 1.6AH SIW 14-A lithium cordless impact wrench (14.4v  2 batteries,   - - 1 pc 3485630
1 charger) For M8-M12
SIW 14-A 3.3AH SIW 14-A lithium cordless impact wrench (14.4v  2 batteries,   1 pc 3485631
- -
1 charger) For M8-M12
SIW 22T-A 3.3AH SIW 22T-A lithium cordless impact wrench (21.6v  2 batteries,   1 pc 3469136
- -
1 charger) For M16
S-TB HSA M8 Torque bar S-TB HSA M8 (For HSA/HSA-R M8) 20 mm 215 mm 1 pc 423774
S-TB HSA M10 ① Torque bar S-TB HSA M10 (For HSA/HSA-R M10) 26 mm 174 mm 1 pc 423775
S-TB HSA M12 Torque bar S-TB HSA M12 (For HSA/HSA-R M12) 28 mm 174 mm 1 pc 423776
S-TB HSA M16 Torque bar S-TB HSA M16 (For HSA/HSA-R M16) 34 mm 174 mm 1 pc 423777
HS-SC M8-M16 ② Setting tool HS-SC M8-M16 - - 1 pc 2051443

Please visit Hilti website for the latest item numbers and related products

Hilti online: www.hilti.com.hk


293
HSA Expansion anchor
Everyday standard expansion anchor for uncracked concrete
Anchor version Benefits
- Fast & convenient setting behaviour
HSA
- Reliable ETA approved torqueing
HSA-F
using impact wrench with torque bar
HSA-R
for torque control
HSA-R2
(M6-M20) - Small edge and spacing distances
- High loads
- Three embedment depths for maximal
design flexibility
- M12, M16 and M20 ETA approved for
diamond cored holes using DD 30-W
HSA-BW
and matching diamond core bit
(M6-M20)
- Suitable for pre- and through fastening
- Long lengths available suitable for
wood structures fastening applications

Base material Load conditions

Concrete Static/ Fire


(non-cracked) quasi-static resistance

Installation conditions Other information

Hammer Diamond Hollow drill- Small edge European CE PROFIS Corrosion


drilled holes drilled holes bit drilling distance and Technical conformity Anchor resistance
spacing Assessment design
Software

Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical assessment a) DIBt, Berlin ETA-11/0374 / 2016-08-08
a) All data given in this section according to ETA-11/0374, issue 2016-08-08.

1 Updated: May-19
Static and quasi-static loading (for a single anchor)

All data in this section applies to:


- Correct setting (See setting instruction)
- No edge distance and spacing influence
- Steel failure
- Minimum base material thickness
- Concrete C 20/25, fck,cube = 25 N/mm²

Effective anchorage depth


Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115

Characteristic resistance
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 6,0 7,5 9,0 8,3 12,8 16,0 12,8 17,9 25,0
Tension
HSA-R2, HSA-R [kN] 6,0 7,5 9,0 8,3 12,8 16,0 12,8 17,9 25,0
NRk
HSA-F 6,0 7,5 9,0 8,3 12,8 15,9 12,8 17,9 25,0
HSA, HSA-BW 6,5 6,5 6,5 8,3 10,6 10,6 18,9 18,9 18,9
Shear
HSA-R2, HSA-R [kN] 7,2 7,2 7,2 8,3 12,3 12,3 22,6 22,6 22,6
VRk
HSA-F 6,5 6,5 6,5 8,3 10,6 10,6 18,9 18,9 18,9
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 17,9 26,5 35,0 26,5 36,1 50,0 32,8 50,5 62,3
Tension
HSA-R2, HSA-R [kN] 17,9 26,5 35,0 26,5 36,1 50,0 32,8 50,5 62,3
NRk
HSA-F 17,9 26,5 35,0 26,5 36,1 50,0 32,8 b) 50,5 b) 62,3 b)
HSA, HSA-BW 29,5 29,5 29,5 51,0 51,0 51,0 65,6 85,8 85,8
Shear
HSA-R2, HSA-R [kN] 29,3 29,3 29,3 56,5 56,5 56,5 65,6 91,9 91,9
VRk
HSA-F 29,5 29,5 29,5 51,0 51,0 51,0 65,6b) 85,8b) 85,8b)
b) Data covered by Hilti Technical Data.

Design resistance
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
Tension
HSA-R2, HSA-R [kN] 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
NRd
HSA-F 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
HSA, HSA-BW 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
Shear
HSA-R2, HSA-R [kN] 5,5 5,8 5,8 5,5 9,8 9,8 18,1 18,1 18,1
VRd
HSA-F 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 11,9 17,6 23,3 17,6 24,1 33,3 21,9 33,7 41,5
Tension
HSA-R2, HSA-R [kN] 11,9 17,6 23,3 17,6 24,1 33,3 21,9 33,7 41,5
NRd
HSA-F 11,9 17,6 23,3 17,6 24,1 33,3 21,9 b) 33,7 b) 41,5 b)
HSA, HSA-BW 23,6 23,6 23,6 40,8 40,8 40,8 43,7 68,6 68,6
Shear
HSA-R2, HSA-R [kN] 23,4 23,4 23,4 45,2 45,2 45,2 43,7 73,5 73,5
VRd
HSA-F 23,6 23,6 23,6 40,8 40,8 40,8 43,7 b) 68,6 b) 68,6 b)
b) Data covered by Hilti Technical Data.

Updated: May-19 2
Recommended loads a)
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 2,9 3,6 4,3 4,0 6,1 7,6 6,1 8,5 11,9
Tension 4,0 6,1
HSA-R2, HSA-R [kN] 2,9 3,6 4,3 7,6 6,1 8,5 11,9
Nrec
HSA-F 2,9 3,6 4,3 4,0 6,1 7,6 6,1 8,5 11,9
HSA, HSA-BW 3,7 3,7 3,7 4,0 6,1 6,1 10,8 10,8 10,8
Shear 4,0
HSA-R2, HSA-R [kN] 4,0 4,1 4,1 7,0 7,0 12,9 12,9 12,9
Vrec
HSA-F 3,7 3,7 3,7 4,0 6,1 6,1 10,8 10,8 10,8
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 8,5 12,6 16,7 12,6 17,2 23,8 15,6 24,0 29,7
Tension
HSA-R2, HSA-R [kN] 8,5 12,6 16,7 12,6 17,2 23,8 15,6 24,0 29,7
Nrec
HSA-F 8,5 12,6 16,7 12,6 17,2 23,8 15,6 b) 24,0 b) 29,7 b)
HSA, HSA-BW 16,9 16,9 16,9 29,1 29,1 29,1 31,2 49,0 49,0
Shear
HSA-R2, HSA-R [kN] 16,7 16,7 16,7 32,3 32,3 32,3 31,2 52,5 52,5
Vrec
HSA-F 16,9 16,9 16,9 29,1 29,1 29,1 31,2 b) 49,0 b) 49,0 b)
a) With overall partial safety factor for action  = 1,4. The partial safety factors for action depend on the type of loading and shall be
taken from national regulations.
b) Data covered by Hilti Technical data

Materials

Mechanical properties
Anchor size M6 M8 M10 M12 M16 M20
Nominal tensile HSA, HSA-BW, HSA-F 650 580 650 700 650 700
[N/mm²]
strength fuk,thread
HSA-R2, HSA-R 650 560 650 580 600 625
Yield strength HSA, HSA-BW, HSA-F 520 464 520 560 520 560
fyk,thread HSA-R2, HSA-R [N/mm²] 520 448 520 464 480 500
Stressed cross-section As [mm²] 20,1 36,6 58 84,3 157 245
Moment of resistance W [mm³] 12,7 31,2 62,3 109,2 277,5 540,9
Char. bending HSA, HSA-BW, HSA-F 9,9 21,7 48,6 91,7 216,4 454,4
[Nm]
resistance HSA-R2, HSA-R 9,9 21 48,6 76 199,8 405,7
M0Rk,s

3 Updated: May-19
Material quality
Part Material
Bolt Galvanized (≥5 µm)
HSA
Sleeve Galvanized (≥5 µm)
HSA-BW
Washer Galvanized (≥5 µm)
(Carbon steel)
Hexagon nut Strength class 8 / Galvanized (≥5 µm)
Bolt Stainless steel A2, 1.4301; M6-M20 coated
HSA-R2 Sleeve Stainless steel A2
(Stainless steel) Washer Stainless steel A2
Hexagon nut Stainless steel A2; / M6-M20 coated
Bolt Stainless steel A4, 1.4401 or 1.4362 / M6-M20 coated
HSA-R Sleeve Stainless steel A2
(Stainless steel) Washer Stainless steel A4
Hexagon nut Stainless steel A4; / M6-M20 coated
Bolt Hot-dip galvanized (≥42 µm)
HSA-F Sleeve Stainless steel A2
(Carbon steel) Washer Hot-dip galvanized (≥42 µm)
Hexagon nut Strength class 8 / Hot-dip galvanized (≥42 µm)

Geometry washer
Anchor size M6 M8 M10 M12 M16 M20
Inner diameter d1
HSA, HSA-R2, HSA-R, HSA-F d1 [mm] 6,4 8,4 10,5 13,0 17,0 21
HSA-BW d1 [mm] 6,4 8,4 10,5 13,0 17,0 22
Outer diameter d2
HSA, HSA-R2, HSA-R, HSA-F d2 [mm] 12,0 16,0 20,0 24,0 30,0 37,0
HSA-BW d2 [mm] 18,0 24,0 30,0 37,0 50,0 60,0
Thickness h
HSA, HSA-R2, HSA-R, HSA-F h [mm] 1,6 1,6 2,0 2,5 3,0 3,0
HSA-BW h [mm] 1,8 2,0 2,5 3,0 3,0 4,0
Product marking and identification of anchor:

Updated: May-19 4
Material code for identification of different materials
HSA, HSA-BW, HSA-F HSA-R2 HSA-R
Type
(carbon steel) (Stainless steel grade A2) (stainless steel grade A4)

Material code

Letter code Letter code


Letter code without mark
with two marks with three marks

Letter code for anchor length and maximum thickness of the fixture t fix
Type HSA, HSA-BW, HSA-R2, HSA-R, HSA-F
Size M6 M8 M10 M12 M16 M20
90 / 115 /
hnom [mm] 37 / 47 / 67 39 / 49 / 79 50 / 60 / 90 64 / 79 / 114 77 / 92 / 132
130
Letter tfix tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3
z 5/-/- 5/-/- 5/-/- 5/ -/- 5/-/- 5/-/-
y 10/-/- 10/-/- 10/-/- 10/-/- 10/-/- 10/-/-
x 15/5/- 15/5/- 15/5/- 15/-/- 15/-/- 15/-/-
w 20/10/- 20/10/- 20/10/- 20/5/- 20/5/- 20/-/-
v 25/15/- 25/15/- 25/15 25/10/- 25/10/- 25/-/-
u 30/20/- 30/20/- 30/20/- 30/15/- 30/15/- 30/5/-
t 35/25/5 35/25/- 35/25/- 35/20/- 35/20/- 35/10/-
s 40/30/10 40/30/- 40/30/- 40/25/- 40/25/- 40/15/-
r 45/35/15 45/35/5 45/35/5 45/30/- 45/30/- 45/20/5
q 50/40/20 50/40/10 50/40/10 50/35/- 50/35/- 50/25/10
p 55/45/25 55/45/15 55/45/15 55/40/5 55/40/- 55/30/15
o 60/50/30 60/50/20 60/50/20 60/45/10 60/45/5 60/35/20
n 65/55/35 65/55/25 65/55/25 65/50/15 65/50/10 65/40/25
m 70/60/40 70/60/30 70/60/30 70/55/20 70/55/15 70/45/30
l 75/65/45 75/65/35 75/65/35 75/60/25 75/60/20 75/50/35
k 80/70/50 80/70/40 80/70/40 80/65/30 80/65/25 80/55/40
j 85/75/55 85/75/45 85/75/45 85/70/35 85/70/30 85/60/45
i 90/80/60 90/80/50 90/80/50 90/75/40 90/75/35 90/65/50
h 95/85/65 95/85/55 95/85/55 95/80/45 95/80/40 95/70/55
g 100/90/70 100/90/60 100/90/60 100/85/50 100/85/45 100/75/60
f 105/95/75 105/95/65 105/95/65 105/90/55 105/90/50 105/80/65
e 110/100/80 110/100/70 110/100/70 110/95/60 110/95/55 110/85/70
d 115/105/85 115/105/75 115/105/75 115/100/65 115/100/60 115/90/75
c 120/110/90 120/110/80 120/110/80 125/110/75 120/105/65 120/95/80
b 125/115/95 125/115/85 125/115/85 135/120/85 125/110/70 125/100/85
a 130/120/100 130/120/90 130/120/90 145/130/95 135/120/80 130/105/90
aa - - - 155/140/105 145/130/90 -
ab - - - 165/150/115 155/140/100 -
ac - - - 175/160/125 165/150/110 -
ad - - - 180/165/130 190/175/135 -
ae - - - 230/215/180 240/225/185 -
af - - - 280/265/230 290/275/235 -
ag - - - 330/315/280 340/325/285 -
Anchor length in bolt type and grey shaded are standard items. For selection of other anchor length, check availability of the items.
5 Updated: May-19
Setting information

Setting details
Anchor size M6 M8 M10
Nominal anchorage depth hnom [mm] 37 47 67 39 49 79 50 60 90
Minimum base material
hmin [mm] 100 100 120 100 100 120 100 120 160
thickness
Minimun spacing smin [mm] 35 35 35 35 35 35 50 50 50
Minimum edge distance cmin [mm] 35 35 35 40 35 35 50 40 40
Nominal diameter of drill
d0 [mm] 6 8 10
bit
Cutting diameter of drill bit dcut ≤ [mm] 6,4 8,45 10,45
Depth of drill hole h1 ≥ [mm] 42 52 72 44 54 84 55 65 95
Diameter of clearance
dr ≤ [mm] 7 9 12
hole in the fixture
Torque moment Tinst [Nm] 5 15 25
Width across SW [mm] 10 13 17
Anchor size M12 M16 M20
Nominal anchorage depth hnom [mm] 64 79 114 77 92 132 90 115 130
Minimum base material
hmin [mm] 100 140 180 140 160 180 160 220 220
thickness
Minimun spacing smin [mm] 70 70 70 90 90 90 195 175 175
Minimum edge distance cmin [mm] 70 65 55 80 75 70 130 120 120
Nominal diameter of drill
d0 [mm] 12 16 20
bit
Cutting diameter of drill bit dcut ≤ [mm] 12,5 16,5 20,55
Depth of drill hole h1 ≥ [mm] 72 87 122 85 100 140 98 123 138
Diameter of clearance
dr ≤ [mm] 14 18 22
hole in the fixture
Torque moment Tinst [Nm] 50 80 200
Width across SW [mm] 19 24 30

For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to
be reduced.

Updated: May-19 6
Installation equipment
Anchor size M6 M8 M10 M12 M16 M20
Rotary hammer TE40 –
TE2 – TE16
TE80
Other tools hammer, torque wrench, blow out pump
Machine tightening
Setting tool - S-TB HSA -
Impact screw driver Hilti S/W 14-A Hilti S/W
- -
Hilti S/W 22-A 22T-A
Speed HAS, HAS-BW, HAS-F - 1 -
3 -1)
HAS-R2, HAS-R - 3 -
Setting time tset [sec] - 4 -
1) The impact screw driver operates with a fixed speed.

Setting parameters
Anchor size M6 M8 M10
Nominal anchorage depth hnom [mm] 37 47 67 39 49 79 50 60 90
Effective anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
Critical spacing for
scr,sp [mm] 100 120 130 130 180 200 190 210 290
splitting failure
Critical edge distance for
ccr,sp [mm] 50 60 65 65 90 100 95 105 145
splitting failure
Critical spacing for
scr,N [mm] 90 120 180 90 120 210 120 150 240
concrete cone failure
Critical edge distance for
ccr,N [mm] 45 60 90 45 60 105 60 75 120
concrete cone failure
Anchor size M12 M16 M20
Nominal anchorage depth hnom [mm] 64 79 114 77 92 132 90 115 130
Effective anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
Critical spacing for
scr,sp [mm] 200 250 310 230 280 380 260 370 400
splitting failure
Critical edge distance for
ccr,sp [mm] 100 125 155 115 140 190 130 185 200
splitting failure
Critical spacing for
scr,N [mm] 150 195 300 195 240 360 225 300 345
concrete cone failure
Critical edge distance for
ccr,N [mm] 75 97,5 150 97,5 120 180 112,5 150 172,5
concrete cone failure

7 Updated: May-19
Setting instructions

*For detailed information on installation see instruction for use given with the package of the product
1. Hole drilling
Hammer drilling with Hilti hollow
Hammer drilling (HD): M6-M20 Diamond drilling (DD): M10-M20
drill bit (HDB): M12-M20

2. Cleaning
Manual cleaning (MC): M6-M20 Automatic cleaning (AC): M12-M20

3. Anchor setting
Machine setting (impact screw driver with setting
Hammer setting: M6-M20
tool): M8-M16

4. Check setting

5. Anchor torqueing
Torque wrench: M6-M20 Impact screw driver with setting tool: M8-M16

Updated: May-19 8
Printed in UAE © 2021 Right of technical and programme changes reserved S. E. & O.
Hilti = registered trademark of Hilti Corp., Schaan MTCAT-AE 06 2021-en

The data contained in this literature was current as of the date of publication. Updates and changes may
be made based on later testing. If verification is needed that data is still current,
www.hilti.group please contact local Hilti representative.

You might also like