Table of content
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 18
Version: 1.8.1
1.1 Supports
1.2 Nodes
Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
3 -700.00 0.00 0.00 Base 1 HST3 M10x90 30/10 HST3 M10 (C)
4 -300.00 0.00 0.00 Base 2 HST3 M10x90 30/10 HST3 M10 (C)
1.3 Members
Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2268498 MT-30 1 2 - - 90.00
No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 18
Version: 1.8.1
2 Part list
2.1 Channels
Quantity Description Item No. Weight [kg] Length [mm] Member No.
1 I.-Channel MT-30 2268498 1.04 700.00 1
2.4 Accessories
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 18
Version: 1.8.1
3 Load Types
3. Loads
No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
2 Design 1 50.00 0.00 0.00 -1.25 0.00 0.00 0.00
3 Design 1 650.00 0.00 0.00 -1.25 0.00 0.00 0.00
4 Self Weight Support 1 150.00 0.00 0.00 -0.00 0.00 0.00 0.00
5 Self Weight Support 1 550.00 0.00 0.00 -0.00 0.00 0.00 0.00
Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
6 Self Weight Support 1 0.00 700.00 0.00 0.00 -0.01 0.00 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 18
Version: 1.8.1
4 Load Combinations
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 18
Version: 1.8.1
5 Results
5.1 Calculation summary
5.1.1 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 18
Version: 1.8.1
5.2 Members
5.2.2.1 Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 18
Version: 1.8.1
Beam No. 1
Normal load
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 18
Version: 1.8.1
Torsion around X
Moment around Y
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 18
Version: 1.8.1
Moment around Z
Buckling ratio
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 18
Version: 1.8.1
The reference length and/or limits for the deflection evaluation in this project was manually adjusted by
the user.
Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview
Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 700.00 L/200 -0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 18
Version: 1.8.1
5.3.1 Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 18
Version: 1.8.1
5.4.1Overview
Base 3 - HST3 M10x90 30/10 Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]
Local Forces: 0.00 -0.00 -0.00 0.00 0.00 -0.00
Resistance: 0.00 0.00 0.00 0.00 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: -5000000000000000.00 % OK
Governing Load
1.00 * LC1
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 18
CL 900 x1
Submitted by:
Phone Mobile/Office:
E-mail:
Date: 14/02/2022
Table of content
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 18
Version: 1.8.1
1.1 Supports
1.2 Nodes
Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
3 -800.00 0.00 0.00 Base 1 HST3 M10x90 30/10 HST3 M10 (C)
4 -200.00 0.00 0.00 Base 2 HST3 M10x90 30/10 HST3 M10 (C)
1.3 Members
Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2268498 MT-30 1 2 - - 90.00
No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 18
Version: 1.8.1
2 Part list
2.1 Channels
Quantity Description Item No. Weight [kg] Length [mm] Member No.
1 I.-Channel MT-30 2268498 1.49 1000.00 1
2.4 Accessories
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 18
Version: 1.8.1
3 Load Types
3. Loads
No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 1 950.00 0.00 0.00 -1.78 0.00 0.00 0.00
2 Design 1 50.00 0.00 0.00 -1.78 0.00 0.00 0.00
3 Self Weight Support 1 200.00 0.00 0.00 -0.00 0.00 0.00 0.00
4 Self Weight Support 1 800.00 0.00 0.00 -0.00 0.00 0.00 0.00
Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
5 Self Weight Support 1 0.00 1000.00 0.00 0.00 -0.01 0.00 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 18
Version: 1.8.1
4 Load Combinations
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 18
Version: 1.8.1
5 Results
5.1 Calculation summary
5.1.1 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 18
Version: 1.8.1
5.2 Members
5.2.2.1 Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 18
Version: 1.8.1
Beam No. 1
Normal load
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 18
Version: 1.8.1
Torsion around X
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 18
Version: 1.8.1
Moment around Y
Moment around Z
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 18
Version: 1.8.1
Buckling ratio
Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 18
Version: 1.8.1
Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 1000.00 L/200 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 18
Version: 1.8.1
5.3.1 Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 18
Version: 1.8.1
5.4.1Overview
Base 3 - HST3 M10x90 30/10 Fx[kN] Fy[kN] Fz[kN] Mx[kNm] My[kNm] Mz[kNm]
Local Forces: 0.00 -0.01 -0.00 0.00 0.00 -0.00
Resistance: 0.00 0.00 0.00 0.00 0.00 0.00
Equation: Fx.ed/Fx.rd+Fy.ed/Fy.rd+Fz.ed/Fz.rd+Mx.ed/Mx.rd+My.ed/My.rd+Mz.ed/Mz.rd
Utilization: -8000000000000000.00 % OK
Governing Load
1.00 * LC1
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 18
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 18
double on concrete 900
Submitted by:
Phone Mobile/Office:
E-mail:
Date: 10/03/2022
Table of content
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 19
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 19
Version: 1.8.1
1.1 Supports
1.2 Nodes
Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
1 -2700.00 0.00 2750.00 Base 1 MT-BR-40 450 OC MT-BR-40 450 OC (C)
3 -2700.00 1100.00 2750.00 Base 2 MT-BR-40 450 OC MT-BR-40 450 OC (C)
5 -2400.00 0.00 2750.00 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
6 -2400.00 1100.00 2750.00 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
1.3 Members
Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2271445 MT-40 1 2 - - 0.00
2 2271445 MT-40 3 4 - - 0.00
3 2268508 MT-40 5 6 1 2 90.00
No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 19
Version: 1.8.1
2 Part list
2.1 Channels
Quantity Description Item No. Weight [kg] Length [mm] Member No.
2 Bracket MT-BR-40 450 OC 2271445 2.69 400.00 1, 2
1 I.-Channel MT-40 OC 2268508 2.36 1157.50 3
2.4 Accessories
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 19
Version: 1.8.1
3 Load Types
3. Loads
No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 3 100.00 0.00 0.00 -1.62 0.00 0.00 0.00
2 Design 3 1000.00 0.00 0.00 -1.62 0.00 0.00 0.00
3 Self Weight Support 1 300.00 0.00 0.00 -0.00 0.00 0.00 0.00
4 Self Weight Support 2 300.00 0.00 0.00 -0.00 0.00 0.00 0.00
Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
5 Self Weight Support 1 0.00 400.00 0.00 0.00 -0.04 0.00 0.00 0.00
6 Self Weight Support 2 0.00 400.00 0.00 0.00 -0.04 0.00 0.00 0.00
7 Self Weight Support 3 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 19
Version: 1.8.1
4 Load Combinations
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 19
Version: 1.8.1
5 Results
5.1 Calculation summary
5.1.1 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 19
Version: 1.8.1
5.2 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 19
Version: 1.8.1
5.2.2.1 Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 19
Version: 1.8.1
Beam No. 1
Beam No. 2
Beam No. 3
Normal load
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 19
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 12 / 19
Version: 1.8.1
Torsion around X
Moment around Y
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 19
Version: 1.8.1
Moment around Z
Buckling ratio
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 19
Version: 1.8.1
Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview
Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 400.00 L/200 0.00 0.00
2 1.00 * LC1 Relative (Beam) 400.00 L/200 0.00 0.00
3 1.00 * LC1 Relative (Beam) 1100.00 L/200 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 19
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 19
Version: 1.8.1
5.3.1 Overview
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 19
Version: 1.8.1
5.4.1Overview
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 19
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 19 / 19
CL 900 Dx2 on block
Submitted by:
Phone Mobile/Office:
E-mail:
Date: 10/03/2022
Table of content
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 2 / 21
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 3 / 21
Version: 1.8.1
1.1 Supports
1.2 Nodes
Node No. X [mm] Y [mm] Z [mm] Connector Type Support No. Connector name Connector variant
1 -2700.00 0.00 3064.39 Base 1 MT-BR-40 450 OC MT-BR-40 450 OC (C)
3 -2450.00 0.00 3064.39 System - MT-AB-L 45 OC MT-AB-L 45 OC (C)
4 -2700.00 0.00 2814.39 Base 2 MT-AB-L 45 OC MT-AB-L 45 OC (C)
5 -2450.00 1100.00 3064.39 System - MT-AB-L 45 OC MT-AB-L 45 OC (C)
6 -2700.00 1100.00 2814.39 Base 3 MT-AB-L 45 OC MT-AB-L 45 OC (C)
7 -2700.00 1100.00 3064.39 Base 4 MT-BR-40 450 OC MT-BR-40 450 OC (C)
9 -2600.00 1100.00 3064.39 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
10 -2600.00 0.00 3064.39 System - MT-CC-40/50 OC MT-CC-40/50 OC (E)
1.3 Members
Main Member No. Item number Member Name Node start Node end Start Release End Release Rotation[°]
1 2271445 MT-40 1 2 - - 180.00
2 2268508 MT-40 3 4 1 2 180.00
3 2268508 MT-40 5 6 3 4 180.00
4 2271445 MT-40 7 8 - - 180.00
5 2268508 MT-40 9 10 5 6 270.00
6 2268508 MT-40 11 12 - - 270.00
No. Main Member No. Main Member Name Media Interafce Member Start Position Length [mm] Z-Position Y Orientation
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 4 / 21
Version: 1.8.1
2 Part list
2.1 Channels
Quantity Description Item No. Weight [kg] Length [mm] Member No.
2 Bracket MT-BR-40 450 OC 2271445 2.86 450.00 1, 4
2 I.-Channel MT-40 OC 2268508 1.49 365.79 2, 3
1 I.-Channel MT-40 OC 2268508 2.36 1157.50 5
1 I.-Channel MT-40 OC 2268508 2.24 1100.00 6
2.4 Accessories
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 5 / 21
Version: 1.8.1
3 Load Types
3. Loads
No. Load Type Members Position [mm] Fx [kN] Fy [kN] Fz [kN] Mx [kNm] My [kNm] Mz [kNm]
1 Design 5 1000.00 0.00 0.00 -1.78 0.00 0.00 0.00
2 Design 5 100.00 0.00 0.00 -1.78 0.00 0.00 0.00
3 Design 6 1000.00 0.00 0.00 -1.78 0.00 0.00 0.00
4 Design 6 100.00 0.00 0.00 -1.78 0.00 0.00 0.00
5 Self Weight Support 1 250.00 0.00 0.00 -0.00 0.00 0.00 0.00
6 Self Weight Support 2 353.55 0.00 0.00 -0.00 0.00 0.00 0.00
7 Self Weight Support 3 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
8 Self Weight Support 3 353.55 0.00 0.00 -0.00 0.00 0.00 0.00
9 Self Weight Support 4 100.00 0.00 0.00 -0.00 0.00 0.00 0.00
10 Self Weight Support 1 100.00 0.00 0.00 -0.00 0.00 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 6 / 21
Version: 1.8.1
Start End
Mx My Mz
No. Load Type Members Position Position Fx [kN/m] Fy [kN/m] Fz [kN/m]
[kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
11 Self Weight Support 1 0.00 450.00 0.00 0.00 -0.03 0.00 0.00 0.00
12 Self Weight Support 2 0.00 353.55 0.00 0.00 -0.02 0.00 0.00 0.00
13 Self Weight Support 3 0.00 353.55 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 4 0.00 450.00 0.00 0.00 -0.03 0.00 0.00 0.00
15 Self Weight Support 5 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00
16 Self Weight Support 6 0.00 1100.00 0.00 0.00 -0.02 0.00 0.00 0.00
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 7 / 21
Version: 1.8.1
4 Load Combinations
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 8 / 21
Version: 1.8.1
5 Results
5.1 Calculation summary
5.1.1 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 9 / 21
Version: 1.8.1
5.2 Members
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 10 / 21
Version: 1.8.1
5.2.2.1 Overview
Beam No. 1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 11 / 21
Version: 1.8.1
Beam No. 2
Beam No. 3
Beam No. 4
Beam No. 5
Beam No. 6
Normal load
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 13 / 21
Version: 1.8.1
Torsion around X
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 14 / 21
Version: 1.8.1
Moment around Y
Moment around Z
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 15 / 21
Version: 1.8.1
Buckling ratio
Criteria
☑ Maximum Allowable Deflection (Beam) L/200 (System Default)
☑ Maximum Allowable Deflection (Cantilever) L/150 (System Default)
- Maximum Deflection (Absolute) - -
☑ No Deflection checks calculated for 1.50mm (User Defined)
Overview
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 16 / 21
Version: 1.8.1
Results
Member Reference Max
Load Combination: Governing criteria Limit Utilization(%)
No. Length[mm] deflection[mm]
1 1.00 * LC1 Relative (Beam) 450.00 L/200 0.00 0.00
2 1.00 * LC1 Relative (Beam) 353.55 L/200 -0.00 0.00
3 1.00 * LC1 Relative (Beam) 353.55 L/200 -0.00 0.00
4 1.00 * LC1 Relative (Beam) 450.00 L/200 0.00 0.00
5 1.00 * LC1 + 0.70 * LC7 Relative (Beam) 1100.00 L/200 1.59 28.84
6 1.00 * LC1 + 0.70 * LC7 Relative (Beam) 1100.00 L/200 1.51 27.48
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 17 / 21
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 18 / 21
Version: 1.8.1
5.3.1 Overview
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 19 / 21
Version: 1.8.1
5.4.1Overview
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 20 / 21
Version: 1.8.1
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary. Copyright (c) Hilti AG 2010,
FL-9494 Schaan 21 / 21
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HSA-F M12 hnom1
Return period (service life in years): 50
Item number: 2004173 HSA-F M12x100 20/5/-
Effective embedment depth: hef = 50.0 mm, hnom = 64.0 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 10/22/2020 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm
Anchor plate :
R lx x ly x t = 148.0 mm x 60.0 mm x 8.0 mm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: 2
uncracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s
y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
22,500 22,500 75.0 150.0 25.00
Group anchor ID
1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)
0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
29.500 1.000 29.500 1.250 23.600 0.800
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
37,200 22,500 75.0 150.0 2.000 25.00
Group anchor ID
1, 2
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
a a
bN + bV £ 1.0
Concrete failure
a a
bN + bV £ 1.0
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HSA-F M12 hnom1
Profile: no profile Item number: 2004173 HSA-F M12x100 20/5/-
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 50 Nm
Plate thickness (input): 8.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 72.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Hilti HSA stud anchor with 64 mm embedment, M12 hnom1, Hot dip galvanized, installationwith torque control bar per ETA 11/0374
y
74.0 74.0
30.0
30.0
1 2
-0.0
x
30.0
30.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bracket on concrete Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x85
Item number: 2223853 HAS-U 5.8 M8x110 (element) / 2092828 HIT-HY
270 (adhesive) / 375982 HIT-SC 16x85 (sieve sleeve)
Effective embedment depth: hef,act = 80.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm
Anchor plate :
R lx x ly x t = 60.0 mm x 148.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M10 - M20; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C
R
- The anchor calculation is based on a rigid anchor plate assumption.
Geometry [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.000 0.000 -1.000
2 0.000 1.000 0.000 -1.000 x
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
50.0 200.0 7.500 1.000 0.0 1.000 1.000
sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000
gM,m
2.500
b||+^
0.667
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -
gM,m
2.500
b||+^
0.667
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x85
Profile: no profile Item number: 2223853 HAS-U 5.8 M8x110 (element) /
2092828 HIT-HY 270 (adhesive) / 375982 HIT-SC 16x85
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 95.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 115.0 mm
Cleaning: compressed air
Fastening option: Pre fastening
Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x85 sieve sleeve(s) with 80 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160
y
30.0 30.0
25.0
2
74.0
98.0
x
74.0
1
25.0
30.0 30.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL 900 double Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HSA-F M8 hnom1
Return period (service life in years): 50
Item number: 2004113 HSA-F M8x55 5/-/-
Effective embedment depth: hef = 30.0 mm, hnom = 39.0 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 10/22/2020 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm
Anchor plate :
R lx x ly x t = 1,000.0 mm x 42.5 mm x 3.0 mm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: 2
uncracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)
0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
10.600 1.000 10.600 1.250 8.480 1.780
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
8,100 8,100 45.0 90.0 1.000 25.00
Group anchor ID
2
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
7 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HSA-F M8 hnom1
Profile: no profile Item number: 2004113 HSA-F M8x55 5/-/-
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 15 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 8.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 44.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Hilti HSA stud anchor with 39 mm embedment, M8 hnom1, Hot dip galvanized, installationwith torque control bar per ETA 11/0374
y
500.0 500.0
21.2
21.2
2 1
21.2
21.2 x
200.0 600.0 200.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CL riser 900 vertical, single layer Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x50
Item number: 2223852 HAS-U 5.8 M8x80 (element) / 2092828 HIT-HY
270 (adhesive) / 375981 HIT-SC 16x50 (sieve sleeve)
Effective embedment depth: hef,act = 50.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm
Anchor plate :
R lx x ly x t = 900.0 mm x 42.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M10 - M20; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C
R
- The anchor calculation is based on a rigid anchor plate assumption.
Geometry [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
200.0 200.0 6.500 2.000 0.0 1.000 1.000
sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000
gM,m
2.500
b||+^
0.685
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -
gM,m
2.500
b||+^
0.685
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x50
Profile: no profile Item number: 2223852 HAS-U 5.8 M8x80 (element) /
2092828 HIT-HY 270 (adhesive) / 375981 HIT-SC 16x50
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 60.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 80.0 mm
Cleaning: compressed air
Fastening option: Pre fastening
Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x50 sieve sleeve(s) with 50 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160
y
450.0 450.0
21.0
21.0
2 1 21.0
21.0
x
200.0 500.0 200.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry - CL 900 x 1 Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8, HIT-SC 16x85
Item number: 2223853 HAS-U 5.8 M8x110 (element) / 2092828 HIT-HY
270 (adhesive) / 375982 HIT-SC 16x85 (sieve sleeve)
Effective embedment depth: hef,act = 80.0 mm
Material: 5.8
Evaluation Service Report: ETA-19/0160
Issued I Valid: 8/30/2019 | -
Proof: Design Method ETAG 029, Annex C
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm
Anchor plate :
R lx x ly x t = 700.0 mm x 42.0 mm x 3.0 mm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: Brick layout: Stretcher; Brick: B40, f=10, 1.0 (hollow brick), Normal weight concrete, L x W x H: 500.0 mm
x 200.0 mm x 200.0 mm;
2 2
fb,v = 10.00 N/mm ; Ewall = 2,255.34 N/mm
Mortar: M2,5 - M9; Vertical joints filled: YES; vertical: 5.0 mm; horizontal: 5.0 mm
Installation/Use: Installation condition: Dry; Use condition: Dry;
Cleaning: compressed air
Temp. short/long: 40/24 °C
R
- The anchor calculation is based on a rigid anchor plate assumption.
Geometry [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
sETA,|| [mm] cETA,|| [mm] VRk,b,ETA,|| [kN] ag,V,|| ec,V,|| [mm] y g,V,|| aj,||
200.0 200.0 7.500 2.000 0.0 1.000 1.000
sETA,^ [mm] cETA,^ [mm] VRk,b,ETA,^ [kN] ag,V,^ ec,V,^ [mm] y g,V,^ aj,^
0.0 0.0 0.000 0.000 0.0 0.000 0.000
gM,m
2.500
b||+^
0.417
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
sETA,^ [mm] cETA,^ [mm] VRk,c,ETA,^ [kN] ag,V,^ aj,^ ec,V,^ [mm] y g,V,^
- - - - - - -
gM,m
2.500
b||+^
0.417
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. ETAG 029) is the responsibility of the user.
• The Young’s modulus of the wall Ewall (not plastered!) is determined in accordance to EN 1996-1-1:2012
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• Please note that, for ETA approved masonry units, the resistance and parameters are only valid for that particular brick (hollow/solid) or for bricks
of the same base material with larger size and larger compressive strength (solid), according to ETAG 029.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
6 Installation data
2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm
2 Anchor type and diameter: HIT-HY 270 + HAS-U 5.8 M8,
HIT-SC 16x85
Profile: no profile Item number: 2223853 HAS-U 5.8 M8x110 (element) /
2092828 HIT-HY 270 (adhesive) / 375982 HIT-SC 16x85
(sieve sleeve)
Hole diameter in the fixture: df = 9.0 mm Maximum installation torque: 3 Nm
Plate thickness (input): 3.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 95.0 mm
Drilling method: Drilled in rotary mode Minimum thickness of the base material: 115.0 mm
Cleaning: compressed air
Fastening option: Pre fastening
Hilti HAS-U threaded rod with HIT-HY 270 injection mortar and 1 HIT-SC 16x85 sieve sleeve(s) with 80 mm embedment h_ef, M8, Steel
galvanized, Rotary drilled installation per ETA-19/0160
y
350.0 350.0
21.0
21.021.0
2 1 21.0
x
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.76
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Masonry-CL 600x1 Date: 3/10/2022
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
MT SYSTEM
Modular Support System
Catalogue
上海市浦东新区耀元路58号上海环球都会广场2号楼8
免费服务热线: 800-820-2585 更多资讯:
www.hilti.group
Channels Girder
Technical data Technical data
Item Description Material thickness Height × Width Weight Sales pack Item number
50
50
50
3
50
2.75
23x23
50 100
∅11
∅9
∅9
MT-70 OC MT-80 OC
50
50 100
100
4
3
100 150
∅9
∅9
MT-90 OC MT-100 OC
1 2
TECHNICAL DATA MT CHANNEL SYSTEM
Definition of axes
) )
H H
\
H H
]
$ %
Channel wall thickness t [mm] 1.2 1.5 1.75 2.0 1.75 2.0 2.0 2.75 2.75 2.75 3,0 3.0 4,0
Cross-sectional area A [mm2] 48.43 85.2 148.65 180 175.59 214 429.52 276.05 500.1 428.78 592.66 976.08 1555.34
Channel weight [kg/m] 0.3888 0.6784 1.267 1.486 1.69 2.039 4.299 2.744 4.017 3.909 6.058 8.973 15.096
Delivered length [m] 2 2 2 3/6 6 3/6 3/6 3/6 3/6 3/6 3/6 3/6 3/6
Material
Steel grade S280GD S280GD S280GD S250GD S280GD S280GD S280GD S280GD S280GD S350GD S350GD S350GD S350GD
E-Modul [N/mm2] 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000 210000
Surface
pregalvanized
• • • • • • • • •
(DIN EN ISO 10346)
zinc magnesium
• • • • • • • • • • • •
(EN 10346 & ASTM A1046)
Axis of gravity A 1) e1 [mm] 9.25 11.90 21.25 12.04 23.05 21.76 42.50 22.04 36.62 25.00 50.00 50.00 75.00
Axis of gravity B e2 [mm] 16.75 23.10 21.25 10.96 19.45 20.74 42.50 20.46 35.38 25.00 50.00 50.00 75.00
Permtion modulus A Wy1 [cm3] 0.25 0.57 1.73 1.00 2.10 2.65 7.05 3.19 7.83 6.35 17.59 30.17 64.98
Permtion modulus B Wy2 [cm3] 0.41 1.00 1.73 1.10 2.48 2.78 7.05 3.44 8.10 6.35 17.59 30.17 64.98
Radius of gyration iy [cm] 0.91 1.22 1.57 0.82 1.66 1.64 2.64 1.60 2.39 1.92 3.85 3.93 5.60
Permissible moment 2)
My [Nm] 52 180 355 189 421 536 1425 663 1584 1443 4105 7040 15162
Z-axis
Moment of inertia Iz [cm4] 0.23 0.72 1.85 5.19 5.71 6.59 13.18 8.27 17.11 15.87 24.50 150.85 260.98
Radius of gyration iz [cm] 0.69 0.92 1.12 1.70 1.80 1.76 1.75 1.73 1.85 1.92 2.03 3.93 4.10
Design resistance
• MT-10 to MT-70: The permissible stress σD / γG/Q where y = 1,4. σD results from the higher yield strength (point) resulting from cold forming as per EN
1993-1-3: 2010: σD = fyk / γM where γM = 1,1.
• MT-80 to MT-100: The permissible stress σD / γG/Q where y = 1,5“
1) For the arithmetical bending dimensioning is the smaller value (Wy1, Wy2) decisive to (Wy1 = Iy / e1 bzw. Wy2 = Iy / e2).
2) My = δperm x min. (Wy1, Wy2)
3 4
POINT LOAD IN THE MIDDLE OF SPAN
Technical data for channel profiles MT (max. span width/deflection - point Load in the middle of span)
MT-40 T/ MT-40D/
MT-15/ MT-20/ MT-30/ MT-40/ MT-50/ MT-60/
MT-10 MT-40 T MT-40D MT-70 OC MT-80 OC MT-90 OC MT-100 OC
MT-15 OC MT-20 OC MT-30 OC MT-40 OC MT-50 OC MT-60 OC
OC OC
load F [kN] L f L f L f L f L f L f L f L f L f L f L f L f L f
0,25 83 0.4 157 7.8 260 12.9 152 7.6 294 14.7 317 15.8 600 29.4 339 16.9 600 29.9 469 23.4 600 11.6 600 8.3 600 3.6
0,50 42 0.1 93 3.2 188 9.3 109 5.5 215 10.7 234 11.7 489 24.4 254 12.6 482 24.1 368 18.4 600 17.7 600 11.9 600 4.7
0,75 28 0.0 62 1.4 155 7.7 90 4.5 178 8.9 194 9.6 418 20.9 212 10.6 411 20.5 311 15.5 600 23.8 600 15.4 600 5.8
1,00 21 0.0 47 0.8 134 6.6 75 3.5 154 7.6 169 8.4 371 18.5 185 9.3 363 18.1 274 13.6 600 29.9 600 19.0 600 6.9
1,25 17 0.0 37 0.5 113 5.0 60 2.3 134 6.2 151 7.6 336 16.8 167 8.3 329 16.4 247 12.3 551 27.5 600 22.5 600 8.0
1,50 14 0.0 31 0.4 94 3.4 50 1.6 112 4.3 138 6.9 309 15.4 152 7.6 302 15.0 227 11.3 512 25.6 600 26.1 600 9.1
1,75 12 0.0 27 0.3 81 2.5 43 1.2 96 3.2 122 5.5 287 14.4 141 7.0 281 14.0 211 10.5 479 23.9 600 29.6 600 10.2
2,00 10 0.0 23 0.2 71 1.9 38 0.9 84 2.4 107 4.2 270 13.5 132 6.5 264 13.2 198 9.9 452 22.6 572 28.6 600 11.3
2,25 9 0.0 21 0.2 63 1.5 34 0.7 75 1.9 95 3.3 248 11.6 117 5.1 249 12.4 187 9.3 429 21.4 545 27.2 600 12.4
2,50 8 0.0 19 0.1 57 1.2 30 0.6 67 1.6 86 2.7 224 9.5 106 4.2 237 11.8 177 8.8 409 20.4 522 26.0 600 13.5
2,75 8 0.0 17 0.1 52 1.0 27 0.5 61 1.3 78 2.2 204 7.9 96 3.5 227 11.3 169 8.4 391 19.5 501 25.0 600 14.6
3,00 7 0.0 16 0.1 47 0.9 25 0.4 56 1.1 71 1.9 188 6.7 88 2.9 208 9.6 162 8.1 376 18.8 482 24.1 600 15.7
3,50 6 0.0 13 0.1 41 0.6 22 0.3 48 0.8 61 1.4 161 4.9 76 2.1 179 7.1 150 7.5 349 17.4 450 22.5 600 17.9
4,00 5 0.0 12 0.1 36 0.5 19 0.2 42 0.6 54 1.1 141 3.8 66 1.6 157 5.4 141 7.0 328 16.3 424 21.2 600 20.1
4,50 5 0.0 10 0.0 32 0.4 17 0.2 37 0.5 48 0.8 126 3.0 59 1.3 140 4.3 128 5.9 310 15.5 401 20.0 600 22.3
5,00 4 0.0 9 0.0 28 0.3 15 0.1 34 0.4 43 0.7 113 2.4 53 1.1 126 3.5 115 4.8 295 14.7 382 19.0 600 24.5
6,00 3 0.0 8 0.0 24 0.2 13 0.1 28 0.3 36 0.5 95 1.7 44 0.7 105 2.4 96 3.3 270 13.5 350 17.5 600 28.9
7,00 3 0.0 7 0.0 20 0.2 11 0.1 24 0.2 31 0.3 81 1.2 38 0.5 90 1.8 82 2.4 232 10.0 325 16.2 571 28.5
8,00 3 0.0 6 0.0 18 0.1 9 0.1 21 0.2 27 0.3 71 1.0 33 0.4 79 1.4 72 1.9 204 7.7 305 15.2 537 26.8
Design resistance
Selection example:
• 1,0 kN (≈ 100 kg) should be carried by a channel with a channel span width L = 100cm (single span sinply supported).
Solution:
• Select the line with the load, F = 1,0 kN.
• The channels MT-20, MT-40 T up to MT-100 can be used because the permissible span width (table value) is larger or equal to the required span
width of L = 100cm.
Load tables are based on stress and deflection calculations, lateral torsional buckling is not considered.
POINT LOAD IN THE MIDDLE OF SPAN
Technical data for channel profiles MT (max. span width/deflection - point Load in the middle of span)
MT-40 T/
MT-15/ MT-20/ MT-30/ MT-40/ MT-40D/ MT-50/ MT-60/
MT-10 MT-40 T MT-70 OC MT-80 OC MT-90 OC MT-100 OC
MT-15 OC MT-20 OC MT-30 OC MT-40 OC MT-40D OC MT-50 OC MT-60 OC
OC
25 0.83 0.0 1.87 0.2 5.69 0.2 3.02 0.4 6.74 0.2 8.58 0.2 22.80 0.1 10.61 0.2 25.35 0.1 23.08 0.2 65.68 0.1 106.17 0.1 222.70 0.1
50 0.42 0.1 0.94 0.9 2.84 1.0 1.51 1.6 3.36 0.9 4.29 0.9 11.39 0.5 5.30 0.9 12.67 0.5 11.53 0.9 32.83 0.5 56.29 0.5 121.26 0.3
75 0.28 0.3 0.62 2.1 1.89 2.2 1.00 3.5 2.24 1.9 2.85 2.1 7.59 1.1 3.53 2.1 8.44 1.2 7.68 2.0 21.87 1.0 37.51 1.0 80.81 0.7
100 0.21 0.5 0.46 3.7 1.42 3.9 0.60 5.0 1.68 3.5 2.14 3.7 5.68 1.9 2.64 3.7 6.32 2.2 5.75 3.6 16.39 1.9 28.11 1.9 60.57 1.2
125 0.16 0.8 0.37 5.7 1.13 6.1 0.38 6.2 1.34 5.4 1.70 5.8 4.53 3.0 2.11 5.9 5.05 3.4 4.59 5.6 13.10 2.9 22.47 2.9 48.43 1.9
150 0.14 1.2 0.28 7.5 0.80 7.5 0.26 7.5 1.07 7.5 1.27 7.5 3.77 4.3 1.55 7.5 4.20 4.9 3.52 7.5 10.90 4.2 18.70 4.2 40.32 2.8
175 0.12 1.6 0.20 8.7 0.59 8.7 0.18 8.7 0.78 8.7 0.93 8.7 3.22 5.8 1.13 8.7 3.59 6.7 2.57 8.7 9.33 5.7 16.01 5.7 34.52 3.8
200 0.10 2.1 0.15 9.9 0.44 10.0 0.13 9.9 0.59 10.0 0.70 10.0 2.81 7.6 0.85 10.0 3.13 8.8 1.95 10.0 8.15 7.4 13.99 7.4 30.17 4.9
225 0.09 2.6 0.12 11.2 0.34 11.2 0.10 11.0 0.46 11.2 0.54 11.2 2.49 9.6 0.66 11.2 2.77 11.1 1.52 11.2 7.23 9.4 12.41 9.4 26.79 6.3
250 0.08 3.2 0.09 12.4 0.27 12.4 0.07 12.2 0.36 12.4 0.43 12.4 2.23 11.9 0.52 12.4 2.24 12.5 1.21 12.4 6.49 11.6 11.15 11.6 24.07 7.7
275 0.07 3.9 0.07 13.6 0.22 13.6 0.05 13.3 0.29 13.6 0.35 13.6 1.91 13.7 0.42 13.6 1.83 13.7 0.98 13.7 5.75 13.7 9.88 13.7 21.85 9.4
300 0.06 4.7 0.06 14.7 0.18 14.8 0.04 14.4 0.24 14.8 0.28 14.8 1.59 14.9 0.34 14.8 1.52 14.9 0.81 14.9 4.80 15.0 8.26 15.0 19.99 11.1
325 0.06 5.5 0.05 15.9 0.15 16.0 0.02 15.4 0.19 16.0 0.23 16.0 1.33 16.1 0.27 16.0 1.28 16.1 0.67 16.1 4.06 16.2 7.00 16.2 18.42 13.1
350 0.05 6.4 0.04 17.0 0.12 17.2 0.01 16.3 0.16 17.2 0.19 17.2 1.13 17.4 0.22 17.1 1.08 17.4 0.56 17.3 3.47 17.4 5.99 17.4 17.06 15.2
375 0.05 7.4 0.03 18.1 0.10 18.3 0.13 18.3 0.15 18.3 0.96 18.6 0.18 18.3 0.92 18.6 0.47 18.4 3.00 18.7 5.17 18.7 15.89 17.4
400 0.04 8.5 0.02 19.1 0.08 19.4 0.11 19.4 0.13 19.4 0.83 19.8 0.15 19.4 0.79 19.8 0.39 19.6 2.60 19.9 4.50 19.9 14.86 19.9
425 0.04 9.6 0.02 20.1 0.06 20.5 0.09 20.5 0.10 20.5 0.71 20.9 0.12 20.4 0.68 21.0 0.33 20.7 2.28 21.1 3.95 21.1 13.16 21.2
450 0.04 10.8 0.01 21.1 0.05 21.6 0.07 21.6 0.08 21.6 0.61 22.1 0.09 21.5 0.59 22.1 0.27 21.9 2.00 22.3 3.48 22.3 11.66 22.4
475 0.03 12.1 0.01 22.0 0.04 22.6 0.05 22.6 0.06 22.6 0.53 23.3 0.07 22.5 0.51 23.3 0.23 22.9 1.77 23.5 308 23.6 10.39 23.6
500 0.03 13.5 0.03 23.6 0.04 23.6 0.05 23.6 0.46 24.4 0.05 23.4 0.44 24.4 0.19 24.0 1.56 24.7 2.73 24.8 9.30 24.9
Design resistance
Load tables are based on stress and deflection calculations, lateral torsional buckling is not considered.
BUCKLING
MT-10 MT-15 / MT-15 OC MT-20 / MT-20 OC MT-30 / MT-30 OC MT-40 T / MT-40 T OC MT-40 / MT-40 OC MT-40D / MT-40D OC MT-50 / MT-50 OC MT-60 / MT-60 OC MT-70 OC MT-80 OC MT-90 OC MT-100 OC
Buckling length
permissible buckling load permissible buckling load permissible buckling load permissible buckling load permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling permissible buckling
Sk [cm]
[kN] [kN] [kN] [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN] load [kN]
25 29.40 30.51 34.41 42.22 87.97 55.68 68.93 99.01 128.31 219.78 350.41
50 24.86 22.72 29.93 36.62 80.21 47.92 52.16 90.61 118.07 210.74 336.93
75 19.67 15.10 24.91 30.33 72.00 39.23 36.33 81.79 107.42 202.00 323.55
100 14.70 10.03 19.75 23.90 62.95 30.58 25.80 72.10 95.79 193.28 310.24
125 10.86 7.02 15.34 18.45 53.45 23.51 19.47 61.82 83.33 184.34 296.65
150 8.19 5.16 12.00 14.38 44.43 18.32 15.55 51.88 70.94 175.02 282.54
N/A N/A
175 6.33 3.96 9.58 11.44 36.66 14.62 12.97 43.12 59.66 165.24 267.77
200 5.03 3.13 7.82 9.31 30.34 11.94 11.18 35.87 50.05 155.00 252.31
225 4.08 2.54 6.51 7.73 25.32 9.97 9.86 30.04 42.18 144.40 236.27
250 3.37 2.11 5.52 6.54 21.35 8.46 8.86 25.40 35.81 133.67 219.89
275 2.83 1.78 4.75 5.62 18.20 7.29 8.06 21.68 30.67 123.05 203.52
300 2.41 1.52 4.14 4.89 15.67 6.36 7.41 18.70 26.51 112.80 187.54
Flexural buckling:
Rod length l (cm) / euler factor
β/Sk (cm) effective length
=l۰β 2,0 (l) 1,0 (l) 0,7 (l) 0,5 (l)
Design resistance
*(design value)
Twist Lock (MT-TL) Thread Forming Bolt (MT-TFB)
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
Fastening of any component, media to Maximum connection reliability, no Fastening of any component, media to One bolt for all girder connections
MT open C-channels with MT-TLB reliance on friction, no restriction of MT girders
positioning steps For use with MT-TLB Fast installation easy to release
Fastening of any component, media to
One handed installation - No need for
MT open C-channels with MT-TLB
bolts or complex fixation elements
Guaranteed performance & productivity
缺清晰图 setting with SIW-AT module
Guaranteed performance &
productivity setting with SIW-AT
module
MT-TL M8 M8 32 50 2273630
MT-TL M8 OC M8 32 50 2273631 Item Description For Girder Types Tightening torque - Nm Pull out Load - kN Shear Load - kN
* MT-TL M10 is the primary size for
MT-TL M10 M10 35 50 2272080 MT-TFB OC MT-70,MT-80 60 11 17
MT-TL M10 OC M10 35 50 2272082 connections within the system
MT-TFB OC MT-90 60 11 20
MT-TL M12 M12 38 50 2273632 * (with connectors & baseplates)
MT-TFB OC MT-100 60 17 20
MT-TL M12 OC M12 38 50 2273633
MT-TL M16 M16 37 50 2273634 > 10 mm
MT-TL M16 OC M16 37 50
60 Nm
2273635 (44 ft-lb)
1 2 3
Item Description Thread - M Thread length Wrench size Weight Sales pack Item number
MT-TLB M10 24 17 25 50 2273254 Item Description For channel/girder types Weight Sales pack Item number
MT-TLB OC M10 24 17 25 50 2273256 MT-EC-30 MT-30 3.7 20 2273642
MT-TLB 30 M10 30 17 31 50 2282190 MT-EC-40/50 MT-40,50,40D 5.8 20 2273643
MT-TLB 30 OC M10 30 17 31 50 2282191 MT-EC-60 MT-60 9.1 20 2273644
MT-EC-70 MT-70 8.4 20 2273697
* MT-TLB is the primary size for connections within the system (with connectors & baseplates)
MT-EC-80 MT-80 15.4 20 2273698
MT-EC-90 MT-90 31.0 20 2273699
MT-TLB 30 is used only with brackets (MT-BR’s) for fixation to open channels with TL’s MT-EC-100 MT-100 45.5 20 2273700
6
5
Open C-Channel Baseplates Open C-Channel Connectors
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
For fastening of MT channels to Reliable and easy to use Assembly of frames and other Universal few parts for all applications
base material Connection of channels to any structures using MT channels Simplified connectors for multi purpose
base material Simplest form of connectors, for usage
Simplest and most cost effective Easy to use
building standard L junctions
solution Three-dimensional, thus high strength
Item Description Plate thickness For Channel types Weight Sales pack Item number 90° Angle connector
MT-B-L 4.0 MT-30,MT-40,MT-50,MT-60 119 20 2272086
Angle Material thickness For Channel types
MT-B-L OC 4.0 MT-30,MT-40,MT-50,MT-60 119 20 2272088 Item Description Weight Sales pack Item number
MT-B-T 4.0 MT-30,MT-40,MT-50,MT-60 565 20 2272090 MT-C-L1 90° 6.0 MT-30,MT-40 199 20 2271514
MT-B-T OC 4.0 MT-30,MT-40,MT-50,MT-60 565 20 2272092 MT-C-L1 OC 90° 6.0 MT-50,MT-60 199 20 2271516
MT-B-O2 4.0 MT-30,MT-40,MT-50,MT-60 1027 12 2272094 MT-C-L2 90° 6.0 MT-30~MT-100 257 20 2271518
MT-B-O2 OC 4.0 MT-30,MT-40,MT-50,MT-60 1027 12 2272096 MT-C-L2 OC 90° 6.0 MT-30~MT-100 257 20 2271519
MT-B-O2B 8.0 MT-40D 2072 6 2282212 MT-C-LL1 90° 4.0 MT-30,MT-40 334 10 2272047
MT-B-O2B OC 8.0 MT-40D 2072 6 2282213 MT-C-LL1 OC 90° 4.0 MT-50,MT-60 334 10 2272049
MT-B-O4 8.0 MT-40D 3315 4 2272098 MT-C-LL2 90° 4.0 MT-30,MT-40 592 10 2272051
MT-B-O4 OC 8.0 MT-40D 3315 4 2272099 MT-C-LL2 OC 90° 4.0 MT-50,MT-60 592 10 2272053
* MT-C-L2/MT-C-L2 OC
Z Z Z Z
-FZ Design Load kN +FZ Design Load kN -F Design Load kN +FZ Design Load
Item Description Twist-Lock Qty.(pc) kN Item Description Twist-Lock Qty. Z
168.7 ∅11
∅11 112 ∅11
14x19
105
14x19 52
57
4 ∅11
52 108 57
42 42 42 41
4 6 6
∅11 ∅11
106 ∅11 106 105
105 ∅11 55
∅11 ∅14.7
4 8 8
14x20 14x20
MT-B-O2 / MT-B-O2 OC MT-B-O2B / MT-B-O2B OC MT-B-O4 / MT-B-O4 OC MT-C-LL1 / MT-C-LL1 OC MT-C-LL2 / MT-C-LL2 OC
7 8
Angle Brace Connectors Transverse Connectors - 2D
APPLICATIONS ADVANTAGES Item Description Material Material thickness Weight Sales pack Item number
$QJOHEUDFLQJZLWK07FKDQQHOV Wide range of channel compatibility MT-C-T/1 Q235B 6.0 435 20 2272040
MT-C-T/1 OC Q235B 6.0 435 20 2272042
Possibility to be used as baseplate (MT-AB A and MT-AB L MT-C-T/2
45) Q355B 4.0 782 15 2272054
MT-C-T/2 OC Q355B 4.0 782 15 2272055
MT-C-T A Q355B 4.0 323 20 2272056
MT-C-T A OC Q355B 4.0 323 20 2272057
Technical data
∅11 A B C
6
Q235B GB/T 700-2006
Material composition
51.5
4
∅11.5 ∅11
59 114 MT-C-T A / MT-C-T A OC
135°
45° Z
∅11 114 +FZ Design Load kN
Item Description Twist-Lock Qty.(pc)
14x20 ∅14
MT-C-T/1 2 4.3 5.5
MT-C-T/2 4 11.9 11.3
51.5 40.5 46 4
114 MT-C-T A 2 14 8.8
∅11
2
∅11
∅7 46
6
6
∅11 MT-TL M10
MT-ES-40 / MT-ES-40 OC
9 10
Girder Baseplates Girder Baseplates
APPLICATIONS ADVANTAGES APPLICATIONS ADVANTAGES
For fastening of MT channels to base Connection of girders to both For fastening of MT channels to Connection of girders to I-beam
material (concrete) concrete and steel for MT-B-GS base material(steel) with sandwich plates
connectors
Item Description Plate thickness I-beam width (mm) Weight Sales pack Item number
17x64 ∅14.7 12
11x14
165.4 165.4 140 12
∅11 ∅11 ∅11 MI-SGC-M16
∅14.7
∅18 ∅18
144
12 12 70
144
70 215
12 280
215 185
280
280
GXL S1
140 Z
+FZ Design Load kN 11x14 165 11x14
165
Item Description ±FZ Design Load kN
∅14.7 12
8 MT-B-GS T OC 33.4 25.9 17x64 12 17x64
∅11
MT-B-GS O4U OC 27.0 90.1
MT-B-GL O4 OC 82.8 183.6
294
50
175 MT-B-GXL O4 OC 140.1 218.6 214 420
215 155
350
155
90 220 220 * MT-B-GXL S1 OC
MT-P-GXL-S1 OC
* MT-B-GXL S2 OC, MT-B-GXL S3 OC
MT-B-GS T OC MT-B-GXL S3 OC
MT-B-GXL S2 OC
A B Item Description Plate thickness For Girder Types Weight Sales pack Item number
MT-70,MT-80
MT-90 MT-B-G WS OC 6.0 4345 4 2272109
MT-100 MT-90,MT-100
1 3 4 6
11x14
1
MT-70
226 226
MT-80
*MT-B-GS T OC MT-B-G WS OC
11 12
Girder Connectors Girder Connectors
APPLICATIONS ADVANTAGES Item Description Material thickness Surface finish Weight Sales pack Item number
Simplest form of connectors, for Possibility to be used as baseplate. MT-C-GSP L OC 4.0 HDG 424 10 2272073
building standard L junctions with MT MT-C-GSP T OC 4.0 HDG 455 10 2272074
girders Designed to provide extra adjustability MT-C-GLP T OC 4.0 HDG 884 8 2272075
4 ੋ11
ੋ11 45
4 90
ੋ11 45 4
145
140
Technical data 210
140
265
215
Item Description Material thickness Surface finish Weight Sales pack Item number
MT-U-GL1 OC MT-U-GL OC
A B
∅14.7
4
Splice Connectors
∅14.7
122.5 Item Description Material thickness Surface finish Weight Sales pack For Girder Types Item number
150
∅11 MT-ES-70 OC 5.0 HDG 1831 8 MT-70,MT-80 2272078
∅11
MT-ES-90 OC 6.0 HDG 4429 4 MT-90,MT-100 2272076
122.5 100 150
50 53
ੋ11 ੋ11
106
MT-C-GS OC MT-C-GL OC * MT-C-GS OC/ MT-C-GL OC
11x13 11x13
320
A B 320
MT-70 / 5 6
3 4 MT-80 /
MT-90/
MT-100
∅8 MT-ES-70 OC MT-ES-90 OC
11x25
122.5
11x25
150 Angle bracing connector
∅7
MT-70 /
122.5 MT-80
Item Description Angle Material thickness Surface finish Weight Sales pack Item number
50 100 150
MT-AB-G T OC 30°~60° 4.0 HDG 348 4 2272116
108
ੋ11 4
30°
60°
241
13 14
Hilti. Outperform. Outlast.
www.hilti.sa
sa.tso@hilti.com
Hilti Saudi Arabia
21454 Jeddah, Saudi Arabia
Kilo 14 | King Fahd Street | P. O. Box 15930
Free Toll Number: 800 1200 013
Fax Number: 800 2445 554
Hilti. Outperform. Outlast.
www.hilti.sa
sa.tso@hilti.com
Hilti Saudi Arabia
21454 Jeddah, Saudi Arabia
Kilo 14 | King Fahd Street | P. O. Box 15930
Free Toll Number: 800 1200 013
Fax Number: 800 2445 554
MC Installation system
Technical Data
Material Structural steel with minimum yield strength
280 N/mm2
Coating Sendzimir galvanized
Material
Height Length weight Designation Article number
thickness
Technical Data
Material Structural steel with minimum yield strength
250 N/mm2
Coating Sendzimir galvanized
Material
Height Length weight Designation Article number
thickness
HIT-SC
sieve sleeve
(16-22)
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical Approval a) DIBt, Berlin, Germany ETA-15/0197 / 2015-12-09
c) All data given in this section according to ETA-15/0197, issue 2015-12-09.
13 Updated: Sep-19
Brick types and properties
Interior dimensions
Exterior brick dimensions
of the majority of the holes
Generic bricks
Updated: Sep-19 14
Anchor installation parameters
cmin – Minimum edge distance smin ║ - Min. spacing distance smin ┴ - Min. spacing distance
parallel to the bed joint perpendicular to the bed joint
ccr – Characteristic edge scr ║ - Characteristic spacing scr ┴ - Characteristic spacing
distance distance parallel to the bed joint distance perpendicular to the
bed joint
s┴ ≥ scr ┴ = smin ┴
s┴ ≥ scr ┴ = smin ┴
15 Updated: Sep-19
Edge and spacing distances per brick
cmin= ccr sminII= scrII smin┴ = scr┴
Brick code
[mm] [mm] [mm]
SC 115 240 115
HC 150 300 240
SCS 115 240 115
HCS 125 248 240
HLC 250 240 240
HNC 200 200 200
Anchor dimensions
Anchor size M8 M10 M12
Embedment depth HIT-V-(R, HCR) hef [mm] 80
Embedment depth HIT-IT hef [mm] 80
Design
Anchorages are designed under the responsibility of an engineer experienced in anchorages and masonry work.
Verifiable calculation notes and drawings are prepared taking account of the loads to be anchored. The position
of the anchor is indicated on the design drawings (e.g. position of the anchor relative to supports, etc.).
Anchorages under static or quasi-static loading are designed in accordance with: ETAG 029, Annex C, Design
method A.
Updated: Sep-19 16
Tension loading
The design tensile resistance is the lower value of
- Steel resistance: NRd,s
- Pull-out of the anchor: NRd,p
- Brick breakout failure: NRd,b
- Pull out of one brick NRd,pb
Shear loading
The design shear resistance is the lower value of
- Steel resistance: VRd,s
- Local brick failure: VRd,b
- Pushing out of one brick: VRd,pb
Design tension and shear resistances – Steel failure for internally threaded sleeves HIT-IC
Anchor size M8 M10 M12
Tension NRd,s HIT-IC [kN] 3,9 4,8 9,1
HIT-IC 7,4 11,6 16,9
Shear VRd,s [kN]
Screw 8.8 11,7 18,6 27,0
HIT-IC 15,0 29,9 52,4
M0Rd,s [Nm]
Screw 8.8 24,0 47,8 83,8
17 Updated: Sep-19
Design tension and shear resistances – Pull-out failure of the anchor, brick breakout
failure and local brick failure at characteristic edge distance (c ≥ ccr = cmin) for single anchor
applications
w/w and w/d d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
SC - Solid clay brick
Mz, 2DF
HIT-V M8, M10, M12 1,2 1,0 1,2 1,0
HIT-IC M8 1,2 1,0 1,2 1,0
NRd,p = NRd,b
HIT-IC M10, M12 80 12 1,6 1,4 1,6 1,4
(ccr = cmin = 115mm)
HIT-V + HIT-SC M8, M10, M12 1,6 1,4 1,6 1,4
HIT-IC + HIT-SC M8, M10, M12 1,6 1,4 1,6 1,4
HIT-V M8, M10, M12
VRd,b HIT-V + HIT-SC M8, M10, M12
80 12 1,4
(ccr = cmin = 115mm) HIT-IC M8, M10, M12
HIT-IC + HIT-SC M8, M10, M12
HC - Hollow clay brick
Hlz, 10DF
NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 12 1,2 1,0 1,2 1,0
80
(ccr = cmin = 150 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,4 1,2 1,4 1,2
VRd,b HIT-V + HIT-SC M8, M10, M12 12 0,8
80
(ccr = cmin = 150 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,2
SCS - Solid silica brick
KS, 2DF
NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 12 1,2 1,0 1,4 1,2
80
(ccr = cmin = 125 mm) HIT-IC + HIT-SC M8, M10, M12 20 1,6 1,4 2,0 1,8
VRd,b HIT-V + HIT-SC M8, M10, M12 12 3,4
80
(ccr = cmin = 125 mm) HIT-IC + HIT-SC M8, M10, M12 20 4,8
Updated: Sep-19 18
w/w and w/d d/d
hef fb
Load type Anchor size Ta Tb Ta Tb
[mm] [N/mm²]
Loads [kN]
HLWC – Hollow lightweight concrete brick
HBL, 16DF
NRd,p = NRd,b HIT-V + HIT-SC M8, M10, M12 2 0,5 0,4 0,6 0,5
80
(ccr = cmin = 250 mm) HIT-IC + HIT-SC M8, M10, M12 6 0,8 0,6 1,0 0,8
VRd,b HIT-V + HIT-SC M8, M10, M12 2 1,0
80
(ccr = cmin = 250 mm) HIT-IC + HIT-SC M8, M10, M12 6 1,6
HNWC – Hollow normal weight concrete brick
Parpaing creux
Design tension and shear resistances – Pull out and pushing out of one brick failures
19 Updated: Sep-19
On-site test
For other bricks in solid or hollow masonry, not covered by the Hilti HIT-HY 170 ETA or this technical data manual,
the characteristic resistance may be determined by on-site tension tests (pull-out tests or proof-load tests), according
to ETAG029, Annex B.
For the evaluation of test results, the characteristic resistance shall be obtained taking into account the factor, which
considers the different influences of the product.
The factor for the brick types covered by the Hilti HIT-HY 170 ETA is provided in the following table:
Updated: Sep-19 20
Materials
Material quality
Part Material
Threaded rod Strength class 5.8, A5 > 8% ductile
HIT-V 5.8 (F) Steel galvanized 5m; (F) Hot dip galvanized ≥ 45 m
Threaded rod Strength class 8.8, A5 > 8% ductile
HIT-V 8.8 (F) Steel galvanized 5m; (F) Hot dip galvanized ≥ 45 m
Threaded rod Strength class 70 for ≤ M24 and class 50 for > M24, A5 > 8% ductile
HIT-V-R Stainless steel 1.4401; 1.4404; 1.4578; 1.4571; 1.4439; 1.4362
Threaded rod A5 > 8% ductile
HIT-V-HCR High corrosion resistant steel 1.4528, 1.4565
A5 > 8% ductile
Internally threaded sleeve HIT-IC
Electroplated zinc coated 5m
Steel galvanized
Washer Stainless steel 1.4401; 1.4404; 1.4578; 1.4571; 1.4439; 1.4362
High corrosion resistant steel 1.4529, 1.4565 EN 10088
Strength class 8
Electroplated zinc coated 5m
Hot dip galvanized 45m
Hexagon nut
Strength class 70
Stainless steel grade A4 1.4401;1.4404;1.4578;1.4571;1.4439; 1.4362
Strength class 70, high corrosion resistant steel,1.4529; 1.4565
A5 > 8% ductile
Internally threaded sleeve HIT-IC
Electroplated zinc coated 5 m
Frame: Polyfort FPP 20T
Sieve sleeve HIT-SC
Sieve: PA6.6 N500/200
Base materials:
Solid brick masonry. The characteristic resistances are also valid for larger brick sizes and larger compressive
strengths of the masonry unit.
Hollow brick masonry
Mortar strength class of the masonry: M2,5 at minimum according to EN 998-2: 2010.
For other bricks in solid masonry and in hollow or perforated masonry, the characteristic resistance of the anchor
may be determined by on-site tests according to ETAG 029, Annex B under consideration of the β-factor
according to Table page 9.
Setting information
Base material Max. long term base Max. short term base
Temperature range
temperature material temperature material temperature
Temperature range I -40 °C to + 40 °C + 24 °C + 40 °C
Temperature range II -40 °C to + 80 °C + 50 °C + 80 °C
21 Updated: Sep-19
Max. short term base material temperature
Short term elevated base material temperatures are those that occur over brief intervals, e.g. as a result of diurnal
cycling.
Max. long term base material temperature
Long term elevated base material temperatures are roughly constant over significant periods of time.
Insallation Paramenters
Installation parameters of HIT-V with sieve sleeve HIT-SC in hollow and solid brick
Threaded rods and HIT-V M8 M10 M12
with HIT-SC 16x85 18x85
Nominal diameter of drill bit d0 [mm] 16 16 18
Drill hole depth h0 [mm] 95 95 95
Effective embedment depth hef [mm] 80 80 80
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 16 16 18
Number of strokes HDM 6 6 8
Number of strokes HDE 500- 5 5 6
A
Maximum torque moment for
all brick types except Tmax [Nm] 3 4 6
“parpaing creux”
Maximum torque moment for
Tmax [Nm] 2 2 3
“parpaing creux”
Updated: Sep-19 22
Installation parameters of HIT-IC with HIT-SC in hollow and solid brick
HIT-IC M8 M10 M12
with HIT-SC 16x85 18x85 22x85
Nominal diameter of drill bit d0 [mm] 16 18 22
Drill hole depth h0 [mm] 95 95 95
Effective embedment depth hef [mm] 80 80 80
Thread engagement length hs [mm] 8…75 10…75 12…75
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 16 18 22
Number of strokes HDM 6 8 10
Number of strokes HDE-500 5 6 8
Maximum torque moment Tmax [Nm] 3 4 6
23 Updated: Sep-19
Installation parameters of HIT-IC in solid bricks
HIT-IC M8x80 M10x80 M12x80
Nominal diameter of drill bit d0 [mm] 14 16 18
Drill hole depth =
h0= hef [mm] 80 80 80
Effective embedment depth
Thread engagement length hs [mm] 8…75 10…75 12…75
Maximum diameter of
df [mm] 9 12 14
clearance hole in the fixture
Minimum wall thickness hmin [mm] 115 115 115
Brush HIT-RB 14 16 18
Maximum torque moment Tmax [Nm] 5 8 10
a) Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks
when it is guaranteed that it has not any hole or void.
Installation equipment
Anchor size M8 M10 M12
Rotary hammer TE2(A) – TE30(A)
compressed air gun or blow out pump, set of cleaning brushes,
Other tools
dispenser
M8 - - - 10 10 -
M10 - - - 12 12 12
M12 - M8 - 14 14 14
- M8 - - 16 16 16
- M10 M10 M8 16 16 16
- M12 M12 M10 18 18 18
- - - M12 22 22 22
a) Installation without the sieve sleeve HIT-SC can be used only in case of solid bricks.
Updated: Sep-19 24
Setting instructions
*For detailed information on installation see instruction for use given with the package of the product.
Safety regulations.
Review the Material Safety Data Sheet (MSDS) before use for proper and safe
handling! Wear well-fitting protective goggles and protective gloves when working
with Hilti HIT-HY 170.
Drilling
Cleaning
25 Updated: Sep-19
Setting the element
Injection system
Updated: Sep-19 26
Hilti HSA
EXPANSION ANCHOR
Technical Datasheet
Update: May-19
Standard stud anchor HSA
ADVANTAGES
● ETA-approved torquing using SIW 14-A or 22-A impact wrench
and S-TB
● Fast and easy anchor setting with HS-SC and S-TB
● Excellent edge and spacing distances
● 3 embedment depths offering maximum flexibility
● Suitable for presetting and through-fastening in uncracked
concrete
These are abbreviated instructions which may vary according to the application.
Material composition (Galvanized) Steel, zinc-plated (min. HSA Tensile Load, Nrec 2.5 4.2 5.9 8.8 12.0 16.8
5 μm); (standard
(Hot-dip galvanized) Steel, hot-dip embedment) Shear Load, Vrec 2.1 3.5 6.3 9.8 17.0 28.6
galvanized (min. 5 μm); HSA-R/R2 Tensile Load, Nrec 2.5 4.2 5.9 8.8 12.0 16.8
(Stainless steel) Steel, A4(SS316), (standard
A2(SS304) embedment) Shear Load, Vrec 2.4 4.1 7.5 9.7 18.8 30.6
Head configuration Externally threaded Remarks:
Type of fastening Pre-fastening, Through-fastening 1) All the data applies to no edge distance, spacing and other influences
2) For detail design method and cracked concrete information, please refer to Fastening
Approvals / test reports ETA, Fire Technology Manual
Order Now
Ordering designation Anchor Anchor Drill bit Drill. hole Drill. hole Drill. hole Fastening Fastening Fastening Base Required Sales Item number
size length diameter depth at depth at depth at thick- thick- thick- plate tight- pack
embed.1 embed.2 embed.3 ness at ness at ness at clear- ening quantity
embed.1 embed.2 embed.3 ance torque
hole
HSA M6x50 5/-/- M6 50 mm 6 mm 42 mm - - 5 mm - - 7 mm 5 Nm 200 pc 2036084
HSA M6x65 20/10/- M6 65 mm 6 mm 42 mm 52 mm - 20 mm 10 mm - 7 mm 5 Nm 200 pc 2036085
HSA M6x85 40/30/10 M6 85 mm 6 mm 42 mm 52 mm 72 mm 40 mm 30 mm 10 mm 7 mm 5 Nm 100 pc 2036086
HSA M6x100 55/45/25 M6 100 mm 6 mm 42 mm 52 mm 72 mm 55 mm 45 mm 25 mm 7 mm 5 Nm 100 pc 2036087
HSA M8x55 5/-/- M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004122
HSA M8x70 20/10/- M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004123
HSA M8x85 35/25/- M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004124
HSA M8x105 55/45/15 M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 2004125
HSA M8x130 80/70/40 M8 129.5 mm 8 mm 44 mm 54 mm 84 mm 80 mm 70 mm 40 mm 9 mm 15 Nm 50 pc 20041261)
HSA M10X68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 2004127
HSA M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004128
HSA M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 2004129
HSA M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004150
HSA M10x133 70/60/30 M10 133 mm 10 mm 55 mm 65 mm 95 mm 70 mm 60 mm 30 mm 12 mm 25 Nm 25 pc 20041511)
HSA M10x153 90/80/50 M10 153 mm 10 mm 55 mm 65 mm 95 mm 90 mm 80 mm 50 mm 12 mm 25 Nm 25 pc 2004152
HSA M10x168 105/95/65 M10 168 mm 10 mm 55 mm 65 mm 95 mm 105 mm 95 mm 65 mm 12 mm 25 Nm 25 pc 20041531)
HSA M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004154
HSA M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004155
HSA M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004156
HSA M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 2004157
HSA M12x175 95/80/45 M12 174.5 mm 12 mm 72 mm 87 mm 122 mm 95 mm 80 mm 45 mm 14 mm 50 Nm 25 pc 2004158
HSA M12x205 25/110/75 M12 204.5 mm 12 mm 72 mm 87 mm 122 mm 125 mm 110 mm 75 mm 14 mm 50 Nm 25 pc 20041591)
HSA M12x225 45/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20041601)
HSA M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 2004161
HSA M16x117 20/5/- M16 116.5 mm 16 mm 85 mm 100 mm - 20 mm 25 mm - 18 mm 80 Nm 16 pc 2004162
HSA M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004163
HSA M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004164
HSA M16x232 35/120/80 M16 231.5 mm 16 mm 85 mm 100 mm 140 mm 135 mm 120 mm 80 mm 18 mm 80 Nm 16 pc 2004165 8
HSA M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 2036088
HSA M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 2036089
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products
Customer Hotline: Hong Kong 8228 8118, Macau 00800 8228 8118 Email: hksales@hilti.com
290
HSA-F (Hot-dip galvanized min. 35μm)
Order Now
Ordering designation Anchor Anchor Drill bit Drilling Drilling Drilling Fastening Fastening Fastening Base Required Sales Item
size length diameter Hole Hole Hole thickness thickness thickness plate tightening pack number
Depth at Depth at Depth at at at at clearance torque quantity
embed. 1 embed. 2 embed. 3 embed.1 embed.2 embed.3 hole
HSA-F M8x55 5/-/- M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004113
HSA-F M8x70 20/10/- M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004114
HSA-F M8x85 35/25/- M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004115
HSA-F M8x105 55/45/15 M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 20041161)
HSA-F M8x130 80/70/40 M8 129.5 mm 8 mm 44 mm 54 mm 84 mm 80 mm 70 mm 40 mm 9 mm 15 Nm 50 pc 20041171)
HSA-F M10x68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 20041181)
HSA-F M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004119
HSA-F M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 20041701)
HSA-F M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004171
HSA-F M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004172
HSA-F M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004173
HSA-F M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004174
HSA-F M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 2004175
HSA-F M12x225 145/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20041761)
HSA-F M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 20041771)
HSA-F M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004178
HSA-F M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004179
HSA-F M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 20363121)
HSA-F M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 2036313
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products
Order Now
Ordering designation Anchor Anchor Drill bit Drilling Drilling Drilling Fastening Fastening Fastening Base Required Sales Item
size length diameter Hole Hole Hole thickness thickness thickness plate tightening pack number
Depth at Depth at Depth at at at at clearance torque quantity
embed. 1 embed. 2 embed. 3 embed.1 embed.2 embed.3 hole
HSA-R M6x50 5/-/- M6 50 mm 6 mm 42 mm - - 5 mm - - 7 mm 5 Nm 200 pc 2036314
HSA-R M6x65 20/10/- M6 65 mm 6 mm 42 mm 52 mm - 20 mm 10 mm - 7 mm 5 Nm 200 pc 2036315
HSA-R M6x85 40/30/10 M6 85 mm 6 mm 42 mm 52 mm 72 mm 40 mm 30 mm 10 mm 7 mm 5 Nm 100 pc 2036316
HSA-R M8x55 5/-/- M8 54.5 mm 8 mm 44 mm - - 5 mm - - 9 mm 15 Nm 100 pc 2004197
HSA-R M8x70 20/10/- M8 69.5 mm 8 mm 44 mm 54 mm - 20 mm 10 mm - 9 mm 15 Nm 100 pc 2004198
HSA-R M8x85 35/25/- M8 84.5 mm 8 mm 44 mm 54 mm - 35 mm 25 mm - 9 mm 15 Nm 80 pc 2004199
HSA-R M8x105 55/45/15 M8 104.5 mm 8 mm 44 mm 54 mm 84 mm 55 mm 45 mm 15 mm 9 mm 15 Nm 50 pc 2004200
HSA-R M10x68 5/-/- M10 68 mm 10 mm 55 mm - - 5 mm - - 12 mm 25 Nm 50 pc 2004201
HSA-R M10x83 20/10/- M10 83 mm 10 mm 55 mm 65 mm - 20 mm 10 mm - 12 mm 25 Nm 50 pc 2004202
HSA-R M10x98 35/25/- M10 98 mm 10 mm 55 mm 65 mm - 35 mm 25 mm - 12 mm 25 Nm 40 pc 2004203
HSA-R M10x113 50/40/10 M10 113 mm 10 mm 55 mm 65 mm 95 mm 50 mm 40 mm 10 mm 12 mm 25 Nm 40 pc 2004204
HSA-R M10x133 70/60/30 M10 133 mm 10 mm 55 mm 65 mm 95 mm 70 mm 60 mm 30 mm 12 mm 25 Nm 25 pc 20042051)
HSA-R M10x153 90/80/50 M10 153 mm 10 mm 55 mm 65 mm 95 mm 90 mm 80 mm 50 mm 12 mm 25 Nm 25 pc 20042061)
HSA-R M12x85 5/-/- M12 84.5 mm 12 mm 72 mm - - 5 mm - - 14 mm 50 Nm 25 pc 2004207
HSA-R M12x100 20/5/- M12 99.5 mm 12 mm 72 mm 87 mm - 20 mm 5 mm - 14 mm 50 Nm 25 pc 2004208
HSA-R M12x115 35/20/- M12 114.5 mm 12 mm 72 mm 87 mm - 35 mm 20 mm - 14 mm 50 Nm 25 pc 2004209
HSA-R M12x145 65/50/15 M12 144.5 mm 12 mm 72 mm 87 mm 122 mm 65 mm 50 mm 15 mm 14 mm 50 Nm 25 pc 20042101)
HSA-R M12x175 95/80/45 M12 174.5 mm 12 mm 72 mm 87 mm 122 mm 95 mm 80 mm 45 mm 14 mm 50 Nm 25 pc 20042111)
HSA-R M12x205 125/110/75 M12 204.5 mm 12 mm 72 mm 87 mm 122 mm 125 mm 110 mm 75 mm 14 mm 50 Nm 25 pc 20042121)
HSA-R M12x225 145/130/95 M12 224.5 mm 12 mm 72 mm 87 mm 122 mm 145 mm 130 mm 95 mm 14 mm 50 Nm 25 pc 20042131)
HSA-R M16x102 5/-/- M16 101.5 mm 16 mm 85 mm - - 5 mm - - 18 mm 80 Nm 16 pc 2004214
HSA-R M16x117 20/5/- M16 116.5 mm 16 mm 85 mm 100 mm - 20 mm 25 mm - 18 mm 80 Nm 16 pc 20042151)
HSA-R M16x137 40/25/- M16 136.5 mm 16 mm 85 mm 100 mm - 40 mm 25 mm - 18 mm 80 Nm 16 pc 2004216
HSA-R M16x182 85/70/30 M16 181.5 mm 16 mm 85 mm 100 mm 140 mm 85 mm 70 mm 30 mm 18 mm 80 Nm 16 pc 2004217
HSA-R M20x125 10/-/- M20 125 mm 20 mm 98 mm - - 10 mm - - 22 mm 200 Nm 10 pc 20363171)
HSA-R M20x170 55/30/- M20 170 mm 20 mm 98 mm 123 mm 138 mm 55 mm 30 mm 15 mm 22 mm 200 Nm 10 pc 20363181)
1)
This is a non-stock item. For detailed lead time information please contact your Hilti representative.
Please visit Hilti website for the latest item numbers and related products
8
Order Now
Ordering designation Anchor size Drill bit diameter Fastening Base plate Required Sales pack Item number
thickness clearance tightening quantity
at embed.2 hole torque
Customer Hotline: Hong Kong 8228 8118, Macau 00800 8228 8118 Email: hksales@hilti.com
292
Torque bar S-TB
Ordering Drive connection Drive head Material coating/ Material Tool type Base material Connection end Sales Item number
designation plating/finish composition size pack
quantity
S-TB HSA M8 1/2 in square, 1/2 in, square, Black Impact-grade Impact tools, Concrete 12.7 mm 1 pc 423774
female male chrome SIW (uncracked)
molybdenum
steel
S-TB HSA M10 1/2 in square, 1/2 in, square, Black Impact-grade Impact tools, Concrete 12.7 mm 1 pc 423775
female male chrome SIW (uncracked)
molybdenum
steel
S-TB HSA M12 1/2 in square, 1/2 in, square, Black Impact-grade Impact tools, Concrete 12.7 mm 1 pc 423776
female male chrome SIW (uncracked)
molybdenum
steel
S-TB HSA M16 1/2 in square, 1/2 in, square, Black Impact-grade Impact tools, Concrete 12.7 mm 1 pc 423777
female male chrome SIW (uncracked)
molybdenum
steel
Please visit Hilti website for the latest item numbers and related products
① ②
Please visit Hilti website for the latest item numbers and related products
Approvals / certificates
Description Authority / Laboratory No. / date of issue
European technical assessment a) DIBt, Berlin ETA-11/0374 / 2016-08-08
a) All data given in this section according to ETA-11/0374, issue 2016-08-08.
1 Updated: May-19
Static and quasi-static loading (for a single anchor)
Characteristic resistance
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 6,0 7,5 9,0 8,3 12,8 16,0 12,8 17,9 25,0
Tension
HSA-R2, HSA-R [kN] 6,0 7,5 9,0 8,3 12,8 16,0 12,8 17,9 25,0
NRk
HSA-F 6,0 7,5 9,0 8,3 12,8 15,9 12,8 17,9 25,0
HSA, HSA-BW 6,5 6,5 6,5 8,3 10,6 10,6 18,9 18,9 18,9
Shear
HSA-R2, HSA-R [kN] 7,2 7,2 7,2 8,3 12,3 12,3 22,6 22,6 22,6
VRk
HSA-F 6,5 6,5 6,5 8,3 10,6 10,6 18,9 18,9 18,9
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 17,9 26,5 35,0 26,5 36,1 50,0 32,8 50,5 62,3
Tension
HSA-R2, HSA-R [kN] 17,9 26,5 35,0 26,5 36,1 50,0 32,8 50,5 62,3
NRk
HSA-F 17,9 26,5 35,0 26,5 36,1 50,0 32,8 b) 50,5 b) 62,3 b)
HSA, HSA-BW 29,5 29,5 29,5 51,0 51,0 51,0 65,6 85,8 85,8
Shear
HSA-R2, HSA-R [kN] 29,3 29,3 29,3 56,5 56,5 56,5 65,6 91,9 91,9
VRk
HSA-F 29,5 29,5 29,5 51,0 51,0 51,0 65,6b) 85,8b) 85,8b)
b) Data covered by Hilti Technical Data.
Design resistance
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
Tension
HSA-R2, HSA-R [kN] 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
NRd
HSA-F 4,0 5,0 6,0 5,5 8,5 10,7 8,5 11,9 16,7
HSA, HSA-BW 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
Shear
HSA-R2, HSA-R [kN] 5,5 5,8 5,8 5,5 9,8 9,8 18,1 18,1 18,1
VRd
HSA-F 5,2 5,2 5,2 5,5 8,5 8,5 15,1 15,1 15,1
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 11,9 17,6 23,3 17,6 24,1 33,3 21,9 33,7 41,5
Tension
HSA-R2, HSA-R [kN] 11,9 17,6 23,3 17,6 24,1 33,3 21,9 33,7 41,5
NRd
HSA-F 11,9 17,6 23,3 17,6 24,1 33,3 21,9 b) 33,7 b) 41,5 b)
HSA, HSA-BW 23,6 23,6 23,6 40,8 40,8 40,8 43,7 68,6 68,6
Shear
HSA-R2, HSA-R [kN] 23,4 23,4 23,4 45,2 45,2 45,2 43,7 73,5 73,5
VRd
HSA-F 23,6 23,6 23,6 40,8 40,8 40,8 43,7 b) 68,6 b) 68,6 b)
b) Data covered by Hilti Technical Data.
Updated: May-19 2
Recommended loads a)
Anchor size M6 M8 M10
Eff. Anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
HSA, HSA-BW 2,9 3,6 4,3 4,0 6,1 7,6 6,1 8,5 11,9
Tension 4,0 6,1
HSA-R2, HSA-R [kN] 2,9 3,6 4,3 7,6 6,1 8,5 11,9
Nrec
HSA-F 2,9 3,6 4,3 4,0 6,1 7,6 6,1 8,5 11,9
HSA, HSA-BW 3,7 3,7 3,7 4,0 6,1 6,1 10,8 10,8 10,8
Shear 4,0
HSA-R2, HSA-R [kN] 4,0 4,1 4,1 7,0 7,0 12,9 12,9 12,9
Vrec
HSA-F 3,7 3,7 3,7 4,0 6,1 6,1 10,8 10,8 10,8
Anchor size M12 M16 M20
Eff. Anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
HSA, HSA-BW 8,5 12,6 16,7 12,6 17,2 23,8 15,6 24,0 29,7
Tension
HSA-R2, HSA-R [kN] 8,5 12,6 16,7 12,6 17,2 23,8 15,6 24,0 29,7
Nrec
HSA-F 8,5 12,6 16,7 12,6 17,2 23,8 15,6 b) 24,0 b) 29,7 b)
HSA, HSA-BW 16,9 16,9 16,9 29,1 29,1 29,1 31,2 49,0 49,0
Shear
HSA-R2, HSA-R [kN] 16,7 16,7 16,7 32,3 32,3 32,3 31,2 52,5 52,5
Vrec
HSA-F 16,9 16,9 16,9 29,1 29,1 29,1 31,2 b) 49,0 b) 49,0 b)
a) With overall partial safety factor for action = 1,4. The partial safety factors for action depend on the type of loading and shall be
taken from national regulations.
b) Data covered by Hilti Technical data
Materials
Mechanical properties
Anchor size M6 M8 M10 M12 M16 M20
Nominal tensile HSA, HSA-BW, HSA-F 650 580 650 700 650 700
[N/mm²]
strength fuk,thread
HSA-R2, HSA-R 650 560 650 580 600 625
Yield strength HSA, HSA-BW, HSA-F 520 464 520 560 520 560
fyk,thread HSA-R2, HSA-R [N/mm²] 520 448 520 464 480 500
Stressed cross-section As [mm²] 20,1 36,6 58 84,3 157 245
Moment of resistance W [mm³] 12,7 31,2 62,3 109,2 277,5 540,9
Char. bending HSA, HSA-BW, HSA-F 9,9 21,7 48,6 91,7 216,4 454,4
[Nm]
resistance HSA-R2, HSA-R 9,9 21 48,6 76 199,8 405,7
M0Rk,s
3 Updated: May-19
Material quality
Part Material
Bolt Galvanized (≥5 µm)
HSA
Sleeve Galvanized (≥5 µm)
HSA-BW
Washer Galvanized (≥5 µm)
(Carbon steel)
Hexagon nut Strength class 8 / Galvanized (≥5 µm)
Bolt Stainless steel A2, 1.4301; M6-M20 coated
HSA-R2 Sleeve Stainless steel A2
(Stainless steel) Washer Stainless steel A2
Hexagon nut Stainless steel A2; / M6-M20 coated
Bolt Stainless steel A4, 1.4401 or 1.4362 / M6-M20 coated
HSA-R Sleeve Stainless steel A2
(Stainless steel) Washer Stainless steel A4
Hexagon nut Stainless steel A4; / M6-M20 coated
Bolt Hot-dip galvanized (≥42 µm)
HSA-F Sleeve Stainless steel A2
(Carbon steel) Washer Hot-dip galvanized (≥42 µm)
Hexagon nut Strength class 8 / Hot-dip galvanized (≥42 µm)
Geometry washer
Anchor size M6 M8 M10 M12 M16 M20
Inner diameter d1
HSA, HSA-R2, HSA-R, HSA-F d1 [mm] 6,4 8,4 10,5 13,0 17,0 21
HSA-BW d1 [mm] 6,4 8,4 10,5 13,0 17,0 22
Outer diameter d2
HSA, HSA-R2, HSA-R, HSA-F d2 [mm] 12,0 16,0 20,0 24,0 30,0 37,0
HSA-BW d2 [mm] 18,0 24,0 30,0 37,0 50,0 60,0
Thickness h
HSA, HSA-R2, HSA-R, HSA-F h [mm] 1,6 1,6 2,0 2,5 3,0 3,0
HSA-BW h [mm] 1,8 2,0 2,5 3,0 3,0 4,0
Product marking and identification of anchor:
Updated: May-19 4
Material code for identification of different materials
HSA, HSA-BW, HSA-F HSA-R2 HSA-R
Type
(carbon steel) (Stainless steel grade A2) (stainless steel grade A4)
Material code
Letter code for anchor length and maximum thickness of the fixture t fix
Type HSA, HSA-BW, HSA-R2, HSA-R, HSA-F
Size M6 M8 M10 M12 M16 M20
90 / 115 /
hnom [mm] 37 / 47 / 67 39 / 49 / 79 50 / 60 / 90 64 / 79 / 114 77 / 92 / 132
130
Letter tfix tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3 tfix,1/tfix,2/tfix,3
z 5/-/- 5/-/- 5/-/- 5/ -/- 5/-/- 5/-/-
y 10/-/- 10/-/- 10/-/- 10/-/- 10/-/- 10/-/-
x 15/5/- 15/5/- 15/5/- 15/-/- 15/-/- 15/-/-
w 20/10/- 20/10/- 20/10/- 20/5/- 20/5/- 20/-/-
v 25/15/- 25/15/- 25/15 25/10/- 25/10/- 25/-/-
u 30/20/- 30/20/- 30/20/- 30/15/- 30/15/- 30/5/-
t 35/25/5 35/25/- 35/25/- 35/20/- 35/20/- 35/10/-
s 40/30/10 40/30/- 40/30/- 40/25/- 40/25/- 40/15/-
r 45/35/15 45/35/5 45/35/5 45/30/- 45/30/- 45/20/5
q 50/40/20 50/40/10 50/40/10 50/35/- 50/35/- 50/25/10
p 55/45/25 55/45/15 55/45/15 55/40/5 55/40/- 55/30/15
o 60/50/30 60/50/20 60/50/20 60/45/10 60/45/5 60/35/20
n 65/55/35 65/55/25 65/55/25 65/50/15 65/50/10 65/40/25
m 70/60/40 70/60/30 70/60/30 70/55/20 70/55/15 70/45/30
l 75/65/45 75/65/35 75/65/35 75/60/25 75/60/20 75/50/35
k 80/70/50 80/70/40 80/70/40 80/65/30 80/65/25 80/55/40
j 85/75/55 85/75/45 85/75/45 85/70/35 85/70/30 85/60/45
i 90/80/60 90/80/50 90/80/50 90/75/40 90/75/35 90/65/50
h 95/85/65 95/85/55 95/85/55 95/80/45 95/80/40 95/70/55
g 100/90/70 100/90/60 100/90/60 100/85/50 100/85/45 100/75/60
f 105/95/75 105/95/65 105/95/65 105/90/55 105/90/50 105/80/65
e 110/100/80 110/100/70 110/100/70 110/95/60 110/95/55 110/85/70
d 115/105/85 115/105/75 115/105/75 115/100/65 115/100/60 115/90/75
c 120/110/90 120/110/80 120/110/80 125/110/75 120/105/65 120/95/80
b 125/115/95 125/115/85 125/115/85 135/120/85 125/110/70 125/100/85
a 130/120/100 130/120/90 130/120/90 145/130/95 135/120/80 130/105/90
aa - - - 155/140/105 145/130/90 -
ab - - - 165/150/115 155/140/100 -
ac - - - 175/160/125 165/150/110 -
ad - - - 180/165/130 190/175/135 -
ae - - - 230/215/180 240/225/185 -
af - - - 280/265/230 290/275/235 -
ag - - - 330/315/280 340/325/285 -
Anchor length in bolt type and grey shaded are standard items. For selection of other anchor length, check availability of the items.
5 Updated: May-19
Setting information
Setting details
Anchor size M6 M8 M10
Nominal anchorage depth hnom [mm] 37 47 67 39 49 79 50 60 90
Minimum base material
hmin [mm] 100 100 120 100 100 120 100 120 160
thickness
Minimun spacing smin [mm] 35 35 35 35 35 35 50 50 50
Minimum edge distance cmin [mm] 35 35 35 40 35 35 50 40 40
Nominal diameter of drill
d0 [mm] 6 8 10
bit
Cutting diameter of drill bit dcut ≤ [mm] 6,4 8,45 10,45
Depth of drill hole h1 ≥ [mm] 42 52 72 44 54 84 55 65 95
Diameter of clearance
dr ≤ [mm] 7 9 12
hole in the fixture
Torque moment Tinst [Nm] 5 15 25
Width across SW [mm] 10 13 17
Anchor size M12 M16 M20
Nominal anchorage depth hnom [mm] 64 79 114 77 92 132 90 115 130
Minimum base material
hmin [mm] 100 140 180 140 160 180 160 220 220
thickness
Minimun spacing smin [mm] 70 70 70 90 90 90 195 175 175
Minimum edge distance cmin [mm] 70 65 55 80 75 70 130 120 120
Nominal diameter of drill
d0 [mm] 12 16 20
bit
Cutting diameter of drill bit dcut ≤ [mm] 12,5 16,5 20,55
Depth of drill hole h1 ≥ [mm] 72 87 122 85 100 140 98 123 138
Diameter of clearance
dr ≤ [mm] 14 18 22
hole in the fixture
Torque moment Tinst [Nm] 50 80 200
Width across SW [mm] 19 24 30
For spacing (edge distance) smaller than critical spacing (critical edge distance) the design loads have to
be reduced.
Updated: May-19 6
Installation equipment
Anchor size M6 M8 M10 M12 M16 M20
Rotary hammer TE40 –
TE2 – TE16
TE80
Other tools hammer, torque wrench, blow out pump
Machine tightening
Setting tool - S-TB HSA -
Impact screw driver Hilti S/W 14-A Hilti S/W
- -
Hilti S/W 22-A 22T-A
Speed HAS, HAS-BW, HAS-F - 1 -
3 -1)
HAS-R2, HAS-R - 3 -
Setting time tset [sec] - 4 -
1) The impact screw driver operates with a fixed speed.
Setting parameters
Anchor size M6 M8 M10
Nominal anchorage depth hnom [mm] 37 47 67 39 49 79 50 60 90
Effective anchorage depth hef [mm] 30 40 60 30 40 70 40 50 80
Critical spacing for
scr,sp [mm] 100 120 130 130 180 200 190 210 290
splitting failure
Critical edge distance for
ccr,sp [mm] 50 60 65 65 90 100 95 105 145
splitting failure
Critical spacing for
scr,N [mm] 90 120 180 90 120 210 120 150 240
concrete cone failure
Critical edge distance for
ccr,N [mm] 45 60 90 45 60 105 60 75 120
concrete cone failure
Anchor size M12 M16 M20
Nominal anchorage depth hnom [mm] 64 79 114 77 92 132 90 115 130
Effective anchorage depth hef [mm] 50 65 100 65 80 120 75 100 115
Critical spacing for
scr,sp [mm] 200 250 310 230 280 380 260 370 400
splitting failure
Critical edge distance for
ccr,sp [mm] 100 125 155 115 140 190 130 185 200
splitting failure
Critical spacing for
scr,N [mm] 150 195 300 195 240 360 225 300 345
concrete cone failure
Critical edge distance for
ccr,N [mm] 75 97,5 150 97,5 120 180 112,5 150 172,5
concrete cone failure
7 Updated: May-19
Setting instructions
*For detailed information on installation see instruction for use given with the package of the product
1. Hole drilling
Hammer drilling with Hilti hollow
Hammer drilling (HD): M6-M20 Diamond drilling (DD): M10-M20
drill bit (HDB): M12-M20
2. Cleaning
Manual cleaning (MC): M6-M20 Automatic cleaning (AC): M12-M20
3. Anchor setting
Machine setting (impact screw driver with setting
Hammer setting: M6-M20
tool): M8-M16
4. Check setting
5. Anchor torqueing
Torque wrench: M6-M20 Impact screw driver with setting tool: M8-M16
Updated: May-19 8
Printed in UAE © 2021 Right of technical and programme changes reserved S. E. & O.
Hilti = registered trademark of Hilti Corp., Schaan MTCAT-AE 06 2021-en
The data contained in this literature was current as of the date of publication. Updates and changes may
be made based on later testing. If verification is needed that data is still current,
www.hilti.group please contact local Hilti representative.