You are on page 1of 8

Behavior of Distance Protections near Wind Farms

Rita Isabel Alexandre Lúcio


Instituto Superior Técnico

Abstract—Over the years, the concern for the environment lead to the smaller than the branch impedance, the protection will detect the
introduction of the renewable energy, particularly wind energy, into the fault and send a signal to the relay to trip.
electrical national grid. The liberalization of energy markets in renewable
The fault impedance detected by the protection is proportional
energy and the interest of private investors had created small units of
production that lead the new concept of Distributed Generation. This with the distance between the protection and the fault local.
new concept of energy production leads to the need of stability studies
mainly due to the unpredictability of wind generation.
The major requirement to connect a new unit of Distributed Genera- B. Principles of Operation
tion to the electrical national grid is the good coordination between the Some requirements have to be accomplished to make sure that the
protection scheme of the generation unit and the remaining network.
protective system is effective:
This thesis intends to study the impact on Distance Protection of voltage
drops near wind turbines. • Sensibility - the protection must only trip when there is a fault
In this sense, fault simulations on electrical national grid near a
wind farm are performed using PSS/E software. The purpose of this in the branch where the protection is installed. The protection
simulations are the study of the influence on the voltage drop of the must have back-up zones to protect the branches that are
most commonly wind turbines used in Portugal, the influence on voltage downstream of the protection location;
drop of fluctuation of frequency, the influence of a reconnection of the
branch after a voltage drop and the behavior of Distance Relays under • Selectivity - the protection has to be ability to isolate the faulty
power swing conditions. branch from the remaining network;
Index Terms—Distance Protection, Wind Turbine, Distributed Gener- • Speed of operation - the protection must eliminate the fault
ation, Voltage Drop, Power Swing. in the shortest time possible to decrease the damage that it can
cause to electrical equipment. The faster the protection operates
I. I NTRODUCTION the less will be the probability that the electrical grid turns into
A. Motivation an unstable system;
In the latest years, the preservation of the environment and the • Dependency - the protection must operate if the fault occur
increase of the price of fossil fuels became the major reasons for in the branch where it is located or in case the downstream
the increase of Renewable Energy. The wind energy is the most protection does not operate.
developed renewable energy.
Due to the unpredictability of wind production and the number of C. Operating Characteristics
wind turbines installed in Portugal, the national grid had to suffer
some changes to keep the stability of the system. As has been described, the sensibility of the protection is defined
in zones of operation. This zones have operating characteristics that
are defined by a region limited by the operation impedance, zop , that
B. Distributed Generation is obtained in function of δp [3].
The concept of Distributed Generation (DG) is a new definition The Distance Protection only operates when zp ≤ zop and stays
for some power sources with characteristics mentioned below ([1] inactive if zp > zop [4]. As has been referred, zp is the impedance
and [2]): measured by the protection and can also be represented as zp =
• Small units of generation, compared to conventional power rp + jxp , where rp and xp are, respectively, the resistance and the
plants; reactance measured by the protection.
• Privately owned; The impedance is a complex number so it is represented in a
• Not centrally dispatched; complex plan, where the real axis represents values of resistance,
• Connected to Medium Voltage or Low Voltage distributed r, and the imaginary axis represents values of reactance, x. Also
networks; the operating characteristics and the values of impedance measured
• Contribute to frequency and voltage control; on relay terminals are represented in a complex plan called R-X
• Not considered when the grid is planned. Diagram [3].
The major reasons for the increase of DG are the energy markets The Distance Protections can operate in many ways, depending on
liberalization and the policy for reduction of CO2 emissions. their operating characteristic. Below, the most used types of Distance
Protections are presented ([5] and [3]):
II. D ISTANCE P ROTECTION a) Non-directional: this protection has a circular shape witch
A. Concept the center is coincident with the R-X Diagram origin and the radius
is zop (Fig. 1(a));
The purpose of Distance Protection is to detect a fault in a network.
The protection calculates the impedance (zp ) of the branch from the b) Mho: this protection has also a circular characteristic that
local where the protection is installed to the local where the fault passes through the origin of the R-X Diagram. The fact of the
occurred. The impedance calculation is made using the voltage (Vp ) protection doesn’t operate in the third quadrant (π < δp < 3π/2),
and current (Ip ) measured by the protection. means that the protection is directional (Fig. 1(b)).
Vp c) Offset Mho: this type of protection is very similar to Mho
zp = (1) protection but this one covers a part of the third quadrant, this means
Ip
that the Offset Mho type of protection has the ability to protect the
The impedance value calculated by the protection is compared
bus where the protection is installed (Fig. 1(c));
with the known value of the branch. If the protection impedance is
2

d) Elliptical: the operating characteristic of this protection has


an elliptical shape that passes through the origin of R-X Diagram.
This type of protection has directionality and presents more selec-
tivity than the Mho protection (Fig. 1(d));
e) Reactance: this protection trips when xp ≤ xop . The
operating characteristic of this relay is represented by a horizontal
straight line. The main characteristic of this relay is the fact of
the resistive component of the impedance doesn’t have influence its
operation (Fig. 1(e));
Fig. 3: Schematic representation of Distance Protection selectivity,
f) Polygonal: this type of protection has a characteristic with figure adapted from [3].
a polygonal shape. This protection represents the type that is more
similar with the real area described by zp in case of a fault (Fig.
1(f)). E. Problems of Application
Distance Protection does not have a 100% precision index, due to
several errors that can be caused by:
• Relays intrinsic precision - this imprecision is caused by
material limitations. This error is around 5% [6];
• Measuring Transformers imprecisions - to measure the
branch voltage and current measuring transformers are needed.
(a) (b) (c) As all electrical equipments, also measuring transformers have
precision errors [6];
• Imprecisions on branches impedance calculations - branch
impedance value has some variations. This variations are due to
climacteric conditions like humidity, wind speed and tempera-
ture [6];
• Transverse line capacitance - transversal capacitance is usually
despised on short circuit calculations. For branches longer than
(d) (e) (f) 100km the value of this parameter starts to increase when a
fault occurs [6];
Fig. 1: Schematic representation of types of Operating
Characteristics of Distance Protection, figure adapted from [3]: a) • Electromagnetic transient associated with faults - a fault
Non-directional; b) Mho; c) Offset Mho; d) Elliptical; e) is always followed by electromagnetic transient phenomena.
Reactance; f) Polygonal. The transient leads to current and voltage harmonics with fre-
quencies than fundamental frequency. The impedance measured
by Distance Protection considers the current and the voltage
harmonics. This harmonics are noises and can lead to errors
D. Mode of Operation
[6];
Most of the Distance Protections have directionality that makes
• Underreaching and Overreaching errors - an Underreach
the protection to operate only operates when the current has a direct
Distance Protection concept occurs when the fault impedance
direction. To protect the electrical grid in direct and reverse directions
calculated by the protection is higher than the protection
two protections in each branch of the network must be installed (Fig.
impedance setting. For the other hand, an Overreach Distance
2).
Protection concept occurs when the fault impedance calculated
by the protection is smaller than the protection impedance
setting [6].

F. Settings of Relay zones


Fig. 2: Representation of the mode of operation of Distance To avoid the errors mentioned on section II-E a safety factor is
Protections, figure adapted from [3]. considered. The values of the safety factor are the typical values used
on Distance Protection zones calculation.
With this mode of installation of Distance Protections it is possible The first zone (Z1 ) is a zone of instantaneous operation. The time
to protect all the quadrants of R-X Diagram and protect the network delay should be smaller than 40ms. This zone is normally set to
faults. reach of 90% of the branch where the protection is installed.
The protection system coordination is essential to accomplish with Z1 = 0, 9 × ZIR (2)
principles described in section II-B, so each Distance Protection has
(ZIR represents the impedance of the branch where the protection
three operation zones temporized with each other.
is installed.)
The first zone is an instantaneous zone, the second and the third
The second zone (Z2 ) is considered the first backup zone. The
zones are backup zones that operate only when the fault happens on
time delay typically selected is between 200ms and 500ms. The
downstream branches and the protection of that branch doesn’t trip
reach of zone 2 is set cover the entire protection branch and the
at the right time.
downstream bus.
With the purpose of preventing Distance Protections from tripping
at the same time and unnecessarily (selectivity), each zone has a Z2 = 0, 85 × (ZIR + 0, 9 × ZIIB ) (3)
delay time (ta ). In this article steps of time for each zone are
considered (Fig. 3). ZIIB = 0, 9 × ZIIR (4)
3

(ZIIR represents the impedance of the largest electrical branch 1) Zero Power Mode (ZPM) - during a voltage drop the wind
connected with the downstream bus and ZIIB is the ZIIR parcel turbines stops the injection of active and reactive power. When
considered on zone 2 calculation.) the voltage starts to increase and passes through a particular
At last, the third zone (Z3 ) should have a time delay approximately value the wind turbine starts to inject active and reactive power
of 1000ms. This zone is the second backup zone that should protect with a ramp function till this electrical characteristics get to
the branch where is installed the Distance Protection and all the the initial values.
largest downstream branch [7]. 2) Active Power Mode (APM) - during the drop voltage the
Iccrest wind turbine injects active current.
Z3 = ZIR + 1, 2 × ZIIR × (1 + ) (5)
Iccprotection
3) Current Angle Mode (CAM) - during the drop voltage
(Iccprotection represents the current measured by the protection the wind turbine injects current with a configurable voltage
and Iccrest represents the sum of all currents that are linked to argument.
protection downstream bus except the protection bus and the branch Operation modes APM and CAM are only possible if the voltage
where occurred the fault, equation 6 (Fig.4).) on generator terminals is greater than 0.1pu, otherwise the generator
control system forces it to operate on ZPM mode [11]. All kinds of
Iccrest = IB + ID + IE (6)
wind turbines (DFIG and VSSG) are protected by an undervoltage
protection, this protection trips when the voltage drops under 0.8pu
and disconnects the wind farm from the electrical grid.

C. Simulation of wind turbine transient

Fig. 4: Schematic representation of a fault on simple electrical grid,


figure adapted from [7].

III. S TUDY OF WIND TURBINE TRANSIENT BEHAVIOR


A. Wind Turbines
In the 90’s, due to the high number of installed wind turbines in
Portugal, wind turbines with power electronics were installed. The
advantage of these wind turbines is the facility of power control and
the maximization of the performance when the wind turbine operates
with a variable speed.
There are two groups of wind turbines that are distinguished by Fig. 5: Electrical grid on analysis.
the type of electromechanical conversion used [8]:
In this section a fault is simulated on Pereiro [30206] - Espariz
• Double Fed Induction Generator (DFIG) - this wind turbine [30233] bus, near Espariz [30233] bus, from the electrical grid on
has the rotor connected to the generator by a gearbox to adapt Fig. 5, using each kind of wind turbines described on this article.
the speed of the turbine to the generator rotation speed. The In Fig. 6 temporal evolution of voltage is represented, active and
stator of the machine is connected to the electrical grid trough reactive power on EP1 [72334] bus (bus where the wind farm is
AC/DC/AC converter and through a elevator transformer, [9]; installed). The fault occurs at t = 100ms and at t = 200ms the
• Variable Speed Synchronous Generator (VSSG) - the main branch where the fault occurred trip due to the distance protection
characteristic of this kind of with turbine is the absence of operation.
a gearbox, this means that the machine rotation speed is the
• DFIG wind farm installed at EP1 [72334] bus - At Fig. 6(a)
same of the speed of the wind turbine. The adjustment of the
it’s visible that the voltage on EP1 bus is greater than 0.1pu,
electrical frequency of the generator to the frequency of the
so the wind farm keeps connected with the electrical grid. The
electrical grid is done using an AC/DC/AC converter system.
active power injected in the grid is practically zero, on the other
This wind turbine also has an elevator transformer that makes
hand the reactive power injected in the grid, during 20ms, is
the connection between the converter and the electrical grid,
greater than the reactive power injected in the grid before the
[9];
fault, Fig. 6(b) and Fig. 6(c).
These two kinds of wind turbines are very sensitive to drop • VSSG wind farm installed at EP1 [72334] bus, with ZPM
voltages. This drop voltage causes high currents and high voltages mode active - The control system has a time delay of 20ms on
that could destroy the electrical components of converters. voltage measurement (Fig. 6(a)). The voltage value measured at
Nowadays, DFIG and VSSG wind turbines have the ability to EP1 bus is null due to the block of the inverter that connects the
support drop voltages without disconnecting from the electrical grid. generator with the electrical grid. When the fault is eliminated
(at t = 200ms) the generator starts to inject active and reactive
B. Wind Turbine Transient power on grid, Fig. 6(b) and Fig. 6(c).
• VSSG wind farm installed at EP1 [72334] bus, with APM
The DFIG and VSSG wind generators have different performances
mode active - On Fig. 6(a) can be verified that after 60ms
during and after a drop voltage.
from the fault the voltage at EP1 bus drops under 0.1pu, so
During the fault, the DFIG wind generator injects reactive power
the control system forces the wind turbine to operate on ZPM
on electrical grid but if the voltage drops under 0.1pu the generator
mode.
is disconnected from electrical grid. On the other hand, the VSSG
• VSSG wind farm installed at EP1 [72334] bus, with CAM
wind turbine has three mode to operate when a fault occurs [8]:
mode active - This mode of operation is different from the other
4

two modes of VSSG wind turbines. These differences are due SEI-EZ bus has the aim to protect the grid on the direct direction of
to the injection of reactive power during the fault, Fig. 6(c). The the current, the protection installed near Espariz bus has the aim to
injection of reactive power is the support of voltage to avoid protect the grid from the reverse currents.
ZPM mode operation. Fig. 7 shows, on a r-x diagram, the impedances trajectory mea-
sured by distance protection, installed on SEI-EZ bus under the
conditions mentioned before. As can be verified through the Fig.7,
the distance protection detect the fault and operates tripping the
expecting zone, Zone 2, independently of the type of wind turbine
installed on EP1 bus. The only difference that can be observed
between the behaviors of the distance protection referring with
the differents wind turbine is the impedance trajectory after the
elimination of the fault.

(a)

Fig. 7: Impedance trajectory measured by distance protection


during the occurrence of a fault at Espariz-Pereiro branch, near
Espariz bus.

Temporal evolutions of the current that passes through the distance


protection are shown in Fig. 8. Also on Fig. 8 it can be observed
(b) that the current measured on ZPM and APM modes drops under the
established minimum of current of 0.8pu, forcing the protection to
turn off.

(c)

Fig. 6: Temporal evolution of voltage, (a), active power, (b), and Fig. 8: Temporal evolution of current measured by distance
reactive power, (c), on EP1bus. On EP1 bus there are connected a protection during the occurrence of a fault at Espariz-Pereiro
DFIG wind farm, or a VSSG wind farm with one of operate modes branch, near Espariz bus.
activated: ZPM, APM, or CAM. The fault occurred at Espariz
[30233] - Pereiro [30206] branch, near Espariz bus.

B. Impact of frequency fluctuation on Distance Protection


IV. S TUDY OF D ISTANCE P ROTECTION BEHAVIOR
When a fault occurs on an electrical grid some frequency varia-
A. Behavior of Distance Protection during a voltage drop tions are detected due to generator speed variations. To understand
To analyze the behavior of distance protection installed near wind the influence of frequency variations, the frequencies on Espariz and
farms when the occurrence of a fault, in this section, a fault at SEI-EZ buses were monitorized during the occurrence of faults on
Espariz-Pereiro branch, near Espariz bus, is simulated, Fig. 5. At Espariz - Pereiro branch and Espariz - Penela branch. For each
bus EP1 [72334] is installed a wind farm that is composed by DFIG simulation fault it is considered that on EP1 bus a wind farm is
wind turbines, or VSSG wind turbines with a ZPM mode active, or connected and it is composed with DFIG wind turbines or with
VSSG with a APM mode active or VSSG with a CAM mode active. VSSG wind turbines with a CAM mode active.
In the electrical grid represented on Fig. 5 there are installed two A fault can originate an increase of about 0.8% of the initial value
protections on SEI-EZ - Espariz branch. The protection installed near measured on SEI-EZ bus, as may be observed in Fig. 9.
5

(a)

Fig. 9: Temporal evolution of frequency at SEI-EZ (in blue) and


Espariz (in red) buses when a fault at Espariz-Pereiro branch and
at Espariz-Penela branch occurs.

DFIG wind turbines cause bigger frequency variations than VSSG


- CAM mode wind turbines, as may be observed in Fig. 9.
Comparing the frequency variations measured in function of a bus
position, it is visible that the bus closer to the wind farm (SEI-EZ)
has frequency variations with a larger magnitude than the values (b)
measured from Espariz bus.
Fig. 10: Impedance trajectory measured by distance protection with
The influence of frequency on impedance is larger when the VSSG
and without reclosure of the faulted branch (in pink and blue,
wind turbines are connected to EP1 bus. In the other hand, when EP1
respectively). A VSSG wind farm connected at EP1 bus is
bus is connected to a DFIG wind generator the influence of frequency
simulated in Fig. a) while in Fig. b) a DFIG wind farm connected
variations on the impedance measured by the protection is smaller
at EP1 bus is simulated .
than 1%, which can be considered insignificant.

C. Impact of Reclosure on Distance Protection


or not, can cause undesirable trips of the protection system that can
In this section the influence of a reclosure of the faulted branch
cause more damage to the system.
after the elimination of the fault is analyzed. In the simulation
presented below it is considered that the fault happens at t = 0.1s,
the fault is eliminated at t = 0.2s, and the reclosure at t = 0.5s. B. Effect of Power Swing on Distance Protection
On Fig. 10 the simulations with and without reclosure are com-
pared. On Fig. 10(a), where a VSSG-CAM mode active wind farm is To study the power swing effects that the electrical grid presented
connected on EP1 bus, it’s visible that the two impedance trajectories below on Fig. 11 was used. This grid is composed by one DFIG
match with each other. On Fig. 10(b), where a DFIG wind farm is wind farm connected to Ribatejo bus and two VSSG wind farms
connected on EP1 bus, it’s visible that the two impedance trajectories with CAM mode active connected to Sines bus.
match with each other, at t = 0.5s the two trajectories have a small
divergence.

V. P OWER S WING
A. Power System Stability
The stability of a power system is determined by the ability
to return to the initial operation mode after the system has been
disturbed [12]. The stability of a system can be classified as:
Static Stability - when the system has a steady state and after an
occurrence of a small fault, the system returns to the initial point of
operation.
Transient stability - when the system has a steady state and after
an occurrence of a large disturbance, the system returns nearly to
the initial point of operation.
In a AC system all the generator rotates on synchronism. A
disturbance on the system can put it on a transient state and cause
a loss of synchronism between the generators [12].
When the generators lose the synchronism they can cause great
fluctuations on voltage and current values. The current swing, steady Fig. 11: Unifilar scheme of the electrical grid on study.
6

Using the grid presented in Fig. 11 a fault in the middle of one


of the branches that connect Ribatejo and Sines buses is simulated.
In this simulations the fault occurs at t = 0.1s and the fault is
eliminated at t = 0.6s (Fig. 12 and 13) and t = 1.5s (Fig. 14 and
15).
• Fault elimination time: t = 0.6s.

Fig. 15: Impedance trajectory measured on A1 (cyan) and A2


(blue) distance protection.

The analysis of Fig. 12 to 15 shows that the increase of elimination


Fig. 12: Temporal evolution of Active Power of Thermoelectric time generates the increase of the fluctuations of the impedance and
Power Plants of Sines (blue) and Ribatejo (red) and of Wind farms the active power. The impedance oscillations when the elimination
connected to Sines bus (pink and cyan) and to Ribatejo bus (green). time is 1.5s cause the trip of Distance Protection.

C. Influence of the type of wind farms


To understand the influence of the weight of DFIG wind turbines
and VSSG in an electrical grid, the grid on Fig. 11 was adapted and
the wind farm connected to Ribatejo bus was changed to a VSSG
wind farm and the one connected to Sines bus was changed to a
DFIG wind farm, Fig 16.

Fig. 13: Impedance trajectory measured on A1 (cyan) and A2


(blue) distance protection.

• Fault elimination time: t = 1.5s.

Fig. 16: Unifilar scheme of the electrical grid for the study of the
influence of the type of wind farms.

Using the grid presented in Fig. 16, like in the section V-B, a fault
in the middle of one of the branches that connect Ribatejo and Sines
buses was simulated . In this simulations the fault occurs at t = 0.1s
and the fault is eliminated at t = 0.6s (Fig. 17 and 18) and t = 1.5s
(Fig. 19 and 20).

Fig. 14: Temporal evolution of Active Power of Thermoelectric


Power Plants of Sines (blue) and Ribatejo (red) and of Wind farms
connected to Sines bus (pink and cyan) and to Ribatejo bus (green).
7

• Fault elimination time: t = 0.6s.

Fig. 20: Impedance trajectory measured on A1 (cyan) and A2


Fig. 17: Temporal evolution of Active Power of Thermoelectric (blue) distance protection.
Power Plants of Sines (blue) and Ribatejo (red) and of Wind farms
connected to Sines bus (pink and cyan) and to Ribatejo bus (green).
behavior on both electrical grids. The oscillations of impedances
measured on Distance Protection terminals on the grid of Fig. 16 are
more significant than on the ones measured on distance protection
terminals on the grid of Fig. 11.

VI. C ONCLUSION
The purpose of this study was to analyze the behavior of Distance
Protections installed near wind farms under a voltage drop. To
accomplish this aim several simulations using PSS/E software were
performed.
In Chapter III the behavior of the most used wind turbines in
Portugal in a transient system was study. The most popular wind
turbines in Portugal are: DFIG (Doubly fed induction Generator)
and VSSG (Variable Speed Synchronous Generator). In this work
it was assumed that wind turbines have a control system that gives
the ability to remain connected to the grid during a voltage drop.
The VSSG supplier gives three options of performance during a
fault: ZPM (Zero Power Mode), APM (Active Power Mode), CAM
Fig. 18: Impedance trajectory measured on A1 (cyan) and A2 (Current Angle Mode).
(blue) distance protection. In Chapter IV the behavior of Distance Protections near DFIG
wind turbine, or VSSG wind turbine with ZPM active mode, or with
• Fault elimination time: t = 1.5s. APM active mode or with CAM active mode, were analyzed. Besides
the different operation modes of wind turbines the tripping zone of
Distance Protection is the same. The type of wind turbine in action
only influences the trajectory of impedance measured by Distance
Protection.
This study does not consider the influence of frequency fluctu-
ations on impedance value, so for this reason, there was made a
study to understand the importance of frequency fluctuations on
Distance Protection operation. This analysis lead to the conclusion
that the frequency fluctuations do not have impact on the operation of
Distance Protections but it is important to refer that this fluctuations
have more effect on impedance value when there are a DFIG wind
turbine.
Also in section IV-C the influence of line reclosure after the fault
clear in the Distance Protection, was tested. The reclosure doesn’t
have any influence in Distance Protection operation.
At last, on Chapter V, a study on the behavior of Distance
Protections about the influence of power swing on wind turbines
Fig. 19: Temporal evolution of Active Power of Thermoelectric
was made. The effects of power swing on a network with wind
Power Plants of Sines (blue) and Ribatejo (red) and of Wind farms
turbine only cause a undesirable trip of Distance Protection for a high
connected to Sines bus (pink and cyan) and to Ribatejo bus (green).
value of elimination time, this values are not normal to the protection
system. In this chapter the behavior of Distance Protections was also
Comparing the results of the simulation of this section with results analyzed having in consideration the value of power produced by
on the section V-B it’s verified that the active power has a similar DFIG and VSSG generated on the network. With this study it was
8

concluded that when there was more energy produced by VSSG


wind turbines the value of impedance measured on the protection
terminals have greater swings.
In summary, the behavior of Distance Protections installed near
wind farms was not influenced by wind turbines when typical fault
elimination times are considered for the national grid.

R EFERENCES
[1] M. Delgado, "Sistemas Eléctricos Trifásicos - A Média, Alta e Muito
Alta Tensão". Publindústria, 2010.
[2] M. Geidl, "Protection of Power Systems with Distributed Generation:
State of the Art". Swiss Federal Institute of Technology (ETH) Zurich,
20 de Julho de 2005.
[3] N. Chernobrovov, "Protective Relaying". MIR Publishers, 1974.
[4] G. Ziegler, "Numerical Distance Protection - Principles and Applica-
tions", 3rd ed. Siemens, 2008.
[5] C. R. Mason, "Art & Science of Protective Relaying". General Electric
Company, 2010.
[6] "Apontamentos Teóricos - Protecções de Distância".
Protecções e Automação em Sistemas de Energia
(https://fenix.ist.utl.pt/disciplinas/ttde3/2010-2011/2-semestre),
Consultado em 20 de Outubro de 2011.
[7] S. H. H. A. G. Phadke, "Third Zone Revisited". I.E.E.E, 2006.
[8] J. M. F. de Jesus, "Comportamento das Protecções de Distância na
Vizinhança de Parques Eólicos". IST, 2011.
[9] J. M. F. de Jesus e Rui M. G. Castro, "Energias Renováveis e Produção
Descentralizada - Equipamento Eléctrico dos Geradores Eólicos".
Primeira edição. Instituto Sueprior Técnico - DEEC / Área Científica
de Energia, 2008.
[10] E. Link and M. NZ, "Wind Energy Integration in New Zealand 2005".
Ministry of Economic Development - Energy Efficiency and Conserva-
tion Authority, 2005.
[11] ENERCON, "ENERCON Wind Energy Converter(WEC) - User Model
Documentation for PSS/E". ENERCON - GmbH, 2009.
[12] J. P. S. Paiva, "Redes de Energia Eléctrica - Uma Análise Sistémica".
Primeira edição. IST Press, 2005.

You might also like