You are on page 1of 39

GE Energy

Rev. : F
Page : 1/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

GAS TURBINE AUXILIARIES

MAINTENANCE SCHEDULE GUIDE

FOR FRAME 6B, 6C, 6FA, 9E

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 2/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

SUMMARY OF DOCUMENT

1. INTRODUCTION ................................................................................................................................... 4

2. SAFETY ................................................................................................................................................... 4

3. CONTENT OF TABLES. ....................................................................................................................... 5

4. STANDARD DEVICES .......................................................................................................................... 6

5. LUBRICATING OIL SYSTEM........................................................................................................... 11

6. COOLING AND SEALING AIR SYSTEM........................................................................................ 13

7. TRIP OIL SYSTEM.............................................................................................................................. 13

8. COOLING WATER SYSTEM ............................................................................................................ 14

9. STARTING MEANS SYSTEM............................................................................................................ 16

10. GAS FUEL SYSTEM ............................................................................................................................ 17

11. LIQUID FUEL SYSTEM ..................................................................................................................... 18

12. ATOMIZING AIR SYSTEM ............................................................................................................... 20

13. FIRE FIGHTING SYSTEM................................................................................................................. 21

14. STEAM INJECTION SYSTEM .......................................................................................................... 25

15. AIR INLET BLEED HEATING SYSTEM......................................................................................... 27

16. HYDRAULIC SUPPLY SYSTEM....................................................................................................... 27

17. HEATING AND VENTILATION SYSTEM ...................................................................................... 28

18. COMPRESSOR WASHING SYSTEM............................................................................................... 29

19. WATER INJECTION SYSTEM.......................................................................................................... 30

20. COMPRESSOR INLET GUIDE VANES SYSTEM.......................................................................... 31

21. INLET AND EXHAUST SYSTEM ..................................................................................................... 32

22. GAS DETECTION SYSTEM............................................................................................................... 34

23. FUEL PURGE SYSTEM ...................................................................................................................... 35

24. ADDITIVE INJECTION SYSTEM..................................................................................................... 36

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 3/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

25. ACCESSORY AND LOAD GEAR AND COUPLINGS.................................................................... 36

26. ACOUSTICAL ENCLOSURE............................................................................................................. 37

27. ELECTRICAL AUXILIAIRIES.......................................................................................................... 38

28. CONTROL SYSTEM AND PARAMETERS ..................................................................................... 39

29. LIST OF REFERENCED DOCUMENT ............................................................................................ 39

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 4/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

1. INTRODUCTION
The present document related to the maintenance of the accessories of gas turbines is a guide for the
End User’s maintenance Engineers.
The aim of this document is to give maintenance interval and recommendation for the gas turbine
accessories systems and their components.
The maintenance activities recommended in this guide are typical and do not pertain to any particular
plant equipment model.

Maintenance activities are mainly driven by periodical check up and routine inspections.
x Periodical check up are jobs to be carried out at predetermined frequencies like monthly, annually, or
during gas turbine inspections as combustion, hot gas path, major.
x Routine inspections are check up carried out more often like daily, weekly, in relation with gas
turbine operation. They are related to parameters read out and analysis, visual inspection, abnormal
noise, as explained in the Operation volume.
x Routine inspections may impact periodical maintenance activities and may shorten the frequencies
defined in the tables here below.

The present document applies for accessories of gas turbines frame 6B, 6C, 6FA, 9E.

2. SAFETY
The End User shall take appropriate steps to ensure that only workers who have received adequate
instruction shall have access to equipment. The End User shall ensure site safe work practices are
implemented and enforced (e.g. proper operator response action to control system alarms, energy
isolation procedures (lockout/tagout), personal protective equipment, permit space entry procedures,
posting of warning signs, training, Material Safety Data Sheets (MSDS), etc.).
The End User shall ensure that site safe work practices integrate access permit, work permit and relevant
permits and procedures to cover all aspect of safety.
Please refer to Safety recommendation in tab Safety of the Operating and maintenance manual, to
residual risk summary and to Original Equipment Manufacturer literature.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 5/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

3. CONTENT OF TABLES.
Maintenance schedule and maintenance activities of each device of a single system are listed, system by
system, in the different tables below.
Some devices like pressure transducers, check valves, orifices, . . . , installed in different systems have
identical maintenance schedule and maintenance activities whatever the system they belong to. These
devices are grouped in the first table called “Standard devices”.

The tables are divided into several columns. The two first are:
Device: designation of the device,
Note: underlined device names are only for a specific gas turbine frame
Check / inspect: list the maintenance activities

The other columns tell how often a device or equipment should be inspected and whether or not the
turbine can be operating at the time of the inspection. The meaning of the letters used is:
D : Daily Inspection
W : Weekly Inspection
M : Monthly Inspection
Q : Quarterly Inspection
SA : Semi-annual Inspection
CI : Combustion Inspection
HGPI : Hot Gas Path Inspection
MI : Major Overhaul Inspection
O : Turbine Operating
S : Turbine Shutdown

The recommended maintenance activities, frequencies and turbine status are representative of an
average power plant installation and include both peaking and continuous operating stations. They are
not intended to cover all variations of equipment supplied and may depend upon station environment. In
some cases, a shutdown may be recommended solely as a precaution against possible injury to
maintenance personnel, because the location of the component or device is in a hazardous area.

As per GER 3620 maintenance activities are influenced by many factors like the type and quality of fuel,
the starting cycle, the power setting and duty application, the steam/water injection.
Maintenance interval requirement for below listed devices may also be impacted by those factors. Due to
enormous variety of operating conditions from a power plant to another, maintenance adjustment has
to be based on experience and observations made by the End User.

Lubrication frequency will vary, depending on turbine operating hours and ambient temperature. It is therefore
suggested to keep records of lubrication intervals to determine variances between periods listed on the
chart and those scheduled for a specific installation.

For all the devices listed here below, always refer to the Original Equipment Manufacturer (OEM)
technical literature / equipment publication for accurate information regarding maintenance
schedule and maintenance activities for each device.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 6/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

4. STANDARD DEVICES

Standard Devices
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for fluid leak, device damage O
Accumulator ƒ Check inert gas pressure, fill up or change the parts S
as necessary
ƒ External visual check for fluid leak, device damage O
Check valve ƒ Check good operation, erosion, corrosion, sealing on S
back pressure, cracking pressure if applicable
ƒ External visual check device damage O
Dew point
ƒ Check settings and adjust if necessary according to S
transducer
device summary
ƒ External visual check for fluid leak, device damage O
ƒ Check pressure drop. O
Filter
ƒ Replace cartridges at high level pressure drop S
ƒ Replace cartridges regardless of pressure drop S
ƒ Check during each start up and shut down sequence S
that the flame detector detect presence of flame and
absence of flame
Flame detector ƒ Check cleanliness of lens. Check detection of flame
S S S
using an ultraviolet source in front of the sensor (at
400-500 mm distance) before starting at the end of
maintenance period
ƒ Visual external and internal inspection per S
Flexible metal GEK111694. Replace the component by new one if
hose any defect appears on visual inspection.
ƒ Pressure test per GEK111694 S

ƒ External visual check for fluid leak, device damage O


Flowmeter ƒ Check flow signal with test bench and adjust if S
possible according to device specification or replace
it
ƒ Check filter (if any) for dirt, clogging O
ƒ Clean device, fan blades (if any), ducts S
Heater (space
ƒ Electrical insulation, electrical consumption, loose S
heater)
connection
ƒ Check performances S

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 7/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Standard Devices
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for fluid leak, device damage O
ƒ Tube and shell inspection if loss of performance : S
Heat exchanger pressure droop increase or reduction of thermal
efficiency
ƒ Check Wall thickness S
ƒ External visual inspection : no physical damage O
Heat tracing ƒ Electrical part insulation measurement and good S
operation test before winter every year
ƒ External visual check device damage O
Humidity
ƒ Check settings and adjust if necessary according to S
transducer
device summary
ƒ External visual check for fluid leak, device damage O
Liquid level
ƒ Check device accuracy and adjust if necessary S
indicator
according to device specification
ƒ External visual check for device damage, good O
operation of actuator mechanism
ƒ Check that the mechanism move freely without S
Limit switch jamming, check mechanism alignment, check if
excessive wear, adjust or replace if necessary,
according to device specification.
ƒ Check electrical connection and cable gland S
ƒ External visual check for device damage, good O
LVDT (Linear operation of actuator mechanism
voltage ƒ Check electrical circuits for loose connection or S
differential corrosion
transducer) ƒ Check that output signal versus valve stroke is S
according to device summary
ƒ Check electrical circuits for loose connection or S
Magnetic pick up corrosion
ƒ Check gap is within the specified limits S

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 8/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Standard Devices
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check vibration level O
ƒ Cleanliness, abnormal noise O
ƒ Brush connection S
ƒ No loose mounting bolts, no loose electrical S
Motors connection, check cable gland
(Electrical) ƒ No loose mounting bolt for driven equipment S
ƒ Alignment within tolerances (when applicable) S
ƒ Coupling : bolt tightening and grease S
ƒ Grease bearing as necessary S
ƒ External visual check for fluid leak, device damage O
ƒ Check for erosion, plugging, deterioration, sharp S
Orifice plate
edge or irregular chamfer, original diameter, replace
if out of tolerances
ƒ External visual check for fluid leak, pipe damage, O
Pipe slip joint loose support, damage insulation
coupling ƒ Coupling in the alignment of the pipe, not in contact S
to the stop lateral limit
ƒ External visual check for fluid leak, pipe damage, O
Piping loose support, damaged insulation
ƒ External visual check for fluid leak, device damage, O
corrosion
Pressure gauge ƒ Reading and accuracy : test the pressure gauge S
using a dead weight tester or other equivalent
calibrated means

ƒ External visual check for fluid leak, device damage, O


leak at stem
Pressure O
ƒ Control regulated pressure when measuring means
regulating valve
is available
(VPR)
ƒ Check settings with test bench and adjust if S
necessary according to device summary
ƒ External visual check for fluid leak, device damage O
ƒ When test valve is provided, check alarm sequence if O
Pressure switch applicable
ƒ Check settings with test bench and adjust if S
necessary according to device summary

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 9/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Standard Devices
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for fluid leak, device damage O
Pressure
ƒ Check settings with test bench and adjust if S
Transducer
necessary according to device summary
ƒ Clean the filter housing, clean or replace the filter S
Porous stone element, check the cleanliness of continuous blow
filter down line
ƒ External visual check for fluid leak, device damage, O
chattering
Relief valve ƒ Check settings with test bench and adjust if S
necessary according to device summary
Rubber bellow ƒ External visual check for fluid leak, device damage O
Rubber ƒ Replace the device every ten years if necessary S
compensator
ƒ External visual check for fluid leak, device damage, O
Servovalve chattering
ƒ Check fixing screw, tightening torque, Null Bias S
ƒ External visual check for fluid leak, device damage, O
chattering, leak at packing or stem
Solenoid valve ƒ Check proper operation and seat air tightness with S
air pressure if necessary
External visual check for fluid leak, device damage
ƒ O
Strainer
Check cleanliness, dirt characteristics, scale
ƒ S
External visual check for fluid leak, device damage
ƒ O
Temperature Control regulated temperature when measuring
ƒ O
regulating valves means is available
(VTR) ƒ Check settings with test bench and adjust if S
necessary according to device summary
Temperature ƒ External visual check for fluid leak, device damage O
switch ƒ Check settings with test bench and adjust if S
Thermostat necessary according to device summary
ƒ External visual check for fluid leak, device damage, O
corrosion
Thermometer ƒ Reading and accuracy : test the device in an S
agitated bath with reference thermometer or other
equivalent calibrated means

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 10/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Standard Devices
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for fluid leak, device damage O
Valve ƒ Leakage at stem O
ƒ State of valve plug, seat and seals S
ƒ External visual check for device damage and O
mounting secure
Vibration seismic ƒ Check vibration signal with vibrating table. Adjust if
S
sensor possible according to device summary or replace the
device
ƒ Check routing of cabling for any probe that has S
errors at the control panel. Check the electrical
connection at each junction for corrosion/humidity.
Vibration shaft
Check for oil leak.
displacement
probe ƒ Proceed to same checks as above for key phasor
S
ƒ Check and recalibrate each probe loop according to
S
OEM. Refer to TIL1607

Always refer to the Original Equipment Manufacturer (OEM)

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 11/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

5. LUBRICATING OIL SYSTEM

LUBRICATING OIL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Take a sample for routine control analysis (defined in
specification 91-438752) and check characteristics O
according to GE specification
ƒ Take a sample for complete analysis (defined in
Lubricating oil specification 91-438752) and check characteristics S
according to GE specification
ƒ Change oil if out of specification
ƒ Check the oil level indicated by the oil tank level S
O
gauge.
ƒ External visual check for lube oil level, lube oil leak O
Lube oil tank ƒ Check inside the tank : peeling paint, loose S
component, loose fitting, loose clamp
ƒ External visual check for fluid leak, device damage, O
excessive noise
ƒ Gas turbine on continuous operation: check starting O
sequence of AC pump using test valve except if
included in the software by weekly test.
Lube oil pumps
ƒ Check outlet pressure, electrical power and vibration
S
are according to pump and motor characteristics
ƒ Grease motor and pump according to manufacturer
literature S

ƒ Replace cartridges by a set of new one regardless of S


Lube oil filter
the pressure drop, including standby filter
ƒ External visual check for fluid leak, device damage, O
excessive noise
ƒ Replace coalescent cartridges by a new set. New S
cartridges must be manually fully oil imbibed before
Oil Mist operation
eliminator ƒ check good operation of internal damper and check S
valves
ƒ Clean the vent area S
ƒ Adjust oil tank pressure after maintenance after O
inspection

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 12/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

LUBRICATING OIL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
6FA : bearing #2 ƒ Change insulation of bearing #2 return line for 6FA S
insulation unit

Refer to "STANDARD DEVICES" table for other components and to the


Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 13/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

6. COOLING AND SEALING AIR SYSTEM

COOLING AND SEALING AIR SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Test the valve for smooth open/close movement, S
Compressor lubricate with high temperature anti-seize
bleed valve compound to all moving parts, as necessary. Check
air tightness
Compressor S
ƒ Test the valve for smooth open/close movement
Bleed Solenoid
Apply anti-seize compound to all moving parts
Valve
ƒ External visual check for excessive noise or O
vibration
Blower ƒ Cleanliness of ducts, housing, screens, blades S
ƒ Erosion of blades, deposit on blades, rust, corrosion, S
peeling
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

7. TRIP OIL SYSTEM

TRIP OIL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check good operation of tripping device S
Tripping device ƒ Check for sludge and/or varnishing deposit on spool S
and bore of tripping device
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 14/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

8. COOLING WATER SYSTEM

COOLING WATER SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down

H M
Device Check/inspect D W M Q S CI GP X
I I
ƒ Check cooling water properties, corrosion inhibitor O
Cooling water and antifreeze, according to GEI 41004
ƒ External visual check for fluid leak, device damage, O
cleanliness, water level
Water tank
ƒ Check inside the tank : peeling paint or corrosion, S
deposit, dirt, clean if necessary
ƒ External visual check for fluid leak, device damage, O
cleanliness, abnormal noise,
ƒ Water leak at gland packing or slight drip during O
operation, according to manufacturer literature
ƒ Check vibration level, O
ƒ No loose mounting bolts, no loose electrical S
connection
Water pump
ƒ Alignment within tolerances (when applicable)
S
ƒ Check outlet pressure, electrical power and
S
vibration are according to pump and motor
characteristics
ƒ Grease motor and pump according to manufacturer S
literature

ƒ External visual check for fluid leak, device damage, O


excessive noise or vibration, erosion of fins
ƒ Cleanliness of ducts, housing, screens O
Fin fan coolers or ƒ Tube and shell inspection if loss of performance :
pressure droop increase or reduction of thermal S
other coolers
efficiency
ƒ Erosion of blades, deposit on blades, rust, corrosion, S
peeling

ƒ External visual check for excessive noise or O


vibration
Fan ƒ Cleanliness of ducts, housing, screens, blades S
ƒ Erosion of blades, deposit on blades, rust, corrosion, S
peeling

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 15/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

COOLING WATER SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down

H M
Device Check/inspect D W M Q S CI GP X
I I
Air trap ƒ External visual check for fluid leak, device damage O
automatic vent ƒ Cleanliness of internal parts S
valve
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 16/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

9. STARTING MEANS SYSTEM

STARTING MEANS SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check oil level, liquid fuel tank level, external visual O
check for leak
ƒ Take oil sampling for analysis O
6B : Diesel ƒ Filters : clean or replace S
engine ƒ Diesel Engine test if the gas turbine is running O
continuously: test once a month at idle speed
ƒ Proceed to maintenance according to diesel engine S S
running hours
ƒ External visual check for fluid leak, device damage, S
6B : jaw type cleanliness of sliding tooth, smooth sliding
clutch ƒ Grease sliding tooth using Molybdenum bisulphide S
grease aerosol spray
9E : Torque ƒ Replace the input and output side bearings. Refer to S
converter manufacturer literature.
ƒ Visual check for external oil leaks at shaft seals, O
Torque converter bolted flanges, cover plates
All units ƒ Check vibration level, O
ƒ Check alignment S
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 17/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

10. GAS FUEL SYSTEM

GAS FUEL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check gas fuel properties still in accordance with O
Gas fuel GEI 41040 and Control specification
ƒ External visual check for hydraulic oil leak, pipe O
Gas fuel system damage, loose support, damage insulation
ƒ Check for gas leakage at stem O
ƒ Check the good operation of the valve according to S
command signal
Gas stop valves ƒ Proceed to valve seat leak test to confirm the valve S
operate in the defined leakage class as per ANSI/FCI
70-2-2006
ƒ Check good operation of tripping system
S
ƒ Check for gas leakage at stem O
Gas control ƒ Accurate stroke versus control signal according to S
valves control specification, proper setting of null bias and
good operation of trip relay
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 18/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

11. LIQUID FUEL SYSTEM

LIQUID FUEL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check liquid fuel properties still in accordance with O
Liquid fuel GEI 41047 and Control specification
Liquid fuel ƒ External visual check for fluid leak, pipe damage, O
system loose support, insulation damage
ƒ Check for leaks at the valve sealing system O
(packing, gland, stem).
ƒ Check the good operation of the valve according to S
Stop valve command signal
ƒ Proceed to valve seat leak test to confirm valve S
operation
ƒ Fuel leak at gland packing or slight drip during O
operation, according to manufacturer literature
ƒ Check vibration level, O
ƒ No loose mounting bolts, no loose electrical O
connection
Forwarding
ƒ Alignment within tolerances (when applicable) S
pump
ƒ Check outlet pressure, electrical power and S
vibration are according to pump and motor
characteristics
ƒ Grease motor and pump according to manufacturer S
literature
ƒ Purge at filter top level to vent any air O
Filter
ƒ Replace cartridges S
ƒ External visual check for fluid leak O
Main fuel pump ƒ Pump overall maintenance according to operating S S
hours
ƒ Liquid fuel leakage at stem O
By pass valve ƒ Accurate stroke versus control signal according to S
control specification, proper setting of null bias
ƒ Leakage Outside O
Flow divider
ƒ Speed pickups secure and properly set S
ƒ For each Jansen’s valve, replace the internal S
Three way purge gaskets by the Manufacturer set referenced
valves VA19-3 101254-100.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 19/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

LIQUID FUEL SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Air leak or liquid fuel leak at drain funnel after each O
start up
False start drain ƒ Free liquid draining and no obstructive matter, no S
valves obstructive deposit inside the drain pipe from
turbine casing to sump tank
ƒ External visual check for fluid leak, device damage, O
cleanliness, fluid level
ƒ Good operation of float level device O
Sump tank ƒ Check inside the tank : peeling paint or corrosion, S
deposit, dirt, clean if necessary
ƒ Grease motor and pump bearings as necessary S
ƒ External visual check for skin damage, loose part or S
Sprayshield fuel leak of Sprayshield (called also spray retainer)
(Spray retainer) installed around flanges
ƒ Replace sprayshield by new one S
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 20/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

12. ATOMIZING AIR SYSTEM

ATOMIZING AIR SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check lubricating oil level O
Starting ƒ Grease bearing as necessary S
atomizing air ƒ Check cleanliness of continuous blow down at S
booster booster outlet
ƒ Check Belt according to specification 154A3418 S
ƒ External visual check for fluid leak, loose support, O
hot spot
Atomizing air ƒ Check vibration level O
compressor ƒ Absence of oil or vapor at vent O
ƒ Check compressor ratio if differential pressure O
transducer is provided
ƒ Apply a coating of lubricant "Never-Seez" or S
By-pass valve equivalent anti-seize lubricant to all moving parts
and check good operation.
ƒ Check cleanliness of drain line S
Air separator ƒ Check all surfaces and deflector against dirt and S
wear
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 21/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

13. FIRE FIGHTING SYSTEM

CO2 Extinguishing agent (IF APPLICABLE)

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
Storage ƒ Check availability of extinguishing agent (from O
cylinders pressure gage, weight indicator, level gauge). Fill up
Storage tank or replace cylinder as necessary.
ƒ External visual check loose support, loose nozzle, O
Piping and hoses hose damage
ƒ Check good operation of fire detectors using an S
Fire detectors adjustable heat source. Replace the device if out of
specification
ƒ Check for device damage, and check good S
Break-glass units
operation of the break glass system
Flashing lights, ƒ Check for device damage, and check good S
Sirens operation of devices
Nozzles ƒ Check cleanliness of nozzle holes S
CO2 latch and ƒ Check manually good and free mechanical S
damper operation of latch and damper
ƒ Visual check of sealing between acoustical panel at S
walls, at roof, quality of joints, sealing of pipe wall
Sealing of crossing, sealing of electrical cables wall crossing.
enclosure No day light should be visible from inside through
joints. Initiate corrective action as necessary

ƒ After major inspection, check for enclosure sealing S


and organize carefully with all the necessary safety
System precaution a manually real discharge. Check good
operation operation of the system, the latches and dampers.
Measure the CO2 concentration inside
compartment when applicable.
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 22/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Condensed Aerosol Extinguishing agent (IF APPLICABLE)

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
O
ƒ Check all electrical connections
Aerosol generators
(MLI A283)
ƒ Check generators for damaged or missing parts O
ƒ Replace all the generators (each 10 years) S
ƒ Check good operation of fire detectors using an S
Fire detectors adjustable heat source. Replace the device if out
of specification
ƒ Check for device damage, and check good S
Break-glass units
operation of the break glass system
Flashing lights, ƒ Check for device damage, and check good S
Sirens operation of devices
ƒ Check for device damage, and check good S
Key switch inhibit
operation of the break glass system
ƒ Check manually good and free mechanical S
Dampers &
closure operation of spring return damper
electrical actuators
actuator
ƒ Leak rate check: visual check of sealing between
acoustical panels at walls, at roof, quality of
joints, sealing of pipe wall crossing, sealing of S
electrical cables wall crossing. No day light
Sealing of enclosure should be visible from inside through joints.
Initiate corrective action as necessary: If no
change to enclosure leak rate cannot be visually
determined, it shall be positively established by
repeating the integrity enclosure test.
ƒ After major inspection, check for enclosure S
sealing and organize carefully with all the
necessary safety precaution an integrity
System operation enclosure test. Measure the enclosures
equivalent leakage area and check with upper
specified limits.
Check good operation of the system.
Refer to "STANDARD DEVICES" table for other components and
to the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 23/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

Watermist Extinguishing agent (with Gas Pump Unit HI FOG technology)


(IF APPLICABLE)

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
ƒ Check availability of extinguishing agent (from O
Storage gas
pressure gage). Fill up or replace cylinder as
cylinders
necessary.
O
ƒ Check availability of water (from level gauge)
Water tank
ƒ Check the bacteriological growth O

Water filter ƒ Check the water filters O


ƒ External visual check loose support, hose damage O

Piping, hoses
ƒ Verify lack of corrosion on or near any components O

ƒ Check network pressure is approximately 25 bar O


Stand by pump

ƒ Carry out a functional actuation checks by using O


Gas pump test valves and test air cylinders
ƒ Check good operation of fire detectors using an S
Fire detectors adjustable heat source. Replace the device if out of
specification
ƒ Check for device damage, and check good S
Break-glass units
operation of the break glass system
Flashing lights, ƒ Check for device damage, and check good S
Sirens operation of devices
ƒ Check the physical integrity O
Spray heads
ƒ Inspect all spray head locations (obstruction….) S
ƒ After major inspection, check for enclosure sealing S
System and organize carefully with all the necessary safety
operation precaution a manually real discharge. Check good
operation of the system, the latches and dampers.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 24/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

Watermist Extinguishing agent (with Mechanical accumulators HI FOG


technology) (IF APPLICABLE)

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
O
ƒ Check availability of extinguishing agent (from
Storage gas pressure gage, level gauge). Fill up or replace
cylinders and cylinder as necessary.
water O
ƒ Change stored water inside cylinders

ƒ External visual check loose support, hose damage O

Piping, hoses….
ƒ Verify lack of corrosion on or near any components O

Mechanical ƒ Carry out a functional actuation checks by using O


accumulator test valves and test air cylinders
system
ƒ Check good operation of fire detectors using an S
Fire detectors adjustable heat source. Replace the device if out of
specification
ƒ Check for device damage, and check good S
Break-glass units
operation of the break glass system
Flashing lights, ƒ Check for device damage, and check good S
Sirens operation of devices

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 25/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

FIRE FIGHTING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
H
C G M
Device Check/inspect D W M Q S X
I P I
I
ƒ Inspect all spray head locations (obstruction….) S
Spray heads

ƒ After major inspection, check for enclosure sealing S


System and organize carefully with all the necessary safety
operation precaution a manually real discharge. Check good
operation of the system, the latches and dampers.

14. STEAM INJECTION SYSTEM

STEAM INJECTION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check steam properties still in accordance with GEK O
Steam 101944 and Control specification
ƒ External visual check for steam or water leak, loose O
Steam system support, damage insulation
ƒ Check for leaks at the valve sealing system O
Flow control (packing, gland, stem).
valve ƒ Check for wear S
ƒ Check the valve stroke according to control signal S
ƒ Check for leaks at the valve sealing system O
(packing, gland, stem).
ƒ Check the good operation of the valve according to S
Stop valve command signal
ƒ Proceed to valve seat leak test to confirm valve S
operation

Pressure ƒ Check level of condensate pot, fill up with water if S


transducer necessary

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 26/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

STEAM INJECTION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 27/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

15. AIR INLET BLEED HEATING SYSTEM

AIR INLET BLEED HEATING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
Bleed heating ƒ External visual check for leak, abnormal noise, loose O
system support, damage insulation
ƒ Check for leaks at the control valves sealing system O
(packing, gland, stem).
Control valve ƒ Check for wear S
ƒ Check the valve stroke according to control signal S
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

16. HYDRAULIC SUPPLY SYSTEM

HYDRAULIC SUPPLY SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
Hydraulic supply ƒ External visual check leak, abnormal noise, loose O
system support, damage insulation
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 28/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

17. HEATING AND VENTILATION SYSTEM

HEATING AND VENTILATION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for device damage, cleanliness O
Inlet duct filter ƒ Clean or replace the filter element according to O
clogging frequency
ƒ External visual check for device damage, excessive O
Damper noise, good operation of damper element
ƒ Cleanliness and lubrication of linkage and bearing S
ƒ External visual check for device damage, excessive S
Ducting noise, loose bolt
ƒ External visual check for device damage, O
Flow sensor ƒ Check good operation according to device S
summary
ƒ External visual check for excessive noise or O
vibration
Fans ƒ Cleanliness of ducts, housing, screens, blades S
ƒ Erosion of blades, deposit on blades, rust, corrosion, S
peeling
ƒ External visual check for device damage, excessive O
noise, good operation
ƒ No loose mounting bolts, no loose electrical S
Space heaters connection, check cable gland
ƒ Check cleanliness of heating elements, blades and S
louvers
ƒ Check proper thermostat setting
S
ƒ Visual check of sealing between acoustical panel at S
Sealing of walls, at roof, quality of joints, sealing of pipe wall
enclosure crossing, sealing of electrical cables wall crossing
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 29/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

18. COMPRESSOR WASHING SYSTEM

COMPRESSOR WASHING SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
Washing water ƒ Check washing water properties according to GEK O
Detergent 107122
ƒ External visual check for fluid leak at connection O
Water tank (pipe, heater, level indicator, . .) device damage,
Detergent tank cleanliness, water level, detergent level
ƒ Check inside the tank, clean if necessary S

ƒ External visual check for fluid leak, device damage, O


cleanliness, abnormal noise,
ƒ Check for water leak at gland packing or slight drip X
during operation, according to manufacturer
literature
ƒ No loose mounting bolts, no loose electrical S
connection
Water pump
ƒ Alignment within tolerances (when applicable) S
ƒ Check outlet pressure, electrical power and S
vibration are according to pump and motor
characteristics S
ƒ Grease motor and pump according to manufacturer
literature

Refer to "STANDARD DEVICES" table for other components and to


the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 30/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

19. WATER INJECTION SYSTEM

WATER INJECTION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
Water ƒ Check water properties according to GEK 101944 O
ƒ External visual check for fluid leak, device damage, O
cleanliness, abnormal noise,
ƒ Check for water leak at gland packing or slight drip O
during operation, according to manufacturer
literature
ƒ Check vibration level, O
S
ƒ No loose mounting bolts, no loose electrical
Water pump
connection
S
ƒ Alignment within tolerances (when applicable)
S
ƒ Check outlet pressure, electrical power and
vibration are according to pump and motor
characteristics
ƒ Grease motor and pump according to manufacturer S
literature
ƒ Check for leaks at the valve sealing system O
(packing, gland, stem).
ƒ Check the good operation of the valve according to S
Stop valve command signal
ƒ Proceed to valve seat leak test to confirm valve S
operation
ƒ Check for leaks at the valve sealing system O
Flow control (packing, gland, stem).
valve ƒ Check for wear S
ƒ Check the valve stroke according to control signal S
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 31/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

20. COMPRESSOR INLET GUIDE VANES SYSTEM

COMPRESSOR INLET GUIDE VANES SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Accurate stroke versus control signal according to S
Operation and control specification, proper setting of null bias
calibration
ƒ Check good operation of tripping system S
Ring, rack, gear ƒ Clean, then Grease with lithium grease S
Actuator ƒ Grease fitting S
ƒ Clean if necessary S
Inlet Guide ƒ Check for Corrosion, abrasion, pitting, S
Vanes leading/trailing edge damage
ƒ Check backlash and bushing clearance S
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 32/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

21. INLET AND EXHAUST SYSTEM

INLET AND EXHAUST SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for excess accumulation of O
Inlet screen
birds, insects, debris, screen damage
ƒ Visual check for cleanliness, good operation of O
Inlet air filter
lighting (when applicable)
ƒ Visual check for cleanliness, leak, O
ƒ Check good operation of condensate drains trap O
Self cleaning air systems, drain manually if necessary
processing unit ƒ Check oil level at standstill, check the belts tension X
(when applicable)
ƒ Replace filter element according to pressure droop X
ƒ Visual check for scale formation at drift eliminator O
panels
ƒ Replace drift eliminator panel S
Evaporative
ƒ Visual check of media pads O
cooler
ƒ Check water quality regarding corrosion, scaling, O
micro biological infestation, refer to GEK 107158
ƒ Clean all evaporative cooler S
ƒ Visual check for filter element properly seated and O
secure
Inlet filter ƒ Check pressure drop.
O
element ƒ Replace cartridges at high level pressure drop and S
brush or vacuum clean the area before next start
up
ƒ Visual check for internal parts properly seated and S
Inlet duct, secure
silencer ƒ Visual check for state/condition, sealing of S
expansion joint
Inlet structure ƒ External visual check damage, loose mounting bolts S
ƒ Visual check for state/condition, sealing of joint S
ƒ Check good operation of door, of rubber heat S
Bypass door tracing (when applicable), good operation of
electrical control system : electromagnet, limit
switch

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 33/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

INLET AND EXHAUST SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Visual check for hot gas leak O
ƒ Visual check for internal parts properly seated and S
Exhaust duct secure, quality of insulation material
ƒ Visual check of external support system S
ƒ Visual check of outer cover for any discoloration or O
damage, indicative of excessive heat or movement
or hot gas leak
ƒ Visual check from inside and outside for adequate
Expansion joints S
ventilation around the expansion joint, loose bolt,
on exhaust duct signs of damage or leakage, cracks, discoloration,
signs of damage on the external insulation
ƒ Replace the expansion joints by a new one every 5 S
years
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 34/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

22. GAS DETECTION SYSTEM

GAS DETECTION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check cleanliness of gas detector filter. Replace if S
necessary
ƒ Perform calibration procedure of zero and span S
response of each sensor by injecting gas sample at
Gas detector
10% LIE through detector protection housing.
installed in base
Calibrate only one sensor at a time. Concurrent
frame
calibration of more than one sensor may result in
automatic forced turbine shutdown.
ƒ Replace gas detector every 3 years and proceed to S
calibration
ƒ Check one after one the cleanliness of each gas O
detector filter. Replace it if necessary
ƒ Perform calibration procedure of zero and span O
response of each sensor by injecting gas sample at
Gas detector
10% LIE through detector protection housing.
installed in
Calibrate only one sensor at a time. Concurrent
ventilation ducts
calibration of more than one sensor may result in
automatic forced turbine shutdown.
ƒ Replace each gas detector every 3 years and S
proceed to calibration
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device
Silicones, hydrogen sulfide, lead compounds and
halides have been proven to degrade the ability to
accurately measure the hazardous gas
WARNING
concentration in compartment. Please refer to
Original Equipment Manufacturer literature for
complementary information.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 35/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

23. FUEL PURGE SYSTEM

FUEL PURGE SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for leak, pipe damage, loose O
Purge system support, damage insulation, cleanliness of funnel
ƒ Check for leakage at stem S
ƒ Check the good operation of the valve according to S
command signal
Purge valves ƒ Proceed to valve seat leak test to confirm the valve S
operate in the defined leakage class as per ANSI/FCI
70-2-2006
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 36/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

24. ADDITIVE INJECTION SYSTEM

ADDITIVE INJECTION SYSTEM


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check for cleanliness, leak, pipe O
System damage, loose support
ƒ Check the good operation and the setting of S
Additive flow injection pump
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

25. ACCESSORY AND LOAD GEAR AND COUPLINGS

ACCESSORY AND LOAD GEAR AND COUPLINGS


Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
6B Accessory ƒ Visual check according to OEM technical literature S
coupling
9E Accessory ƒ Visual check according to OEM technical literature S
coupling
Load coupling ƒ Visual check according to OEM technical literature S
ƒ Visual check for leak, damage, loose bolts, anchor S
Accessory gear bolts, cleanliness, maintenance as per OEM
box literature
ƒ Gear box inspection through inspection door S
ƒ Visual check for leak, damage, loose bolts, anchor S
bolts, cleanliness, maintenance as per OEM
Load gear box literature
ƒ Gear box inspection through inspection door S

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 37/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

26. ACOUSTICAL ENCLOSURE

ACOUSTICAL ENCLOSURE
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ External visual check damage, loose mounting S
Structure bolts, corrosion
ƒ External visual check for cleanliness, painting, O
Panel, Roof panel damage
and gasket ƒ External visual check for air tightness between S
panels, water tightness, acoustical insulation
ƒ External visual check for damage, paint, easy S
Door opening and closing, good operation of locking
system, quality of gasket
Hoist, traveling ƒ Check good operation of the system, of the brake, S
crane lubricate as necessary
Lighting ƒ Check good operation O
ƒ Visual check of sealing regarding air tightness and S
Wall and floor
acoustical insulation at electrical cable and piping
sealing
crossing
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 38/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

27. ELECTRICAL AUXILIAIRIES

ELECTRICAL AUXILIAIRIES
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Visual check cleanliness of battery and battery rack O
Battery
ƒ Check battery capacity S
ƒ Check for cleanliness and good operation, no over O
Battery charger heating
ƒ Inspection of battery charger as per OEM S
Control panel ƒ Check for any indication of corrosion or O
and components discoloration due to heat
Indicating lamps ƒ Check good operation, replace if necessary O
ƒ Check filter for dirt, clogging O
Space heaters ƒ Clean device, fan blades (if any), ducts S
ƒ Check performances S
ƒ General cleanliness O
Motor Control
Center ƒ Bus bar loose connection, insulation, cleanliness of S
insulator, good operation of doors and drawers
ƒ Check for cleanliness, damage, good operation O
Air conditioner ƒ Clean filter or replace as necessary, clean water X
drain, clean dust and dirt from the condenser and
evaporative coils
Refer to "STANDARD DEVICES" table for other components and to
the Original Equipment Manufacturer (OEM) for each device

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013
GE Energy

Rev. : F
Page : 39/39
OPERATION AND MAINTENANCE MANUAL
MAINTENANCE

28. CONTROL SYSTEM AND PARAMETERS

SYSTEM
Daily – Weekly- Monthly – Quarterly – Semi-annually – Combustion Inspection – Hot Gas Path Inspection
Major Inspection – X other period O : turbine Operating – S : turbine Shut down
C H M
Device Check/inspect D W M Q S G X
I PI I
ƒ Check operating parameters according to gas O
turbine operation
Parameters
ƒ Check stroke of fuel control valves according to S
control signal
ƒ Check operation of overspeed trip system S
Overspeed
according to GEK 111521
Refer to GAS TURBINE OPERATION

29. LIST OF REFERENCED DOCUMENT


The table here below lists the GE document identified in the above tables.

Reference number Designation


Inspection and Maintenance Recommendations for Handling
GEK111694
and Inspection of Flexible Metal Hoses
TIL1607 Bently Nevada equipment inspection and maintenance
91-438752 Monitoring of lubricating oil
Cooling Water Recommendations
GEI 41004
for Combustion Gas Turbine Closed Cooling Systems
GEI 41040 Specification for fuel gas for combustion in heavy duty gas turbines
GEI 41047 Gas Turbine Liquid Fuel Specifications
154A3418 Atomizing air booster belt adjustment
GEK 101944 Requirements for Water/Steam Purity in Gas Turbines
F-Class Gas Turbine Compressor Washing
GEK 107122 Liquid Washing Recommendations for Gas Turbines with Pulsed Water Wash
Systems
GEK 107158 Water Supply Requirement for Gas Turbine Inlet Air Evaporative Coolers
GEK 111521 Functional Test-Overspeed Tests-OFF-LINE
Heavy-duty Gas Turbine Operating and Maintenance Considerations
GER 3620
This document is included in the Gas turbine Maintenance Volume.

All rights reserved Copyright - Droits de reproduction réservés


OMMM_GT Auxiliaries_F_V1_EN 11/2013

You might also like