Rectangular Tank Design-Bluetax MEA-2
Rectangular Tank Design-Bluetax MEA-2
b/a 0.5
x/a for support 1
x/a for center 0.5
pt = 50 fck/fy[1-sqrt{1-4.6xMy/fckxbxd^2}]
= 0.01917485 %
Min. Pt should be 0.24 %
Sheet1
Ast pt x b x d/100
240 mm^2
providing 8 mm dia reinforcement at 200 mm c/c
Ast provided 251.328 mm^2
https://www.youtube.com/watch?v=QZa9F8J5VKY
Page 2
Sheet2
Design of Rectangular Underground Water Tank
h = H/4
h 0.1125 <1 m
provide h = 1 m
k = m σcbc
m σcbc + σst
= 0.41791045
j = 1-k/3
= 0.86069652
Q = 1/2 x σcbc x k x j
= 1.79847033
Page 3
Sheet2
H= 0.45
P= 7.173 kN/m2
Mf AB = -PL^2/12
-0.59775 kN.m
Bm Plan
Mf AD = +PL^2/12
0.0537975 kN.m
D C
Distribution factor (D.F.)
D A B
0.76923077 0.23076923 D.F.
- 0.0537975 -0.59775 -FEM
B.M. At center of AB
=PL^2/8 – Ma
= 0.4244025 kN.m
B.M. At center of AD
=PB^2/8 – Ma
=-0.39152625 kN.m
Page 4
Sheet2
Adopt d = 50mm 30 4.14 3.99
Total D = 100 mm
Ast required = M
σst x j x d
= 84.4079346 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on remote face)
Total D = 100 mm
effective D = 50 mm
Distribution steel:
Min. Ast = 240 mm^2 for one zone (on each face)
Provide 8 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
(ii) At center
M = 0.4244025 kN.m
C= 1.07595 kN
Modified moment M-Cx
0.4244025 kN.m
Ast required = M
σst x j x d
= 75.8602957 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
M =Q x b x d^2
Q= 1.8
Page 5
Sheet2
d = 16.1970934 mm
Adopt d = 50mm
Total D = 100 mm
Ast required = M
σst x j x d
= 84.4079346 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
Total D = 100 mm
effective D = 50 mm
Distribution steel:
Min. Ast = 120 mm^2 for one zone (on each face)
Provide 8 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
(ii) At center
M = -0.39152625 kN.m
C= 3.5865 kN
Ast required = M
σst x j x d
= 69.9837939 mm^2
Provide 8 mm dia bars @ 175 c/c spacing ( Verticle steel on remote face)
Cantilever Moment
Pressure at base = ka Ɣ' H + Ɣw
= 7.173 kN/m^2
M = 1.1955 kN.m
Ast required = 213.690974 mm^2
Total D = 100 mm
effective D = 50 mm
Provide 10 mm dia bars @ 100 c/c spacing (Both direction both face upto 1 m)
Page 6
Sheet2
Mf AB = -PL^2/12
-0.375 kN.m
Bm Plan
Mf AD = +PL^2/12
0.03375 kN.m
D
Distribution factor (D.F.)
D A B
0.76923077 0.23076923 D.F.
- 0.03375 -0.375 -FEM
B.M. At center of AB
=PL^2/8 – Ma
= 0.26625 kN.m
B.M. At center of AD
=PL^2/8 – Ma
=0.346875 kN.m
Page 7
Sheet2
M =Q x b x d^2
Q= 1.8
d = 12.8290036 mm
Adopt d = 75mm
Total D = 100 mm
Ast required = M
for moment σst x j x d
= 35.3023566 mm^2
Ast required = T
for tension σst
= 5.19230769 mm^2
Total Ast
required = 40.4946643 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
(ii) At center
M= 0.26625 kN.m
T= 0.675 kN (Tension on remote face)
Modified moment M-Tx
0.26625 kN.m
Ast required = M
for moment σst x j x d
= 31.7274344 mm^2
Ast required = T
for tension σst
= 5.19230769 mm^2
Total Ast
required = 36.9197421 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on remote face)
Total D = 100 mm
effective D = 50 mm
Distribution steel:
Min. Ast = 120 mm^2 for one zone (on each face)
Page 8
Sheet2
Provide 8 mm dia bars @ 200 c/c spacing ( Horizontal steel on both face)
M =Q x b x d^2
Q= 1.8
d = 12.8290036 mm
Adopt d = 50mm
Total D = 75 mm
Ast required = M
for moment σst x j x d
= 52.9535349 mm^2
Ast required = T
for tension σst
= 17.3076923 mm^2
Total Ast
required = 70.2612272 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on remote face)
(ii) At center
M= 0.346875 kN.m
T= 2.25 kN (Tension on liquid face)
Ast required = M
for moment σst x j x d
= 62.0025567 mm^2
Ast required = T
for tension σst
= 17.3076923 mm^2
Total Ast
required = 79.310249 mm^2
Provide 8 mm dia bars @ 200 c/c spacing ( Verticle steel on liquid face)
Page 9
Sheet2
Total H = 0.7 m
or Downward pressure
< 1 Unsafe
Upward Pressure
Downward pressure
1) Weight of long walls = 2.7 kN
2) Weight of short walls = 0.675 kN providing all around projection o 0.25
3) Wight of bottom slab = 10.625 kN
4) Weight of soil on toe slab = 2.43 kN
Total Downward pressure = 16.43 kN
Upward pressure for B.M. = kN/m^2 (here, 0 is taken as no water surrounding the tank, otherw
load transfer by wall per meter length of slab = weight of 1 m long wall
1.125 kN/m
M =Q x b x d^2
Q= 1.8
d= Err:502
Adopt d = 200
Total D = 250
Ast required = M
Page 10
Sheet2
for moment σst x j x d
= 81.6442964 mm^2
Provide 12 mm dia bars @ 120 c/c spacing at face of bottom main direction
Ast required = M
for moment σst x j x d
= -48.9672732 mm^2
Provide 20 mm dia bars @ 175 c/c spacing at center portion of bottom main direction
Distribution steel:
Minimum reinforcement, pt (min) 0.24 %
Total D = 250 mm
effective D = 125 mm
Provide 10 mm dia bars @ 200 c/c spacing at top of slab both ways and
at bottom in secondary direction
Ast provided = 392.7 mm^2
X1 = 17.230175 mm
X2 = -24.0692798 mm
M= 7.30296743
Icr = 4811312.49 mm^4
Page 11
Sheet2
Strain taken by section Ɛ' = 0.0006754
Page 12
Sheet2
18
8
Page 13
Sheet2
Page 14
Sheet2
wise 10*H))
d soil)
is spanning horizontally.
ull height needs to be