Professional Documents
Culture Documents
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.....................................................................27
This manual......................................................................................27
Intended audience............................................................................27
Product documentation.....................................................................28
Product documentation set..........................................................28
Document revision history...........................................................29
Related documents......................................................................29
Symbols and conventions.................................................................30
Safety indication symbols............................................................30
Manual conventions.....................................................................31
1
Technical Manual
Table of contents
Settings........................................................................................47
Operation principle...........................................................................48
Local HMI....................................................................................48
Display....................................................................................48
LEDs.......................................................................................51
Keypad...................................................................................51
LED..............................................................................................54
Functionality...........................................................................54
Status LEDs...........................................................................54
Indication LEDs......................................................................54
Function keys..............................................................................62
Functionality...........................................................................62
Operation principle.................................................................62
2
Technical Manual
Table of contents
Function block.............................................................................96
Signals.........................................................................................96
Settings........................................................................................97
Monitored data.............................................................................97
Operation principle......................................................................97
Logic diagram.........................................................................97
Technical data.............................................................................98
Generator differential protection GENPDIF .....................................98
Identification................................................................................98
Functionality................................................................................99
Function block...........................................................................100
Signals.......................................................................................100
Settings......................................................................................101
Operation principle....................................................................102
Function calculation principles.............................................103
Fundamental frequency differential currents........................103
Supplementary criteria.........................................................108
Harmonic restrain.................................................................111
Cross-block logic scheme....................................................111
Simplified block diagrams.....................................................111
Technical data...........................................................................114
3
Technical Manual
Table of contents
4
Technical Manual
Table of contents
5
Technical Manual
Table of contents
Operation principle....................................................................186
Technical data...........................................................................187
Pole discordance protection CCRPLD ..........................................187
Identification .............................................................................187
Functionality..............................................................................187
Function block...........................................................................188
Signals.......................................................................................188
Settings......................................................................................189
Monitored data...........................................................................189
Operation principle....................................................................189
Pole discordance signaling from circuit breaker...................191
Unsymmetrical current detection..........................................191
Technical data...........................................................................192
Directional over-/under-power protection GOPPDOP/
GUPPDUP......................................................................................192
Functionality..............................................................................192
Directional overpower protection GOPPDOP ...........................192
Identification.........................................................................192
Function block......................................................................193
Signals..................................................................................193
Settings................................................................................194
Monitored data.....................................................................195
Directional underpower protection GUPPDUP..........................195
Identification.........................................................................195
Function block......................................................................195
Signals..................................................................................196
Settings................................................................................196
Monitored data.....................................................................197
Operation principle....................................................................197
Low pass filtering..................................................................199
Technical data...........................................................................200
Accidental energizing protection for synchronous generator
AEGGAPC......................................................................................200
Identification..............................................................................200
Functionality .............................................................................201
Function block...........................................................................201
Input and output signals............................................................201
Settings......................................................................................202
Operation principle....................................................................202
Technical data...........................................................................203
Negative-sequence time overcurrent protection for machines
NS2PTOC ......................................................................................204
Identification..............................................................................204
Functionality..............................................................................204
6
Technical Manual
Table of contents
Function block...........................................................................205
Signals.......................................................................................205
Settings......................................................................................206
Monitored data...........................................................................206
Operation principle....................................................................207
Start sensitivity.....................................................................208
Alarm function......................................................................209
Logic diagram.......................................................................209
Technical data...........................................................................210
Voltage-restrained time overcurrent protection VR2PVOC ...........210
Identification..............................................................................210
Functionality..............................................................................210
Function block...........................................................................211
Signals.......................................................................................211
Settings......................................................................................212
Monitored data...........................................................................213
Operation principle....................................................................213
Measured quantities.............................................................213
Base quantities.....................................................................213
Overcurrent protection..........................................................213
Logic diagram.......................................................................215
Undervoltage protection.......................................................215
Technical data...........................................................................216
7
Technical Manual
Table of contents
Monitored data...........................................................................225
Operation principle....................................................................226
Measurement principle.........................................................226
Time delay............................................................................227
Blocking................................................................................228
Design..................................................................................228
Technical data...........................................................................230
Two step residual overvoltage protection ROV2PTOV .................230
Identification..............................................................................230
Functionality..............................................................................230
Function block...........................................................................231
Signals.......................................................................................231
Settings......................................................................................231
Monitored data...........................................................................232
Operation principle....................................................................232
Measurement principle.........................................................233
Time delay............................................................................233
Blocking................................................................................234
Design..................................................................................234
Technical data...........................................................................236
Overexcitation protection OEXPVPH ............................................236
Identification..............................................................................236
Functionality..............................................................................236
Function block...........................................................................237
Signals.......................................................................................237
Settings......................................................................................237
Monitored data...........................................................................238
Operation principle....................................................................238
Measured voltage.................................................................240
Operate time of the overexcitation protection.......................241
Cooling.................................................................................243
Overexcitation protection function measurands...................244
Overexcitation alarm............................................................244
Logic diagram.......................................................................245
Technical data...........................................................................245
100% Stator earth fault protection, 3rd harmonic based
STEFPHIZ......................................................................................246
Identification..............................................................................246
IntroductionFunctionality............................................................246
Function block...........................................................................247
Signals.......................................................................................247
Settings......................................................................................248
Monitored data...........................................................................249
8
Technical Manual
Table of contents
Operation principle....................................................................249
Technical data...........................................................................254
9
Technical Manual
Table of contents
Identification..............................................................................267
Functionality..............................................................................267
Function block...........................................................................268
Signals.......................................................................................268
Settings......................................................................................269
Monitored data...........................................................................270
Operation principle....................................................................270
Zero and negative sequence detection................................270
Delta current and delta voltage detection.............................271
Dead line detection...............................................................274
Main logic.............................................................................274
Technical data...........................................................................278
Breaker close/trip circuit monitoring TCSSCBR.............................278
Identification..............................................................................278
Functionality..............................................................................278
Function block...........................................................................278
Signals.......................................................................................279
Settings......................................................................................279
Operation principle....................................................................279
Technical data...........................................................................280
Section 11 Control..........................................................................281
Synchrocheck, energizing check, and synchronizing
SESRSYN......................................................................................281
Identification..............................................................................281
Functionality..............................................................................281
Function block...........................................................................282
Signals.......................................................................................282
Settings......................................................................................284
Monitored data...........................................................................285
Operation principle....................................................................286
Basic functionality.................................................................286
Synchrocheck.......................................................................286
Synchronizing.......................................................................288
Energizing check..................................................................289
Voltage selection..................................................................289
Fuse failure supervision.......................................................289
Voltage selection for a single circuit breaker with double
busbars.................................................................................290
Technical data...........................................................................291
Apparatus control...........................................................................292
Functionality..............................................................................292
Bay control QCBAY...................................................................292
Identification ........................................................................292
10
Technical Manual
Table of contents
Functionality.........................................................................292
Function block......................................................................292
Signals..................................................................................293
Settings................................................................................293
Local remote LOCREM.............................................................293
Identification ........................................................................293
Functionality.........................................................................293
Function block......................................................................294
Signals..................................................................................294
Settings................................................................................294
Local remote control LOCREMCTRL........................................294
Identification ........................................................................294
Functionality.........................................................................295
Function block......................................................................295
Signals..................................................................................295
Settings................................................................................296
Operation principle....................................................................296
Bay control QCBAY..............................................................296
Local remote/Local remote control LOCREM/
LOCREMCTRL.....................................................................298
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................299
Identification..............................................................................299
Functionality..............................................................................299
Function block...........................................................................299
Signals.......................................................................................300
Settings......................................................................................301
Monitored data...........................................................................301
Operation principle....................................................................301
Selector mini switch VSGGIO.........................................................302
Identification..............................................................................302
Functionality..............................................................................302
Function block...........................................................................302
Signals.......................................................................................303
Settings......................................................................................303
Operation principle....................................................................303
IEC 61850 generic communication I/O functions DPGGIO............304
Identification..............................................................................304
Functionality..............................................................................304
Function block...........................................................................305
Signals.......................................................................................305
Settings......................................................................................305
Operation principle....................................................................305
Single point generic control 8 signals SPC8GGIO.........................305
11
Technical Manual
Table of contents
Identification..............................................................................305
Functionality..............................................................................306
Function block...........................................................................306
Signals.......................................................................................306
Settings......................................................................................307
Operation principle....................................................................307
Automation bits AUTOBITS............................................................308
Identification..............................................................................308
Functionality..............................................................................308
Function block...........................................................................308
Signals.......................................................................................309
Settings......................................................................................310
Operation principle....................................................................310
Function commands for IEC 60870-5-103 I103CMD.....................310
Functionality..............................................................................310
Function block...........................................................................310
Signals.......................................................................................311
Settings......................................................................................311
IED commands for IEC 60870-5-103 I103IEDCMD.......................311
Functionality..............................................................................311
Function block...........................................................................311
Signals.......................................................................................311
Settings......................................................................................312
Function commands user defined for IEC 60870-5-103
I103USRCMD.................................................................................312
Functionality..............................................................................312
Function block...........................................................................312
Signals.......................................................................................312
Settings......................................................................................313
Function commands generic for IEC 60870-5-103
I103GENCMD.................................................................................313
Functionality..............................................................................313
Function block...........................................................................314
Signals.......................................................................................314
Settings......................................................................................314
IED commands with position and select for IEC 60870-5-103
I103POSCMD.................................................................................314
Functionality..............................................................................314
Function block...........................................................................315
Signals.......................................................................................315
Settings......................................................................................315
Section 12 Logic.............................................................................317
Tripping logic SMPPTRC................................................................317
12
Technical Manual
Table of contents
Identification..............................................................................317
Functionality..............................................................................317
Function block...........................................................................317
Signals.......................................................................................318
Settings......................................................................................318
Operation principle....................................................................318
Technical data...........................................................................319
Trip matrix logic TMAGGIO............................................................319
Identification..............................................................................319
Functionality..............................................................................319
Function block...........................................................................320
Signals.......................................................................................320
Settings......................................................................................321
Operation principle....................................................................322
Configurable logic blocks................................................................323
Standard configurable logic blocks............................................323
Functionality.........................................................................323
OR function block.................................................................324
Inverter function block INVERTER.......................................325
PULSETIMER function block ..............................................326
Controllable gate function block GATE................................327
Exclusive OR function block XOR........................................328
Loop delay function block LOOPDELAY..............................329
Timer function block TIMERSET..........................................329
AND function block ..............................................................331
Set-reset memory function block SRMEMORY....................332
Reset-set with memory function block RSMEMORY...........333
Technical data...........................................................................334
Fixed signals FXDSIGN..................................................................335
Identification..............................................................................335
Functionality..............................................................................335
Function block...........................................................................335
Signals.......................................................................................336
Settings......................................................................................336
Operation principle....................................................................336
Boolean 16 to integer conversion B16I...........................................336
Identification..............................................................................336
Functionality..............................................................................337
Function block...........................................................................337
Signals.......................................................................................337
Settings......................................................................................338
Monitored data...........................................................................338
Operation principle....................................................................338
13
Technical Manual
Table of contents
Section 13 Monitoring.....................................................................345
IEC 61850 generic communication I/O functions SPGGIO............345
Identification..............................................................................345
Functionality..............................................................................345
Function block...........................................................................345
Signals.......................................................................................345
Settings......................................................................................345
Operation principle....................................................................346
IEC 61850 generic communication I/O functions 16 inputs
SP16GGIO.....................................................................................346
Identification..............................................................................346
Functionality..............................................................................346
Function block...........................................................................346
Signals.......................................................................................347
Settings......................................................................................347
MonitoredData...........................................................................347
Operation principle....................................................................348
IEC 61850 generic communication I/O functions MVGGIO............348
Identification..............................................................................348
14
Technical Manual
Table of contents
Functionality..............................................................................349
Function block...........................................................................349
Signals.......................................................................................349
Settings......................................................................................349
Monitored data...........................................................................350
Operation principle....................................................................350
Measurements................................................................................350
Functionality..............................................................................350
Measurements CVMMXN..........................................................352
Identification ........................................................................352
Function block......................................................................352
Signals..................................................................................353
Settings................................................................................354
Monitored data.....................................................................357
Phase current measurement CMMXU.......................................357
Identification ........................................................................357
Function block......................................................................357
Signals..................................................................................358
Settings................................................................................358
Monitored data.....................................................................359
Phase-phase voltage measurement VMMXU...........................359
Identification ........................................................................359
Function block......................................................................360
Signals..................................................................................360
Settings................................................................................361
Monitored data.....................................................................361
Current sequence component measurement CMSQI...............362
Identification ........................................................................362
Function block......................................................................362
Signals..................................................................................362
Settings................................................................................363
Monitored data.....................................................................364
Voltage sequence measurement VMSQI..................................364
Identification ........................................................................364
Function block......................................................................365
Signals..................................................................................365
Settings................................................................................366
Monitored data.....................................................................367
Phase-neutral voltage measurement VNMMXU........................367
Identification ........................................................................367
Function block......................................................................367
Signals..................................................................................368
Settings................................................................................368
15
Technical Manual
Table of contents
Monitored data.....................................................................369
Operation principle....................................................................369
Measurement supervision....................................................369
Measurements CVMMXN.....................................................374
Phase current measurement CMMXU.................................379
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU..............................................................380
Voltage and current sequence measurements VMSQI,
CMSQI..................................................................................380
Technical data...........................................................................380
Event Counter CNTGGIO...............................................................381
Identification..............................................................................381
Functionality..............................................................................381
Function block...........................................................................381
Signals.......................................................................................381
Settings......................................................................................382
Monitored data...........................................................................382
Operation principle....................................................................382
Reporting..............................................................................383
Technical data...........................................................................383
Disturbance report..........................................................................383
Functionality..............................................................................383
Disturbance report DRPRDRE..................................................384
Identification.........................................................................384
Function block......................................................................384
Signals..................................................................................385
Settings................................................................................385
Monitored data.....................................................................385
Measured values..................................................................389
Analog input signals AxRADR...................................................390
Identification.........................................................................390
Function block......................................................................390
Signals..................................................................................390
Settings................................................................................391
Analog input signals A4RADR...................................................394
Identification.........................................................................394
Function block......................................................................395
Signals..................................................................................395
Settings................................................................................395
Binary input signals BxRBDR....................................................399
Identification.........................................................................399
Function block......................................................................399
Signals..................................................................................400
Settings................................................................................400
16
Technical Manual
Table of contents
Operation principle....................................................................405
Disturbance information.......................................................407
Indications ...........................................................................407
Event recorder .....................................................................407
Event list ..............................................................................407
Trip value recorder ..............................................................407
Disturbance recorder ...........................................................407
Time tagging.........................................................................407
Recording times...................................................................408
Analog signals......................................................................408
Binary signals.......................................................................410
Trigger signals......................................................................410
Post Retrigger......................................................................411
Technical data...........................................................................412
Indications......................................................................................412
Functionality..............................................................................412
Function block...........................................................................413
Signals.......................................................................................413
Input signals.........................................................................413
Operation principle....................................................................413
Technical data...........................................................................414
Event recorder ...............................................................................414
Functionality..............................................................................414
Function block...........................................................................414
Signals.......................................................................................414
Input signals.........................................................................414
Operation principle....................................................................414
Technical data...........................................................................415
Event list.........................................................................................415
Functionality..............................................................................415
Function block...........................................................................415
Signals.......................................................................................416
Input signals.........................................................................416
Operation principle....................................................................416
Technical data...........................................................................416
Trip value recorder.........................................................................416
Functionality..............................................................................416
Function block...........................................................................417
Signals.......................................................................................417
Input signals.........................................................................417
Operation principle....................................................................417
Technical data...........................................................................418
Disturbance recorder......................................................................418
17
Technical Manual
Table of contents
Functionality..............................................................................418
Function block...........................................................................418
Signals.......................................................................................418
Input and output signals.......................................................418
Setting parameters....................................................................419
Operation principle....................................................................419
Memory and storage............................................................419
Technical data...........................................................................421
Measured value expander block MVEXP.......................................421
Identification..............................................................................421
Functionality..............................................................................421
Function block...........................................................................421
Signals.......................................................................................422
Settings......................................................................................422
Operation principle....................................................................422
Insulation gas monitoring function SSIMG.....................................423
Identification..............................................................................423
Functionality..............................................................................423
Function block...........................................................................423
Signals.......................................................................................423
Settings......................................................................................424
Operation principle....................................................................424
Technical data...........................................................................425
Insulation liquid monitoring function SSIML....................................425
Identification..............................................................................425
Functionality..............................................................................425
Function block...........................................................................426
Signals.......................................................................................426
Settings......................................................................................427
Operation principle....................................................................427
Technical data...........................................................................428
Circuit breaker condition monitoring SSCBR..................................428
Identification..............................................................................428
Functionality..............................................................................428
Function block...........................................................................428
Signals.......................................................................................429
Settings......................................................................................430
Monitored data...........................................................................431
Operation principle....................................................................431
Circuit breaker status...........................................................432
Circuit breaker operation monitoring....................................433
Breaker contact travel time...................................................434
Operation counter.................................................................435
18
Technical Manual
Table of contents
Accumulation of Iyt................................................................436
Remaining life of the circuit breaker.....................................438
Circuit breaker spring charged indication.............................439
Gas pressure supervision.....................................................440
Technical data...........................................................................441
Measurands for IEC 60870-5-103 I103MEAS................................441
Functionality..............................................................................441
Function block...........................................................................442
Signals.......................................................................................443
Settings......................................................................................443
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR...............................................................................444
Functionality..............................................................................444
Function block...........................................................................444
Signals.......................................................................................444
Settings......................................................................................445
Function status auto-recloser for IEC 60870-5-103 I103AR...........445
Functionality..............................................................................445
Function block...........................................................................445
Signals.......................................................................................446
Settings......................................................................................446
Function status earth-fault for IEC 60870-5-103 I103EF................446
Functionality..............................................................................446
Function block...........................................................................446
Signals.......................................................................................446
Settings......................................................................................447
Function status fault protection for IEC 60870-5-103
I103FLTPROT................................................................................447
Functionality..............................................................................447
Function block...........................................................................448
Signals.......................................................................................448
Settings......................................................................................449
IED status for IEC 60870-5-103 I103IED.......................................449
Functionality..............................................................................449
Function block...........................................................................450
Signals.......................................................................................450
Settings......................................................................................450
Supervison status for IEC 60870-5-103 I103SUPERV...................450
Functionality..............................................................................450
Function block...........................................................................451
Signals.......................................................................................451
Settings......................................................................................451
Status for user defined signals for IEC 60870-5-103
I103USRDEF..................................................................................451
19
Technical Manual
Table of contents
Functionality..............................................................................451
Function block...........................................................................452
Signals.......................................................................................452
Settings......................................................................................453
Section 14 Metering.......................................................................455
Pulse counter PCGGIO..................................................................455
Identification..............................................................................455
Functionality..............................................................................455
Function block...........................................................................455
Signals.......................................................................................455
Settings......................................................................................456
Monitored data...........................................................................456
Operation principle....................................................................456
Technical data...........................................................................458
Energy calculation and demand handling ETPMMTR....................458
Identification..............................................................................458
Functionality..............................................................................458
Function block...........................................................................459
Signals.......................................................................................459
Settings......................................................................................460
Monitored data...........................................................................461
Operation principle....................................................................461
Technical data...........................................................................462
20
Technical Manual
Table of contents
Identification..............................................................................471
Functionality..............................................................................471
Function block...........................................................................471
Signals.......................................................................................471
Settings......................................................................................472
Operation principle ...................................................................472
GOOSE function block to receive an integer value
GOOSEINTRCV.............................................................................472
Identification..............................................................................472
Functionality..............................................................................472
Function block...........................................................................473
Signals.......................................................................................473
Settings......................................................................................473
Operation principle ...................................................................473
GOOSE function block to receive a measurand value
GOOSEMVRCV.............................................................................474
Identification..............................................................................474
Functionality..............................................................................474
Function block...........................................................................474
Signals.......................................................................................474
Settings......................................................................................475
Operation principle ...................................................................475
GOOSE function block to receive a single point value
GOOSESPRCV..............................................................................475
Identification..............................................................................475
Functionality..............................................................................476
Function block...........................................................................476
Signals.......................................................................................476
Settings......................................................................................476
Operation principle ...................................................................476
IEC 60870-5-103 communication protocol.....................................477
Functionality..............................................................................477
Settings......................................................................................477
21
Technical Manual
Table of contents
Settings................................................................................482
Internal event list SELFSUPEVLST...........................................482
Identification.........................................................................482
Settings................................................................................482
Operation principle....................................................................482
Internal signals.....................................................................484
Run-time model....................................................................486
Technical data...........................................................................487
Time synchronization......................................................................488
Functionality..............................................................................488
Time synchronization TIMESYNCHGEN...................................488
Identification.........................................................................488
Settings................................................................................488
Time synchronization via SNTP................................................488
Identification.........................................................................488
Settings................................................................................489
Time system, summer time begin DSTBEGIN..........................489
Identification.........................................................................489
Settings................................................................................489
Time system, summer time ends DSTEND...............................490
Identification.........................................................................490
Settings................................................................................490
Time zone from UTC TIMEZONE..............................................490
Identification.........................................................................490
Settings................................................................................491
Time synchronization via IRIG-B...............................................491
Identification.........................................................................491
Settings................................................................................491
Operation principle....................................................................491
General concepts.................................................................491
Real-time clock (RTC) operation..........................................493
Synchronization alternatives................................................494
Technical data...........................................................................495
Parameter setting group handling..................................................495
Functionality..............................................................................495
Setting group handling SETGRPS............................................495
Identification.........................................................................495
Settings................................................................................495
Parameter setting groups ACTVGRP........................................496
Identification.........................................................................496
Function block......................................................................496
Signals..................................................................................496
Settings................................................................................496
22
Technical Manual
Table of contents
Operation principle....................................................................497
Test mode functionality TESTMODE..............................................498
Identification..............................................................................498
Functionality..............................................................................498
Function block...........................................................................498
Signals.......................................................................................498
Settings......................................................................................499
Operation principle....................................................................499
Change lock function CHNGLCK ..................................................500
Identification..............................................................................500
Functionality..............................................................................500
Function block...........................................................................501
Signals.......................................................................................501
Settings......................................................................................501
Operation principle....................................................................501
IED identifiers TERMINALID..........................................................502
Identification..............................................................................502
Functionality..............................................................................502
Settings......................................................................................502
Product information .......................................................................503
Identification..............................................................................503
Functionality..............................................................................503
Settings......................................................................................503
Primary system values PRIMVAL...................................................503
Identification..............................................................................503
Functionality..............................................................................504
Settings......................................................................................504
Signal matrix for analog inputs SMAI.............................................504
Functionality..............................................................................504
Signal matrix for analog inputs SMAI_20_1...............................504
Identification.........................................................................504
Function block......................................................................504
Signals..................................................................................505
Settings................................................................................506
Signal matrix for analog inputs SMAI_20_2...............................507
Identification.........................................................................507
Function block......................................................................507
Signals..................................................................................507
Settings................................................................................508
Operation principle ...................................................................509
Summation block 3 phase 3PHSUM..............................................509
Identification..............................................................................509
Functionality..............................................................................509
23
Technical Manual
Table of contents
Function block...........................................................................510
Signals.......................................................................................510
Settings......................................................................................511
Operation principle....................................................................511
Global base values GBASVAL.......................................................511
Identification..............................................................................511
Functionality..............................................................................511
Settings......................................................................................512
Authority check ATHCHCK.............................................................512
Identification..............................................................................512
Functionality..............................................................................512
Settings......................................................................................512
Operation principle....................................................................512
Authorization handling in the IED.........................................513
Authority status ATHSTAT.............................................................514
Identification..............................................................................514
Functionality..............................................................................514
Function block...........................................................................514
Signals.......................................................................................514
Settings......................................................................................515
Operation principle....................................................................515
Denial of service.............................................................................515
Functionality..............................................................................515
Denial of service, frame rate control for front port
DOSFRNT.................................................................................515
Identification.........................................................................515
Function block......................................................................516
Signals..................................................................................516
Settings................................................................................516
Monitored data.....................................................................516
Denial of service, frame rate control for LAN1 port
DOSLAN1..................................................................................517
Identification.........................................................................517
Function block......................................................................517
Signals..................................................................................517
Settings................................................................................517
Monitored data.....................................................................517
Operation principle....................................................................518
24
Technical Manual
Table of contents
Binary inputs..............................................................................522
Outputs...........................................................................................525
Outputs for tripping, controlling and signalling...........................525
Outputs for signalling.................................................................527
IRF.............................................................................................529
Communication connections..........................................................530
Ethernet RJ-45 front connection................................................530
Station communication rear connection....................................530
Optical serial rear connection....................................................531
Communication interfaces and protocols..................................531
Recommended industrial Ethernet switches.............................531
Connection diagrams......................................................................532
Connection diagrams for REG650 B01.....................................532
Connection diagrams for REG650 B05.....................................540
Section 21 Glossary.......................................................................589
25
Technical Manual
26
1MRK 502 034-UEN - Section 1
Introduction
Section 1 Introduction
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
27
Technical Manual
Section 1 1MRK 502 034-UEN -
Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 60870-5-103, IEC 61850
and DNP3.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
28
Technical Manual
1MRK 502 034-UEN - Section 1
Introduction
well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
29
Technical Manual
Section 1 1MRK 502 034-UEN -
Introduction
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
30
Technical Manual
1MRK 502 034-UEN - Section 1
Introduction
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:
To navigate between the options, use and .
• HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
• LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
• The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
31
Technical Manual
32
1MRK 502 034-UEN - Section 2
Available functions
REG650 (B01)
REG650 (B05)
Gen+Trafo diff
Gen diff
Differential protection
T3WPDIF 87T Transformer differential protection, three winding 1
HZPDIF 87 1Ph High impedance differential protection 1 1
GENPDIF 87G Generator differential protection 1
Impedance protection
ZGPDIS 21G Underimpedance protection for generators and transformers 1 1
LEXPDIS 40 Loss of excitation 1 1
OOSPPAM 78 Out-of-step protection 1 1
LEPDIS Load encroachment 1 1
REG650 (B05)
Gen+Trafo diff
Gen diff
Current protection
OC4PTOC 51/67 Four step directional phase overcurrent protection 2 2
EF4PTOC 51N/67N Four step directional residual overcurrent protection 2 2
SDEPSDE 67N Sensitive directional residual overcurrent and power protection 1 1
TRPTTR 49 Thermal overload protection, two time constants 2 2
CCRBRF 50BF Breaker failure protection 1 1
CCRPLD 52PD Pole discordance protection 1 1
GUPPDUP 37 Directional underpower protection 1 1
Table continues on next page
33
Technical Manual
Section 2 1MRK 502 034-UEN -
Available functions
REG650 (B01)
REG650 (B05)
Gen+Trafo diff
Gen diff
GOPPDOP 32 Directional overpower protection 2 2
AEGGAPC 50AE Accidental energizing protection for synchronous generator 1 1
NS2PTOC 46I2 Negative-sequence time overcurrent protection for machines 1 1
VR2PVOC 51V Voltage-restrained time overcurrent protection 1 1
Voltage protection
UV2PTUV 27 Two step undervoltage protection 1 1
OV2PTOV 59 Two step overvoltage protection 1 1
ROV2PTOV 59N Two step residual overvoltage protection 2 2
OEXPVPH 24 Overexcitation protection 1 1
STEFPHIZ 59THD 100% Stator earth fault protection, 3rd harmonic based 1 1
Frequency protection
SAPTUF 81 Underfrequency function 4 4
SAPTOF 81 Overfrequency function 4 4
SAPFRC 81 Rate-of-change frequency protection 2 2
REG650 (B05)
Gen+Trafo diff
Gen diff
Control
SESRSYN 25 Synchrocheck, energizing check, and synchronizing 1 1
QCBAY Bay control 1 1
LOCREM Handling of LR-switch positions 1 1
LOCREMCTRL LHMI control of Permitted Source To Operate (PSTO) 1 1
SLGGIO Logic Rotating Switch for function selection and LHMI presentation 15 15
VSGGIO Selector mini switch extension 20 20
DPGGIO IEC 61850 generic communication I/O functions double point 16 16
SPC8GGIO Single point generic control 8 signals 5 5
AUTOBITS AutomationBits, command function for DNP3.0 3 3
I103CMD Function commands for IEC60870-5-103 1 1
I103IEDCMD IED commands for IEC60870-5-103 1 1
Table continues on next page
34
Technical Manual
1MRK 502 034-UEN - Section 2
Available functions
REG650 (B01)
REG650 (B05)
Gen+Trafo diff
Gen diff
I103USRCMD Function commands user defined for IEC60870-5-103 4 4
I103GENCMD Function commands generic for IEC60870-5-103 50 50
I103POSCMD IED commands with position and select for IEC60870-5-103 50 50
Secondary system supervision
SDDRFUF Fuse failure supervision 1 1
TCSSCBR Breaker close/trip circuit monitoring 3 3
Logic
SMPPTRC 94 Tripping logic 6 6
TMAGGIO Trip matrix logic 12 12
OR Configurable logic blocks, OR gate 283 283
INVERTER Configurable logic blocks, Inverter gate 140 140
PULSETIMER Configurable logic blocks, Pulse timer 40 40
GATE Configurable logic blocks, Controllable gate 40 40
XOR Configurable logic blocks, exclusive OR gate 40 40
LOOPDELAY Configurable logic blocks, loop delay 40 40
TIMERSET Configurable logic blocks, timer function block 40 40
AND Configurable logic blocks, AND gate 280 280
SRMEMORY Configurable logic blocks, set-reset memory flip-flop gate 40 40
RSMEMORY Configurable logic blocks, reset-set memory flip-flop gate 40 40
FXDSIGN Fixed signal function block 1 1
B16I Boolean 16 to Integer conversion 16 16
B16IFCVI Boolean 16 to Integer conversion with logic node representation 16 16
IB16A Integer to Boolean 16 conversion 16 16
IB16FCVB Integer to Boolean 16 conversion with logic node representation 16 16
Monitoring
CVMMXN Measurements 6 6
CMMXU Phase current measurement 10 10
VMMXU Phase-phase voltage measurement 6 6
CMSQI Current sequence component measurement 6 6
VMSQI Voltage sequence measurement 6 6
VNMMXU Phase-neutral voltage measurement 6 6
CNTGGIO Event counter 5 5
DRPRDRE Disturbance report 1 1
AxRADR Analog input signals 4 4
BxRBDR Binary input signals 6 6
Table continues on next page
35
Technical Manual
Section 2 1MRK 502 034-UEN -
Available functions
REG650 (B01)
REG650 (B05)
Gen+Trafo diff
Gen diff
SPGGIO IEC 61850 generic communication I/O functions 64 64
SP16GGIO IEC 61850 generic communication I/O functions 16 inputs 16 16
MVGGIO IEC 61850 generic communication I/O functions 16 16
MVEXP Measured value expander block 66 66
SPVNZBAT Station battery supervision 1 1
SSIMG 63 Insulation gas monitoring function 2 2
SSIML 71 Insulation liquid monitoring function 2 2
SSCBR Circuit breaker condition monitoring 1 1
I103MEAS Measurands for IEC60870-5-103 1 1
I103MEASUSR Measurands user defined signals for IEC60870-5-103 3 3
I103AR Function status auto-recloser for IEC60870-5-103 1 1
I103EF Function status earth-fault for IEC60870-5-103 1 1
I103FLTPROT Function status fault protection for IEC60870-5-103 1 1
I103IED IED status for IEC60870-5-103 1 1
I103SUPERV Supervison status for IEC60870-5-103 1 1
I103USRDEF Status for user defined signals for IEC60870-5-103 20 20
Metering
PCGGIO Pulse counter logic 16 16
ETPMMTR Function for energy calculation and demand handling 3 3
REG650 (B05)
Gen+Trafo diff
Gen diff
Station communication
IEC 61850 communication protocol, LAN1 1 1
DNP3.0 for TCP/IP communication protocol, LAN1 1 1
IEC61870-5-103 IEC60870-5-103 serial communication via ST 1 1
GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59 59
GOOSEBINRCV GOOSE binary receive 4 4
Table continues on next page
36
Technical Manual
1MRK 502 034-UEN - Section 2
Available functions
REG650 (B01)
REG650 (B05)
Gen+Trafo diff
Gen diff
ETHFRNT Ethernet configuration of front port, LAN1 port and gateway
ETHLAN1
GATEWAY
GOOSEDPRCV GOOSE function block to receive a double point value 32 32
GOOSEINTRCV GOOSE function block to receive an integer value 32 32
GOOSEMVRCV GOOSE function block to receive a mesurand value 16 16
GOOSESPRCV GOOSE function block to receive a single point value 64 64
37
Technical Manual
38
1MRK 502 034-UEN - Section 3
Analog inputs
3.1 Introduction
Analog input channels are already configured inside the IED. However the IED has
to be set properly to get correct measurement results and correct protection
operations. For power measuring and all directional and differential functions the
directions of the input currents must be defined properly. Measuring and protection
algorithms in the IED use primary system quantities. Set values are done in
primary quantities as well and it is important to set the data about the connected
current and voltage transformers properly.
The direction of a current to the IED depends on the connection of the CT. The
main CTs are typically star connected and can be connected with the star point to
the object or from the object. This information must be set to the IED.
• Positive value of current or power means quantity direction into the object.
• Negative value of current or power means quantity direction out from the object.
39
Technical Manual
Section 3 1MRK 502 034-UEN -
Analog inputs
en05000456.vsd
IEC05000456 V1 EN
The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.
The CT and VT ratio and the name on respective channel is done under Main
menu/Hardware/Analog modules in the Parameter Settings tool.
40
Technical Manual
1MRK 502 034-UEN - Section 3
Analog inputs
41
Technical Manual
Section 3 1MRK 502 034-UEN -
Analog inputs
42
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
4.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Local HMI screen behaviour SCREEN - -
4.1.2 Settings
Table 4: SCREEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
DisplayTimeout 10 - 120 Min 10 60 Local HMI display timeout
ContrastLevel -100 - 100 % 10 0 Contrast level for display
DefaultScreen Main menu - - Main menu Default screen
Events
Measurements
Diagnostics
Disturbance
records
Single Line
Diagram
EvListSrtOrder Latest on top - - Latest on top Sort order of event list
Oldest on top
AutoIndicationDRP Off - - Off Automatic indication of disturbance report
On
SubstIndSLD No - - No Substitute indication on single line
Yes diagram
InterlockIndSLD No - - No Interlock indication on single line diagram
Yes
BypassCommands No - - No Enable bypass of commands
Yes
4.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Local HMI signals LHMICTRL - -
43
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
LHMICTRL
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
IEC09000320-1-en.vsd
IEC09000320 V1 EN
4.2.3 Signals
Table 5: LHMICTRL Input signals
Name Type Default Description
CLRLEDS BOOLEAN 0 Input to clear the LCD-HMI LEDs
4.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Basic part for LED indication module LEDGEN - -
Basic part for LED indication module GRP1_LED1 - - -
GRP1_LED15
GRP2_LED1 -
GRP2_LED15
GRP3_LED1 -
GRP3_LED15
44
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
LEDGEN
BLOCK NEWIND
RESET ACK
IEC09000321-1-en.vsd
IEC09000321 V1 EN
GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN
4.3.3 Signals
Table 7: LEDGEN Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Input to block the operation of the LEDs
RESET BOOLEAN 0 Input to acknowledge/reset the indication LEDs
45
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
4.3.4 Settings
Table 10: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of a
disturbance
4.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
LCD part for HMI Function Keys FNKEYMD1 - - -
Control module FNKEYMD5
FNKEYMD1
^LEDCTL1 ^FKEYOUT1
IEC09000327 V1 EN
Only the function block for the first button is shown above. There is a similar block
for every function button.
46
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
4.4.3 Signals
Table 12: FNKEYMD1 Input signals
Name Type Default Description
LEDCTL1 BOOLEAN 0 LED control input for function key
4.4.4 Settings
Table 14: FNKEYMD1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Mode Off - - Off Output operation mode
Toggle
Pulsed
PulseTime 0.001 - 60.000 s 0.001 0.200 Pulse time for output controlled by
LCDFn1
LabelOn 0 - 18 - 1 LCD_FN1_ON Label for LED on state
LabelOff 0 - 18 - 1 LCD_FN1_OFF Label for LED off state
47
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
GUID-23A12958-F9A5-4BF1-A31B-F69F56A046C7 V2 EN
4.5.1.1 Display
48
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
GUID-97DA85DD-DB01-449B-AD1F-EEC75A955D25 V1 EN
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
• The path shows the current location in the menu structure. If the path is too
long to be shown, it is truncated from the beginning, and the truncation is
indicated with three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in
and the object identification string which is settable via the LHMI or with
PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar
appears on the right. The text in content area is truncated from the beginning if
it does not fit in the display horizontally. Truncation is indicated with three dots.
49
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
GUID-1ECF507D-322A-4B94-B09C-49F6A0085384 V1 EN
The number before the function instance, for example 1:ETHFRNT, indicates the
instance number.
The function button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a
feedback signal for the function button control action. The LED is connected to the
required signal with PCM600.
GUID-11D6D98C-A2C9-4B2C-B5E0-FF7E308EC847 V1 EN
The alarm LED panel shows on request the alarm text labels for the alarm LEDs.
50
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
GUID-D20BB1F1-FDF7-49AD-9980-F91A38B2107D V1 EN
The function button and alarm LED panels are not visible at the same time. Each
panel is shown by pressing one of the function buttons or the Multipage button.
Pressing the ESC button clears the panel from the display. Both the panels have
dynamic width that depends on the label string length that the panel contains.
4.5.1.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 15 matrix programmable alarm LEDs on front of the LHMI. Each
LED can indicate three states with the colors: green, yellow and red. The alarm
texts related to each three-color LED are divided into three pages.The 15 physical
three-color LEDs in one LED group can indicate 45 different signals. Altogether,
135 signals can be indicated since there are three LED groups. The LEDs can be
configured with PCM600 and the operation mode can be selected with the LHMI
or PCM600.
4.5.1.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either
as menu shortcut or control buttons.
51
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
GUID-23A12958-F9A5-4BF1-A31B-F69F56A046C7 V2 EN
52
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
GUID-5BF45085-F0E8-4FCB-A941-A2E7FE197EC6 V2 EN
Figure 13: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
53
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
22 Communication port
4.5.2 LED
4.5.2.1 Functionality
Each indication LED on local HMI can be set individually to operate in six
different sequences; two as follow type and four as latch type. Two of the latching
sequence types are intended to be used as a protection indication system, either in
collecting or restarting mode, with reset functionality. The other two are intended
to be used as signalling system in collecting mode with acknowledgment
functionality.
There are three status LEDs above the LCD in the front of the IED, green, yellow
and red.
The green LED has a fixed function, while the yellow and red LEDs are user
configured. The yellow LED can be used to indicate that a disturbance report is
created (steady) or that the IED is in test mode (flashing). The red LED can be used
to indicate a trip command.
Operating modes
Collecting mode
Re-starting mode
• In the re-starting mode of operation each new start resets all previous active
LEDs and activates only those, which appear during one disturbance. Only
LEDs defined for re- starting mode with the latched sequence type 6
(LatchedReset-S) will initiate a reset and a restart at a new disturbance. A
54
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
disturbance is defined to end a settable time after the reset of the activated
input signals or when the maximum time limit has elapsed.
Acknowledgment/reset
• From local HMI
• The active indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function
is positive edge triggered, not level triggered. The acknowledgment/reset
is performed via the button and menus on the LHMI.
• Automatic reset
• The automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When
the automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.
Operating sequence
The sequences can be of type Follow or Latched. For the Follow type the LED
follow the input signal completely. For the Latched type each LED latches to the
correspond¬ing input signal until it is reset.
The figures below show the function of available sequences selectable for each
LED separately. For sequence 1 and 2 (Follow type), the acknowledgment/reset
function is not applicable. Sequence 3 and 4 (Latched type with acknowledgement)
are only work¬ing in collecting mode. Sequence 5 is working according to Latched
type and collecting mode while sequence 6 is working according to Latched type
and re-starting mode. The letters S and F in the sequence names have the meaning
S = Steady and F = Flash.
At the activation of the input signal, the indication obtains corresponding color
corresponding to the activated input and operates according to the selected
sequence diagrams below.
55
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN
If inputs for two or more colors are active at the same time to one LED the priority
is as described above. An example of the operation when two colors are activated
in parallel is shown in Figure 16.
Activating
signal GREEN
Activating
signal RED
LED G G R G
IEC09000312_1_en.vsd
IEC09000312 V1 EN
Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing
instead of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if
56
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN
Activating
signal GREEN
Activating
signal RED
R R G
LED
Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN
If all three signals are activated the order of priority is still maintained.
Acknowledgment of indications with higher priority will acknowledge also low
priority indications, which are not visible according to Figure 19.
57
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED
LED G Y R R Y
Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN
Activating
signal GREEN
Activating
signal YELLOW
Activating
signal RED
LED G G R R Y
Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing
light have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the
activation of the input signal, the indication will light up with a steady light. The
difference to sequence 3 and 4 is that indications that are still activated will not be
affected by the reset that is, immediately after the positive edge of the reset has
been executed a new reading and storing of active signals is performed. Every LED
is independent of the other LEDs in its operation.
58
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
Activating
signal
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN
That means if an indication with higher priority has reset while an indication with
lower priority still is active at the time of reset, the LED will change color
according to Figure 22.
Activating
signal GREEN
Activating
signal RED
R G
LED
Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN
Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the
positive edge of that the manual reset has been executed a new reading and storing
of active signals is performed. LEDs set for sequence 6 are completely independent
in its operation of LEDs set for other sequences.
59
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN
Figure 24 shows the timing diagram for a new indication after tRestart time has
elapsed.
Disturbance Disturbance
tRestart tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN
60
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
Figure 25 shows the timing diagram when a new indication appears after the first
one has reset but before tRestart has elapsed.
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN
61
Technical Manual
Section 4 1MRK 502 034-UEN -
Local Human-Machine-Interface LHMI
4.5.3.1 Functionality
When used as a menu shortcut, a function button provides a fast way to navigate
between default nodes in the menu tree. When used as a control, the button can
control a binary signal.
Operating sequence
The operation mode is set individually for each output, either OFF, TOGGLE or
PULSED.
Mode 0 (OFF)
This mode always gives the output the value 0 (FALSE). Changes on the IO
attribute are ignored.
Input value
Output value
IEC09000330-1-en.vsd
IEC09000330 V1 EN
Mode 1 (TOGGLE)
In this mode the output toggles each time the function block detects that the input
has been written. Note that the input attribute is reset each time the function block
executes. The function block execution is marked with a dotted line below.
62
Technical Manual
1MRK 502 034-UEN - Section 4
Local Human-Machine-Interface LHMI
Input value
Output value
IEC09000331_1_en.vsd
IEC09000331 V1 EN
Mode 2 (PULSED)
In this mode the output will be high for as long as the setting pulse time. After this
time the output will go back to 0. The input attribute is reset when the function
block detects it being high and there is no output pulse.
Note that the third positive edge on the input attribute does not cause a pulse, since
the edge was applied during pulse output. A new pulse can only begin when the
output is zero; else the trigger edge is lost.
Input value
Output value
tpulse tpulse
IEC09000332_1_en.vsd
IEC09000332 V1 EN
Input function
All inputs work the same way: When the LHMI is configured so that a certain
function button is of type CONTROL, then the corresponding input on this
function block becomes active, and will light the yellow function button LED when
high. This functionality is active even if the function block operation setting is set
to off.
There is an exception for the optional extension EXT1 function keys 7 and 8, since
they are tri-color (they can be red, yellow or green). Each of these LEDs are
controlled by three inputs, which are prioritized in the following order: Red -
Yellow - Green
INPUT OUTPUT
RED YELLOW GREEN Function key LED color
1 0/1 0/1 red
- 1 0/1 yellow
- - 1 green
0 0 0 off
63
Technical Manual
64
1MRK 502 034-UEN - Section 5
Differential protection
5.1.1 Functionality
The Transformer differential protection, two-winding (T2WPDIF) and Transformer
differential protection, three-winding (T3WPDIF) are provided with internal CT
ratio matching and vector group compensation and settable, zero sequence current
elimination.
The function can be provided with two or three-phase sets of current inputs. All
current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer arrangements.
Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN
Three-winding applications
three-winding power
transformer with all
three windings
connected
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with
unconnected delta
xx05000049.vsd tertiary winding
IEC05000049 V1 EN
The setting facilities cover for applications of the differential protection to all types
of power transformers and auto-transformers with or without load tap changer as
well as for shunt reactors or and local feeders within the station. An adaptive
stabilizing feature is included for heavy through-faults.
65
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
5.1.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Transformer differential protection, T3WPDIF 87T
three-winding
3Id/I
SYMBOL-BB V1 EN
IEC09000269_1_en.vsd
IEC09000269 V1 EN
5.1.2.3 Signals
Table 16: T3WPDIF Input signals
Name Type Default Description
I3PW1CT1 GROUP - Three phase current connection winding 1 (W1)
SIGNAL CT1
I3PW2CT1 GROUP - Three phase current connection winding 2 (W2)
SIGNAL CT1
I3PW3CT1 GROUP - Three phase current connection winding 3 (W3)
SIGNAL CT1
BLOCK BOOLEAN 0 Block of function
66
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
5.1.2.4 Settings
Table 18: T3WPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.10 - 0.60 IB 0.01 0.30 Section 1 sensitivity current, usually W1
current
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, multiple of W1 rated
current
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, multiple of W1 rated
current
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristics
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate-restrain
characteristics
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained protection limit, multiple of
W1 rated current
Table continues on next page
67
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
68
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
69
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
The main CTs are normally supposed to be star connected. The main CTs can be
earthed in anyway (that is, either "ToObject" or "FromObject"). However
internally the differential function will always use reference directions towards the
protected transformer as shown in figure 32. Thus the IED will always internally
measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in figure 32.
IW1 IW2
Z1S1 Z1S2
E1S1 E1S2
IW1 IW2
IED
en05000186.vsd
IEC05000186 V1 EN
Even in a healthy power transformer, the currents are generally not equal when
they flow through the power transformer, due to the ratio of the number of turns of
the windings and the connection group of the protected transformer. Therefore the
differential protection must first correlate all currents to each other before any
calculation can be performed.
70
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
Before any differential current can be calculated, the power transformer phase
shift, and its transformation ratio, must be allowed for. Conversion of all currents
to a common reference is performed in two steps:
• all current phasors are phase-shifted to (referred to) the phase-reference side,
(whenever possible a first winding with star connection)
• all currents magnitudes are always referred to the first winding of the power
transformer (typically transformer high-voltage side)
The two steps of conversion are made simultaneously on-line by the pre-
programmed coefficient matrices, as shown in equation 1 for a two-winding power
transformer, and in equation 2 for a three-winding power transformer.
1 2 3
EQUATION1880 V1 EN (Equation 1)
where:
1. is Differential Currents
2. is Differential current contribution from W1 side
3. is Differential current contribution from W2 side
71
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
1 2 3 4
EQUATION1556 V2 EN (Equation 2)
where:
1. is Differential Currents
2. is Differential current contribution from W1 side
3. is Differential current contribution from W2 side
4. is Differential current contribution from W3 side
1. Power transformer winding connection type, such as star (Y/y) or delta (D/d)
2. Transformer vector group such as Yd1, Dy11, YNautod5, Yy0d5 and so on,
which introduce phase displacement between individual windings currents in
multiples of 30°.
3. Settings for elimination of zero sequence currents for individual windings.
72
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
When the end user enters all these parameters, transformer differential function
automatically calculates off-line the matrix coefficients. During this calculations
the following rules are used:
For the phase reference, the first winding with set star (Y) connection is always
used. For example, if the power transformer is a Yd1 power transformer, the HV
winding (Y) is taken as the phase reference winding. If the power transformer is a
Dy1, then the LV winding (y) is taken for the phase reference. If there is no star
connected winding, such as in Dd0 type of power transformers, then the HV delta
winding (D) is automatically chosen as the phase reference winding.
As it can be seen from equation 1 and equation 2 the first entered winding (W1) is
always taken for ampere level reference (current magnitudes from all other sides
are always transferred to W1 side). In other words, within the differential
protection function, all differential currents and bias current are always expressed
in HV side primary Amperes.
It can be shown that the values of the matrix A, B & C coefficients (see equation 1
and equation 2) can be in advanced pre-calculated depending on the relative phase
shift between the reference winding and other power transformer windings.
Table 21 summarizes the values of the matrices for all standard phase shifts
between windings.
73
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
74
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
With help of table 21, the following matrix equation can be written for this power
transformer:
where:
IDL1 is the fundamental frequency differential current in phase L1 (in W1 side primary amperes)
IDL2 is the fundamental frequency differential current in phase L2 (in W1 side primary amperes)
IDL3 is the fundamental frequency differential current in phase L3 (in W1 side primary amperes)
IL1_W1 is the fundamental frequency phase current in phase L1 on W1 side
Table continues on next page
75
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
As marked in equation 1 and equation 2, the first term on the right hand side of the
equation, represents the total contribution from the individual phase currents from
W1 side to the fundamental frequency differential currents compensated for
eventual power transformer phase shift. The second term on the right hand side of
the equation, represents the total contribution from the individual phase currents
from W2 side to the fundamental frequency differential currents compensated for
eventual power transformer phase shift and transferred to the power transformer
W1 side. The third term on the right hand side of the equation, represents the total
contribution from the individual phase currents from W3 side to the fundamental
frequency differential currents compensated for eventual power transformer phase
shift and transferred to the power transformer W1 side. These current contributions
are important, because they are used for calculation of common bias current.
Fundamental frequency differential current level is monitored all the time within
the differential function. As soon as all three fundamental frequency differential
currents are set, a threshold defined by setting parameter IDiffAlarm a delay on
pickup timer is started. When the pre-set time, defined by setting parameter
tAlarmDelay, has expired the differential current alarm is generated and output
signal IDALARM is set to logical value one.
The bias current is calculated as the highest current amongst individual winding
current contributions to the total fundamental frequency differential currents. All
individual winding current contributions are already referred to the power
transformer winding one side (power transformer HV winding) and therefore they
can be compared regarding their magnitudes. There are six (or nine in case of three-
winding transformer) contributions to the total fundamental differential currents,
76
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
which are the candidates for the common bias current. The highest individual
current contribution is taken as a common bias (restrain) current for all three
phases. This "maximum principle" makes the differential protection more secure,
with less risk to operate for external faults and in the same time brings more
meaning to the breakpoint settings of the operate - restrain characteristic.
The magnitudes of the common bias (restrain) current expressed in the HV side
Amperes can be read as service values from the function. At the same time it is
available as outputs IBIAS from the differential protection function block. Thus, it
can be connected to the disturbance recorder and automatically recorded during
any external or internal fault condition.
The zero sequence currents can be explicitly eliminated from the differential
currents and common bias current calculation by special, dedicated parameter
settings, which are available for every individual winding.
• the protected power transformer cannot transform the zero sequence currents
to the other side, for any reason.
• the zero sequence currents can only flow on one side of the protected power
transformer.
In most cases, power transformers do not properly transform the zero sequence
current to the other side. A typical example is a power transformer of the star-delta
type, for example YNd1. Transformers of this type do not transform the zero
sequence quantities, but zero sequence currents can flow in the earthed star-
connected winding. In such cases, an external earth-fault on the star-side causes the
zero sequence currents to flow on the star-side of the power transformer, but not on
the other side. This results in false differential currents - consisting exclusively of
the zero sequence currents. If high enough, these false differential currents can
cause an unwanted disconnection of the healthy power transformer. They must
therefore be subtracted from the fundamental frequency differential currents if an
unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if an earthing transformer
exist within differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to
some extent sensitivity of the differential protection for internal earth-faults. In
order to counteract this effect to some degree, the zero sequence currents are
subtracted not only from the three fundamental frequency differential currents, but
automatically from the bias current as well.
77
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
Power transformer differential protection function uses two limits, to which actual
magnitudes of the three fundamental frequency differential currents are compared
at each execution of the function.
The restrained (that is, stabilized) part of the differential protection compares the
calculated fundamental differential (that is, operating) currents, and the bias (that
is, restrain) current, by applying them to the operate - restrain characteristic.
Practically, the magnitudes of the individual fundamental frequency differential
currents are compared with an adaptive limit. This limit is adaptive because it is
dependent on the bias (that is, restrain) current magnitude. This limit is called the
operate - restrain characteristic. It is represented by a double-slope, double-
breakpoint characteristic, as shown in figure 33. The restrained characteristic is
determined by the following 5 settings:
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
78
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
operate current
[ times IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1 Section 2 Section 3
SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en05000187-2.vsd
IEC05000187 V2 EN
where:
Section 1: This is the most sensitive part on the characteristic. In section 1, normal
currents flow through the protected circuit and its current transformers, and risk for
higher false differential currents is relatively low. Un-compensated on-load tap-
changer is a typical reason for existence of the false differential currents in this
section. Slope in section 1 is always zero percent.
79
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
The operate - restrain characteristic should be designed so that it can be expected that:
• for internal faults, the operate (differential) currents are always safely, that is,
with a good margin, above the operate - restrain characteristic
• for external faults, the false (spurious) operate currents are safely, that is, with
a good margin, below the operate - restrain characteristic
80
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
1 2 3
where:
1. is Negative Sequence Differential Currents
2. is Negative Sequence current contribution from W1 side
3. is Negative Sequence current contribution from W2 side
and where:
IDL1_NS is the negative sequence differential current in phase L1 (in
W1 side primary amperes)
IDL2_NS is the negative sequence differential current in phase L2 (in
W1 side primary amperes)
IDL3_NS is the negative sequence differential current in phase L3 (in
W1 side primary amperes)
INS_W1 is negative sequence current on W1 side in primary
amperes (phase L1 reference)
INS_W2 is negative sequence current on W1 side in primary
amperes (phase L1 reference)
Ur_W1 is transformer rated phase-to-phase voltage on W1 side
(setting parameter)
Ur_W2 is transformer rated phase-to-phase voltage on W2 side
(setting parameter)
j ×120
o 1 3
a=e =- + j×
2 2
EQUATION1248 V1 EN (Equation 24)
Because the negative sequence currents always form the symmetrical three phase
current system on each transformer side (that is, negative sequence currents in
every phase will always have the same magnitude and be phase displaced for 120
electrical degrees from each other), it is only necessary to calculate the first
negative sequence differential current that is, IDL1_NS.
As marked in equation 23, the first term on the right hand side of the equation,
represents the total contribution of the negative sequence current from W1 side
compensated for eventual power transformer phase shift. The second term on the
right hand side of the equation, represents the total contribution of the negative
sequence current from W2 side compensated for eventual power transformer phase
81
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
shift and transferred to the power transformer W1 side. These negative sequence
current contributions are phasors, which are further used in directional
comparisons, made in order to characterize a fault as internal or external. See
section "Internal/external fault discriminator" for more information.
82
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
1. IMinNegSeq
2. NegSeqROA
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement
NegSeqROA
is done, and (Relay
120 degrees
Operate
is mapped Angle)
IMinNegSeq
External Internal
fault fault
region region
270 deg
en05000188-2-en.vsd
IEC05000188 V2 EN
83
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
For example, for any unsymmetrical external fault, ideally the respective negative
sequence current contributions from the W1 and W2 power transformer sides will
be exactly 180 degrees apart and equal in magnitude, regardless the power
transformer turns ratio and phase displacement. One such example is shown in
figure 35, which shows trajectories of the two separate phasors representing the
negative sequence current contributions from HV and LV sides of an Yd5 power
transformer (for example, after the compensation of the transformer turns ratio and
phase displacement for an unsymmetrical external fault. Observe that the relative
phase angle between these two phasors is 180 electrical degrees at any point in
time. No current transformer saturation was assumed for this case.
84
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
"steady state"
for HV side 90
neg. seq. phasor
60
150 30
10
ms
180 0
0.1 kA
0.2 kA
0.3 kA
10 0.4 kA
ms
210 330
"steady state"
240 for LV side
270 neg. seq. phasor
en05000189.vsd
IEC05000189 V1 EN
Therefore, under all external fault condition, the relative angle is theoretically
equal to 180 degrees. During internal fault, the angle shall ideally be 0 degrees, but
due to possible different negative sequence source impedance angles on W1 and
W2 sides of the protected power transformer, it may differ somewhat from the
ideal zero value. However, during heavy faults, CT saturation might cause the
measured phase angle to differ from 180 degrees for external, and from about 0
degrees for internal fault. See figure 36 for an example of a heavy internal fault
with transient CT saturation.
85
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
Dire ctiona l Compa ris on Crite rion: Inte rna l fa ult a s s e e n from the HV s ide
90
e xcurs ion
120 60
from 0 de gre e s
35 ms due to CT
s a tura tion
150 30
de finite ly
a n inte rna l
fa ult
180 0
trip c o mmand
in 12 ms
e xte rna l
fa ult Inte rna l fa ult
0.5 kA de cla re d 7 ms
re gion
210 330 a fte r inte rna l
fa ult occure d
1.0 kA
240 300
1.5 kA
270
HV s ide contribution to the tota l ne ga tive s e que nce diffe re ntia l curre nt in kA
Dire ctiona l limit (within the re gion de limite d by ± 60 de gre e s is inte rna l fa ult)
en05000190.vsd
IEC05000190 V1 EN
However, it shall be noted that additional security measures are implemented in the
internal/external fault discriminator algorithm in order to guaranty proper operation
with heavily saturated current transformers. The trustworthy information on
whether a fault is internal or external is typically obtained in about 10ms after the
fault inception, depending on the setting IminNegSeq, and the magnitudes of the
fault currents. At heavy faults, approximately 5ms time to full saturation of the
main CT is sufficient in order to produce a correct discrimination between internal
and external faults.
Two sub functions, which are based on the internal/external fault discriminator
with the ability to trip a faulty power transformer, are parts to the traditional power
transformer differential protection.
86
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
If the same fault has been positively recognized as internal, then the unrestrained
negative sequence differential protection places its own trip request.
If the bias current is higher than 110% IBase of the power transformer winding
W1, then any block signals by the harmonic and/or waveform criteria, which can
block the traditional differential protection are overridden, and the differential
protection operates quickly without any further delay. If the bias current is lower
than 110%, where harmonic block should not exist for internal faults, then this
negative sequence differential protection is restrained by any harmonic block
signal.
This logic guarantees a fast disconnection of a faulty power transformer for any
heavier internal faults.
If the same fault has been classified as external, then generally, but not
unconditionally, a trip command is prevented. If a fault is classified as external, the
further analysis of the fault conditions is initiated. If all the instantaneous
differential currents in phases where start signals have been issued are free of
harmonic pollution, then a (minor) internal fault, simultaneous with a predominant
external fault can be suspected. This conclusion can be drawn because at external
faults, major false differential currents can only exist when one or more current
transformers saturate. In this case, the false instantaneous differential currents are
polluted by higher harmonic components, the 2nd, the 5th etc.
87
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
The instantaneous differential currents are calculated from the instantaneous values
of the input currents in order to perform the harmonic analysis and waveform
analysis upon each one of them (see section "Harmonic and waveform block
criteria" for more information).
The two block criteria are the harmonic restrain and the waveform restrain. These
two criteria have the power to block (that is, to prevent) a trip command by the
traditional differential protection, which produces start signals by applying the
differential currents, and the bias current, to the operate - restrain characteristic.
Harmonic restrain
The harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal is to prevent an unwanted trip
command due to magnetizing inrush currents at switching operations, or due to
magnetizing currents at over-voltages.
The magnetizing currents of a power transformer flow only on one side of the
power transformer (one or the other) and are therefore always the cause of false
differential currents. The harmonic analysis (the 2nd and the 5th harmonic) is
applied to instantaneous differential currents. Typically instantaneous differential
currents during power transformer energizing are shown in figure 37. The
harmonic analysis is only applied in those phases, where start signals have been
set. For example, if the content of the 2nd harmonic in the instantaneous differential
current of phase L1 is above the setting I2/I1Ratio, then a block signal is set for
that phase.
Waveform restrain
The waveform restrain criterion is a good complement to the harmonic analysis.
The waveform restrain is a pattern recognition algorithm, which looks for intervals
within each fundamental power system cycle with low instantaneous differential
current. This interval is often called current gap in protection literature. However,
within differential function this criterion actually searches for long-lasting intervals
with low rate-of-change in instantaneous differential current, which are typical for
the power transformer inrush currents. Block signal BLKWAV is set in those
phases where such behavior is detected. The algorithm do not requires any end user
settings. The waveform algorithm is automatically adapted dependent only on the
power transformer rated data.
88
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
IEC05000343 V1 EN
Transformer differential function in the IED has a built-in, advanced switch onto
fault feature. This feature can be enabled or disabled by a setting parameter
SOTFMode. When enabled this feature ensures quick differential protection
tripping in cases where a transformer is energized with a more severe (minor faults
cannot be discovered) internal fault (for example, forgotten earthing on transformer
LV side for example, after a regular service). The feature is based on the waveform
check. If a severe internal fault exists, then, when the power transformer is
89
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
energized, the magnetic density in the iron core will be low and high sinusoidal
currents will flow from the very beginning. The waveform block algorithm will in
such a case remove all its three block signals in a very short interval of time. A
quick reset of the waveblock criterion will temporarily disable the second harmonic
blocking feature within the differential function. This consequently ensures fast
operation of the transformer differential function for a switch onto a fault
condition. It shall be noted that this feature is only active during initial power
transformer energizing, more exactly, under the first 50 ms. When the switch onto
fault feature is disabled by the setting parameter SOTFMode, the waveblock and
second harmonic blocking features work in parallel and are completely
independent from each other.
The simplified internal logics, for transformer differential protection are shown in
the following figures.
IDL2
Derive equation to calculate differential currents
individual windings
phase current
IDL1MAG
Fundamental frequency (phasor
based) Diff current, phase L1 &
ratio
IDL2MAG
Fundamental frequency (phasor
based) Diff current, phase L2 &
phase current contributions from
individual windings
IDL3MAG
Fundamental frequency (phasor
based) Diff current, phase L3 &
phase current contributions from
individual windings
MAX IBIAS
IEC09000162_1_en.vsd
IEC09000162 V1 EN
Figure 38: Treatment of measured currents within IED for transformer differential function
90
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
Figure 38 shows how internal treatment of measured currents is done in case of two-
winding transformer.
The following currents are inputs to the power transformer differential protection
function. They must all be expressed in true power system (primary) A, that is, as
measured.
1. Instantaneous values of currents (samples) from HV, and LV sides for two-
winding power transformers, and from the HV, the first LV, and the second
LV sides for three-winding power transformers.
2. Currents from all power transformer sides expressed as fundamental frequency
phasors, with their real, and imaginary parts. These currents are calculated
within the protection function by the fundamental frequency Fourier filters.
3. Negative sequence currents from all power transformer sides expressed as
phasors. These currents are calculated within the protection function by the
symmetrical components module.
91
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
BLKUNRES
IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG
IBIAS STL1
AND
BLOCK
BLKRES
TRIPRESL1
AND
OR 1
IDL1
to fault logic
2nd BLK2HL1
Switch on
Harmonic
Wave BLKWAVL1
block
5th BLK5HL1
Harmonic
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
OR
AND
OpCrossBlock=On
en06000545.vsd
IEC06000545 V1 EN
IEC05000167-TIFF V1 EN
92
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3
TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3
TRIP
TRNSSENS OR
TRNSUNR
en05000278.vsd
IEC05000278 V1 EN
IEC05000279-TIFF V1 EN
93
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
respective block signals, a restrained trip TRIPRES and common trip TRIP are
issued
3. If a start signal is issued in a phase, and the fault has been classified as
internal, then any eventual block signals are overridden and a unrestrained
negative-sequence trip TRNSUNR and common trip TRIP are issued without
any further delay. This feature is called the unrestrained negative-sequence
protection.
4. The sensitive negative sequence differential protection is independent of any
start signals. It is meant to detect smaller internal faults, such as turn-to-turn
faults, which are often not detected by the traditional differential protection.
The sensitive negative sequence differential protection starts whenever both
contributions to the total negative sequence differential current (that must be
compared by the internal/external fault discriminator) are higher than the value
of the setting IMinNegSeq. If a fault is positively recognized as internal, and
the condition is stable with no interruption for at least one fundamental
frequency cycle the sensitive negative sequence differential protection
TRNSSENS and common trip TRIP are issued. This feature is called the
sensitive negative sequence differential protection.
5. If a start signal is issued in a phase (see signal STL1), even if the fault has
been classified as an external fault, then the instantaneous differential current
of that phase (see signal IDL1) is analyzed for the 2nd and the 5th harmonic
contents (see the blocks with the text inside: 2nd Harmonic; Wave block and
5th Harmonic). If there is less harmonic pollution, than allowed by the settings
I2/I1Ratio, and I5/I1Ratio, (then the outputs from the blocks 2nd harmonic and
5th harmonic is 0) then it is assumed that a minor simultaneous internal fault
must have occurred. Only under these conditions a trip command is allowed
(the signal TRIPRESL1 is = 1). The cross-block logic scheme is automatically
applied under such circumstances. (This means that the cross block signals
from the other two phases L2 and L3 is not activated to obtain a trip on the
TRIPRESL1 output signal in figure 39)
6. All start and blocking conditions are available as phase segregated as well as
common (that is three-phase) signals.
IDL1 MAG
a
a>b
I Diff Alarm b
IDL3 MAG
a
a>b
I Diff Alarm b
en06000546.vsd
IEC06000546 V1 EN
94
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
5.2.1 Identification
IEC 61850 IEC 60617 ANSI/IEEE C37.2
Function description
identification identification device number
SYMBOL-CC V2 EN
95
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
5.2.2 Introduction
The 1Ph High impedance differential protection HZPDIF function can be used
when the involved CT cores have the same turn ratio and similar magnetizing
characteristics. It utilizes an external summation of the currents in the
interconnected CTs and a series resistor and a voltage dependent resistor externally
to the IED.
IEC05000363-2-en.vsd
IEC05000363 V2 EN
5.2.4 Signals
Table 23: HZPDIF Input signals
Name Type Default Description
ISI GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
96
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
5.2.5 Settings
Table 25: HZPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
U>Alarm 2 - 500 V 1 10 Alarm voltage level in volts on CT
secondary side
tAlarm 0.000 - 60.000 s 0.001 5.000 Time delay to activate alarm
U>Trip 5 - 900 V 1 100 Operate voltage level in volts on CT
secondary side
SeriesResistor 10 - 20000 ohm 1 1800 Value of series resistor in Ohms
See the application manual for operating voltage and sensitivity calculation.
The logic diagram shows the operation principles for the 1Ph High impedance
differential protection function HZPDIF, see figure 45. It is a simple one step
function with an additional lower alarm level. By activating inputs, the HZPDIF
function can either be blocked completely, or only the trip output.
97
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
IEC05000301 V1 EN
Figure 45: Logic diagram for 1Ph High impedance differential protection
HZPDIF
5.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Generator differential protection GENPDIF 87G
Id>
SYMBOL-NN V1 EN
98
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
5.3.2 Functionality
Short circuit between the phases of the stator windings causes normally very large
fault currents. The short circuit gives risk of damages on insulation, windings and
stator iron core. The large short circuit currents cause large forces, which can cause
damage even to other components in the power plant, such as turbine and generator-
turbine shaft.
To limit the damage due to stator winding short circuits, the fault clearance must be
as fast as possible (instantaneous). If the generator block is connected to the power
system close to other generating blocks, the fast fault clearance is essential to
maintain the transient stability of the non-faulted generators.
Normally, the short circuit fault current is very large, that is, significantly larger
than the generator rated current. There is a risk that a short circuit can occur
between phases close to the neutral point of the generator, thus causing a relatively
small fault current. The fault current can also be limited due to low excitation of
the generator. Therefore, it is desired that the detection of generator phase-to-phase
short circuits shall be relatively sensitive, detecting small fault currents.
It is also of great importance that the generator differential protection does not trip
for external faults, with large fault currents flowing from the generator. To
combine fast fault clearance, as well as sensitivity and selectivity, the generator
differential protection is normally the best choice for phase-to-phase generator
short circuits. A negative-sequence-current-based internal-external fault
discriminator can be used to determine whether a fault is internal or external. The
internal-external fault discriminator not only positively discriminates between
internal and external faults, but can independently detect minor faults which may
not be felt (until they develop into more serious faults) by the "usual" differential
protection based on operate-restrain characteristic.
99
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
IEC07000025_2_en.vsd
IEC07000025 V2 EN
5.3.4 Signals
Table 28: GENPDIF Input signals
Name Type Default Description
I3PNCT GROUP - Neutral side CT input
SIGNAL
I3PTCT GROUP - Terminal side CT input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKRES BOOLEAN 0 Block of trip from the restrained diff. protection
BLKUNRES BOOLEAN 0 Block of trip from unrestrained diff. prot.
BLKNSUNR BOOLEAN 0 Block of trip for unrestr. neg. seq. differential
feature
BLKNSSEN BOOLEAN 0 Block of trip for sensitive neg. seq. differential
feature
DESENSIT BOOLEAN 0 Raise pick up: function temporarily desensitized
100
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
5.3.5 Settings
Table 30: GENPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.10 - 1.00 IB 0.01 0.25 Section 1 sensitivity, multiple of
generator rated current
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestr. prot. limit, multiple of generator
rated current
OpNegSeqDiff No - - Yes Negative Sequence Differential Enable
Yes Off/On
IMinNegSeq 0.02 - 0.40 IB 0.01 0.10 Neg. sequence curr. limit, as multiple of
gen. rated curr.
101
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
xx06000430.vsd
IEC06000430 V1 EN
If the fault is internal, the faulty generator must be quickly tripped, that is,
disconnected from the network, the field breaker tripped and the power to the
prime mover interrupted.
GENPDIF function always uses reference (default) directions of CTs towards the
protected generator as shown in figure 47. Thus, it always measures the currents on
the two sides of the generator with the same reference direction towards the
generator windings. With the orientation of CTs as in figure 47, the difference of
currents flowing in, and out, of a separate stator winding phase is simply obtained
by summation of the two currents fed to the differential protection function.
102
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
Numerical IEDs have brought a large number of advantages and new functionality
to the protective relaying. One of the benefits is the simplicity and accuracy of
calculating symmetrical components from individual phase quantities. Within the
firmware of a numerical IED, it is no more difficult to calculate negative-sequence
components than it is to calculate zero-sequence components. Diversity of
operation principles integrated in the same protection function enhances the overall
performance without a significant increase in cost.
The fundamental frequency phasors of the phase currents from both sides of the
generator (the neutral side and the terminal side) are delivered to the differential
protection function by the pre-processing module of the IED.
The fundamental frequency RMS differential current is a vectorial sum (that is,
sum of fundamental frequency phasors) of the individual phase currents from the
two sides of the protected generator. The magnitude of the fundamental frequency
RMS differential current, in phase L1, is as calculated in equation 26:
103
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
One common fundamental frequency bias current is used. The bias current is the
magnitude of the highest measured current in the protected circuit. The bias current
is not allowed to drop instantaneously, instead, it decays exponentially with a
predefined time constant. These principles make the differential IED more secure,
with less risk to operate for external faults. The “maximum” principle brings as
well more meaning to the breakpoint settings of the operate-restrain characteristic.
IL1n IL1t
IL1t Idiff
IL1n
IEC07000018_3_en.vsd
IEC07000018 V3 EN
104
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
IL1n IL1t
IL1t IL1n
Idiff = 0 en07000019-2.vsd
IEC07000019 V2 EN
The stabilized differential protection applies a differential (operate) current, and the
common bias (restrain) current, on the operate-restrain characteristic, as shown in
figure 51. Here, the actual limit, where the protection can operate, is dependent on
the bias (restrain) current. The operate value, is stabilized by the bias current. This
operate – restrain characteristic is represented by a double-slope, double-breakpoint
characteristic. The restrained characteristic is determined by the following 5 settings:
105
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
Note that both slopes are calculated from the characteristics break
points.
Note that both slopes are calculated from the characteristics break
points.
AddTripDelay: If the input DESENSIT is activated also the operation time of the
protection function can be increased by using the setting AddTripDelay.
106
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
operate current
[ times IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1 Section 2 Section 3
SlopeSection3
1
TempIdMin
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en06000637.vsd
IEC06000637 V2 EN
107
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
If a fault is classified as internal, then any eventual block signals by the harmonic
criterion are ignored, and the differential protection can operate very quickly
without any further delay.
If all the differential currents which caused their respective start signals to be set,
are free of harmonic pollution, that is, if no harmonic block signal has been set,
then a (minor) internal fault, simultaneous with a predominant external fault, can
be suspected. This conclusion can be drawn because at external faults, major false
differential currents can only exist when one or more current transformers saturate
transiently. In this case, the false instantaneous differential currents are highly
polluted by higher harmonic components, the 2nd, and the 5th.
The internal or external fault discriminator responds to the relative phase angles of
the negative sequence fault currents at both ends of the stator winding. Observe
that the source of the negative sequence currents at unsymmetrical faults is at the
fault point.
108
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
• If the two negative sequence currents, as seen by the differential relay, flow in
the same direction (that is with the CTs oriented as in figure 47), the fault is
internal. If the two negative sequence currents flow in opposite directions, the
fault is external.
• Under external fault condition, the relative angle is theoretically equal to 180°.
Under internal fault condition, the angle is ideally 0°, but due to possible
different negative-sequence impedance angles on both sides of the internal
fault, it may differ somewhat from 0°.
The setting NegSeqROA, as shown in figure 52, represents the so called Relay
Operate Angle, which determines the boundary between the internal and external
fault regions. It can be selected in the range ±30° to ±90°, with a step of 1°. The
default value is ±60°. The default setting, ±60°, favors somewhat security in
comparison to dependability.
109
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
90 deg
120 deg
NegSeqROA
Angle could not be (Relay Operate Angle)
measured. One or both
currents too small
Internal fault
region
IminNegSeq
External fault
region
Internal /
external fault
boundary.
Default ± 60 deg
The characteristic is defined by the
settings:
IMinNegSeq and NegSeqROA
270 deg
en06000433-2.vsd
IEC06000433 V2 EN
Figure 52: NegSeqROA determines the boundary between the internal and
external fault regions
110
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
Harmonic restrain is the classical restrain method traditionally used with power
transformer differential protections. The goal there was to prevent an unwanted trip
command due to magnetizing inrush currents at switching operations, due to
magnetizing currents at over-voltages, or external faults. Harmonic restrain is just
as useful with Generator differential protection GENPDIF. The harmonic analysis
is only executed in those phases, where start signals have been set.
At external faults dangerous false differential currents can arise for different
reasons, mainly due to saturation of one or more current transformers. The false
differential currents display in this case a considerable amount of higher
harmonics, which can, therefore, be used to prevent an unwanted trip of a healthy
generator or shunt reactor.
The cross-block logic says that in order to issue a common trip command, the
harmonic contents in all phases with a start signal set (start = TRUE) must be
below the limit defined with the setting HarmDistLimit. In the opposite case, no
trip command will be issued.
The cross-block logic is active if the setting OpCrossBlock = Yes. By always using
the cross-block logic, the false trips can be prevented for external faults in cases
where the internal or external fault discriminator should for some reason fail to
declare an external fault. For internal faults, the higher frequency components of an
instantaneous differential current are most often relatively low, compared to the
fundamental frequency component. While for an external (heavy) fault, they can be
relatively high. For external faults with moderate fault currents, there can be little
or no current transformer saturation and only small false differential currents.
The principle design of the generator differential protection is shown in figure 53.
111
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
TRIP
Signals
Start
Phasors IL1N, IL2N,IL3N Magnitude phase
Calculation Idiff and Ibias Diff.prot. selective
Idiff and Ibias characteristic
Phasors IL1T, IL2T,IL3T
START
Signals
BLOCK
Signals
en06000434-2.vsd
IEC06000434 V3 EN
112
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
BLKUNRES
IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG
IBIAS STL1
AND
BLOCK
BLKRES
INTFAULT TRIPRESL1
AND
OR 1
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
AND
OpCrossBlock=On
en07000020.vsd
IEC07000020 V2 EN
Internal/ EXTFAULT
Neg.Seq. Diff External INTFAULT
Current Fault
Contributions discrimin
ator TRNSSENS
AND
OpNegSeqDiff=On
IBIAS
a
b>a
b
Constant
BLKNSSEN
BLKNSUNR
BLOCK
TRNSUNR
STL1 AND
STL2
OR
STL3
en07000021.vsd
IEC07000021 V2 EN
113
Technical Manual
Section 5 1MRK 502 034-UEN -
Differential protection
STL1
STL2 START
OR
STL3
BLKHL1
BLKHL2 BLKH
OR
BLKHL3
en07000022.vsd
IEC07000022 V1 EN
TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3
TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3
TRIP
TRNSSENS OR
TRNSUNR
en07000023.vsd
IEC07000023 V1 EN
114
Technical Manual
1MRK 502 034-UEN - Section 5
Differential protection
115
Technical Manual
116
1MRK 502 034-UEN - Section 6
Impedance protection
6.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Underimpedance protection for ZGPDIS 21G
generators and transformers
6.1.2 Functionality
The underimpedance protection for generators and transformers ZGPDIS, has the
offset mho characteristic as a three zone back-up protection for detection of short
circuits in transformers and generators. The three zones have independent
measuring and settings that gives high flexibility for all types of applications.
Load encroachment characteristic is available for third zone as shown in figure 58.
jX
Operation area
en07000117.vsd
IEC07000117 V1 EN
117
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
IEC10000122-1-en.vsd
IEC10000122 V1 EN
6.1.4 Signals
Table 34: ZGPDIS Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block due to fuse failure
LDCND INTEGER 56 External load condition (loop enabler)
118
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
6.1.5 Settings
Table 36: ZGPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
ImpedanceAng 0 - 90 Deg 1 80 Impedance angle in degrees, common
for all zones
OpModeZ1 Disable-Zone - - Disable-Zone Operation mode of zone 1
Enable-Zone
Z1Fwd 0.005 - 3000.000 ohm/p 0.001 30.000 Forward positive sequence impedance
setting for zone 1
Z1Rev 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse positive sequence impedance
setting for zone 1
tZ1 0.000 - 60.000 s 0.001 0.100 Time delay to trip for zone 1
OpModeZ2 Disable-Zone - - Disable-Zone Operation mode of zone 2
Enable-Zone
Z2Fwd 0.005 - 3000.000 ohm/p 0.001 30.000 Forward positive sequence impedance
setting for zone 2
Z2Rev 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse positive sequence impedance
setting for zone 2
tZ2 0.000 - 60.000 s 0.001 0.500 Time delay to trip for zone 2
OpModeZ3 Disable-Zone - - Disable-Zone Operation mode of zone 3
Enable-Zone
Z3Fwd 0.005 - 3000.000 ohm/p 0.001 30.000 Forward positive sequence impedance
setting for zone 3
Z3Rev 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse positive sequence impedance
setting for zone 3
tZ3 0.000 - 60.000 s 0.001 1.000 Time delay to trip for zone 3
LoadEnchModZ3 Off - - Off Load enchroachment mode Off/On of
On zone 3
The execution of the different fault loops for phase-to-phase faults are executed in
parallel. The use of full scheme technique gives faster operation time compared to
the switched schemes that uses a start element to select correct voltage and current
depending on the fault type.
119
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
The distance function consists of three zones. Each zone is self polarized offset
mho characteristics with reverse offset. The operating characteristic is in
accordance to figure 60.
jx
Mho, zone3
Mho, zone2
Mho, zone1
IEC09000172_1_en.vsd
IEC09000172 V1 EN
Zone 3 can be equipped with a load encroachment function which cuts off a section
of the characteristic when enabled. The function is activated by setting the
parameter LoadEnchModZ3 to On. Enabling of the load encroachment function
increases the possibility to detect high resistive faults without interfering with the
load impedance. The algorithm for the load encroachment is located in the Load
encroachment (LEPDIS) function, where the relevant settings can be found.
Information about load encroachment from LEPDIS function to zone measurement
is sent via the input signal LDCND in binary format.
Each impedance zone can be On and Off by setting OpModex (where x is 1-3
depending on selected zone).
The zone reach for phase-to-phase fault is set individually in polar coordinates. The
impedance is set by the parameter ZxFwd and ZxRev and the corresponding
120
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
d
Fw
Z1
ImpedanceAng
IEC10000176-1-en.vsd
IEC10000176 V1 EN
Figure 61: Mho, offset mho characteristic for Zone 1 with setting parameters
Z1Fwd, Z1Rev and ImpedanceAng
The measuring loops can be time delayed individually by setting the parameter tZx
(where x is 1-3 depending on selected zone). To release the time delay, the
operation mode for the timers, OpModeZx (where x is 1-3 depending on selected
zone), has to be set to On. This is also the case for instantaneous operation.
The activation of input signal BLKZ can be made by external or internal fuse
failure function.
The mho algorithm is based on the phase comparison of a operating phasor and a
polarizing phasor. When the operating phasor leads the polarizing phasor by more
than 90 degrees, the function operates and gives a trip output.
121
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
The characteristic for offset mho is a circle where two points on the circle are the
setting parameters ZxFwd and ZxRev. The vector ZxFwd in the impedance plane
has the settable angle ImpadenceAng and the angle for ZxRev is ImpedanceAng
+180°.
The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is between 90° and 270° (figure
62). The angle will be 90° or 270° for fault location on the boundary of the circle.
The angle β for L1-to-L2 fault can be defined according to equation 30.
æ U - I L1L2 × ZxFwd ö
b = Arg çç ÷÷
è U - (- I L1L2 × Zx Re v) ø
IECEQUATION2320 V1 EN (Equation 30)
where
IL1L2·X
IL1L2·R
-IL1L 2 × ZxRev
IEC09000174_1_en.vsd
IEC09000174 V1 EN
Figure 62: Simplified offset mho characteristic and voltage vectors for phase
L1-to-L2 fault.
122
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
• Voltage range:
(0.1-1.1) x Ur
• Current range:
(0.5-30) x Ir
• Angle: at 0 degrees
and 85 degrees
6.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Loss of excitation LEXPDIS 40
Z<
SYMBOL-KK V1 EN
6.2.2 Functionality
There are limits for the low excitation of a synchronous machine. A reduction of
the excitation current weakens the coupling between the rotor and the stator. The
machine may lose the synchronism and start to operate like an induction machine.
Then, the reactive power consumption will increase. Even if the machine does not
loose synchronism it may not be acceptable to operate in this state for a long time.
Reduction of excitation increases the generation of heat in the end region of the
synchronous machine. The local heating may damage the insulation of the stator
winding and the iron core.
123
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
IEC07000031_2_en.vsd
IEC07000031 V2 EN
6.2.4 Signals
Table 39: LEXPDIS Input signals
Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRZ1 BOOLEAN 0 Block trip of zone Z1
BLKTRZ2 BOOLEAN 0 Block trip of zone Z2
124
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
6.2.5 Settings
Table 41: LEXPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationZ1 Off - - On Operation Off/On zone Z1
On
XoffsetZ1 -1000.00 - 1000.00 % 0.01 -10.00 Offset of Z1 circle top point along X axis
in % of Zbase
Z1diameter 0.01 - 3000.00 % 0.01 100.00 Diameter of imedance circle for Z1 in %
of Zbase
tZ1 0.00 - 6000.00 s 0.01 0.01 Trip time delay for Z1
OperationZ2 Off - - On Operation Off/On zone Z2
On
XoffsetZ2 -1000.00 - 1000.00 % 0.01 -10.00 Offset of Z2 circle top point along X axis
in % of Zbase
Z2diameter 0.01 - 3000.00 % 0.01 200.00 Diameter of imedance circle for Z2 in %
of Zbase
tZ2 0.00 - 6000.00 s 0.01 1.00 Trip time delay for Z2
Zposseq U posseq
=
I posseq
EQUATION1771 V1 EN (Equation 31)
125
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
Naimly:
• Offset mho circle for Z1
• Offset mho circle for Z2
• Directional blinder
UnderexitationProtection
Underexcitation protection
Restrainarea
Restrain area
R
Directional
blinder
IEC06000455-2-en.vsd
IEC06000455 V2 EN
When the apparent impedance reaches the zone Z1 this zone will operate, normally
with a short delay. The zone is related to the dynamic stability of the generator.
When the apparent impedance reaches the zone Z2 this zone will operate, normally
with a longer delay. The zone is related to the static stability of the generator.
LEXPDIS protection also has a directional blinder (supervision). See figure 64.
126
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
Offset
R
XoffsetZ1
Z (apparent impedance)
Z1 = Z - (XoffsetZ1 +
Z1diameter Z1diameter/2)
Z1 or Z2
en06000456-2.vsd
IEC06000456 V2 EN
The impedance Z1 is constructed out from the measured apparent impedance Z and
the impedance corresponding to the centre point of the impedance characteristic
(Z1 or Z2). If the amplitude of this impedance is less than the radius (diameter/2)
of the characteristic, this part of the protection will operate.
If the directional restrain is set off the impedance zone operation will start the
appropriate timer and LEXPDIS will trip after the set delay (tZ1 or tZ2).
If the directional restrain is set On the directional release function must also
operate to enable operation. A new impedance is constructed as XoffsetDirLine. If
the phase angle of this impedance is less than the set DirAngle LEXPDIS function
will be released, see figure 66.
127
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
Underexcitation Protection
Restrain area
R
XoffsetDirLine
DirAngle
Z (apparent impedance)
en06000457.vsd
IEC06000457 V1 EN
Positive tZ1
sequence Z in startZ1 t TripZ1
&
current Z1 char.
phasor
Dir.
Restrain
Dir.Restrain ON ³1
en06000458-2.vsd
IEC06000458 V3 EN
128
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
6.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Out-of-step protection OOSPPAM 78
<
6.3.2 Functionality
Out-of-step protection (OOSPPAM) function in the IED can be used both for
generator protection application as well as, line protection applications.
The main purpose of the OOSPPAM function is to detect, evaluate, and take the
required action during pole slipping occurrences in the power system.
The OOSPPAM function detects pole slip conditions and trips the generator as fast
as possible, that is after the first pole-slip if the centre of oscillation is found to be
in zone 1 which normally includes the generator and its step-up power transformer.
If the centre of oscillation is found to be further out in the power system, that is, in
zone 2, more than one pole-slip is usually allowed before the generator-transformer
unit is disconnected. If there are several out-of-step relays in the power system,
then one which finds the centre of oscillation in its zone 1 shall operate first.
129
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
IEC10000106 V1 EN
6.3.4 Signals
Table 45: OOSPPAM Input signals
Name Type Default Description
I3P GROUP - Group connection for three-phase current input
SIGNAL
U3P GROUP - Group connection for three-phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOT BOOLEAN 0 Block operation in motor direction
EXTZONE1 BOOLEAN 0 Extension of zone1 reach to zone2 settings
130
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
6.3.5 Settings
Table 47: OOSPPAM Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
OperationZ1 Off - - On Operation Zone1 On / Off
On
ReachZ1 1.00 - 100.00 - 0.01 50.00 Percentage part of total forward
impedance; defines Z1 reach
OperationZ2 Off - - On Operation Zone2 On / Off
On
tBreaker 0.000 - 1.000 s 0.001 0.000 Breaker opening time; use default 0s
value if it is unknown
131
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
1.5 ← trajectory
of Z(R, X)
to the 3rd
The 2nd pole-slip
Imaginary part (X) of Z in Ohms
-1
-1.5 -1 -0.5 0 0.5 1 1.5
Real part (R) of Z in Ohms
IEC10000109-1-en.vsd
IEC10000109 V1 EN
Figure 69: Loci of the complex impedance Z(R, X) for a typical case of
generator losing step after a short circuit that was not cleared fast
enough
Under typical, normal load conditions, when the protected generator supplies the
active and the reactive power to the power system, the complex impedance Z(R, X)
is in the 1st quadrant, point 0 in Figure 69. One can see that under a three-phase
fault conditions, the centre of oscillation is at the point of fault, point 1, which is
logical, as all three voltages are zero or near zero at that point. Under the fault
conditions the generator accelerated and when the fault has finally been cleared,
the complex impedance Z(R, X) jumped to the point 2. By that time, the generator
has already lost its step, Z(R, X) continues it way from the right-hand side to the left-
hand side, and the 1st pole-slip cannot be avoided. If the generator is not
immediately disconnected, it then continues pole-slipping see Figure 69, where two
pole-slips (two pole-slip cycles) are shown. Under out-of-step conditions, the
132
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
centre of oscillation is where the locus of the complex impedance Z(R, X) crosses
the (impedance) line connecting the points SE (Sending End), and RE (Receiving
End). The point on the SE – RE line where the trajectory of Z(R, X) crosses the
impedance line can change with time and is mainly a function of the internal
induced voltages at both ends of the equivalent two-machine system, that is, at
points SE and RE.
Rotor (power) angle δ can be thought of as the angle between the two lines,
connecting point 0 in Figure 69, that is, Z(R, X) under normal load, with the points
SE and RE, respectively. These two lines are not shown in Figure 69. Normal
values of the power angle, that is, under stable, steady-state, load conditions are
from 30 to 60 electrical degrees. It can be observed in Figure 70 that the angle
reaches 180 degrees when the complex impedance Z(R, X) crosses the impedance
line SE – RE. It then changes the sign, and continues from -180 degrees to 0
degrees, and so on. Figure 70 shows the rotor (power) angle and the magnitude of
Z(R, X) against the time for the case from Figure 69.
4
|Z| in Ohms
rotor (power)
Impedance Z in Ohm and rotor angle in radian →
0
fault 500 ms
-1 fault
occurrs
Under 3-phase fault
-2 condition rotor angle
of app. ±180 degrees
is measured ...
-3 Z(R,X) crossed
the impedance line, Z-line,
connecting points SE - RE
-4
0 200 400 600 800 1000 1200 1400
Time in milliseconds →
IEC10000110-1-en.vsd
IEC10000110 V1 EN
Figure 70: Rotor (power) angle and magnitude of the complex impedance
Z(R, X) against the time
133
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
1
SE RE
G X [Ohm]
0.8 Z(R,X) 20 ms
fault
relay after line out
- - - RE - - -
0.6 - - -- -
-- ---- ----- 4 - - pre-fault
Figure 71: A stable case where the disturbance does not make the generator
to go out-of-step
It shall be observed that in a stable case, as shown in Figure 71, where the
disturbance does not cause the generator to lose step, the complex impedance Z(R,
X) exits the lens characteristic on the same side (point 4) it entered it (point 2), and
never re-enters the lens. In a stable case, where the protected generator remains in
synchronism, the complex impedance returns to quadrant 1, and, after the
oscillations fade, it returns to the initial normal load position (point 0), or near.
134
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
X
Position of the OOS
- - - RE- - -
0.6 - - - - relay is the origin of
- - --
- -- ----
- -- -the R - X plane
- - --- Ze --
---
-
- Zone 2 -- -
0.4 X-line - - - - -
SE RE
IEC10000113-1-en.vsd
IEC10000113 V1 EN
135
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
voltage level. The impedances from the position of the out-of-step protection in the
direction of the normal load flow can be taken as forward.
The out-of-step relay, as in Figure 73 looks into the system and the impedances in
that direction are forward impedances:
• ForwardX = Xtr + Xline + Xeq (All values referred to generator voltage)
• ForwardR = Rtr + Rline + Req (All values referred to generator voltage)
Resistances are much smaller than reactances, but can in general not be neglected.
The ratio (ForwardX + ReverseX) / (ForwardR + ReverseR) determines the
inclination of the Z-line, connecting the point SE (Sending End) and RE
(Receiving End), and is typically approximately 85 degrees. While the length of the
Z-line depends on the values of ForwardX, ReverseX, ForwardR, and ReverseR,
the width of the lens is a function of the setting StartAngle.The lens is broader for
smaller values of the StartAngle, and becomes a circle for StartAngle = 90 degrees.
When the complex impedance Z(R, X) enters the lens, trouble is imminent, and a
start signal is issued. The angle recommended to form the lens is 110 or 120
degrees, because it is this rotor (power) angle where real trouble with dynamic
stability usually begins. Rotor (power) angle 120 degrees is sometimes called “the
angle of no return” because if this angle is reached under generator swings, the
generator is most likely to lose step.
136
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
fault has been cleared. Transition of the measured Z from point 1 to point 2 takes
approximately 20 ms, due to Fourier filters. The complex impedance then travels in
the direction from the right to the left, and exits the lens on the opposite side. When
the complex impedance exits the lens on the side opposite to its entrance, the 1st pole-
slip has already occurred and more pole-slips can be expected if the generator is
not disconnected. Figure 69 shows two pole-slips. Figures like Figure 69 and
Figure 71 are always possible to draw by means of the analogue output data from
the pole-slip function, and are of great help with eventual investigations of the
performance of the out-of-step function.
The maximum slip frequency fsMax in Hz where a pole-slip can be detected when
using a specific value of the setting (parameter) StartAngle (which determines the
width of the lens characteristic) is as follows. A parameter in this calculation
routine is the value of the minimum traverse time, traverseTimeMin. The minimum
traverse time determines the minimum time, the complex impedance Z(R, X) must
travel through the lens from one side to the other, in order to recognize that a pole-
slip has occurred. The value of the internal constant traverseTimeMin is a function
of the set StartAngle.For values of StartAngle <= 110°, traverseTimeMin = 50 ms.
For values StartAngle > 110°, traverseTimeMin = 40 ms. The expression which
relates the maximum slip frequency fsMax and the traverseTimeMin is as follows:
137
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
second pole-slip, if the protected machine is not already disconnected after the first
pole-slip. The measured value of slipsPerSecond (SLIPFREQ) is equal to the
average slip-frequency of the machine between the last two successive pole-slips.
Although out-of-step events are relatively rare, the out-of-step protection should
take care of the circuit breaker safety. The electro-mechanical stress to which the
breaker is exposed shall be minimized. The maximum currents flowing under out-of-
step conditions can be even greater that those for a three-phase short circuit on
generator terminals; see Figure 75. The currents flowing are highest at rotor angle
180 degrees, and smallest at 0 degrees, where relatively small currents flow. To
open the circuit breaker at 180 degrees, when not only the currents are highest, but
the two internal (that is, induced) voltages at both ends are in opposition, could be
fatal for the circuit breaker. There are two methods available to a user in order to
minimize the stress, of which the 2nd one is more advanced.
138
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
X[Ohm]
0.6 trip RE - Receiving End (infinite bus)
region
loci of Z(R, X)
0.4 3
Figure 74: The imaginary offset Mho circle represents loci of the impedance
Z(R, X) for which the rotor angle is 90 degrees
35
very high currents due
Current in kA, trip command to CB, rotor angle in rad →
← rotor angle
0
angle towards 0°
-5
0 200 400 600 800 1000 1200
Time in milliseconds →
IEC10000115-1-en.vsd
IEC10000115 V1 EN
Figure 75: Trip initiation when the break-time of the circuit breaker is known
139
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
6.3.6.5 Design
When the complex impedance Z(R, X) enters the limit-of-reach region, the
algorithm determines the direction impedance Z moves, that is, the direction the
lens is traversed and measures the time taken to traverse the lens from one side to
the other. If the traverse time is more than the limit 40 or 50 ms, a pole-slip is
declared. If the complex impedance Z(R, X) exits the lens on the same side it
entered, then it is a stable case and the protected machine is still in synchronism. If
a pole-slip has been detected, then it is determined in which zone the centre of
oscillation is located. If the number of actual pole-slips exceeds the maximum
number of allowed pole-slips in either of the zones, a trip command is issued
taking care of the circuit breaker safety.
R R
UPSRE Calculation of X X
UPSIM R and X parts
UPSMAG
of the complex Z(R,X)
positive-
IPSRE
sequence Z(R,X) NO P
IPSIM
impedance within limit of Return
Z(R, X) reach? Q
YES UCOSPHI
Z(R,X) ROTORANG
within lens NO
Function alert
characteristic?
SLIPFREQ
YES GEBMODE
Z(R,X) MOTMODE
LEFT Z(R,X) RIGHT NO
exited lens
entered lens
on the left-hand
from?
Motor losing Generator losing side?
step ? step ?
YES
Was
traverse time NO
more than
Calculation of 50 ms?
P
positive-sequence YES (pole-slip!)
active power P, Q TRIP
>= 1
reactive power Q, Number
ZONE 2 NO
rotor angle UCOSPHI
of pole-slips
ROTORANG exceeded in TRIPZ1
and
a zone? Open
UCOSPHI ROTORANG circuit
ZONE 1 TRIPZ2
breaker
safely
IEC10000116-1-en.vsd
IEC10000116 V1 EN
140
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
6.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Load encroachment LEPDIS - -
6.4.2 Functionality
Heavy load transfer is common in many power networks and may make fault
resistance coverage difficult to achieve. In such a case, Load encroachment
(LEPDIS) function can be used to enlarge the resistive setting of the
underimpedance measuring zones without interfering with the load.
141
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
IEC10000119-1-en.vsd
IEC10000119 V1 EN
6.4.4 Signals
Table 52: LEPDIS Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
6.4.5 Settings
Table 54: LEPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
RLd 0.05 - 3000.00 ohm/p 0.01 1.00 Load resistive reach in ohm/phase
ArgLd 5 - 85 Deg 1 38 Load encroachment inclination of load
angular sector
142
Technical Manual
1MRK 502 034-UEN - Section 6
Impedance protection
Each of the three measuring loops has its own load encroachment characteristic
based on the corresponding loop impedance. The load encroachment functionality
is always active but can be switched off by selecting a high setting.
RLd
ArgLd ArgLd
R
ArgLd ArgLd
RLd
IEC10000144-1-en.vsd
IEC10000144 V1 EN
The reach is limited by the minimum operation current and the distance measuring
zones.
143
Technical Manual
Section 6 1MRK 502 034-UEN -
Impedance protection
X
L1
R
L1L2
Block
3I 0 ³ 0.05
& &
&
3I 0 ³ 0.2 × Iphmax
STCNDLE
Bool to &
BLOCK integer
&
3I 0 < 0.1 10 ms 20 ms
OR & t t
IEC10000226-1-en.vsd
IEC10000226 V1 EN
144
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Four step phase overcurrent protection OC4PTOC 51/67
3I>
4
alt
4
TOC-REVA V1 EN
7.1.2 Functionality
The four step phase overcurrent protection function OC4PTOC has an inverse or
definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always
definite time delayed.
The directional function is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.
145
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.1.4 Signals
Table 57: OC4PTOC Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
BLKST3 BOOLEAN 0 Block of step 3
BLKST4 BOOLEAN 0 Block of step 4
146
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.1.5 Settings
Table 59: OC4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
DirMode1 Off - - Non-directional Directional mode of step 1 off / non-
Non-directional directional / forward / reverse
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
I1> 5 - 2500 %IB 1 1000 Phase current operate level for step1 in
% of IBase
t1 0.000 - 60.000 s 0.001 0.000 Definite time delay of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in %
of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 1
DirMode2 Off - - Non-directional Directional mode of step 2 off / non-
Non-directional directional / forward / reverse
Forward
Reverse
I2> 5 - 2500 %IB 1 500 Phase current operate level for step 2 in
% of IBase
t2 0.000 - 60.000 s 0.001 0.400 Definite time delay of step 2
DirMode3 Off - - Non-directional Directional mode of step 3 off / non-
Non-directional directional / forward / reverse
Forward
Reverse
I3> 5 - 2500 %IB 1 250 Phase current operate level for step3 in
% of IBase
t3 0.000 - 60.000 s 0.001 0.800 Definite time delay of step 3
DirMode4 Off - - Non-directional Directional mode of step 4 off / non-
Non-directional directional / forward / reverse
Forward
Reverse
Table continues on next page
147
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
148
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component
and higher harmonic current components are almost completely suppressed. If
RMS option is selected then the true RMS values is used. The true RMS value in
addition to the fundamental frequency component includes the contribution from
the current DC component as well as from higher current harmonic. The selected
current values are fed to OC4PTOC.
In a comparator, for each phase current, the DFT or RMS values are compared to
the set operation current value of the function (I1>, I2>, I3> or I4>). If a phase
current is larger than the set operation current, outputs START, STx, STL1, STL2
and STL3 are, without delay, activated. Output signals STL1, STL2 and STL3 are
common for all steps. This means that the lowest set step will initiate the
activation. The START signal is common for all three phases and all steps. It shall
be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.
Service value for individually measured phase currents are also available on the
local HMI for OC4PTOC function, which simplifies testing, commissioning and in
service operational checking of the function.
The function can be directional. The direction of the fault current is given as
current angle in relation to the voltage angle. The fault current and fault voltage for
the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
149
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN (Equation 33)
U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN (Equation 34)
U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN (Equation 35)
U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN (Equation 36)
U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN (Equation 37)
U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN (Equation 38)
150
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
Uref
2
4
Idir
IEC09000636_1_vsd
IEC09000636 V1 EN
If no blockings are given the start signals will start the timers of the step. The time
characteristic for step 1 and 4 can be chosen as definite time delay or inverse time
characteristic. Step 2 and 3 are always definite time delayed. A wide range of
standardized inverse time characteristics is available. The possibilities for inverse
time characteristics are described in section "Inverse time characteristics".
All four steps in OC4PTOC can be blocked from the binary input BLOCK. The
binary input BLKSTx (x=1, 2, 3 or 4) blocks the operation of respective step.
151
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Four step residual overcurrent EF4PTOC IN 51N/67N
protection
4
alt
4
TEF-REVA V1 EN
7.2.2 Functionality
The four step residual overcurrent protection (EF4PTOC) has a settable inverse or
definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always
definite time delayed.
152
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.2.4 Signals
Table 63: EF4PTOC Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for polarizing voltage
SIGNAL inputs
I3PPOL GROUP - Three phase group signal for polarizing current
SIGNAL inputs
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1 (start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (start and trip)
153
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.2.5 Settings
Table 65: EF4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
polMethod Voltage - - Voltage Type of polarization
Current
Dual
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization in
% of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization in
% of IBase
RNPol 0.50 - 1000.00 ohm 0.01 5.00 Real part of source Z to be used for
current polarisation
XNPol 0.50 - 3000.00 ohm 0.01 40.00 Imaginary part of source Z to be used for
current polarisation
IN>Dir 1 - 100 %IB 1 10 Residual current level for direction
release in % of IBase
2ndHarmStab 5 - 100 % 1 20 Second harmonic restrain operation in %
of IN amplitude
DirMode1 Off - - Non-directional Directional mode of step 1 (off, non-
Non-directional directional, forward, reverse)
Forward
Reverse
Table continues on next page
154
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
155
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
156
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.
The function always uses Residual Current (3I0) for its operating quantity. The
residual current can be:
157
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
PCM600). In such case the pre-processing block will calculate 3I0 from the
first three inputs into the pre-processing block by using the following formula:
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of
the fundamental frequency component of the residual current is derived. The
phasor magnitude is used within the EF4PTOC protection to compare it with the
set operation current value of the four steps (IN1>, IN2>, IN3> or IN4>). If the
residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This
signal will, without delay, activate the output signal STINx (x=step 1-4) for this
step and a common START signal.
The function can be set to use voltage polarizing, current polarizing or dual polarizing.
Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage
-3U0 as polarizing quantity U3P. This voltage can be:
where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
Note! In order to use this all three phase-to-earth voltages must be connected to three IED VT inputs.
158
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor
of the fundamental frequency component of the residual voltage is derived. This
phasor is used together with the phasor of the operating current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a
minimum level defined by setting parameter UpolMin.
It shall be noted that –3U0 is used to determine the location of the earth fault. This
insures the required inversion of the polarizing voltage within the earth-fault function.
Current polarizing
When current polarizing is selected the function will use the residual current (3I0)
as polarizing quantity IPol. This current can be:
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
159
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
which will be then used, together with the phasor of the operating current, in order
to determine the direction to the earth fault (Forward/Reverse). In order to enable
current polarizing the magnitude of polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.
Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the
voltage based and current based polarizing in accordance with the following formula:
Then the phasor of the total polarizing voltage UTotPol will be used, together with
the phasor of the operating current, to determine the direction of the earth fault
(Forward/Reverse).
The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx(where x
indicates the relevant step within the protection) to provide external directional
control (that is, torque control) by for example using one of the following functions
if available in the IED:
The base quantities are entered as global settings for all functions in the IED. Base
current (IBase) shall be entered as rated phase current of the protected object in
primary amperes. Base voltage (UBase) shall be entered as rated phase-to-phase
voltage of the protected object in primary kV.
160
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:
Simplified logic diagram for one residual overcurrent step is shown in figure 83.
Characteristn=DefTime tx
|IOP| TRINx
a OR
a>b
INx> b
AND
STINx
Inverse
BLKSTx
BLOCK Characteristn=Inverse
2ndH_BLOCK_Int
OR
HarmRestrainx=Disabled
DirModex=Off OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
IEC09000638_1_en.vsd
IEC09000638 V1 EN
Figure 83: Simplified logic diagram for residual overcurrent step n= step 1 and
4
The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, STINx and TRINx, can be blocked from the binary
input BLKSTn.
161
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
The protection has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the parameter setting
polMethod. The polarizing quantity will be selected by the function in one of the
following three ways:
The operating and polarizing quantity are then used inside the directional element,
as shown in figure 84, in order to determine the direction of the earth fault.
Reverse
Area
0.6·IN>Dir
AngleRCA Upol=-3Uo
IN>Dir
Forward
Area
Iop=3Io
IEC07000066-3-en.vsd
IEC07000066 V3 EN
162
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
163
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
|Iop|
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b
AND STFW
IN>Dir b
FORWARD_Int
X
0.4
FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin
Characteristic
Directional
polMethod=Dual UPol IPolMin
T
Iop
polMethod=Current 0.0 F
OR
UTotPol
IPol AND REVERSE_Int
T RVS
0.0 F
UIPol STAGE1_DIR_Int
RNPol Complex X T STAGE2_DIR_Int
XNPol Number 0.0 F STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND
IEC07000067-4-en.vsd
IEC07000067 V4 EN
Figure 85: Simplified logic diagram for directional supervision element with integrated directional
comparison step
164
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Sensitive directional residual over SDEPSDE - 67N
current and power protection
7.3.2 Functionality
In isolated networks or in networks with high impedance earthing, the earth fault
current is significantly smaller than the short circuit currents. In addition to this, the
magnitude of the fault current is almost independent on the fault location in the
network. The protection can be selected to use either the residual current or
residual power component 3U0·3I0·cos j, for operating quantity. There is also
available one non-directional 3I0 step and one non-directional 3U0 overvoltage
tripping step.
165
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.3.4 Signals
Table 69: SDEPSDE Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKUN BOOLEAN 0 Blocks the non-directional voltage residual outputs
166
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.3.5 Settings
Table 71: SDEPSDE Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode 3I0Cosfi - - 3I0Cosfi Selection of operation mode for protection
3I03U0Cosfi
3I0 and fi
DirMode Forward - - Forward Direction of operation forward or reverse
Reverse
RCADir -179 - 180 Deg 1 -90 Relay characteristic angle RCA
RCAComp -10.0 - 10.0 Deg 0.1 0.0 Relay characteristic angle compensation
ROADir 0 - 90 Deg 1 90 Relay open angle ROA used as release
in phase mode
INCosPhi> 0.25 - 200.00 %IB 0.01 1.00 Set level for 3I0cosPhi, directional
residual overcurrent, in % of IBase
SN> 0.25 - 200.00 %SB 0.01 10.00 Set level for 3I0U0cosPhi, starting
inverse time count, in % of SBase
INDir> 0.25 - 200.00 %IB 0.01 5.00 Set level for directional residual
overcurrent protection, in % of IBase
tDef 0.000 - 60.000 s 0.001 0.100 Definite time delay directional residual
overcurrent
SRef 0.03 - 200.00 %SB 0.01 10.00 Reference value of residual power for
inverse time count, in % of SBase
kSN 0.00 - 2.00 - 0.01 0.10 Time multiplier setting for directional
residual power mode
OpINNonDir> Off - - Off Operation of non-directional residual
On overcurrent protection
INNonDir> 1.00 - 400.00 %IB 0.01 10.00 Set level for non-directional residual
overcurrent, in % of IBase
tINNonDir 0.000 - 60.000 s 0.001 1.000 Time delay for non-directional residual
overcurrent
TimeChar ANSI Ext. inv. - - IEC Norm. inv. Operation curve selection for IDMT
ANSI Very inv. operation
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
tMin 0.000 - 60.000 s 0.001 0.040 Minimum operate time for IEC IDMT
curves
Table continues on next page
167
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from pre-
processor blocks.
The sensitive directional earth fault protection has the following sub-functions
included:
168
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
φ is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (φ=ang(3I0)-ang(Uref) ).
Uref = -3U0 ejRCADIr. RCADir is normally set equal to 0 in a high impedance
earthed network with a neutral point resistor as the active current component is
appearing out on the faulted feeder only. RCADir is set equal to -90° in an isolated
network as all currents are mainly capacitive. The function operates when 3I0·cos φ
gets larger than the set value.
RCADir = 0 , ROADir = 0
3I0
ϕ = ang(3I0 ) − ang(3Uref )
−3U0 = Uref
3I0 ⋅ cosϕ
IEC06000648-3-en.vsd
IEC06000648 V3 EN
Uref
RCADir = −90 , ROADir = 90
3I0
3I0 ⋅ cos ϕ
−3U0
IEC06000649_3_en.vsd
IEC06000649 V3 EN
169
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
For trip, both the residual current 3I0·cos φ and the release voltage 3U0, must be
larger than the set levels: INCosPhi> and UNRel>.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated. The trip from this sub-function has definite time
delay.
There is a possibility to increase the operate level for currents where the angle φ is
larger than a set value as shown in figure 89. This is equivalent to blocking of the
function if φ > ROADir. This option is used to handle angle error for the instrument
transformers.
RCADir = 0o
3I0
Operate area
j
-3U0 = Uref
3I0 × cos j
ROADir
IEC06000650_2_en.vsd
IEC06000650 V2 EN
170
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
RCADir = 0º
Operate area
-3U0 =Uref
Instrument
transformer a
RCAcomp
angle error
Characteristic after
angle compensation
en06000651.vsd
IEC06000651 V2 EN
φ is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (φ=ang(3I0)—ang(Uref) ).
Uref = -3U0 e-jRCA. The function operates when 3I0 · 3U0 · cos φ gets larger than
the set value.
For trip, both the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the
release voltage 3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN are activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction
is defined as 3I0 · 3U0·cos (φ + 180°) ³ the set value.
This variant has the possibility of choice between definite time delay and inverse
time delay.
171
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
The function will operate if the residual current is larger that the set value and the
angle φ = ang(3I0)-ang(Uref) is within the sector RCADir ± ROADir
RCADir = 0º
ROADir = 80º
Operate area
3I0
80 -3U0
en06000652.vsd
IEC06000652 V2 EN
For trip, both the residual current 3I0 and the release voltage 3U0, shall be larger
than the set levels INDir> and UNREL> and the angle φ shall be in the set sector
ROADir and RCADir.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated.
172
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
For all the directional functions there are directional start signals STFW: fault in
the forward direction, and STRV: start in the reverse direction. Even if the
directional function is set to operate for faults in the forward direction a fault in the
reverse direction will give the start signal STRV. Also if the directional function is
set to operate for faults in the reverse direction a fault in the forward direction will
give the start signal STFW.
This function will measure the residual current without checking the phase angle.
The function will be used to detect cross-country faults. This function can serve as
alternative or back-up to distance protection with phase preference logic.
This variant shall have the possibility of choice between definite time delay and
inverse time delay. The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set levels (INNonDir>).
When the function is activated binary output signal STNDIN is activated. If the
activation is active after the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN are activated.
The directional function shall be released when the residual voltage gets higher
than a set level.
There shall also be a separate trip, with its own definite time delay, from this set
voltage level.
For trip, the residual voltage 3U0 shall be larger than the set levels (UN>).
Trip from this function can be blocked from the binary input BLKUN.
When the function is activated binary output signal STUN is activated. If the
activation is active after the set delay tUNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 92.
173
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
INNonDir> STNDIN
t TRNDIN
UN> STUN
t TRUN
OpMODE=3I0cosfi
IN>
&
INcosPhi>
OpMODE=3I03U0cosfi
INUNcosPhi> t
SN
& TRDIRIN
Phi in RCA +- ROA
TimeChar = InvTime
&
OpMODE=3I0 and fi
&
TimeChar = DefTime
DirMode = Reverse
&
Reverse STRV
IEC09000147-2-en.vsd
IEC09000147 V2 EN
Figure 92: Simplified logical diagram of the sensitive earth-fault current protection
174
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
175
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Thermal overload protection, two time TRPTTR 49
constants
SYMBOL-A V1 EN
7.4.2 Functionality
If a power transformer or generator reaches very high temperatures the equipment
might be damaged. The insulation within the transformer/generator will have
forced ageing. As a consequence of this the risk of internal phase-to-phase or phase-
to-earth faults will increase. High temperature will degrade the quality of the
transformer/generator insulation.
The thermal overload protection estimates the internal heat content of the transformer/
generator (temperature) continuously. This estimation is made by using a thermal
model of the transformer/generator with two time constants, which is based on
current measurement.
Two warning levels are available. This enables actions in the power system to be
done before dangerous temperatures are reached. If the temperature continues to
increase to the trip value, the protection initiates a trip of the protected transformer/
generator.
176
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.4.4 Signals
177
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.4.5 Settings
Table 77: TRPTTR Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IRef 10.0 - 1000.0 %IB 1.0 100.0 Reference current in % of IBase
IBase1 30.0 - 250.0 %IB 1.0 100.0 Base current IBase1 without cooling
input in % of IBase
IBase2 30.0 - 250.0 %IB 1.0 100.0 Base current IBase2 with cooling input in
% of IBase
Tau1 1.0 - 500.0 Min 1.0 60.0 Time constant without cooling input
Tau2 1.0 - 500.0 Min 1.0 60.0 Time constant with cooling input
IHighTau1 30.0 - 250.0 %IB1 1.0 100.0 Current setting for rescaling TC1 by TC1-
IHIGH
Tau1High 5 - 2000 %tC1 1 100 Multiplier to TC1 when current is >IHIGH-
TC1
ILowTau1 30.0 - 250.0 %IB1 1.0 100.0 Current setting for rescaling TC1 by TC1-
ILOW
Tau1Low 5 - 2000 %tC1 1 100 Multiplier to TC1 when current is <ILOW-
TC1
IHighTau2 30.0 - 250.0 %IB2 1.0 100.0 Current setting for rescaling TC2 by TC2-
IHIGH
Tau2High 5 - 2000 %tC2 1 100 Multiplier to TC2 when current is >TC2-
IHIGH
ILowTau2 30.0 - 250.0 %IB2 1.0 100.0 Current setting for rescaling TC2 by TC2-
ILOW
Tau2Low 5 - 2000 %tC2 1 100 Multiplier to TC2 when current is <ILOW-
TC2
ITrip 50.0 - 250.0 %IBx 1.0 110.0 Steady state operate current level
Alarm1 50.0 - 99.0 %Itr 1.0 80.0 First alarm level
Alarm2 50.0 - 99.0 %Itr 1.0 90.0 Second alarm level
ResLo 10.0 - 95.0 %Itr 1.0 60.0 Lockout reset level
Warning 1.0 - 500.0 Min 0.1 30.0 Time setting, below which warning would
be set
178
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
From the largest of the three phase currents a relative final temperature (heat
content) is calculated according to the expression:
2
æ I ö
Q final =ç ÷÷
ç I ref
è ø
EQUATION1171 V1 EN (Equation 45)
where:
I is the largest phase current
Iref is a given reference current
If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current a start output signal START is activated.
179
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
If Q final > Q n
EQUATION1172 V1 EN (Equation 46)
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø
EQUATION1173 V1 EN (Equation 47)
If Q final < Qn
EQUATION1174 V1 EN (Equation 48)
Dt
Qn = Q final - ( Q final - Q n -1 ) × e
-
t
where:
Qn is the calculated present temperature
When the transformer temperature reaches any of the set alarm levels Alarm1 or
Alarm2 the corresponding output signals ALARM1 or ALARM2 are activated.
When the temperature of the object reaches the set trip level which corresponds to
continuous current equal to ITrip the output signal TRIP is activated.
There is also a calculation of the present time to operation with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1176 V1 EN (Equation 50)
The calculated time to trip can be monitored as it is exported from the function as a
real figure TTRIP.
180
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the temperature of the object is above the set lockout release temperature
setting ResLo.
The time to lockout release is calculated, That is, a calculation of the cooling time
to a set value.
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q - Q
è final n ø
EQUATION1177 V1 EN (Equation 51)
In the above equation, the final temperature is calculated according to equation 45.
Since the transformer normally is disconnected, the current I is zero and thereby
the Θfinal is also zero. The calculated component temperature can be monitored as it
is exported from the function as a real figure, TRESLO.
When the current is so high that it has given a start signal START, the estimated
time to trip is continuously calculated and given as analogue output TTRIP. If this
calculated time get less than the setting time Warning, set in minutes, the output
WARNING is activated.
181
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
I3P
Calculation
of final
temperature
ALARM1
Actual Temp >
Alarm1,Alarm2
ALARM2
Temp
S LOCKOUT
Binary input:
Forced cooling R
Management of
On/Off
setting
parameters: Tau Actual Temp
Tau used
< Recl
Temp
TTRIP
Calculation
of time to
WARNING if time to trip < set value
trip
Calculation
of time to TRESLO
reset of
lockout
IEC08000040-2-en.vsd
IEC08000040 V2 EN
182
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
Operate time: Ip = load current before overload IEC 60255–8, class 5 + 200
occurs ms
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 52)
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
7.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Breaker failure protection CCRBRF 50BF
3I>BF
SYMBOL-U V1 EN
7.5.2 Functionality
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case the own breaker failure to open. CCRBRF can be current based,
contact based, or an adaptive combination of these two principles.
A current check with extremely short reset time is used as check criterion to
achieve a high security against unnecessary operation.
A contact check criteria can be used where the fault current through the breaker is
small.
Breaker failure protection (CCRBRF) current criteria can be fulfilled by one or two
phase currents, or one phase current plus residual current. When those currents
183
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
exceed the user defined settings, the function is activated. These conditions
increase the security of the back-up trip command.
IEC09000272_1_en.vsd
IEC09000272 V1 EN
7.5.4 Signals
Table 81: CCRBRF Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start of breaker failure protection
function
CBCLDL1 BOOLEAN 1 Circuit breaker closed in phase L1
CBCLDL2 BOOLEAN 1 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 1 Circuit breaker closed in phase L3
184
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.5.5 Settings
Table 83: CCRBRF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
FunctionMode Current - - Current Detection principle for back-up trip
Contact
Current&Contact
BuTripMode 2 out of 4 - - 1 out of 3 Back-up trip mode
1 out of 3
1 out of 4
RetripMode Retrip Off - - Retrip Off Operation mode of re-trip logic
CB Pos Check
No CBPos Check
IP> 5 - 200 %IB 1 10 Operate phase current level in % of IBase
IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of re-trip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip
185
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
The start signal is general for all three phases. A re-trip attempt can be made after a
set time delay. The re-trip function can be done with or without current or contact
check. With the current check the re-trip is only performed if the current through
the circuit breaker is larger than the operate current level. With contact check the re-
trip is only performed if breaker is indicated as closed.
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, both by detection of low RMS current and by a special
adapted algorithm. The special algorithm enables a very fast detection of successful
breaker opening, that is, fast resetting of the current measurement. If the current
detection has not detected breaker opening before the back-up timer has run its
time a back-up trip is initiated.
Current
AND
BLOCK
Current & t1
STIL1
Contact t
AND AND OR
START
OR
TRRET
OR
AND AND
CBCLD
Contact
L2 L3
en08000007.vsd
IEC08000007 V1 EN
186
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
Internal logical signals STIL1, STIL2, STIL3 have logical value 1 when current in
respective phase has magnitude larger than setting parameter IP>.
Internal logical signal STN has logical value 1 when neutral current has magnitude
larger than setting parameter IN>.
7.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Pole discordance protection CCRPLD 52PD
PD
SYMBOL-S V1 EN
7.6.2 Functionality
Circuit breakers and disconnectors can end up with the poles in different positions
(close-open), due to electrical or mechanical failures. This can cause negative and
187
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
zero sequence currents which cause thermal stress on rotating machines and can
cause unwanted operation of zero sequence or negative sequence current functions.
Normally the own breaker is tripped to correct such a situation. If the situation
persists the surrounding breakers should be tripped to clear the unsymmetrical load
situation.
The pole discordance function operates based on information from the circuit
breaker logic with additional criteria from unsymmetrical phase currents when
required.
7.6.4 Signals
Table 88: CCRPLD Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
CLOSECMD BOOLEAN 0 Close order to CB
OPENCMD BOOLEAN 0 Open order to CB
EXTPDIND BOOLEAN 0 Pole discordance signal from CB logic
188
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.6.5 Settings
Table 90: CCRPLD Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tTrip 0.000 - 60.000 s 0.001 0.300 Time delay between trip condition and
trip signal
ContSel Off - - Off Contact function selection
PD signal from CB
CurrSel Off - - Off Current function selection
CB oper monitor
Continuous monitor
CurrUnsymLevel 0 - 100 % 1 80 Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel 0 - 100 %IB 1 10 Current magnitude for release of the
function in % of IBase
189
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
circuit breaker
en05000287.vsd
IEC05000287 V2 EN
This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.
BLOCK
ContSel
AND
EXTPDIND
tTrip 150 ms
t TRIP
AND
OR
CLOSECMD tTrip+200 ms
OR
OPENCMD
CurrSel AND
Unsymmetrical
current detection
IEC08000014-2-en.vsd
IEC08000014 V2 EN
Figure 99: Simplified block diagram of pole discordance function - contact and
current based
The pole discordance protection is blocked if the input signal BLOCK is high.
190
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
The BLOCK signal is a general purpose blocking signal of the pole discordance
protection. It can be connected to a binary input in the IED in order to receive a
block command from external devices or can be software connected to other
internal functions in the IED itself in order to receive a block command from
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
If the pole discordance protection is enabled, then two different criteria can
generate a trip signal TRIP:
If one or two poles of the circuit breaker have failed to open or to close (pole
discordance status), then the function input EXTPDIND is activated from the pole
discordance signal in figure 98. After a settable time tTrip, a 150 ms trip pulse
command TRIP is generated by the pole discordance function.
• any phase current is lower than CurrUnsymLevel of the highest current in the
three phases.
• the highest phase current is greater than CurrRelLevel of IBase.
The pole discordance protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs
can be connected to terminal binary inputs if the information are generated from
the field (that is from auxiliary contacts of the close and open push buttons) or may
be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).
191
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.7.1 Functionality
The directional over-/under-power protection GOPPDOP/GUPPDUP can be used
wherever a high/low active, reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check the direction of active or
reactive power flow in the power system. There are a number of applications where
such functionality is needed. Some of them are:
Each function has two steps with definite time delay. Reset times for both steps can
be set as well.
7.7.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Directional overpower protection GOPPDOP 32
P>
DOCUMENT172362-IMG158942
V1 EN
192
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
IEC08000506-2-en.vsd
IEC08000506 V2 EN
7.7.2.3 Signals
Table 94: GOPPDOP Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
193
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.7.2.4 Settings
Table 96: GOPPDOP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - OverPower Operation mode 1
OverPower
Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % of
calculated power base value
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
OpMode2 Off - - OverPower Operation mode 2
OverPower
Power2 0.0 - 500.0 % 0.1 1.0 Power setting for stage 2 in % of
calculated power base value
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
194
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.7.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Directional underpower protection GUPPDUP 37
P<
SYMBOL-LL V1 EN
IEC08000507-2-en.vsd
IEC08000507 V2 EN
195
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.7.3.3 Signals
Table 100: GUPPDUP Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
7.7.3.4 Settings
Table 102: GUPPDUP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - UnderPower Operation mode 1
UnderPower
Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % of
calculated power base value
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
OpMode2 Off - - UnderPower Operation mode 2
UnderPower
Power2 0.0 - 500.0 % 0.1 1.0 Power setting for stage 2 in % of
calculated power base value
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
196
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
197
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC09000018-2-en.vsd
IEC09000018 V2 EN
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 106.
198
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
If the measured power drops under the (Power1(2) - hysteresis) value, the over-
power function will reset after 0.06 seconds. If the measured power comes over the
(Power1(2) + hysteresis) value, the under-power function will reset after 0.06
seconds. The reset means that the start signal will drop out and that the timer of the
stage will reset.
199
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 62)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
TD
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92 in case of slow operating functions.
7.8.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Accidental energizing protection for AEGGAPC U<I> 50AE
synchronous generator
200
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
7.8.2 Functionality
Inadvertent or accidental energizing of off-line generators has occurred often
enough due to operating errors, breaker head flashovers, control circuit
malfunctions, or a combination of these causes. Inadvertently energized generator
operates as induction motor drawing a large current from the system. The voltage
supervised overcurrent protection is used to protect the inadvertently energized
generator.
IEC09000783-1-en.vsd
IEC09000783 V1 EN
201
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.8.5 Settings
Table 110: AEGGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
I> 2 - 900 %IB 1 120 Operate phase current level in % of IBase
tOC 0.000 - 60.000 s 0.001 0.030 Trip time delay for over current level
ArmU< 2 - 200 %UB 1 50 Under-voltage level to arm protection in
% of UBase
tArm 0.000 - 60.000 s 0.001 5.000 Time delay to arm protection with U< level
DisarmU> 2 - 200 %UB 1 80 Over-voltage level to disarm protection in
% of UBase
tDisarm 0.000 - 60.000 s 0.001 0.500 Time delay to disarm protection with U>
level
When the maximum phase-to-phase voltage is less than the ArmU< for the period
tArm, it is ensured that the generator is off-line. The ARMED signal will initiate
the overcurrent function. If the calculated maximum current of the three phases is
larger than I> for the period tOC then the TRIP signal becomes activated. Also
START signal becomes activated when overcurrent is detected.
When the maximum phase-to-phase voltage is larger than DisarmU> for the period
tDisarm, it is ensured generator is on line. During this state, undervoltage operation
is disarmed, blocking the overcurrent operation and thus the function becomes
inoperative.
BLOCK input can be used to block AEGGAPC . In addition, the BLKTR input that
blocks the TRIP signal is also present. The input BLKTR can be used if
AEGGAPC is to be used only for monitoring purposes.
202
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
Imax_DFT
a
a>b
I> b
tOC
AND TRIP
Operation = ON t
BLOCK
START
ARMED
Uph-ph_max_DFT tArm
a
a<b t
ArmU< b AND
S OUT
ON - Delay
R NOUT
tDisarm
a
t OR
a>b
DisarmU> b
ON - Delay
IEC09000784-2-en.vsd
IEC09000784 V2 EN
203
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.9.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Negative sequence time overcurrent NS2PTOC 2I2> 46I2
protection for machines
7.9.2 Functionality
Negative-sequence time overcurrent protection for machines NS2PTOC is intended
primarily for the protection of generators against possible overheating of the rotor
caused by negative sequence component in the stator current.
The negative sequence currents in a generator may, among others, be caused by:
• Unbalanced loads
• Line to line faults
• Line to earth faults
• Broken conductors
• Malfunction of one or more poles of a circuit breaker or a disconnector
NS2PTOC can also be used as a backup protection, that is, to protect the generator
in the event line protections or circuit breakers fail to clear unbalanced system faults.
where:
I2 is negative sequence current expressed in per unit of the rated
generator current
t is operating time in seconds
K is a constant which depends of the generators size and design
NS2PTOC has a wide range of K settings and the sensitivity and capability of
detecting and tripping for negative sequence currents down to the continuous
capability of a generator.
204
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
IEC08000359-2-en.vsd
IEC08000359-1-EN V2 EN
7.9.4 Signals
Table 113: NS2PTOC Input signals
Name Type Default Description
I3P GROUP - Group connection for neg seq.
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
205
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.9.5 Settings
Table 115: NS2PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tAlarm 0.00 - 6000.00 s 0.01 3.00 Time delay for Alarm (operated by
START signal), in sec
OpStep1 Off - - On Enable execution of step 1
On
I2-1> 3 - 500 %IB 1 10 Step 1 Neg. Seq. Current pickup level, in
% of IBase
CurveType1 Definite - - Definite Selection of definite or inverse time-
Inverse characteri. for step 1
t1 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 1, in sec
tResetDef1 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of
step 1, in sec
K1 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generator
for step 1, in sec
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay of
step 1, in sec
t1Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 1, in sec
ResetMultip1 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K1, defines reset
time of inverse curve
OpStep2 Off - - On Enable execution of step 2
On
I2-2> 3 - 500 %IB 1 10 Step 2 Neg. Seq. Current pickup level, in
% of IBase
t2 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 2, in sec
tResetDef2 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer of
step 2, in sec
206
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
To avoid oscillation in the output signals, a certain hysteresis has been included.
For both steps, the reset ratio is 0.97.
Step 1 of NS2PTOC can operate in the Definite Time (DT) or Inverse Time
(IDMT) mode depending on the selected value for the CurveType1 parameter. If
CurveType1= Definite, NS2PTOC operates with a Definite Time Delay
characteristic and if CurveType1 = Inverse, NS2PTOC operates with an Inverse
Time Delay characteristic. Step 2 can only operate in the Definite Time (DT)
mode. The characteristic defines the time period between the moment when
measured negative sequence current exceeds the set start levels in parameter I2-1>
or I2-2> until the trip signal is initiated.
K = I 2 2t
EQUATION2112 V1 EN
Where:
I2 is negative sequence current expressed in per unit of the rated generator current
207
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
Operate
time
t1Max
(Default= 1000 s)
t1Min
(Default= 5 s)
K1
Current I2-1>
IEC09000691-2-en.vsd
IEC09000691 V2 EN
For a detailed description of inverse time characteristic, see chapter "Inverse time
characteristics".
ResetTime [ s ] =
ResetMultip
⋅ K1
I 2
NS − 1
I Start
EQUATION2111 V2 EN (Equation 63)
Where
INS is the measured negative sequence current
ResetMultip is multiplier of the generator capability constant K equal to setting K1 and thus
defines reset time of inverse time characteristic
The trip start levels Current I2-1> and I2-2> of NS2PTOC are freely settable over
a range of 3 to 500 % of rated generator current IBase. The wide range of start
setting is required in order to be able to protect generators of different types and sizes.
208
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
After start, a certain hysteresis is used before resetting NS2PTOC. For both steps
the reset ratio is 0.97.
The alarm function is operated by START signal and used to warn the operator for
an abnormal situation, for example, when generator continuous negative sequence
current capability is exceeded, thereby allowing corrective action to be taken
before removing the generator from service. A settable time delay tAlarm is
provided for the alarm function to avoid false alarms during short-time unbalanced
conditions.
DT time
selected t1
TR1
Negative sequence current OR
a
a>b
b
I2-1> ST1
AND
Inverse
Operation=ON
Inverse time
BLKST1 selected
BLOCK
IEC08000466-2-en.vsd
IEC08000466-1-EN V2 EN
Figure 107: Simplified logic diagram for step 1 of Negative sequence time
overcurrent protection for machines (NS2PTOC)
ST1
START
ST2 OR
tAlarm ALARM
TR1
TRIP
TR2 OR
IEC09000690-2-en.vsd
IEC09000690 V2 EN
Figure 108: Simplified logic diagram for the START, ALARM and TRIP signals
for NS2PTOC
209
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
I 22t = K
I 22t = K
7.10.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Voltage-restrained time overcurrent VR2PVOC U<I> 51V
protection
7.10.2 Functionality
Voltage-restrained time overcurrent protection (VR2PVOC) function is
recommended as a backup protection for generators.
The overcurrent protection feature has a settable current level that can be used
either with definite time or inverse time characteristic. Additionally, it can be
voltage controlled/restrained.
210
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
One undervoltage step with definite time characteristic is also available with the
function in order to provide funcionality for overcurrent protection with
undervoltage seal-in.
IEC10000118-1-en.vsd
IEC10000118 V1 EN
7.10.4 Signals
Table 119: VR2PVOC Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function both stages
BLKOC BOOLEAN 0 Block of voltage restraint overcurrent stage (ANSI
51V)
BLKUV BOOLEAN 0 Block of under voltage function
211
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
7.10.5 Settings
Table 121: VR2PVOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartCurr 2.0 - 5000.0 %IB 1.0 120.0 Start current level in % of IBase
Characterist ANSI Ext. inv. - - IEC Norm. inv. Time delay curve type for 51V
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
tDef_OC 0.00 - 6000.00 s 0.01 0.50 Independent (definite) time delay for OC
k 0.05 - 999.00 - 0.01 1.00 Time multiplier for the IDMT curves
tMin 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curves
Operation_UV Off - - Off Operation of under-voltage stage (ANSI
On 27) Off / On
StartVolt 2.0 - 100.0 %UB 0.1 50.0 Operate undervoltage level for UV in %
of Ubase
tDef_UV 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of UV
EnBlkLowV Off - - On Enable internal low voltage level
On blocking for UV
BlkLowVolt 0.0 - 5.0 %UB 0.1 3.0 Internal low voltage blocking level for UV
in % of Ubase
212
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
The parameter settings for the base quantities, which represent the base (100%) for
start levels of all measuring stages shall be entered as setting parameters for
VR2PVOC function.
Common base IED values for primary current (IBase), primary voltage (UBase),
and primary power (SBase) are set in Global base values for the settings function
GBASVAL. Setting GlobalBaseSel is used to select a GBASVAL function for the
reference of base values.
IBase shall be entered as rated phase current of the protected object in primary
amperes.
The overcurrent step simply compares the magnitude of the measured current
quantity with the set start level. The overcurrent step starts if the magnitude of the
measured current quantity is bigger than the set level.
213
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
StartCurr
VDepFact * StartCurr
0,25 UHighLimit
UBase
IEC10000123-1-en.vsd
IEC10000123 V1 EN
Figure 110: Example for current start level variation as function of measured
voltage magnitude in Slope mode of operation
StartCurr
VDepFact * StartCurr
UHighLimit UBase
IEC10000124-1-en.vsd
IEC10000124 V1 EN
Figure 111: Example for current start level variation as function of measured
voltage magnitude in Step mode of operation
This feature simply changes the set overcurrent start level in accordance with
magnitude variations of the measured voltage. This feature also affects the start
current value for the calculation of operate times for IDMT curves (the overcurrent
with IDMT curve operates faster during low voltage conditions).
214
Technical Manual
1MRK 502 034-UEN - Section 7
Current protection
DEF time
selected
TROC
OR
MaxPhCurr
a STOC
a>b
b
StartCurr
X Inverse
Inverse
Voltage time
control or selected
restraint
feature
MinPh-PhVoltage
IEC10000214-1-en.vsd
IEC10000214 V1 EN
DEF time
selected TRUV
MinPh-phVoltage a
b>a
b STUV
AND
StartVolt
Operation_UV=On
BLKUV
IEC10000213-1-en.vsd
IEC10000213 V1 EN
The undervoltage step simply compares the magnitude of the measured voltage
quantity with the set start level. The undervoltage step starts if the magnitude of the
measured voltage quantity is smaller than the set level.
The start signal starts a definite time delay. If the value of the start signal is one for
longer than the set time delay, the undervoltage step sets its trip signal to one.
215
Technical Manual
Section 7 1MRK 502 034-UEN -
Current protection
This undervoltage with additional ACT logic can be used to provide funcionality
for overcurrent protection with undervoltage seal-in.
216
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
8.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Two step undervoltage protection UV2PTUV 27
2U<
SYMBOL-R-2U-GREATER THAN
V1 EN
8.1.2 Functionality
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed
back-up to primary protection.
UV2PTUV has two voltage steps, where step 1 is settable as inverse or definite
time delayed. Step 2 is always definite time delayed.
IEC09000285_1_en.vsd
IEC09000285 V1 EN
217
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
8.1.4 Signals
Table 126: UV2PTUV Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
8.1.5 Settings
Table 128: UV2PTUV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required to operate (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1< 1 - 100 %UB 1 70 Voltage start value (DT & IDMT) in % of
UBase for step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definite time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
Table continues on next page
218
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
219
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for step 1 can be either definite time delay (DT) or inverse time
delay (IDMT). Step 2 is always definite time delay (DT). For the inverse time
delay two different modes are available; inverse curve A and inverse curve B.
k
t=
æ U < -U ö
ç ÷
è U< ø
EQUATION1431 V1 EN (Equation 66)
k × 480
t= 2.0
+ 0.055
æ U < -U ö
ç 32 × - 0.5 ÷
è U< ø
EQUATION1432 V1 EN (Equation 67)
220
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
The lowest voltage is always used for the inverse time delay integration. The
details of the different inverse time characteristics are shown in section 20.3
"Inverse time characteristics".
Trip signal issuing requires that the undervoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by some special voltage level dependent time curves for the
inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, the corresponding start output is reset.
8.1.7.3 Blocking
8.1.7.4 Design
221
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
Step1
Time integrator TR1
OR
TRIP
MinVoltSelect t1
Comparator
U < U2< Phase1
Voltage Phase ST2
Selector OR
Comparator OpMode2 Phase2
U < U2< 1 out of 3
2 out of 3
Phase3 Start
Comparator 3 out of 3
&
U < U2< Trip
Output
START Logic
Step2
Timer
TRIP TR2
t2 OR
OR START
TRIP
OR
IEC08000016-2-en.vsd
IEC08000016 V2 EN
222
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
8.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Two step overvoltage protection OV2PTOV 59
2U>
8.2.2 Functionality
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines etc.
OV2PTOV has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.
OV2PTOV has an extremely high reset ratio to allow settings close to system
service voltage.
223
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
IEC09000278-2-en.vsd
IEC09000278 V2 EN
8.2.4 Signals
Table 132: OV2PTOV Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
224
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
8.2.5 Settings
Table 134: OV2PTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required to operate (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1> 1 - 200 %UB 1 120 Voltage start value (DT & IDMT) in % of
UBase for step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definite time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
OperationStep2 Off - - On Enable execution of step 2
On
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required to operate (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2> 1 - 200 %UB 1 150 Voltage start value (DT & IDMT) in % of
UBase for step 2
t2 0.000 - 60.000 s 0.001 5.000 Definite time delay of step 2
225
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
The time delay characteristic is settable for step 1 and can be either definite or
inverse time delayed. Step 2 is always definite time delayed.
The voltage related settings are made in percent of the global set base voltage
UBase, which is set in kV, phase-to-phase.
The voltage related settings are made in percent of base voltage which is set in kV
phase-to-phase voltage. OV2PTOV will operate if the voltage gets higher than the
set percentage of the set global base voltage UBase. This means operation for phase-
to-earth voltage over:
All the three voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of
3 measured voltages have to be higher than the corresponding set point to issue the
corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.
226
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
The time delay for step 1 can be either definite time delay (DT) or inverse time
delay (IDMT). Step 2 is always definite time delay (DT). For the inverse time
delay three different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 70)
k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 71)
k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 72)
The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see Figure 117. The details of the different inverse time
characteristics are shown in section "Inverse time characteristics"
227
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
Voltage
IDMT Voltage
UL1
UL2
UL3
Time
en05000016.vsd
IEC05000016 V1 EN
Figure 117: Voltage used for the inverse time characteristic integration
A TRIP requires that the overvoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode
(DT) and by selected voltage level dependent time curves for the inverse time
mode (IDMT). If the START condition, with respect to the measured voltage
ceases during the delay time, the corresponding START output is reset.
8.2.7.3 Blocking
8.2.7.4 Design
228
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
to fulfill the START condition. The design of Two step overvoltage protection
(OV2PTOV) is schematically described in Figure 118.
Step 1
Time integrator
t1 TR1
TRIP OR
MaxVoltSelect
tReset1
ResetTypeCrv1
Comparator
U> U2> Phase 1
Voltage Phase
Selector
Comparator OpMode2 Phase 2 ST2
OR
U> U2> 1 out of 3
2 outof 3
3 out of 3 Phase 3 Start
Comparator &
U > U2> Trip
Output
START Logic
Step 2
START
OR
TRIP
OR
IEC08000012_2_en.vsd
IEC08000012 V2 EN
229
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
8.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Two step residual overvoltage ROV2PTOV 59N
protection
3U0>
IEC10000168 V1 EN
8.3.2 Functionality
Residual voltages may occur in the power system during earth faults.
230
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
ROV2PTOV has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.
IEC09000273_1_en.vsd
IEC09000273 V1 EN
8.3.4 Signals
Table 138: ROV2PTOV Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2
8.3.5 Settings
Table 140: ROV2PTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Table continues on next page
231
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
The time delay characteristic is setable for step 1 and can be either definite or
inverse time delayed. Step 2 is always definite time delayed.
The voltage related settings are made in percent of the global phase-to-phase base
voltage divided by √3.
232
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for step 1 can be either definite time delay (DT) or inverse time
delay (IDMT). Step 2 is always definite time delay (DT). For the inverse time
delay three different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 73)
k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 74)
k × 480
t= 3.0
+ 0.035
æ 32 × ö
U -U >
ç - 0.5 ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 75)
The details of the different inverse time characteristics are shown in section
"Inverse time characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves
for the inverse time mode (IDMT).
233
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
If the START condition, with respect to the measured voltage ceases during the
delay time, the corresponding START output is reset.
8.3.7.3 Blocking
8.3.7.4 Design
234
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
ST2
Comparator Phase 1
UN > U2> TR2
Start
START &
Trip START
Output OR
Logic
Timer TRIP
t2
Step 2
TRIP
OR
IEC08000013-2-en.vsd
IEC08000013 V2 EN
235
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
8.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Overexcitation protection OEXPVPH 24
U/f >
SYMBOL-Q V1 EN
8.4.2 Functionality
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into non-
laminated components not designed to carry flux and cause eddy currents to flow.
The eddy currents can cause excessive heating and severe damage to insulation and
236
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
adjacent parts in a relatively short time. The function has settable inverse operating
curves and independent alarm stages.
IEC09000008-2-en.vsd
IEC09000008 V2 EN
8.4.4 Signals
Table 144: OEXPVPH Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
RESET BOOLEAN 0 Reset of function
8.4.5 Settings
Table 146: OEXPVPH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 Operate level of V/Hz at no load and
rated freq in % of (Ubase/frated)
V/Hz>> 100.0 - 200.0 %UB/f 0.1 140.0 High level of V/Hz above which tMin is
used, in % of (Ubase/frated)
tMin 0.005 - 60.000 s 0.001 7.000 Minimum trip delay for V/Hz curve
kForIEEE 1 - 60 - 1 1 Time multiplier for IEEE inverse type
curve
AlarmLevel 50.0 - 120.0 % 0.1 100.0 Alarm operate level
tAlarm 0.00 - 9000.00 s 0.01 5.00 Alarm time delay
237
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
emergency that includes overexcitation does occur, transformers may be damaged
unless corrective action is promptly taken. Transformer manufacturers recommend
an overexcitation protection as a part of the transformer protection system.
E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN (Equation 76)
238
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN (Equation 77)
The IEC 60076 - 1 standard requires that transformers operate continuously at 10%
above rated voltage at no load, and rated frequency. At no load, the ratio of the
actual generator terminal voltage to the actual frequency should not exceed 1.1
times the ratio of transformer rated voltage to the rated frequency on a sustained
basis, see equation 78.
---- £ 1.1 × Ur
E ------
f fr
EQUATION900 V1 EN (Equation 78)
239
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
E V Hz >
£
f fr
IECEQUATION2297 V2 EN (Equation 79)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does
not know exactly what to set, then the default value for V/Hz> = 110 % for the
standard IEC 60076-1 shall be used.
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 80)
It is clear from the above formula that, for an unloaded power transformer, M = 1
for any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M ≤ V/Hz>, V/Hz> expressed in %
of Ur/fr.
The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 Hz
and 60 Hz respectively.
240
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match the transformer core capability well.
0.18 × k 0.18 × k
top = 2
= 2
æ M ö overexcitation
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V2 EN (Equation 81)
where:
M the relative excitation
V/Hz> Operate level of over-excitation function at no load in % of (UBase/frated)
æ Umeasured ö
ç ÷ Umeasured frated
=è
fmeasured ø
M = ×
æ UBase ö UBase fmeasured
ç ÷
è frated ø
IECEQUATION2404 V1 EN
Inverse delays as per figure 123, can be modified (limited) by a special definite
delay setting tMin, see figure 122.
241
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
delay in s
1800
overexcitation
tMin
IEC09000114-1-en.vsd
IEC09000114 V1 EN
A definite maximum time of 1800 seconds can be used to limit the operate time at
low degrees of overexcitation. Inverse delays longer than 1800 seconds will not be
allowed. In case the inverse delay is longer than 1800 seconds, OEXPVPH trips.
A definite minimum time, tMin, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than tMin,
OEXPVPH function trips after tMin seconds. The inverse delay law is not valid for
values exceeding Mmax. The delay will be tMin, irrespective of the overexcitation
level, when values exceed Mmax (that is, M>V/Hz>).
242
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
1000
100
kForIEEE = 60
kForIEEE = 20
kForIEEE = 10
10 kForIEEE = 9
kForIEEE = 8
kForIEEE = 7
kForIEEE = 6
kForIEEE = 5
kForIEEE = 4
kForIEEE = 3
kForIEEE = 2
kForIEEE = 1
1
1 2 3 4 5 10 20 30 40
OVEREXCITATION IN % (M-Emaxcont)*100)
IEC09000115-1-en.vsd
IEC09000115 V1 EN
(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN (Equation 82)
8.4.7.3 Cooling
243
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
applied, with a default time constant of 20 minutes. This means that if the voltage
and frequency return to normal values (no more overexcitation), the normal
temperature is assumed to be reached not before approximately 5 times the default
time constant of 20 minutes. If an overexcitation condition would return before
that, the time to trip will be shorter than it would be otherwise.
The relative excitation M, shown on the local HMI and in PCM600 has a
monitored data value VPERHZ, is calculated from the expression:
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 83)
If VPERHZ value is less than setting V/Hz> (in %), the power transformer is
underexcited. If VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal
to the power transformer continuous capability. If VPERHZ is higher than V/Hz>,
the protected power transformer is overexcited. For example, if VPERHZ = 1.100,
while V/Hz> = 110 %, then the power transformer is exactly on its maximum
continuous excitation limit.
Monitored data value THERMSTA shows the thermal status of the protected
power transformer iron core. THERMSTA gives the thermal status in % of the trip
value which corresponds to 100%. THERMSTA should reach 100% at the same
time, as TMTOTRIP reaches 0 seconds. If the protected power transformer is then
for some reason not switched off, THERMSTA shall go over 100%.
If the delay as per IEEE law, is limited by tMin, then THERMSTA will generally
not reach 100% at the same time, as TMTOTRIP reaches 0 seconds. For example,
if, at low degrees of overexcitation, the very long delay is limited by 30 minutes,
then the TRIP output signal of OEXPVPH will be set to 1 before THERMSTA
reaches 100%.
244
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
BLOCK
AlarmLevel ALARM
t>tAlarm &
t
tAlarm
M>V/Hz>
t>tMin TRIP
t &
U3P V/Hz> tMin
Calculation
of internal
Ei M=
k
M
induced (Ei / f) M
kForIEEE
voltage Ei (Ur / fr) 1800 s ³1
t
M>V/Hz>>
V/Hz>>
IEC09000161_2_en.vsd
IEC09000161 V2 EN
Simplification of the diagram is in the way the IEEE delays are calculated. The
cooling process is not shown. It is not shown that voltage and frequency are
separately checked against their respective limit values.
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ± 0.5% ± 25 ms
function
Alarm time delay (0.000–60.000) s ± 0.5% ± 25 ms
245
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
8.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
100% Stator earth fault protection, 3rd STEFPHIZ - 59THD
harmonic based
8.5.2 IntroductionFunctionality
Stator earth fault is a fault type having relatively high fault rate. The generator
systems normally have high impedance earthing, that is, earthing via a neutral point
resistor. This resistor is normally dimensioned to give an earth fault current in the
range 3 – 15 A at a solid earth-fault directly at the generator high voltage terminal.
The relatively small earth fault currents give much less thermal and mechanical
stress on the generator, compared to the short circuit case, which is between
conductors of two phases. Anyhow, the earth faults in the generator have to be
detected and the generator has to be tripped, even if longer fault time compared to
internal short circuits, can be allowed.
In normal non-faulted operation of the generating unit the neutral point voltage is
close to zero, and there is no zero sequence current flow in the generator. When a
phase-to-earth fault occurs the neutral point voltage will increase and there will be
a current flow through the neutral point resistor.
To detect an earth fault on the windings of a generating unit one may use a neutral
point overvoltage protection, a neutral point overcurrent protection, a zero
sequence overvoltage protection or a residual differential protection. These
protections are simple and have served well during many years. However, at best
these simple schemes protect only 95% of the stator winding. They leave 5% close
to the neutral end unprotected. Under unfavorable conditions the blind zone may
extend up to 20% from the neutral.
The 95% stator earth fault protection measures the fundamental frequency voltage
component in the generator star point and it operates when it exceeds the preset
value. By applying this principle approximately 95% of the stator winding can be
protected. In order to protect the last 5% of the stator winding close to the neutral
end the 3rd harmonic voltage measurement can be performed. In 100% Stator E/F
3rd harmonic protection either the 3rd harmonic voltage differential principle, the
neutral point 3rd harmonic undervoltage principle or the terminal side 3rd
harmonic overvoltage principle can be applied. However, differential principle is
strongly recommended. Combination of these two measuring principles provides
coverage for entire stator winding against earth faults.
246
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
RN Rf Transformer
uN x 1- x uT
Samples of the Samples of the
neutral voltage 1 or 100 % terminal voltage
from which the from which the
fundamental and 3rd harmonic
3rd harmonic voltage is filtered
Neutral point fundamental frequency
voltages are out
over-voltage protection 5% - 100%
filtered out over- voltage protection 10%– 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30% IEC10000202-1-en.vsd
IEC10000202 V1 EN
IEC07000033-3-en.vsd
IEC07000033 V3 EN
8.5.4 Signals
Table 150: STEFPHIZ Input signals
Name Type Default Description
NEUTVOLT GROUP - Voltage connection neutral side
SIGNAL
TERMVOLT GROUP - Open-Delta connection on Terminal side
SIGNAL
CBCLOSED BOOLEAN 1 Input 1 (TRUE) means breaker between gen. & tr.
is closed
BLOCK BOOLEAN 0 Complete block of the stator earth fault protecion
function
BLOCK3RD BOOLEAN 0 Block of the 3rd harmonic-based parts of the
protection
BLOCKUN BOOLEAN 0 Block of the fund. harmonic-based part of the
protection
247
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
8.5.5 Settings
Table 152: STEFPHIZ Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
Beta 0.50 - 10.00 - 0.01 3.00 Portion of 3rd harm voltage in neutral
point used as bias
CBexists No - - No Defines if generator CB exists (between
Yes Gen & Transformer)
FactorCBopen 1.00 - 10.00 - 0.01 1.00 Beta is multiplied by this factor when CB
is open
UN3rdH< 0.5 - 10.0 % 0.1 2.0 Pickup 3rd Harm U< protection (when
activated) % of UB/1,732
UT3BlkLevel 0.1 - 10.0 % 0.1 1.0 If UT3 is below limit 3rdH Diff is blocked,
in % of UB/1,732
UNFund> 1.0 - 50.0 % 0.1 5.0 Pickup fundamental UN> protection
(95% SEF), % of UB/1,732
t3rdH 0.020 - 60.000 s 0.001 1.000 Operation delay of 3rd harm-based
protection (100% SEF) in s
tUNFund 0.020 - 60.000 s 0.001 0.500 Operation delay of fundamental UN>
protection (95% SEF) in s
248
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
The 3rd harmonic voltage generated by the generator has the same phase angle in
the three phases. It has the characteristic of a zero sequence component. If the
generator is connected to the power system via a block transformer that cannot
transform zero sequence voltages between the voltage levels, the 3rd harmonic
voltage, that is U3N and U3T in fig 127, in the generator system is not influenced by
the external power system. At normal operation the generator third harmonic
voltage characteristic can be described as in figure 127.
Note that angle between U3N and U3T is typically close to 180°.
249
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
- U3 +
- DU3 +
+
U3T,L1
-
+
- U3N + U3T,L2
-
+
U3T,L3
-
U3T
U3N
en06000448.vsd
IEC06000448 V2 EN
250
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
U3N, and U3T are third harmonic phasors with real and imaginary parts. The factor
Beta must be set not to risk operation under non-faulted conditions.
The voltage U3N is measured via a voltage transformer between the generator
neutral point and earth. The voltage U3T can be measured in different ways. The
setting TVoltType defines how the protection function is fed from voltage
transformers at the high voltage side of the generator. (If U3T is lower than the set
level UT3BlkLevel, STEFPHIZ function is blocked. The choices of TVoltType are:
NoVoltage: There is no voltage measured from the generator terminal side. This
can be the case when there are only phase-to-phase voltage transformers available
at the generator terminal side. In this case the protection will operate as a simple
neutral point 3rd harmonic undervoltage protection, which must be blocked
externally during generator start-up and shut-down.
ResidualVoltage: The function is fed from an open delta connection of the phase to
earth connected voltage transformers at the generator terminal side,
U3T=(1/3)*U_Open_Delta.
AllThreePhases: The function is fed from the three phase to earth connected
voltage transformers at the generator terminal side. The 3rd harmonic voltage U3T
is calculated in the IED, U3T=(1/3)*(U3L1+U3L2+U3L3).
PhaseL1, PhaseL2, or PhaseL3: The function is fed from one phase voltage
transformer only. The 3rd harmonic zero sequence voltage is assumed to be equal
to any of the phase voltages, as the third harmonic voltage is of zero sequence type,
U3T=U3Lx.
A simplified block diagram describing the stator earth fault protection function
shown in figure 128.
251
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
Samples:
Generator 3rd
terminal TRIP
harmonic
voltage Complex UT3 Stator Earth
Fourier
filtering Fault
detection TRIP3H
giving UT3
3rd
harmonic
TRIPUN
based Start
Start
and trip
logic START3H
Samples:
Generator 3rd
neutral point STARTUN
harmonic Complex UN3
voltage Fourier
filtering
START
giving UN3
CB Status
Block
IEC10000240-1-en.vsd
IEC10000240 V1 EN
Figure 128: Simplified logic diagram for stator earth fault protection
252
Technical Manual
1MRK 502 034-UEN - Section 8
Voltage protection
IEC07000186 V1 EN
Figure 129: Simplified Start and Trip logical diagram of the STEFPHIZ protection
There are two different cases of generator block configuration; with or without
generator circuit breaker. If there is no generator breaker the capacitive coupling to
earth is the same under all operating conditions. When there is a generator breaker,
the capacitive coupling to earth differs between the operating conditions when the
generator is running with the generator breaker open (before synchronization) and
with the circuit breaker closed. This can be shown as in figure 130.
- U3 +
- DU3 +
+ Ctr/3
U3T,L1
-
+
- U3N + Ctr/3
U3T,L2
-
+
U3T,L3 Ctr/3
-
en07000002-2.vsd
IEC07000002 V2 EN
With the circuit breaker open, the total capacitance will be smaller compared to
normal operating conditions. This means that the neutral point 3rd harmonic
voltage will be reduced compared to the normal operating condition. Therefore,
253
Technical Manual
Section 8 1MRK 502 034-UEN -
Voltage protection
there is a possibility to reduce the sensitivity of the protection when the generator
circuit breaker is open.
With the setting CBexists change of the sensitivity is enabled. If the binary input
signal CBCLOSED is activated the set sensitivity is valid. If the generator circuit
breaker is opened the binary input CBCLOSED is deactivated and the sensitivity is
changed. This is done by changing the factor Beta which is multiplied with a set
constant FactorCBopen.
In addition to the binary outputs also some analog outputs are available from the
protection function in order to enable easier commissioning:
E3: the magnitude of the 3rd harmonic voltage induced in the stator given in
primary volts
UN3: the magnitude of the 3rd harmonic voltage measured in the neutral point of
the generator
UT3: the magnitude of the 3rd harmonic voltage measured in the terminal point of
the generator
ANGLE: the angle between the phasors UN3 and UT3 given in radians
UN: the fundamental frequency voltage measured in the neutral point of the generator
254
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
9.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Underfrequency protection SAPTUF 81
f<
SYMBOL-P V1 EN
9.1.2 Functionality
Underfrequency occurs as a result of lack of generation in the network.
IEC09000282_1_en.vsd
IEC09000282 V1 EN
9.1.4 Signals
Table 156: SAPTUF Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
255
Technical Manual
Section 9 1MRK 502 034-UEN -
Frequency protection
9.1.5 Settings
Table 158: SAPTUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 75.00 Hz 0.01 48.80 Frequency set value
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency if frequency is above
frequency value
256
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
percentage of a global base voltage parameter, SAPTUF gets blocked, and the
output BLKDMAGN is issued. All voltage settings are made in percent of the
setting of the global parameter UBase.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for SAPTUF is a settable definite time delay, specified by the
setting tDelay.
Trip signal issuing requires that the under frequency condition continues for at least
the user set time delay. If the START condition, with respect to the measured
frequency ceases during the delay time, and is not fulfilled again within a defined
reset time, the START output is reset.
On the RESTORE output of SAPTUF a 100 ms pulse is issued, after a time delay
corresponding to the setting of tRestore, when the measured frequency returns to
the level corresponding to the setting RestoreFreq.
9.1.7.3 Blocking
9.1.7.4 Design
257
Technical Manual
Section 9 1MRK 502 034-UEN -
Frequency protection
BLOCK
BLOCK BLKDMAGN
OR
freqNotValid
Start
& START
DefiniteTimeDelay START
Frequency Comparator Trip
f < StartFrequency Output
TimeDlyOperate TRIP Logic
TRIP
100 ms
Comparator RESTORE
TimeDlyRestore
f > RestoreFreq
IEC09000034-1.vsd
IEC09000034 V1 EN
258
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
9.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Overfrequency protection SAPTOF 81
f>
SYMBOL-O V1 EN
9.2.2 Functionality
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs at sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over
frequency.
SAPTOF is used mainly for generation shedding and remedial action schemes. It is
also used as a frequency stage initiating load restoring.
IEC09000280_1_en.vsd
IEC09000280 V1 EN
9.2.4 Signals
Table 161: SAPTOF Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
259
Technical Manual
Section 9 1MRK 502 034-UEN -
Frequency protection
9.2.5 Settings
Table 163: SAPTOF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 75.00 Hz 0.01 51.20 Frequency set value
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
The time delay for SAPTOF is a settable definite time delay, specified by the
setting tDelay.
TRIP signal issuing requires that the over frequency condition continues for at least
the user set time delay. If the START condition, with respect to the measured
260
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
frequency ceases during the delay time, and is not fulfilled again within a defined
reset time, the START output is reset.
9.2.7.3 Blocking
9.2.7.4 Design
BLOCK
BLOCK
OR BLKDMAGN
freqNotValid
Start
&
Trip
Output
Logic
START START
Definite Time Delay
Frequency Comparator
f > StartFrequency
TimeDlyOperate
TRIP
TRIP
IEC09000033-1.vsd
IEC09000033 V1 EN
261
Technical Manual
Section 9 1MRK 502 034-UEN -
Frequency protection
9.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Rate-of-change frequency protection SAPFRC 81
df/dt >
<
SYMBOL-N V1 EN
9.3.2 Functionality
Rate-of-change frequency protection function (SAPFRC) gives an early indication
of a main disturbance in the system. SAPFRC can be used for generation shedding,
load shedding and remedial action schemes. SAPFRC can discriminate between
positive or negative change of frequency.
IEC09000281_1_en.vsd
IEC09000281 V1 EN
262
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
9.3.4 Signals
Table 166: SAPFRC Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
9.3.5 Settings
Table 168: SAPFRC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
StartFreqGrad -10.00 - 10.00 Hz/s 0.01 0.50 Frequency gradient start value, the sign
defines direction
tTrip 0.000 - 60.000 s 0.001 0.200 Operate time delay in positive / negative
frequency gradient mode
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore is enabled if frequency is above
set frequency value
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
263
Technical Manual
Section 9 1MRK 502 034-UEN -
Frequency protection
To avoid oscillations of the output START signal, a hysteresis has been included.
Trip signal issuing requires that SAPFRC condition continues for at least the user
set time delay, tTrip. If the START condition, with respect to the measured
frequency ceases during the delay time, and is not fulfilled again within a defined
reset time, the START output is reset after the reset time has elapsed.
The RESTORE output of SAPFRC is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s
the restore functionality is disabled, and no output will be given. The restore
functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the
restore period, defined by the settings RestoreFreq and tRestore.
264
Technical Manual
1MRK 502 034-UEN - Section 9
Frequency protection
9.3.6.3 Design
BLOCK
BLOCK
OR
freqNotValid BLKDMAGN
Start
Rate-of-Change &
Comparator
of Frequency Trip
If
Definite Time Delay Output START
[StartFreqGrad<0 START Logic
AND
df/dt < StartFreqGrad] tTrip
OR
[StartFreqGrad>0
AND
TRIP
df/dt > StartFreqGrad]
Then
START
100 ms
IEC08000009_en_1.vsd
IEC08000009 V1 EN
265
Technical Manual
266
1MRK 502 034-UEN - Section 10
Secondary system supervision
10.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Fuse failure supervision SDDRFUF - -
10.1.2 Functionality
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage
transformer and the IED in order to avoid unwanted operations that otherwise
might occur.
The fuse failure supervision function basically has three different algorithms,
negative sequence and zero sequence based algorithms and an additional delta
voltage and delta current algorithm.
The zero sequence detection algorithm is recommended for IEDs used in directly
or low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3U0 without the presence of the residual current
3I0.
A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure,
which in practice is more associated with voltage transformer switching during
station operations.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
modes makes it possible to choose different interaction possibilities between the
negative sequence and zero sequence based algorithm.
267
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
10.1.4 Signals
Table 170: SDDRFUF Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
CBCLOSED BOOLEAN 0 Active when circuit breaker is closed
MCBOP BOOLEAN 0 Active when external MCB opens protected
voltage circuit
DISCPOS BOOLEAN 0 Active when line disconnector is open
268
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
10.1.5 Settings
Table 172: SDDRFUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
OpMode Off - - UZsIZs Operating mode selection
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltage
element in % of UBase
3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrent
element in % of IBase
3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltage
element in % of UBase
3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrent
element in % of IBase
OpDUDI Off - - Off Operation of change based function Off/
On On
DU> 1 - 100 %UB 1 60 Operate level of change in phase voltage
in % of UBase
DI< 1 - 100 %IB 1 15 Operate level of change in phase current
in % of IBase
UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of
UBase
IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of
IBase
SealIn Off - - On Seal in functionality Off/On
On
USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage in
% of UBase
IDLD< 1 - 100 %IB 1 5 Operate level for open phase current
detection in % of IBase
UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltage
detection in % of UBase
269
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates: (see figure 138)
The measured signals are compared with their respective set values 3U0< and
3I0>, 3U2< and 3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3U0> and the measured zero-
sequence current is below the set value 3I0<.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
270
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq
Negative
sequence a 3U2
a>b
UL3 filter b
3U2>
IEC10000036-1-en.vsd
IEC10000036 V1 EN
The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local
HMI and monitoring tool in PCM600.
A simplified diagram for the functionality is found in figure 139. The calculation of
the change is based on vector change which means that it detects both amplitude
and phase angle changes. The calculated delta quantities are compared with their
respective set values DI< and DU> and the algorithm, detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in
each phase separately. The following quantities are calculated in all three phases:
• The magnitude of the phase-earth voltage has been above UPh> for more than
1.5 cycle
• The magnitude of DU is higher than the corresponding setting DU>
• The magnitude of DI is below the setting DI>
271
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
• The magnitude of the phase current in the same phase is higher than the setting
IPh>
• The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used
to reduce the risk of false fuse failure detection. If the current on the protected line
is low, a voltage drop in the system (not caused by fuse failure) is not by certain
followed by current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase
at the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way
only the first criterion can activate the delta function.
272
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
DUDI Detection
DUDI detection Phase 1
IL1 One cycle
delay
|DI|
a
a>b
DI< b
20 ms 1.5 cycle
a
a>b t t
UPh> b
UL1
a
a<b
b
IL1
a
a>b
IPh> b AND
OR AND
CBCLOSED AND OR
UL2
a
a<b
b
IL2
a
a>b
b AND
OR AND
AND OR
UL3
a
a<b
b
IL3
a
a>b
b AND
OR AND FuseFailDetDUDI
AND OR
OR
IEC10000034-1-en.vsd
IEC10000034 V1 EN
273
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
A simplified diagram for the functionality is found in figure 140. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated
IL3
a
a<b
b
IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b
UDLD<
intBlock
IEC10000035-1-en.vsd
IEC10000035 V1 EN
Figure 140: Simplified logic diagram for Dead Line detection part
A simplified diagram for the functionality is found in figure 141. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting
parameter Operation to On or Off.
274
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
The delta function can be activated by setting the parameter OpDUDI to On. When
selected it operates in parallel with the sequence based algorithms.
If the fuse failure situation is present for more than 5 seconds and the setting
parameter SealIn is set to On it will be sealed in as long as at least one phase
voltages is below the set value USealIn<. This will keep the BLKU and BLKZ
signals activated as long as any phase voltage is below the set value USealIn<. If
all three phase voltages drop below the set value USealIn< and the setting
parameter SealIn is set to On also the output signal 3PH will be activated. The
signals 3PH, BLKU and BLKZ signals will now be active as long as any phase
voltage is below the set value USealIn<.
If SealIn is set to On fuse failure condition is stored in the non volatile memory in
the IED. At start-up (due to auxiliary power interruption or re-start due to
configuration change) the IED checks the stored value in its non volatile memory
and re-establishes the conditions present before the shut down. All phase voltages
must became above USealIn< before fuse failure is de-activated and inhibits the
block of different protection functions.
The output signal BLKU will also be active if all phase voltages have been above
the setting USealIn< for more than 60 seconds, the zero or negative sequence
voltage has been above the set value 3U0> and 3U2> for more than 5 seconds, all
phase currents are below the setting IDLD< (operate level for dead line detection)
and the circuit breaker is closed (input CBCLOSED is activated).
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode or OpDUDI. An additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
275
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function does not have to be
affected since there will be no line currents that can cause malfunction of the
distance protection.
The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions
occur:
The input BLOCK is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED. Through OR gate it can be connected to both
binary inputs and internal function outputs.
276
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK intBlock
OR
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b
AND
200 ms
DeadLineDet1Ph AND BLKZ
t OR AND
150 ms
MCBOP t
AND BLKU
60 sec
t OR OR
All UL > UsealIn<
AND
VoltZeroSeq 5 sec
VoltNegSeq OR t
AllCurrLow
CBCLOSED
DISCPOS
IEC10000041-1-en.vsd
IEC10000041 V1 EN
Figure 141: Simplified logic diagram for fuse failure supervision function, Main
logic
277
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
10.2.1 Identification
10.2.2 Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The invalidity of a control circuit is detected by using
a dedicated output contact that contains the supervision functionality.
The function operates after a predefined operating time and resets when the fault
disappears.
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
278
Technical Manual
1MRK 502 034-UEN - Section 10
Secondary system supervision
10.2.4 Signals
Table 176: TCSSCBR Input signals
Name Type Default Description
TCS_STATE BOOLEAN 0 Trip circuit fail indication from I/O-card
BLOCK BOOLEAN 0 Block of function
10.2.5 Settings
Table 178: TCSSCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
tDelay 0.020 - 300.000 s 0.001 3.000 Operate time delay
GUID-9D3B79CB-7E06-4260-B55F-B7FA004CB2AC V1 EN
279
Technical Manual
Section 10 1MRK 502 034-UEN -
Secondary system supervision
To protect the trip circuit supervision circuits in the IED, the output
contacts are provided with parallel transient voltage suppressors.
The breakdown voltage of these suppressors is 400 +/– 20 V DC.
Timer
Once activated, the timer runs until the set value tDelay is elapsed. The time
characteristic is according to DT. When the operation timer has reached the
maximum time value, the ALARM output is activated. If a drop-off situation occurs
during the operate time up counting, the reset timer is activated.
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates the ALARM output and resets the internal timer.
280
Technical Manual
1MRK 502 034-UEN - Section 11
Control
Section 11 Control
11.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Synchrocheck, energizing check, and SESRSYN 25
synchronizing
sc/vc
SYMBOL-M V1 EN
11.1.2 Functionality
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time, which improves the network stability.
SESRSYN function includes a built-in voltage selection scheme for double bus
arrangements.
Manual closing as well as automatic reclosing can be checked by the function and
can have different settings.
281
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
IEC08000219-2-en.vsd
IEC08000219 V2 EN
11.1.4 Signals
Table 180: SESRSYN Input signals
Name Type Default Description
U3PB1 GROUP - Voltage input for Bus bar 1
SIGNAL
U3PB2 GROUP - Voltage input for Bus bar 2
SIGNAL
U3PLN1 GROUP - Voltage input for Line 1
SIGNAL
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to
bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to
bus2
Table continues on next page
282
Technical Manual
1MRK 502 034-UEN - Section 11
Control
283
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.1.5 Settings
Table 182: SESRSYN Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PhaseShift -180 - 180 Deg 5 0 Phase shift
URatio 0.20 - 5.00 - 0.01 1.00 Voltage ratio
OperationSynch Off - - Off Operation for synchronizing function Off/
On On
FreqDiffMin 0.003 - 0.250 Hz 0.001 0.010 Minimum frequency difference limit for
synchronizing
FreqDiffMax 0.050 - 0.250 Hz 0.001 0.200 Maximum frequency difference limit for
synchronizing
FreqRateChange 0.000 - 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of
change
tBreaker 0.000 - 60.000 s 0.001 0.080 Closing time of the breaker
tClosePulse 0.050 - 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 - 6000.00 s 0.01 600.00 Resets synchronization if no close has
been made before set time
tMinSynch 0.000 - 60.000 s 0.001 2.000 Minimum time to accept synchronizing
conditions
OperationSC Off - - On Operation for synchronism check
On function Off/On
UDiffSC 2.0 - 50.0 %UB 1.0 15.0 Voltage difference limit in % of UBase
FreqDiffA 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Auto
FreqDiffM 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Manual
PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Manual
Table continues on next page
284
Technical Manual
1MRK 502 034-UEN - Section 11
Control
285
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares
them to both high and low threshold detectors. The output is given only when the
actual measured quantities match the set conditions.
The synchronizing function measures the conditions across the circuit breaker, and
also determines the angle change occurring during the closing delay of the circuit
breaker, from the measured slip frequency. The output is given only when all
measured conditions are simultaneously within their set limits. The issue of the
output is timed to give closure at the optimal time including the time for the circuit
breaker and the closing circuit.
For single circuit breaker arrangements, SESRSYN function blocks have the
capability to make the necessary voltage selection. The selection of correct voltage
is made using auxiliary contacts of the bus disconnectors.
The internal logic for each function block as well as, the input and outputs, and the
settings with default setting and setting ranges is described in this document. For
application related information, please refer to the application manual.
11.1.7.2 Synchrocheck
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.
When the function is set to OperationSC = On, the measuring will start.
The function compares bus and line values with the set values for acceptable
frequency, phase angle and voltage difference: FreqDiffA, FreqDiffM, PhaseDiffA,
PhaseDiffM and UDiffSC. If a compensation factor is set due to the use of different
voltages on the bus and line, the factor is deducted from the line voltage before the
comparison of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and may not exceed the set value.
286
Technical Manual
1MRK 502 034-UEN - Section 11
Control
Two sets of settings for frequency difference and phase angle difference are
available and used for the manual closing and autoreclose functions respectively, as
required.
The inputs BLOCK and BLKSC are available for total block of the complete
Synchrocheck function and block of the Synchrocheck function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK and AUTOSYOK conditions.
OperationSC = On
AND TSTAUTSY
AND
TSTSC
BLKSC AND
BLOCK OR
AUTOSYOK
AND
0-60 s
AND t
tSCA
UDiffSC 50 ms
AND t
Bus voltage >80% of
Ubase
UOKSC
Line voltage >80% of AND
Ubase
UDIFFSC
1
FRDIFFA
FreqDiffA 1
PHDIFFA
PhaseDiffA 1
UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue
IEC08000018_2_en.vsd
IEC08000018 V2 EN
287
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.1.7.3 Synchronizing
The function compares the values for the bus and line voltage which is a
supervision that the voltages are both live. If both sides are live, the measured
values are compared with the set values for acceptable frequency, rate of change of
frequency, phase angle and voltage difference.
Measured frequencies between the settings for the maximum and minimum
frequency will initiate the measuring and the evaluation of the angle change to
allow operation to be sent in the right moment including the set tBreaker time.
There is a phase angle release internally to block any incorrect closing pulses. At
operation the SYNOK output will be activated with a pulse tClosePulse and the
function reset. The function will also reset if the syncronizing conditions are not
fulfilled within the set tMaxSynch time. This prevents that the functions are, by
mistake, maintained in operation for a long time, waiting for conditions to be fulfilled.
The inputs BLOCK and BLKSYNCH are available for total block of the complete
function respective of the synchronizing part. TSTSYNCH will allow testing of the
function where the fulfilled conditions are connected to a separate output.
SESRSYN
OPERATION SYNCH
OFF
ON
TEST MODE
OFF
ON
STARTSYN SYNPROGR
AND
BLOCK
AND
S
BLKSYNCH OR R
AND
FreqDiffMin
tClose
Pulse
FreqRateChange AND
fBus&fLine ± 5 Hz tMax
Synch
SYNFAIL
PhaseDiff < 15 deg
PhaseDiff=closing angle
IEC08000020_3_en.vsd
IEC08000020 V3 EN
288
Technical Manual
1MRK 502 034-UEN - Section 11
Control
Voltage values are measured in the IED centrally and are available for evaluation
by the Energizing check function.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz.
The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse
supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective
MENMODE, which for example, can be connected to a Binary to Integer function
block (B16I). Integers supplied shall be 1=off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input with connection of INTZERO output from Fixed Signals
(FIXDSIGN) function block will mean that the setting is done from Parameter
Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
SESRSYN function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
The default voltages used will be ULine and UBus1. This is also the case when
external voltage selection is provided. Fuse failure supervision for the used inputs
must also be connected.
The voltage selection function, selected voltages, and fuse conditions are the
Synchronizing, Synchrocheck and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type
contacts to supply Disconnector Open and Closed positions but, it is also possible
to use an inverter for one of the positions.
External fuse failure signals or signals from a tripped fuse switch/MCB are
connected to binary inputs that are configured to the inputs of SESRSYN functions
289
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
in the IED. Alternatively, the internal signals from fuse failure supervision can be
used when available. There are two alternative connection possibilities. Inputs
labelled OK must be connected if the available contact indicates that the voltage
circuit is healthy. Inputs labelled FF must be connected if the available contact
indicates that the voltage circuit is faulty.
The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage
and the ULNOK and ULNFF inputs are related to the line voltage. Configure them
to the binary input or function outputs that indicate the status of the external fuse
failure of the busbar and line voltages. In the event of a fuse failure, the energizing
check function is blocked. The synchronizing and the synchrocheck function
requires full voltage on both sides and will be blocked automatically in the event of
fuse failures.
11.1.7.7 Voltage selection for a single circuit breaker with double busbars
This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select
between bus 1 and bus 2 voltages. If the disconnector connected to bus 1 is closed
and the disconnector connected to bus 2 is opened the bus 1 voltage is used. All
other combinations use the bus 2 voltage. The Outputs B1SEL and B2SEL
respectively indicate the selected Bus voltage.
The function checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1 and UB2OK-
UB2FF supervises the fuse for Bus 2. ULNOK -ULNFF supervises the fuse for the
Line voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively be
used dependent on the available signal. If a fuse-failure is detected in the selected
voltage source an output signal USELFAIL is set. This output signal is true if the
selected bus or line voltages have a fuse failure. This output as well as the function
can be blocked with the input signal BLOCK. The function logic diagram is shown
in figure 147.
290
Technical Manual
1MRK 502 034-UEN - Section 11
Control
B1QOPEN
B1SEL
B1QCLD AND
bus1Voltage
busVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
AND selectedFuseOK
UB2OK AND
UB2FF OR USELFAIL
AND
ULN1OK
ULN1FF OR
BLOCK
en08000019.vsd
IEC08000019 V1 EN
Figure 147: Logic diagram for the voltage selection function of a single circuit breaker with double busbars
291
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.2.1 Functionality
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and earthing switches within a bay. Permission to operate
is given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
11.2.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Bay control QCBAY - -
11.2.2.2 Functionality
The Bay control QCBAY function is used together with Local remote and local
remote control functions is used to handle the selection of the operator place per
bay. QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay.
IEC09000080_1_en.vsd
IEC09000080 V1 EN
292
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.2.2.4 Signals
Table 186: QCBAY Input signals
Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote
position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command
11.2.2.5 Settings
Table 188: QCBAY Non group settings (basic)
Name Values (Range) Unit Step Default Description
AllPSTOValid Priority - - Priority Priority of originators
No priority
11.2.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Local remote LOCREM - -
11.2.3.2 Functionality
The signals from the local HMI or from an external local/remote switch are applied
via the function blocks LOCREM and LOCREMCTRL to the Bay control
(QCBAY) function block. A parameter in function block LOCREM is set to
choose if the switch signals are coming from the local HMI or from an external
hardware switch connected via binary inputs.
293
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
IEC09000076_1_en.vsd
IEC09000076 V1 EN
11.2.3.4 Signals
Table 189: LOCREM Input signals
Name Type Default Description
CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control
11.2.3.5 Settings
Table 191: LOCREM Non group settings (basic)
Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch - - Internal LR-switch Control mode for internal/external LR-
External LR-switch switch
11.2.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Local remote control LOCREMCTRL - -
294
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.2.4.2 Functionality
The signals from the local HMI or from an external local/remote switch are applied
via the function blocks LOCREM and LOCREMCTRL to the Bay control
(QCBAY) function block. A parameter in function block LOCREM is set to
choose if the switch signals are coming from the local HMI or from an external
hardware switch connected via binary inputs.
LOCREMCTRL
^PSTO1 ^HMICTR1
^PSTO2 ^HMICTR2
^PSTO3 ^HMICTR3
^PSTO4 ^HMICTR4
^PSTO5 ^HMICTR5
^PSTO6 ^HMICTR6
^PSTO7 ^HMICTR7
^PSTO8 ^HMICTR8
^PSTO9 ^HMICTR9
^PSTO10 ^HMICTR10
^PSTO11 ^HMICTR11
^PSTO12 ^HMICTR12
IEC09000074_1_en.vsd
IEC09000074 V1 EN
11.2.4.4 Signals
Table 192: LOCREMCTRL Input signals
Name Type Default Description
PSTO1 INTEGER 0 PSTO input channel 1
PSTO2 INTEGER 0 PSTO input channel 2
PSTO3 INTEGER 0 PSTO input channel 3
PSTO4 INTEGER 0 PSTO input channel 4
PSTO5 INTEGER 0 PSTO input channel 5
PSTO6 INTEGER 0 PSTO input channel 6
PSTO7 INTEGER 0 PSTO input channel 7
PSTO8 INTEGER 0 PSTO input channel 8
PSTO9 INTEGER 0 PSTO input channel 9
PSTO10 INTEGER 0 PSTO input channel 10
PSTO11 INTEGER 0 PSTO input channel 11
PSTO12 INTEGER 0 PSTO input channel 12
295
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.2.4.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
The functionality of the Bay control (QCBAY) function is not defined in the IEC
61850–8–1 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO)
and blocking conditions to other functions within the bay for example, switch
control functions, voltage control functions and measurement functions.
When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the
PSTO output will always be set to faulty state (3), which means no possibility to
operate.
296
Technical Manual
1MRK 502 034-UEN - Section 11
Control
To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.
Table 194: PSTO values for different Local panel switch positions
Local panel switch PSTO value AllPSTOValid Possible locations that shall be able to
positions (configuration operate
parameter)
0 = Off 0 -- Not possible to operate
1 = Local 1 FALSE Local Panel
1 = Local 5 TRUE Local or Remote level without any
priority
2 = Remote 2 FALSE Remote level
2 = Remote 5 TRUE Local or Remote level without any
priority
3 = Faulty 3 -- Not possible to operate
Blockings
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:
• Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850–8–1). If DO Behavior is set to "blocked" it means that the function is
active, but no outputs are generated, no reporting, control commands are
rejected and functional and configuration data is visible.
The switching of the Local/Remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
297
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 151, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
used. When a local HMI is used, the inputs are not used and are set to FALSE in
the configuration. The outputs from the LOCREM function block control the
output PSTO (Permitted Source To Operate) on Bay control (QCBAY).
LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD REM
BL_ CMD
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12
Figure 151: Configuration for the local/remote handling for a local HMI with two
bays and two screen pages
The switching of the local/remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.
298
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Logic rotating switch for function SLGGIO - -
selection and LHMI presentation
11.3.2 Functionality
The logic rotating switch for function selection and LHMI presentation function
(SLGGIO) (or the selector switch function block) is used to get a selector switch
functionality similar to the one provided by a hardware selector switch. Hardware
selector switches are used extensively by utilities, in order to have different
functions operating on pre-set values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended purchase portfolio.
The logic selector switches eliminate all these problems.
IEC09000091_1_en.vsd
IEC09000091 V1 EN
299
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.3.4 Signals
Table 195: SLGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
UP BOOLEAN 0 Binary "UP" command
DOWN BOOLEAN 0 Binary "DOWN" command
300
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.3.5 Settings
Table 197: SLGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
NrPos 2 - 32 - 1 32 Number of positions in the switch
OutType Pulsed - - Steady Output type, steady or pulse
Steady
tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration
tDelay 0.000 - 60000.000 s 0.010 0.000 Output time delay
StopAtExtremes Disabled - - Disabled Stop when min or max position is reached
Enabled
301
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Selector mini switch VSGGIO - -
11.4.2 Functionality
The Selector mini switch VSGGIO function block is a multipurpose function used
for a variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line
diagram (SLD) on the local HMI.
IEC09000341-1-en.vsd
IEC09000341 V1 EN
302
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.4.4 Signals
Table 199: VSGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input
11.4.5 Settings
Table 201: VSGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CtlModel Dir Norm - - Dir Norm Specifies the type for control model
SBO Enh according to IEC 61850
Mode Steady - - Pulsed Operation mode
Pulsed
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute
signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght
• for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
303
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
The PSTO input is connected to the Local remote switch to have a selection of
operators place , operation from local HMI (Local) or through IEC 61850
(Remote). An INTONE connection from Fixed signal function block (FXDSIGN)
will allow operation from local HMI.
The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11
11.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IEC 61850 generic communication I/O DPGGIO - -
functions
11.5.2 Functionality
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It
is especially used in the interlocking and reservation station-wide logics.
304
Technical Manual
1MRK 502 034-UEN - Section 11
Control
IEC09000075_1_en.vsd
IEC09000075 V1 EN
11.5.4 Signals
Table 202: DPGGIO Input signals
Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication
11.5.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
11.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Single point generic control 8 signals SPC8GGIO - -
305
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.6.2 Functionality
The Single point generic control 8 signals (SPC8GGIO) function block is a
collection of 8 single point commands, designed to bring in commands from
REMOTE (SCADA) to those parts of the logic configuration that do not need
extensive command receiving functionality (for example, SCSWI). In this way,
simple commands can be sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is supposed to be achieved by
other means, such as binary inputs and SPGGIO function blocks. The commands
can be pulsed or steady.
IEC09000086_1_en.vsd
IEC09000086 V1 EN
11.6.4 Signals
Table 204: SPC8GGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
306
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.6.5 Settings
Table 206: SPC8GGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
Latched1 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse Time
Latched2 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse Time
Latched3 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse Time
Latched4 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse Time
Latched5 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse Time
Latched6 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse Time
Latched7 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse Time
Latched8 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time
307
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
AutomationBits, command function for
AUTOBITS - -
DNP3
11.7.2 Functionality
The Automation bits function (AUTOBITS) is used to configure the DNP3
protocol command handling.
IEC09000030-1-en.vsd
IEC09000030 V1 EN
308
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.7.4 Signals
Table 207: AUTOBITS Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
309
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.7.5 Settings
Table 209: AUTOBITS Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
There is a BLOCK input signal, which will disable the operation of the function, in
the same way the setting Operation: On/Off does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts
like an overriding, the function still receives data from the DNP3 master. Upon
deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.
11.8.1 Functionality
I103CMD is a command function block in control direction with pre-defined
output signals.
IEC10000282-1-en.vsd
IEC10000282 V1 EN
310
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.8.3 Signals
Table 210: I103CMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
11.8.4 Settings
Table 212: I103CMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
11.9.1 Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
IEC10000283-1-en.vsd
IEC10000283 V1 EN
11.9.3 Signals
Table 213: I103IEDCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
311
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
11.9.4 Settings
Table 215: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)
11.10.1 Functionality
I103USRCMD is a command block in control direction with user defined output
signals. These function blocks include the FunctionType parameter for each block
in the private range, and the Information number parameter for each output signal.
IEC10000284-1-en.vsd
IEC10000284 V1 EN
11.10.3 Signals
Table 216: I103USRCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
312
Technical Manual
1MRK 502 034-UEN - Section 11
Control
11.10.4 Settings
Table 218: I103USRCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseMode Steady - - Pulsed Pulse mode
Pulsed
PulseLength 0.200 - 60.000 s 0.001 0.400 Pulse length
InfNo_1 1 - 255 - 1 1 Information number for output 1 (1-255)
InfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)
InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)
InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)
InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)
InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)
InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)
InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)
11.11.1 Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
313
Technical Manual
Section 11 1MRK 502 034-UEN -
Control
IEC10000285-1-en.vsd
IEC10000285 V1 EN
11.11.3 Signals
Table 219: I103GENCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of command
11.11.4 Settings
Table 221: I103GENCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 127 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 32 - 239 - 1 32 Information number for command output
(1-255)
11.12.1 Functionality
I103POSCMD has double-point position indicators that are getting the position
value as an integer (for example from the POSITION output of the SCSWI
function block) and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE); as
per standard, 0 and 3 values of the position are not supported.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used
314
Technical Manual
1MRK 502 034-UEN - Section 11
Control
to indicate that the monitored apparatus has been selected (in a select-before-
operate type of control)
IEC10000286-1-en.vsd
IEC10000286 V1 EN
11.12.3 Signals
Table 222: I103POSCMD Input signals
Name Type Description
BLOCK BOOLEAN Block of command
POSITION INTEGER Position of controllable object
SELECT BOOLEAN Select of controllable object
11.12.4 Settings
Table 223: I103POSCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
InfNo 160 - 196 - 4 160 Information number for command output
(1-255)
315
Technical Manual
316
1MRK 502 034-UEN - Section 12
Logic
Section 12 Logic
12.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Tripping logic SMPPTRC 94
I->O
SYMBOL-K V1 EN
12.1.2 Functionality
A function block for protection tripping is provided for each circuit breaker
involved in the tripping of the fault. It provides the pulse prolongation to ensure a
trip pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.
IEC09000284_1_en.vsd
IEC09000284 V1 EN
317
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.1.4 Signals
Table 224: SMPPTRC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
TRIN BOOLEAN 0 Trip all phases
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout
function
12.1.5 Settings
Table 226: SMPPTRC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.
318
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
BLOCK
tTripMin TRIP
TRIN OR
AND t
Operation Mode = On
Program = 3Ph
en05000789.vsd
IEC05000789 V1 EN
The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three-
phase trip, if desired.
12.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Trip matrix logic TMAGGIO - -
12.2.2 Functionality
Trip matrix logic TMAGGIO function is used to route trip signals and other logical
output signals to different output contacts on the IED.
319
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
TMAGGIO output signals and the physical outputs allows the user to adapt the
signals to the physical tripping outputs according to the specific application needs.
12.2.4 Signals
Table 229: TMAGGIO Input signals
Name Type Default Description
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
Table continues on next page
320
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
12.2.5 Settings
Table 231: TMAGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
Table continues on next page
321
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 (TRUE) the first output signal (OUTPUT1) will get logical value 1
(TRUE).
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 (TRUE) the second output signal (OUTPUT2) will get logical value 1
(TRUE).
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 (TRUE) the third output signal (OUTPUT3) will get logical value 1 (TRUE).
322
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
PulseTime
t
&
ModeOutput1
Input 1
Output 1
Ondelay Offdelay
&
³1
³1 t t
Input 16
PulseTime
t
&
ModeOutput2
Input 17
Output 2
Ondelay Offdelay
&
³1
³1 t t
Input 32
PulseTime
t
&
ModeOutput3
Output 3
Ondelay Offdelay
&
³1
³1 t t
IEC09000612_1_en.vsd
IEC09000612 V1 EN
Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.
12.3.1.1 Functionality
A number of logic blocks and timers are available for the user to adapt the
configuration to the specific application needs.
• OR function block.
• PULSETIMER function block can be used, for example, for pulse extensions
or limiting of operation of outputs.
323
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
• GATE function block is used for whether or not a signal should be able to
pass from the input to the output.
• LOOPDELAY function block used to delay the output signal one execution
cycle.
• TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.
• SRMEMORY function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block should be reset or return to the state
before the interruption, after a power interruption. Set input has priority.
• RSMEMORY function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block should be reset or return to the state
before the interruption, after a power interruption. Reset input has priority.
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
OR Function block OR - -
Functionality
The OR function is used to form general combinatory expressions with boolean
variables. The OR function block has six inputs and two outputs. One of the
outputs is inverted.
324
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
Function block
OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6
IEC09000288-1-en.vsd
IEC09000288 V1 EN
Signals
Table 232: OR Input signals
Name Type Default Description
INPUT1 BOOLEAN 0 Input signal 1
INPUT2 BOOLEAN 0 Input signal 2
INPUT3 BOOLEAN 0 Input signal 3
INPUT4 BOOLEAN 0 Input signal 4
INPUT5 BOOLEAN 0 Input signal 5
INPUT6 BOOLEAN 0 Input signal 6
Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Inverter function block INVERTER - -
325
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Function block
INVERTER
INPUT OUT
IEC09000287-1-en.vsd
IEC09000287 V1 EN
Signals
Table 234: INVERTER Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
PULSETIMER function block PULSETIMER - -
Functionality
The pulse function can be used, for example for pulse extensions or limiting of
operation of outputs. The PULSETIMER has a settable length.
Function block
PULSETIMER
INPUT OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
326
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
Signals
Table 236: PULSETIMER Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Settings
Table 238: PULSETIMER Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.000 - 90000.000 s 0.001 0.010 Pulse time length
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Controllable gate function block GATE - -
Functionality
The GATE function block is used for controlling if a signal should pass from the
input to the output or not, depending on setting.
Function block
GATE
INPUT OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Signals
Table 239: GATE Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
327
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Settings
Table 241: GATE Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Exclusive OR function block XOR - -
Functionality
The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal is 1 if the input signals are different and 0 if they are equal.
Function block
XOR
INPUT1 OUT
INPUT2 NOUT
IEC09000292-1-en.vsd
IEC09000292 V1 EN
Signals
Table 242: XOR Input signals
Name Type Default Description
INPUT1 BOOLEAN 0 Input signal 1
INPUT2 BOOLEAN 0 Input signal 2
328
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
The Logic loop delay function block (LOOPDELAY) function is used to delay the
output signal one execution cycle.
Function block
LOOPDELAY
INPUT OUT
IEC09000296-1-en.vsd
IEC09000296 V1 EN
Signals
Table 244: LOOPDELAY Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Timer function block TIMERSET - -
329
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Functionality
The function block TIMERSET has pick-up and drop-out delayed outputs related
to the input signal. The timer has a settable time delay (t).
Input
tdelay
On
Off
tdelay
en08000289-2-en.vsd
IEC08000289 V1 EN
Function block
TIMERSET
INPUT ON
OFF
IEC09000290-1-en.vsd
IEC09000290 V1 EN
Signals
Table 246: TIMERSET Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
330
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
Settings
Table 248: TIMERSET Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
AND function block AND - -
Functionality
The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to
just use the required number of inputs and leave the rest un-connected. The output
OUT has a default value 0 initially, which suppresses one cycle pulse if the
function has been put in the wrong execution order.
Function block
AND
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
IEC09000289-1-en.vsd
IEC09000289 V1 EN
Signals
Table 249: AND Input signals
Name Type Default Description
INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4
331
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Set-reset memory function block SRMEMORY - -
Functionality
The Set-Reset function SRMEMORY is a flip-flop with memory that can set or
reset an output from two inputs respectively. Each SRMEMORY function block
has two outputs, where one is inverted. The memory setting controls if the flip-flop
after a power interruption will return the state it had before or if it will be reset. For
a Set-Reset flip-flop, SET input has higher priority over RESET input.
Table 251: Truth table for the Set-Reset (SRMEMORY) function block
SET RESET OUT NOUT
1 0 1 0
0 1 0 1
1 1 1 0
0 0 0 1
Function block
SRMEMORY
SET OUT
RESET NOUT
IEC09000293-1-en.vsd
IEC09000293 V1 EN
332
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
Signals
Table 252: SRMEMORY Input signals
Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
Settings
Table 254: SRMEMORY Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory function
On
Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Reset-set with memory function block RSMEMORY - -
Functionality
The Reset-set with memory function block (RSMEMORY) is a flip-flop with
memory that can reset or set an output from two inputs respectively. Each
RSMEMORY function block has two outputs, where one is inverted. The memory
setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset. For a Reset-Set flip-flop, RESET input has higher
priority over SET input.
333
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
Function block
RSMEMORY
SET OUT
RESET NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Signals
Table 256: RSMEMORY Input signals
Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
Settings
Table 258: RSMEMORY Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory function
On
334
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
12.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Fixed signals FXDSIGN - -
12.4.2 Functionality
The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed)
signals that can be used in the configuration of an IED, either for forcing the
unused inputs in other function blocks to a certain level/value, or for creating
certain logic.
IEC09000037.vsd
IEC09000037 V1 EN
335
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.4.4 Signals
Table 260: FXDSIGN Output signals
Name Type Description
OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
INTALONE INTEGER Integer signal fixed all ones
REALZERO REAL Real signal fixed zero
STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off
12.4.5 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Boolean 16 to integer conversion B16I - -
336
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
12.5.2 Functionality
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
IEC09000035-1-en.vsd
IEC09000035 V1 EN
12.5.4 Signals
Table 261: B16I Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16
337
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.5.5 Settings
The function does not have any parameters available in local HMI or Protection
and Control IED Manager (PCM600)
12.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Boolean 16 to integer conversion with B16IFCVI - -
logic node representation
12.6.2 Functionality
Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) is used to transform a set of 16 binary (logical) signals into an integer.
338
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
IEC09000624-1-en.vsd
IEC09000624 V1 EN
12.6.4 Signals
Table 264: B16IFCVI Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16
339
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.6.5 Settings
The function does not have any parameters available in local HMI or Protection
and Control IED Manager (PCM600)
12.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Integer to boolean 16 conversion IB16A - -
12.7.2 Functionality
Integer to boolean 16 conversion function (IB16A) is used to transform an integer
into a set of 16 binary (logical) signals.
340
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
IEC09000036-1-en.vsd
IEC09000036 V1 EN
12.7.4 Signals
Table 267: IB16A Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INP INTEGER 0 Integer Input
341
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.7.5 Settings
The function does not have any parameters available in local HMI or Protection
and Control IED Manager (PCM600)
12.8.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Integer to boolean 16 conversion with IB16FCVB - -
logic node representation
12.8.2 Functionality
Integer to boolean conversion with logic node representation function (IB16FCVB)
is used to transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over IEC61850 depending on the
operator position input (PSTO).
342
Technical Manual
1MRK 502 034-UEN - Section 12
Logic
IEC09000399-1-en.vsd
IEC09000399 V1 EN
12.8.4 Signals
Table 269: IB16FCVB Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection
343
Technical Manual
Section 12 1MRK 502 034-UEN -
Logic
12.8.5 Settings
The function does not have any parameters available in local HMI or Protection
and Control IED Manager (PCM600)
The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in “Remote”. If PSTO is in ”Off”
or ”Local”, then no change is applied to the outputs.
344
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Section 13 Monitoring
13.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IEC 61850 generic communication I/O SPGGIO - -
functions
13.1.2 Functionality
IEC61850 generic communication I/O functions (SPGGIO) is used to send one
single logical signal to other systems or equipment in the substation.
IEC09000237_en_1.vsd
IEC09000237 V1 EN
13.1.4 Signals
Table 271: SPGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status
13.1.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
345
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IEC 61850 generic communication I/O SP16GGIO - -
functions 16 inputs
13.2.2 Functionality
IEC 61850 generic communication I/O functions 16 inputs (SP16GGIO) function
is used to send up to 16 logical signals to other systems or equipment in the substation.
IEC09000238_en_1.vsd
IEC09000238 V1 EN
346
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.2.4 Signals
Table 272: SP16GGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1 status
IN2 BOOLEAN 0 Input 2 status
IN3 BOOLEAN 0 Input 3 status
IN4 BOOLEAN 0 Input 4 status
IN5 BOOLEAN 0 Input 5 status
IN6 BOOLEAN 0 Input 6 status
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status
13.2.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
13.2.6 MonitoredData
Table 273: SP16GGIO Monitored data
Name Type Values (Range) Unit Description
OUT1 GROUP - - Output 1 status
SIGNAL
OUT2 GROUP - - Output 2 status
SIGNAL
OUT3 GROUP - - Output 3 status
SIGNAL
OUT4 GROUP - - Output 4 status
SIGNAL
OUT5 GROUP - - Output 5 status
SIGNAL
OUT6 GROUP - - Output 6 status
SIGNAL
Table continues on next page
347
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
There are also 16 output signals that show the input status for each input as well as
an OR type output combined for all 16 input signals. These output signals are
handled in PST.
13.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IEC61850 generic communication I/O MVGGIO - -
functions
348
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.3.2 Functionality
IEC61850 generic communication I/O functions (MVGGIO) function is used to
send the instantaneous value of an analog output to other systems or equipment in
the substation. It can also be used inside the same IED, to attach a RANGE aspect
to an analog value and to permit measurement supervision on that value.
IEC09000239-2-en.vsd
13.3.4 Signals
Table 274: MVGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value
13.3.5 Settings
Table 276: MVGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
BasePrefix micro - - unit Base prefix (multiplication factor)
milli
unit
kilo
Mega
Giga
Tera
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range
MV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
Table continues on next page
349
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4 Measurements
13.4.1 Functionality
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
350
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs. There are no interconnections regarding
any settings or parameters, neither between functions nor between signals within
each function.
Zero clampings are handled by ZeroDb for each signal separately for each of the
functions. For example, the zero clamping of U12 is handled by ULZeroDb in
VMMXU, zero clamping of I1 is handled by ILZeroDb in CMMXU.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
The output values are displayed in the local HMI under Main menu/Tests/
Function status/Monitoring/CVMMXN/Outputs
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
351
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Measurements CVMMXN -
P, Q, S, I, U, f
SYMBOL-RR V1 EN
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
CVMMXN
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC08000222.vsd
IEC08000222 V1 EN
352
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.2.3 Signals
Table 278: CVMMXN Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
353
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4.2.4 Settings
Table 280: CVMMXN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
Mode L1, L2, L3 - - L1, L2, L3 Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.00 - 1.00 - 0.01 0.00 Low pass filter coefficient for power
measurement
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UMin 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UMax 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
URepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
Table continues on next page
354
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
355
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
356
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Phase current measurement CMMXU -
I
SYMBOL-SS V1 EN
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
357
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
CMMXU
I3P IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC08000225 V1 EN
13.4.3.3 Signals
Table 283: CMMXU Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
13.4.3.4 Settings
Table 285: CMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
ILDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
ILMax 0 - 500000 A 1 1300 Maximum value
ILRepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
ILAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
358
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Phase-phase voltage measurement VMMXU -
U
SYMBOL-UU V1 EN
359
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL
IEC08000223-2-en.vsd
IEC08000223 V2 EN
13.4.4.3 Signals
Table 288: VMMXU Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
360
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.4.4 Settings
Table 290: VMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
ULDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
ULMax 0 - 4000000 V 1 170000 Maximum value
ULRepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
ULAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
361
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Current sequence component CMSQI -
measurement
I1, I2, I0
SYMBOL-VV V1 EN
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC08000221-2-en.vsd
IEC08000221 V2 EN
13.4.5.3 Signals
Table 293: CMSQI Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
362
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.5.4 Settings
Table 295: CMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0Min 0 - 500000 A 1 0 Minimum value
3I0Max 0 - 500000 A 1 3300 Maximum value
3I0RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1Min 0 - 500000 A 1 0 Minimum value
I1Max 0 - 500000 A 1 1300 Maximum value
I1RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2Min 0 - 500000 A 1 0 Minimum value
I2Max 0 - 500000 A 1 1300 Maximum value
I2RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
363
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Voltage sequence measurement VMSQI -
U1, U2, U0
SYMBOL-TT V1 EN
364
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL
IEC08000224-2-en.vsd
IEC08000224 V2 EN
13.4.6.3 Signals
Table 298: VMSQI Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
365
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.4.6.4 Settings
Table 300: VMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
3U0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3U0Min 0 - 2000000 V 1 0 Minimum value
3U0Max 0 - 2000000 V 1 318000 Maximum value
3U0RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3U0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U1Min 0 - 2000000 V 1 0 Minimum value
U1Max 0 - 2000000 V 1 106000 Maximum value
U1RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
U1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2Min 0 - 2000000 V 1 0 Minimum value
U2Max 0 - 2000000 V 1 106000 Maximum value
U2RepTyp Cyclic - - Dead band Reporting type
Dead band
Int deadband
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
366
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.4.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Phase-neutral voltage measurement VNMMXU -
U
SYMBOL-UU V1 EN
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
367
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC08000226-2-en.vsd
IEC08000226 V2 EN
13.4.7.3 Signals
Table 303: VNMMXU Input signals
Name Type Default Description
U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
13.4.7.4 Settings
Table 305: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Mode On / Off
On
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
UDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UMax 0 - 2000000 V 1 106000 Maximum value
Table continues on next page
368
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
369
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The information on measured quantities is available for the user at different locations:
• Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
• Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.
370
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
en05000657.vsd
IEC05000657 V1 EN
The logical value of the functional output signals changes according to figure 189.
The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
371
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
Value 5
en05000500.vsd
(*)Set value for t: XDbRepInt
IEC05000500 V1 EN
372
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Value Reported
Y
99000529.vsd
IEC99000529 V1 EN
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the ±ΔY set limits. Even if amplitude dead-band reporting is
selected, there will be a 30 s "back-ground" cyclic reporting as well.
The last value reported, Y1 in figure 192 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).
373
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported
t
99000530.vsd
IEC99000530 V1 EN
Mode of operation
The measurement function must be connected to three-phase current and three-
phase voltage input in the configuration tool (group signals), but it is capable to
measure and calculate above mentioned quantities in nine different ways depending
on the available VT inputs connected to the IED. The end user can freely select by
a parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
1 L1, L2, L3 Used when
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3
three phase-
EQUATION1385 V1 EN
to-earth
I = ( I L1 + I L 2 + I L 3 ) / 3
voltages are
EQUATION1386 V1 EN available
2 Arone Used when
S = U L1 L 2 × I L1 - U L 2 L 3 × I L 3
* *
U = ( U L1 L 2 + U L 2 L 3 ) / 2 three two
phase-to-
(Equation 86)
I = ( I L1 + I L 3 ) / 2 phase
EQUATION1387 V1 EN
voltages are
EQUATION1388 V1 EN (Equation 87) available
3 PosSeq Used when
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq only
symmetrical
(Equation 88) three phase
EQUATION1389 V1 EN
I = I PosSeq
power shall
EQUATION1390 V1 EN (Equation 89) be measured
374
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
4 L1L2 Used when
S = U L1 L 2 × ( I L*1 - I L* 2 ) U = U L1 L 2 only UL1L2
phase-to-
(Equation 90)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN
phase
voltage is
EQUATION1392 V1 EN (Equation 91) available
5 L2L3 Used when
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3 only UL2L3
phase-to-
(Equation 92)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN
phase
voltage is
EQUATION1394 V1 EN (Equation 93) available
6 L3L1 Used when
S = U L 3 L1 × ( I L 3 - I L1 )
* *
U = U L 3 L1 only UL3L1
phase-to-
(Equation 94)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN
phase
voltage is
EQUATION1396 V1 EN (Equation 95) available
7 L1 Used when
S = 3 × U L1 × I L1
*
U = 3 × U L1 only UL1
phase-to-
(Equation 96) earth voltage
I = I L1
EQUATION1397 V1 EN
is available
EQUATION1398 V1 EN (Equation 97)
8 L2 Used when
S = 3 ×U L2 × I L2
*
U = 3 × U L2 only UL2
phase-to-
(Equation 98) earth voltage
I = IL2
EQUATION1399 V1 EN
is available
EQUATION1400 V1 EN (Equation 99)
9 L3 Used when
S = 3 ×U L3 × I L3
*
U = 3 × U L3 only UL3
phase-to-
(Equation 100)
I = I L3 earth voltage
EQUATION1401 V1 EN
is available
EQUATION1402 V1 EN (Equation 101)
* means complex conjugated value
It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating
modes that is, from 3 to 9 it calculates the three-phase power under assumption that
the power system is fully symmetrical. Once the complex apparent power is
calculated then the P, Q, S, & PF are calculated in accordance with the following
formulas:
P = Re( S )
EQUATION1403 V1 EN (Equation 102)
375
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Q = Im( S )
EQUATION1404 V1 EN (Equation 103)
S = S = P +Q
2 2
PF = cosj = P
S
EQUATION1406 V1 EN (Equation 105)
Additionally to the power factor value the two binary output signals from the
function are provided which indicates the angular relationship between current and
voltage phasors. Binary output signal ILAG is set to one when current phasor is
lagging behind voltage phasor. Binary output signal ILEAD is set to one when
current phasor is leading the voltage phasor.
376
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN (Equation 106)
where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
377
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.
Compensation facility
In order to compensate for small amplitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it
is possible to perform on site calibration of the power measurement. This is
achieved by setting the complex constant which is then internally used within the
function to multiply the calculated complex apparent power S. This constant is set
as amplitude (setting parameter PowAmpFact, default value 1.000) and angle
(setting parameter PowAngComp, default value 0.0 degrees). Default values for
these two parameters are done in such way that they do not influence internally
calculated value (complex constant has default value 1). In this way calibration, for
specific operating range (for example, around rated power) can be done at site.
However, to perform this calibration it is necessary to have an external power
meter with high accuracy class available.
Directionality
CTStartPoint defines if the CTs earthing point is located towards or from the
protected object under observation. If everything is properly set power is always
measured towards protection object.
378
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Busbar
IED
P Q
Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN
Practically, it means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.
Frequency
Frequency is actually not calculated within measurement block. It is simply
obtained from the pre-processing block and then just given out from the
measurement block as an output.
379
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".
The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section "Measurement supervision".
380
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur < 0.02 2)
0.2 x Ir< I < 4.0 x Ir
1) Accuracy valid for 50 Hz. At 60 Hz both accuracies are ±2.0%
2) Accuracy valid for 50 Hz. At 60 Hz the accuracy is <0.04.
13.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Event counter CNTGGIO -
S00946 V1 EN
13.5.2 Functionality
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.
IEC09000090_1_en.vsd
IEC09000090 V1 EN
13.5.4 Signals
Table 309: CNTGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
COUNTER1 BOOLEAN 0 Input for counter 1
COUNTER2 BOOLEAN 0 Input for counter 2
COUNTER3 BOOLEAN 0 Input for counter 3
COUNTER4 BOOLEAN 0 Input for counter 4
Table continues on next page
381
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.5.5 Settings
Table 311: CNTGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
382
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
To not risk that the flash memory is worn out due to too many writings, a
mechanism for limiting the number of writings per time period is included in the
product. This however gives as a result that it can take long time, up to several
minutes, before a new value is stored in the flash memory. And if a new
CNTGGIO value is not stored before auxiliary power interruption, it will be lost.
CNTGGIO stored values in flash memory will however not be lost at an auxiliary
power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters
at testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
13.5.7.1 Reporting
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.
13.6.1 Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function block that
is, maximum 40 analog and 96 binary signals.
383
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ring-
buffer. The local HMI is used to get information about the recordings. The
disturbance report files may be uploaded to PCM600 for further analysis using the
disturbance handling tool.
13.6.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Disturbance report DRPRDRE - -
IEC09000346-1-en.vsd
IEC09000346 V1 EN
384
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.6.2.3 Signals
Table 314: DRPRDRE Output signals
Name Type Description
DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used
13.6.2.4 Settings
Table 315: DRPRDRE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PreFaultRecT 0.05 - 3.00 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 8.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off - - Off Post-fault retrig enabled (On) or not (Off)
On
MaxNoStoreRec 10 - 100 - 1 100 Maximum number of stored disturbances
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off - - Off Operation mode during test mode
On
385
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
386
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
387
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
388
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
389
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.6.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Analog input signals A1RADR - -
Analog input signals A2RADR - -
Analog input signals A3RADR - -
IEC09000348-1-en.vsd
IEC09000348 V1 EN
Figure 197: A1RADR function block, analog inputs, example for A1RADR,
A2RADR and A3RADR
13.6.3.3 Signals
390
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.6.3.4 Settings
391
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
392
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
393
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.6.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Analog input signals A4RADR - -
394
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
IEC09000350-1-en.vsd
IEC09000350 V1 EN
Channels 31-40 are not shown in LHMI. They are used for
internally calculated analog signals.
13.6.4.3 Signals
Table 321: A4RADR Input signals
Name Type Default Description
INPUT31 REAL 0 Analog channel 31
INPUT32 REAL 0 Analog channel 32
INPUT33 REAL 0 Analog channel 33
INPUT34 REAL 0 Analog channel 34
INPUT35 REAL 0 Analog channel 35
INPUT36 REAL 0 Analog channel 36
INPUT37 REAL 0 Analog channel 37
INPUT38 REAL 0 Analog channel 38
INPUT39 REAL 0 Analog channel 39
INPUT40 REAL 0 Analog channel 40
13.6.4.4 Settings
Table 322: A4RADR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation31 Off - - Off Operation On/off
On
Operation32 Off - - Off Operation On/off
On
Operation33 Off - - Off Operation On/off
On
Table continues on next page
395
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
396
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
397
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
398
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.6.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Binary input signals B1RBDR - -
Binary input signals B2RBDR - -
Binary input signals B3RBDR - -
Binary input signals B4RBDR - -
Binary input signals B5RBDR - -
Binary input signals B6RBDR - -
IEC09000352-1-en.vsd
IEC09000352 V1 EN
Figure 199: B1RBDR function block, binary inputs, example for B1RBDR -
B6RBDR
399
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.6.5.3 Signals
13.6.5.4 Settings
400
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
401
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
402
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
403
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
404
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
Figure 200 shows the relations between Disturbance Report, included functions
and function blocks. Event list , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
405
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
A4RADR DRPRDRE
Analog signals
Trip value rec
B1-6RBDR Disturbance
recorder
Event recorder
Indications
IEC09000337-2-en.vsd
IEC09000337 V2 EN
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile
flash memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.
406
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).
13.6.6.2 Indications
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged), see Indication section for detailed information.
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see Event recorder section for detailed information.
The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see Event list section for detailed information.
The recorded trip values include phasors of selected analog signals before the fault
and during the fault, see Trip value recorder section for detailed information.
Disturbance recorder records analog and binary signal data before, during and after
the fault, see Disturbance recorder section for detailed information.
The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report
407
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Trig point
TimeLimit
PreFaultRecT PostFaultRecT
1 2 3
en05000487.vsd
IEC05000487 V1 EN
PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the
operate time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as
any valid trigger condition, binary or analog, persists (unless limited by TimeLimit
the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording
was triggered. The limit time is used to eliminate the consequences of a trigger
that does not reset within a reasonable time interval. It limits the maximum
recording time of a recording and prevents subsequent overwriting of already
stored disturbances. Use the setting TimeLimit to set this time.
408
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
SMAI A1RADR
GRPNAME AI3P A2RADR
AI1NAME AI1 GRPINPUT1 A3RADR
External analog
AI2NAME AI2 GRPINPUT2
signals
AI3NAME AI3 GRPINPUT3
AI4NAME AI4 GRPINPUT4
AIN GRPINPUT5
GRPINPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
Internal analog signals INPUT34
INPUT35
INPUT36
...
INPUT40
en05000653-2.vsd
IEC05000653 V2 EN
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used).SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
409
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
If Operation = On, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.
The selected signals are presented in the event recorder, event list and the
disturbance recording. But they affect the whole disturbance report when they are
used as triggers. The indications are also selected from these 96 signals with local
HMI IndicationMask=Show/Hide.
The trigger conditions affect the entire disturbance report, except the event list,
which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition
is fulfilled, there is no disturbance report, no indications, and so on. This implies
the importance of choosing the right signals as trigger conditions.
• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)
Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or
via station bus (IEC 61850). When the trigger is activated, the manual trigger
signal is generated. This feature is especially useful for testing.
410
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a
trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to
generate a trigger from a logic zero, the selected signal will not be listed in the
indications list of the disturbance report.
Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the
average value is above the threshold level for an overvoltage or overcurrent trigger,
this trigger is indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.
This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in
the range of one cycle, 20 ms for a 50 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.
Disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be fetched.
411
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.7 Indications
13.7.1 Functionality
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know, for example binary signals
that have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (trigged).
The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.
412
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.7.3 Signals
The Indications function may log the same binary input signals as the Disturbance
report function.
Green LED:
Yellow LED:
Red LED:
Indication list:
The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
413
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The name of the binary input signal that appears in the Indication function is the user-
defined name assigned at configuration of the IED. The same name is used in
disturbance recorder function , indications and event recorder function .
13.8.1 Functionality
Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time-tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example functional analysis).
The event recorder logs all selected binary input signals connected to the
Disturbance report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
13.8.3 Signals
The Event recorder function logs the same binary input signals as the Disturbance
report function.
414
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
be generated by both internal logical signals and binary input channels. The
internal signals are time-tagged in the main processor module, while the binary
input channels are time-tagged directly in each I/O module. The events are
collected during the total recording time (pre-, post-fault and limit time), and are
stored in the disturbance report flash memory at the end of each recording.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when configuring the IED. The same name is used in the
disturbance recorder function , indications and event recorder function .
The event record is stored as a part of the disturbance report information and
managed via the local HMI or PCM600.
Events can not be read from the IED if more than one user is
accessing the IED simultaneously.
13.9.1 Functionality
Continuous event-logging is useful for monitoring the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the Disturbance report
function. The list may contain up to 1000 time-tagged events stored in a ring-buffer.
415
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.9.3 Signals
The Event list logs the same binary input signals as configured for the Disturbance
report function.
The list can be configured to show oldest or newest events first with a setting on
the local HMI.
The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when the IED is configured. The same name is used in the
disturbance recorder function , indications and the event recorder function .
The event list is stored and managed separate from the disturbance report information .
13.10.1 Functionality
Information about the pre-fault and fault values for currents and voltages are vital
for the disturbance evaluation.
416
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase
angle before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the
IED.
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).
13.10.3 Signals
The trip value recorder function uses analog input signals connected to A1RADR
to A3RADR (not A4RADR).
When the disturbance report function is triggered the sample for the fault
interception is searched for, by checking the non-periodic changes in the analog
input signals. The channel search order is consecutive, starting with the analog
input with the lowest number.
When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated
using the Recursive Least Squares (RLS) method. The calculation starts a few
samples after the fault sample and uses samples during 1/2 - 2 cycles depending on
the shape of the signals.
If no starting point is found in the recording, the disturbance report trig sample is
used as the start sample for the Fourier estimation. The estimation uses samples
during one cycle before the trig sample. In this case the calculated values are used
both as pre-fault and fault values.
The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function .
417
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The trip value record is stored as a part of the disturbance report information and
managed in via the local HMI or PCM600.
13.11.1 Functionality
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system
behavior and related primary and secondary equipment during and after a
disturbance. Recorded information is used for different purposes in the short
perspective (for example corrective actions) and long perspective (for example
functional analysis).
The Disturbance recorder acquires sampled data from selected analog- and binary
signals connected to the Disturbance report function (maximum 40 analog and 96
binary signals). The binary signals available are the same as for the event recorder
function.
The disturbance recorder information for the last 100 disturbances are saved in the
IED and the local HMI is used to view the list of recordings.
13.11.3 Signals
418
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as
long as the fault condition prevails - plus a certain additional time. This is called
the post-fault time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common
for all functions within the disturbance report functionality.
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
419
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
• Saving the data for analog channels with corresponding data for binary signals
• Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
• Compression of the data, which is performed without losing any data accuracy
• Storing the compressed data in a non-volatile memory (flash memory)
The recording files comply with the Comtrade standard IEC 60255-24 and are
divided into three files; a header file (HDR), a configuration file (CFG) and a data
file (DAT).
The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions . The
Disturbance handling tool use this information and present the recording in a user-
friendly way.
General:
Analog:
Binary:
• Signal names
• Status of binary input signals
The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.
420
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.12.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Measured value expander block MVEXP - -
13.12.2 Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-
high limit. The measure value expander block has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary
signals: below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable
logic or for alarming purpose.
IEC09000215-1-en.vsd
IEC09000215 V1 EN
421
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.12.4 Signals
13.12.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in a Global base values for settings function
GBASVAL. Setting GlobalBaseSel is used to select a GBASVAL function for
reference of base values.
422
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.13.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Insulation gas monitoring function SSIMG - 63
13.13.2 Functionality
Insulation gas monitoring function (SSIMG) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit
breaker is used as input signals to the function. In addition, the function generates
alarms based on received information.
IEC09000129-1-en.vsd
IEC09000129 V1 EN
13.13.4 Signals
423
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.13.5 Settings
Table 338: SSIMG Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PressAlmLimit 0.00 - 25.00 - 0.01 5.00 Alarm setting for pressure
PressLOLimit 0.00 - 25.00 - 0.01 3.00 Pressure lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the medium
tPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarm
tPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetPressAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarm
tResetPressLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockout
424
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
circuit breaker is below alarm level, the function initiates output signal
PRES_ALM, pressure below alarm level, after a set time delay and indicate that
maintenance of the circuit breaker is required. Similarly, if the input signal
PRES_LO is high, which indicate gas pressure in the circuit breaker is below
lockout level, the function initiates output signal PRES_LO, after a time delay. The
two time delay settings, tPressureAlarm and tPressureLO, are included in order not
to initiate any alarm for short sudden changes in the gas pressure. If the gas
pressure in the circuit breaker goes below the levels for more than the set time
delays the corresponding signals, PRES_ALM, pressure below alarm level and
PRES_LO, pressure below lockout level alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms and the input signal
BLOCK to block both alarms and the function.
13.14.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Insulation liquid monitoring function SSIML - 71
13.14.2 Functionality
Insulation liquid monitoring function (SSIML) is used for monitoring the circuit
breaker condition. Binary information based on the oil level in the circuit breaker is
used as input signals to the function. In addition, the function generates alarms
based on received information.
425
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
IEC09000128-1-en.vsd
IEC09000128 V1 EN
13.14.4 Signals
426
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.14.5 Settings
Table 342: SSIML Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
LevelAlmLimit 0.00 - 25.00 - 0.01 5.00 Alarm setting for level
LevelLOLimit 0.00 - 25.00 - 0.01 3.00 Level lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the medium
tLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarm
tLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarm
tResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm
The input signal BLK_ALM is used to block the two alarms and the input signal
BLOCK to block both alarms and the function.
427
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.15.1 Identification
13.15.2 Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor
different parameters of the circuit breaker. The breaker requires maintenance when
the number of operations has reached a predefined value. The energy is calculated
from the measured input currents as a sum of Iyt values. Alarms are generated
when the calculated values exceed the threshold settings.
GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
428
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.15.4 Signals
Table 344: SSCBR Input signals
Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLK_ALM BOOLEAN 0 Block all the alarms
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
ALMPRES BOOLEAN 0 Binary pressure alarm input
LOPRES BOOLEAN 0 Binary pressure input for lockout indication
SPRCHRGN BOOLEAN 0 CB spring charging started input
SPRCHRGD BOOLEAN 0 CB spring charged input
CBCNTRST BOOLEAN 0 Reset input for CB remaining life and operation
counter
IACCRST BOOLEAN 0 Reset accumulated currents power
SPCHTRST BOOLEAN 0 Reset spring charge time
TRVTRST BOOLEAN 0 Reset travel time
429
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.15.5 Settings
Table 346: SSCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
AccDisLevel 5.00 - 500.00 A 0.01 10.00 RMS current setting below which energy
accumulation stops
CurrExp 0.00 - 2.00 - 0.01 2.00 Current exponent setting for energy
calculation
RatedFaultCurr 500.00 - 75000.00 A 0.01 5000.00 Rated fault current of the breaker
RatedOpCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the breaker
AccCurrAlmLvl 0.00 - 20000.00 - 0.01 2500.00 Setting of alarm level for accumulated
currents power
AccCurrLO 0.00 - 20000.00 - 0.01 2500.00 Lockout limit setting for accumulated
currents power
DirCoef -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life
calculation
LifeAlmLevel 0 - 99999 - 1 5000 Alarm level for CB remaining life
OpNumRatCurr 1 - 99999 - 1 10000 Number of operations possible at rated
current
OpNumFaultCurr 1 - 10000 - 1 1000 Number of operations possible at rated
fault current
OpNumAlm 0 - 9999 - 1 200 Alarm limit for number of operations
OpNumLO 0 - 9999 - 1 300 Lockout limit for number of operations
tOpenAlm 0 - 200 ms 1 40 Alarm level setting for open travel time
tCloseAlm 0 - 200 ms 1 40 Alarm level setting for close travel time
OpenTimeCorr 0 - 100 ms 1 10 Correction factor for open travel time
CloseTimeCorr 0 - 100 ms 1 10 Correction factor for CB close travel time
DifTimeCorr -10 - 10 ms 1 5 Correction factor for time difference in
auxiliary and main contacts open time
tSprngChrgAlm 0.00 - 60.00 s 0.01 1.00 Setting of alarm for spring charging time
tPressAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarm
TPressLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockout
AccEnerInitVal 0.00 - 9999.99 - 0.01 0.00 Accumulation energy initial value
CountInitVal 0 - 9999 - 1 0 Operation numbers counter initialization
value
CBRemLife 0 - 9999 - 1 5000 Initial value for the CB remaining life
estimates
InactDayAlm 0 - 9999 Day 1 2000 Alarm limit value of the inactive days
counter
InactDayInit 0 - 9999 Day 1 0 Initial value of the inactive days counter
InactHourAlm 0 - 23 Hour 1 0 Alarm time of the inactive days counter
in hours
430
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The operation of the functions can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
431
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
GUID-FE21BBDC-57A6-425C-B22B-8E646C1BD932 V1 EN
The circuit breaker status subfunction monitors the position of the circuit breaker,
that is, whether the breaker is in an open, closed or intermediate position. The
operation of the breaker status monitoring can be described by using a module
diagram. All the modules in the diagram are explained in the next sections.
432
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
GUID-60ADC120-4B5A-40D8-B1C5-475E4634214B V1 EN
Figure 208: Functional module diagram for monitoring circuit breaker status
The status of the breaker is indicated with the binary outputs CBOPEN, CBINVPOS
and CBCLOSED for open, intermediate and closed position respectively.
The operation of the circuit breaker operation monitoring can be described by using
a module diagram. All the modules in the diagram are explained in the next sections.
GUID-82C88B52-1812-477F-8B1A-3011A300547A V1 EN
Figure 209: Functional module diagram for calculating inactive days and alarm
for circuit breaker operation monitoring
433
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
Inactivity timer
The module calculates the number of days the circuit breaker has remained
inactive, that is, has stayed in the same open or closed state. The calculation is done
by monitoring the states of the POSOPEN and POSCLOSE auxiliary contacts.
The inactive days NOOPRDAY is available through the Monitored data view. It is
also possible to set the initial inactive days by using the InactDayInit parameter.
The breaker contact travel time module calculates the breaker contact travel time
for the closing and opening operation. The operation of the breaker contact travel
time measurement can be described by using a module diagram. All the modules in
the diagram are explained in the next sections.
GUID-4D82C157-53AF-40C9-861C-CF131B49072B V1 EN
Figure 210: Functional module diagram for breaker contact travel time
434
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
GUID-3AD25F5A-639A-4941-AA61-E69FA2357AFE V1 EN
There is a time difference t1 between the start of the main contact opening and the
opening of the POSCLOSE auxiliary contact. Similarly, there is a time gap t2
between the time when the POSOPEN auxiliary contact opens and the main contact
is completely open. Therefore, in order to incorporate the time t1+t2, a correction
factor needs to be added with 10 to get the actual opening time. This factor is
added with the OpenTimeCorr (=t1+t2). The closing time is calculated by adding
the value set with the CloseTimeCorr (t3+t4) setting to the measured closing time.
The last measured opening travel time tTravelOpen and the closing travel time
tTravelClose are available through the Monitored data view on the LHMI or
through tools via communications.
It is also possible to block the TRVTCAL and TRVTOAL alarm signals by activating
the BLOCK input.
The operation of the subfunction can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
435
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
GUID-FF1221A4-6160-4F92-9E7F-A412875B69E1 V1 EN
Figure 211: Functional module diagram for counting circuit breaker operations
Operation counter
The operation counter counts the number of operations based on the state change of
the binary auxiliary contacts inputs POSCLOSE and POSOPEN.
The number of operations NO_OPR is available through the Monitored data view
on the LHMI or through tools via communications. The old circuit breaker
operation counter value can be taken into use by writing the value to the
CountInitVal parameter and can be reset by Clear CB wear in the clear menu from
LHMI.
The binary outputs OPRLOALM and OPRALM are deactivated when the BLOCK
input is activated.
The operation of the module can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
436
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
GUID-DAC3746F-DFBF-4186-A99D-1D972578D32A V1 EN
The calculation is initiated with the POSCLOSE input open events. It ends when
the RMS current becomes lower than the AccDisLevel setting value.
GUID-75502A39-4835-4F43-A7ED-A80DC7C1DFA2 V1 EN
The DiffTimeCorr setting is used instead of the auxiliary contact to accumulate the
energy from the time the main contact opens. If the setting is positive, the
calculation of energy starts after the auxiliary contact has opened and when the
delay is equal to the value set with the DiffTimeCorr setting. When the setting is
negative, the calculation starts in advance by the correction time before the
auxiliary contact opens.
The accumulated energy outputs IACCL1 (L2, L3) are available through the
Monitored data view on the LHMI or through tools via communications. The
values can be reset by setting the Clear accum. breaking curr setting to true in the
clear menu from LHMI.
437
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The IACCALM and IACCLOAL outputs can be blocked by activating the binary
input BLOCK.
Every time the breaker operates, the life of the circuit breaker reduces due to
wearing. The wearing in the breaker depends on the tripping current, and the
remaining life of the breaker is estimated from the circuit breaker trip curve
provided by the manufacturer. The remaining life is decremented at least with one
when the circuit breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be
described by using a module diagram. All the modules in the diagram are explained
in the next sections.
GUID-1565CD41-3ABF-4DE7-AF68-51623380DF29 V1 EN
Figure 214: Functional module diagram for estimating the life of the circuit
breaker
438
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
The remaining life is calculated separately for all three phases and it is available as
a monitored data value CB_LIFE_A (_B,_C). The values can be cleared by
setting the parameter CB wear values in the clear menu from LHMI.
The remaining life is calculated separately for all three phases and it is available as
a monitored data value CBLIFEL1 (L2, L3).
The circuit breaker spring charged indication subfunction calculates the spring
charging time.
The operation of the subfunction can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
GUID-37EB9FAE-8129-45AB-B9F7-7F7DC829E3ED V1 EN
Figure 215: Functional module diagram for circuit breaker spring charged
indication and alarm
439
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
The spring charging time SPRCHRT is available through the Monitored data view .
It is possible to block the SPRCHRAL alarm signal by activating the BLOCK binary
input.
The gas pressure supervision subfunction monitors the gas pressure inside the arc
chamber.
The operation of the subfunction can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
GUID-A913D2D7-398B-41F6-9B21-BBCECD3F596D V1 EN
Figure 216: Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals LOPRES and
ALMPRES.
If the pressure drops further to a very low level, the LOPRES binary input becomes
high, activating the lockout alarm PRESLO after a time delay set with the
TPressLO setting. The PRESLO alarm can be blocked by activating the BLOCK input.
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates all outputs and resets internal timers. The alarm signals
from the function can be blocked by activating the binary input BLK_ALM.
440
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.16.1 Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measurand reporting interval set for MMXU function blocks, using the
xDbRepInt and xAngDbRepInt settings, must be coordinated with the event
reporting interval set for the IEC 60870-5-103 communication using setting
CycMeasRepTime.
441
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
GUID-B8A3A04C-430D-4488-9F72-8529FAB0B17D V1 EN
IEC10000287-1-en.vsd
IEC10000287 V1 EN
442
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.16.3 Signals
Table 349: I103MEAS Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
IL1 REAL 0.0 Service value for current phase L1
IL2 REAL 0.0 Service value for current phase L2
IL3 REAL 0.0 Service value for current phase L3
IN REAL 0.0 Service value for residual current IN
UL1 REAL 0.0 Service value for voltage phase L1
UL2 REAL 0.0 Service value for voltage phase L2
UL3 REAL 0.0 Service value for voltage phase L3
UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2
UN REAL 0.0 Service value for residual voltage UN
P REAL 0.0 Service value for active power
Q REAL 0.0 Service value for reactive power
F REAL 0.0 Service value for system frequency
13.16.4 Settings
Table 350: I103MEAS Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
MaxIL1 1 - 99999 A 1 3000 Maximum current phase L1
MaxIL2 1 - 99999 A 1 3000 Maximum current phase L2
MaxIL3 1 - 99999 A 1 3000 Maximum current phase L3
MaxIN 1 - 99999 A 1 3000 Maximum residual current IN
MaxUL1 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L1
MaxUL2 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L2
MaxUL3 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L3
MaxUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase L1-L2
MaxUN 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage UN
MaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active power
MaxQ 0.00 - 2000.00 MVA 0.05 1200.00 Maximum value for reactive power
MaxF 50.0 - 60.0 Hz 10.0 50.0 Maximum system frequency
443
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.17.1 Functionality
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each
block in the private range, and the Information number parameter for each block.
IEC10000288-1-en.vsd
IEC10000288 V1 EN
13.17.3 Signals
Table 351: I103MEASUSR Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
INPUT1 REAL 0.0 Service value for measurement on input 1
INPUT2 REAL 0.0 Service value for measurement on input 2
INPUT3 REAL 0.0 Service value for measurement on input 3
INPUT4 REAL 0.0 Service value for measurement on input 4
INPUT5 REAL 0.0 Service value for measurement on input 5
INPUT6 REAL 0.0 Service value for measurement on input 6
INPUT7 REAL 0.0 Service value for measurement on input 7
INPUT8 REAL 0.0 Service value for measurement on input 8
INPUT9 REAL 0.0 Service value for measurement on input 9
444
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.17.4 Settings
Table 352: I103MEASUSR Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 25 Function type (1-255)
InfNo 1 - 255 - 1 1 Information number for measurands
(1-255)
MaxMeasur1 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 1
MaxMeasur2 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 2
MaxMeasur3 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 3
MaxMeasur4 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 4
MaxMeasur5 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 5
MaxMeasur6 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 6
MaxMeasur7 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 7
MaxMeasur8 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 8
MaxMeasur9 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 9
13.18.1 Functionality
I103AR is a function block with defined functions for autorecloser indications in
monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
IEC10000289-1-en.vsd
IEC10000289 V1 EN
445
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
13.18.3 Signals
Table 353: I103AR Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
16_ARACT BOOLEAN 0 Information number 16, auto-recloser active
128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-
recloser
130_UNSU BOOLEAN 0 Information number 130, unsuccessful reclosing
13.18.4 Settings
Table 354: I103AR Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
13.19.1 Functionality
I103EF is a function block with defined functions for earth fault indications in
monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
IEC10000290-1-en.vsd
IEC10000290 V1 EN
13.19.3 Signals
Table 355: I103EF Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, earth-fault forward
52_EFREV BOOLEAN 0 Information number 52, earth-fault reverse
446
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.19.4 Settings
Table 356: I103EF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 160 Function type (1-255)
13.20.1 Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that
is triggering the Disturbance Recorder and the respective configured signal to the
IEC 60870-5-103 I103FLTPROT.
447
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
IEC10000291-1-en.vsd
IEC10000291 V1 EN
13.20.3 Signals
Table 357: I103FLTPROT Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting.
64_STL1 BOOLEAN 0 Information number 64, start phase L1
65_STL2 BOOLEAN 0 Information number 65, start phase L2
66_STL3 BOOLEAN 0 Information number 66, start phase L3
67_STIN BOOLEAN 0 Information number 67, start residual current IN
68_TRGEN BOOLEAN 0 Information number 68, trip general
69_TRL1 BOOLEAN 0 Information number 69, trip phase L1
70_TRL2 BOOLEAN 0 Information number 70, trip phase L2
71_TRL3 BOOLEAN 0 Information number 71, trip phase L3
72_TRBKUP BOOLEAN 0 Information number 72, back up trip I>>
73_SCL REAL 0 Information number 73, fault location in ohm
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/busbar
Table continues on next page
448
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.20.4 Settings
Table 358: I103FLTPROT Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 128 Function type (1-255)
13.21.1 Functionality
I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as FunctionType, and information number parameter is
defined for each input signal.
449
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
IEC10000292-1-en.vsd
IEC10000292 V1 EN
13.21.3 Signals
Table 359: I103IED Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active
13.21.4 Settings
Table 360: I103IED Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
13.22.1 Functionality
I103SUPERV is a function block with defined functions for supervision indications
in monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
450
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
IEC10000293-1-en.vsd
IEC10000293 V1 EN
13.22.3 Signals
Table 361: I103SUPERV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of
I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of
U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up
protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm
13.22.4 Settings
Table 362: I103SUPERV Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
13.23.1 Functionality
I103USRDEF is a function blocks with user defined input signals in monitor
direction. These function blocks include the FunctionType parameter for each
block in the private range, and the information number parameter for each input
signal.
451
Technical Manual
Section 13 1MRK 502 034-UEN -
Monitoring
I103USRDEF can be used, for example in mapping the INF numbers not supported
directly by specific function blocks, like: INF17, INF18, INF20 or INF35. After
connecting the appropriate signals to the I103USRDEF inputs, the user must also
set the InfNo_x values in the settings.
GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 EN
IEC10000294-1-en.vsd
IEC10000294 V1 EN
13.23.3 Signals
Table 363: I103USRDEF Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
INPUT1 BOOLEAN 0 Binary signal Input 1
INPUT2 BOOLEAN 0 Binary signal input 2
INPUT3 BOOLEAN 0 Binary signal input 3
INPUT4 BOOLEAN 0 Binary signal input 4
INPUT5 BOOLEAN 0 Binary signal input 5
INPUT6 BOOLEAN 0 Binary signal input 6
INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8
452
Technical Manual
1MRK 502 034-UEN - Section 13
Monitoring
13.23.4 Settings
Table 364: I103USRDEF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 5 Function type (1-255)
InfNo_1 1 - 255 - 1 1 Information number for binary input 1
(1-255)
InfNo_2 1 - 255 - 1 2 Information number for binary input 2
(1-255)
InfNo_3 1 - 255 - 1 3 Information number for binary input 3
(1-255)
InfNo_4 1 - 255 - 1 4 Information number for binary input 4
(1-255)
InfNo_5 1 - 255 - 1 5 Information number for binary input 5
(1-255)
InfNo_6 1 - 255 - 1 6 Information number for binary input 6
(1-255)
InfNo_7 1 - 255 - 1 7 Information number for binary input 7
(1-255)
InfNo_8 1 - 255 - 1 8 Information number for binary input 8
(1-255)
453
Technical Manual
454
1MRK 502 034-UEN - Section 14
Metering
Section 14 Metering
14.1.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Pulse counter PCGGIO -
S00947 V1 EN
14.1.2 Functionality
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the BIO (binary input/output)
module and then read by the PCGGIO function. A scaled service value is available
over the station bus.
IEC09000335-2-en.vsd
IEC09000335 V2 EN
14.1.4 Signals
Table 365: PCGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
RS_CNT BOOLEAN 0 Resets pulse counter value
455
Technical Manual
Section 14 1MRK 502 034-UEN -
Metering
14.1.5 Settings
Table 367: PCGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EventMask NoEvents - - NoEvents Report mask for analog events from
ReportEvents pulse counter
CountCriteria Off - - RisingEdge Pulse counter criteria
RisingEdge
Falling edge
OnChange
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to
unit per counted value
Quantity Count - - Count Measured quantity for SCAL_VAL output
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting 1 - 3600 s 1 60 Cycle time for reporting of counter value
456
Technical Manual
1MRK 502 034-UEN - Section 14
Metering
The reporting time period can be set in the range from 1 second to 60 minutes and
is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by IEC 61850.
The reported value to station HMI over the station bus contains Identity, Scaled
Value (pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter
Quality consists of:
The transmission of the counter value can be done as a service value, that is, the
value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can
be time tagged, and transmitted to the station HMI. This time corresponds to the
time when the value was frozen by the function.
The BLOCK and READ_VAL inputs can be connected to blocks, which are
intended to be controlled either from the station HMI or/and the local HMI. As
long as the BLOCK signal is set, the pulse counter is blocked. The signal
connected to READ_VAL performs readings according to the setting of parameter
CountCriteria. The signal must be a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
binary input output module (BIO).
Each PCGGIO function block has four binary output signals that can be used for
for event recording: INVALID, RESTART, BLOCKED and NEW_VAL. These
signals and the SCAL_VAL signal are accessable over IEC 61850.
The INVALID signal is a steady signal and is set if the binary input module, where
the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-
up, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.
457
Technical Manual
Section 14 1MRK 502 034-UEN -
Metering
The BLOCKED signal is a steady signal and is set when the counter is blocked.
There are two reasons why the counter is blocked:
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
14.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Energy calculation and demand ETPMMTR -
handling
Wh
IEC10000169 V1 EN
14.2.2 Functionality
Outputs from the Measurements (CVMMXN) function can be used to calculate
energy consumption. Active as well as reactive values are calculated in import and
export direction. Values can be read or generated as pulses. Maximum demand
power values are also calculated by the function.
458
Technical Manual
1MRK 502 034-UEN - Section 14
Metering
14.2.4 Signals
Table 370: ETPMMTR Input signals
Name Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STACC BOOLEAN 0 Start to accumulate energy values
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading
459
Technical Manual
Section 14 1MRK 502 034-UEN -
Metering
14.2.5 Settings
Table 372: ETPMMTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
StartAcc Off - - Off Activate the accumulation of energy
On values
tEnergy 1 Minute - - 1 Minute Time interval for energy calculation
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls 0.000 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time
tEnergyOffPls 0.000 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value
460
Technical Manual
1MRK 502 034-UEN - Section 14
Metering
461
Technical Manual
Section 14 1MRK 502 034-UEN -
Metering
connected to a pulse counter. Outputs are available for forward as well as reverse
direction. The accumulated energy values can be reset from the local HMI reset
menu or with input signal RSTACC.
The maximum demand values for active and reactive power are calculated for the
set time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until
reset with input signal RSTDMD or from the local HMI reset menu.
CVMMXN ETPMMTR
P_INST P
Q_INST Q
STACC
TRUE
RSTACC
FALSE
RSTDMD
FALSE
IEC09000106.vsd
IEC09000106 V1 EN
462
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
15.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IEC 61850-8-1 communication protocol IEC 61850-8-1 - -
15.2.2 Functionality
The IED supports the communication protocols IEC 61850-8-1 and DNP3 over TCP/
IP. All operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication (GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1
communication protocol.
The IED is equipped with an optical Ethernet rear port for the substation
communication standard IEC 61850-8-1. IEC 61850-8-1 protocol allows intelligent
electrical devices (IEDs) from different vendors to exchange information and
simplifies system engineering. Peer-to-peer communication according to GOOSE
is part of the standard. Disturbance files uploading is provided.
Disturbance files are accessed using the IEC 61850-8-1 protocol. Disturbance files
are available to any Ethernet based application via FTP in the standard Comtrade
format. Further, the IED can send and receive binary values, double point values
and measured values (for example from MMXU functions), together with their
quality, using the IEC 61850-8-1 GOOSE profile. The IED meets the GOOSE
performance requirements for tripping applications in substations, as defined by the
IEC 61850 standard. The IED interoperates with other IEC 61850-compliant IEDs,
tools, and systems and simultaneously reports events to five different clients on the
IEC 61850 station bus.
463
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
The event system has a rate limiter to reduce CPU load. The event channel has a
quota of 10 events/second. If the quota is exceeded the event channel transmission
is blocked until the event changes is below the quota, no event is lost.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the fibre-optic multimode LC connector (100BASE-FX).
The IED supports SNTP and IRIG-B time synchronization methods with a time-
stamping resolution of 1 ms.
The IED supports IEC 60870-5-103 time synchronization methods with a time
stamping resolution of 5 ms.
15.2.3 Settings
Table 377: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
GOOSE Front - - LAN1 Port for GOOSE communication
LAN1
464
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
15.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Horizontal communication via GOOSE GOOSEINTLKR - -
for interlocking CV
465
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
IEC09000099_1_en.vsd
IEC09000099 V1 EN
15.3.3 Signals
Table 379: GOOSEINTLKRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
466
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
467
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
15.3.4 Settings
Table 381: GOOSEINTLKRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
15.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Goose binary receive GOOSEBINRCV - -
468
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
IEC09000236_en.vsd
IEC09000236 V1 EN
15.4.3 Signals
Table 382: GOOSEBINRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
469
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
15.4.4 Settings
Table 384: GOOSEBINRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
470
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
15.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
GOOSE function block to receive a GOOSEDPRCV - -
double point value
15.5.2 Functionality
GOOSEDPRCV is used to receive a double point value from the sender using
IEC61850 protocol over GOOSE.
IEC10000249-1-en.vsd
IEC10000249 V1 EN
15.5.4 Signals
Table 385: GOOSEDPRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
471
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
15.5.5 Settings
Table 387: GOOSEDPRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
15.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
GOOSE function block to receive an GOOSEINTRCV - -
integer value
15.6.2 Functionality
GOOSEINTRCV is used to receive an integer value from the sender using
IEC61850 protocol over GOOSE.
472
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
IEC10000250-1-en.vsd
IEC10000250 V1 EN
15.6.4 Signals
Table 388: GOOSEINTRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
15.6.5 Settings
Table 390: GOOSEINTRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
473
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
15.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
GOOSE function block to receive a GOOSEMVRCV - -
measurand value
15.7.2 Functionality
GOOSEMVRCV is used to receive measured value from the sender using
IEC61850 protocol over GOOSE.
IEC10000251-1-en.vsd
IEC10000251 V1 EN
15.7.4 Signals
Table 391: GOOSEMVRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
474
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
15.7.5 Settings
Table 393: GOOSEMVRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
15.8.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
GOOSE function block to receive a GOOSESPRCV - -
single point value
475
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
15.8.2 Functionality
GOOSESPRCV is used to receive a single point value from the sender using
IEC61850 protocol over GOOSE.
IEC10000248-1-en.vsd
IEC10000248 V1 EN
15.8.4 Signals
Table 394: GOOSESPRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
15.8.5 Settings
Table 396: GOOSESPRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
476
Technical Manual
1MRK 502 034-UEN - Section 15
Station communication
15.9.1 Functionality
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data
transfer rate up to 38400 bit/s. In IEC terminology, a primary station is a master
and a secondary station is a slave. The communication is based on a point-to-point
principle. The master must have software that can interpret IEC 60870-5-103
communication messages.
Function blocks available for the IEC 60870–5–103 protocol are described in
sections Control and Monitoring.The Communication protocol manual for IEC
60870-5-103 includes the 650 series vendor specific IEC 60870-5-103
implementation.
15.9.2 Settings
Table 397: IEC60870-5-103 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
SlaveAddress 1 - 31 - 1 1 Slave address
BaudRate 9600 Bd - - 9600 Bd Baudrate on serial line
19200 Bd
RevPolarity Off - - On Invert polarity
On
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC - - UTC Master time domain
Local
Local with DST
Table continues on next page
477
Technical Manual
Section 15 1MRK 502 034-UEN -
Station communication
478
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
A time counter is used for filtering. The time counter is increased once in a
millisecond when a binary input is high, or decreased when a binary input is low. A
new debounced binary input signal is forwarded when the time counter reaches the
set DebounceTimevalue and the debounced input value is low or when the time
counter reaches 0 and the debounced input value is high.
The binary input ON-event gets the time stamp of the first rising edge, after which
the counter does not reach 0 again. The same happens when the signal goes down
to 0 again.
Each binary input has a filter time parameter DebounceTime#, where # is the
number of the binary input of the module in question (for example DebounceTime1).
Each debounced input signal change increments an oscillation counter. Every time
the oscillation time counter reaches the set OscillationTime, the oscillation counter
is checked and both the counters are reset. If the counter value is above the set
OscillationCount value the signal is declared as oscillating. If the value is below
the set OscillationCount value, the signal is declared as valid again. During
counting of the oscillation time the status of the signal remains unchanged, leading
to a fixed delay in the status update, even if the signal has attained normal status again.
479
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
480
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.2.1 Functionality
The Self supervision with internal event list (INTERRSIG and SELFSUPEVLST)
function reacts to internal system events generated by the different built-in self-
supervision elements. The internal events are saved in an internal event list.
16.2.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Internal error signal INTERRSIG - -
IEC09000334-1-en.vsd
IEC09000334 V1 EN
16.2.2.3 Signals
Table 400: INTERRSIG Output signals
Name Type Description
FAIL BOOLEAN Internal fail
WARNING BOOLEAN Internal warning
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error
STUPBLK BOOLEAN Application startup block
481
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.2.2.4 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
16.2.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Internal event list SELFSUPEVLST - -
16.2.3.2 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
The SELFSUPEVLST function status can be monitored from the local HMI, from
the Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.
482
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
IEC09000390-1-en.vsd
IEC09000390 V1 EN
483
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
LIODEV FAIL
>1
LIODEV STOPPED S e.g.BIO1- ERROR
R
LIODEV STARTED
DNP 3 STARTUP
ERROR S
DNP 3 READY R
CHANGE LOCK ON
S
Change lock
CHANGE LOCK OFF R
SETTINGS CHANGED Setting groups changed
IEC09000381-1-en.vsd
IEC09000381 V1 EN
Some signals are available from the INTERRSIG function block. The signals from
INTERRSIG function block are sent as events to the station level of the control
system. The signals from the INTERRSIG function block can also be connected to
binary outputs for signalization via output relays or they can be used as conditions
for other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix tool. Error signals from time synchronization can be obtained
from the time synchronization block INTERSIG.
SELFSUPEVLST function provides several status signals, that tells about the
condition of the IED. As they provide information about the internal status of the
484
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
IED, they are also called internal signals. The internal signals can be divided into
two groups.
• Standard signals are always presented in the IED, see Table 401.
• Hardware dependent internal signals are collected depending on the hardware
configuration, see Table 402.
485
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see Figure
239.
486
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
ADx
Adx_Low
x1
u1
x2
Adx
Adx_High Controller
x1
u1
x2
en05000296-2-en.vsd
IEC05000296 V2 EN
The technique to split the analog input signal into two A/D converters with
different amplification makes it possible to supervise the incoming signals under
normal conditions where the signals from the two converters should be identical.
An alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.
When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given.
487
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.3.1 Functionality
The time synchronization source selector is used to select a common source of
absolute time for the IED when it is a part of a protection system. This makes it
possible to compare event- and disturbance data between all IEDs in a station
automation system possible.
16.3.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time synchronization TIMESYNCHGE - -
N
16.3.2.2 Settings
Table 405: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off - - Off Coarse time synchronization source
SNTP
DNP
IEC60870-5-103
FineSyncSource Off - - Off Fine time synchronization source
SNTP
IRIG-B
SyncMaster Off - - Off Activate IED as synchronization master
SNTP-Server
16.3.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time synchronization via SNTP SNTP - -
488
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.3.3.2 Settings
Table 406: SNTP Non group settings (basic)
Name Values (Range) Unit Step Default Description
ServerIP-Add 0 - 255 IP 1 0.0.0.0 Server IP-address
Address
RedServIP-Add 0 - 255 IP 1 0.0.0.0 Redundant server IP-address
Address
16.3.4.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time system, summer time begins DSTBEGIN - -
16.3.4.2 Settings
Table 407: DSTBEGIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
MonthInYear January - - March Month in year when daylight time starts
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time starts
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time starts
First
Second
Third
Fourth
UTCTimeOfDay 00:00 - - 1:00 UTC Time of day in hours when daylight
00:30 time starts
1:00
1:30
...
48:00
489
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.3.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time system, summer time ends DSTEND - -
16.3.5.2 Settings
Table 408: DSTEND Non group settings (basic)
Name Values (Range) Unit Step Default Description
MonthInYear January - - October Month in year when daylight time ends
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time ends
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time ends
First
Second
Third
Fourth
UTCTimeOfDay 00:00 - - 1:00 UTC Time of day in hours when daylight
00:30 time ends
1:00
1:30
...
48:00
16.3.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time zone from UTC TIMEZONE - -
490
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.3.6.2 Settings
Table 409: TIMEZONE Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoHalfHourUTC -24 - 24 - 1 0 Number of half-hours from UTC
16.3.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Time synchronization via IRIG-B IRIG-B - -
16.3.7.2 Settings
Table 410: IRIG-B Non group settings (basic)
Name Values (Range) Unit Step Default Description
TimeDomain LocalTime - - LocalTime Time domain
UTC
Encoding IRIG-B - - IRIG-B Type of encoding
1344
1344TZ
TimeZoneAs1344 MinusTZ - - PlusTZ Time zone as in 1344 standard
PlusTZ
Time definitions
The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called
the clock accuracy and means how much the error increases, that is how much the
clock gains or loses time. A disciplined (trained) clock knows its own faults and
tries to compensate for them.
491
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
IEC09000210-2-en.vsd
IEC09000210 V2 EN
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical
structure. A function is synchronized from a higher level and provides
synchronization to lower levels.
Synchronization from
a higher level
Function
Optional synchronization of
modules at a lower level
IEC09000342-1-en.vsd
IEC09000342 V1 EN
492
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
The IED has a built-in real-time clock (RTC) with a resolution of one second. The
clock has a built-in calendar that handles leap years through 2038.
Synchronization messages configured as coarse are only used for initial setting of
the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds resets the time.
Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized
for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. Normally, it takes 20 minutes to reach full accuracy.
493
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
To receive IRIG-B there are one dedicated connector for the IRIG-B port. IRIG-B
00x messages can be supplied via the galvanic interface, where x (in 00x) means a
number in the range of 1-7.
The IRIG-B input also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
compatible with IRIG-B and contains year information and information of the time-
zone.
It is recommended to use IEEE 1344 for supplying time information to the IRIG-B
module. In this case, send also the local time in the messages.
494
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.4.1 Functionality
Use the four sets of settings to optimize the IED operation for different system
conditions. Creating and switching between fine-tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can
cope with a variety of system scenarios.
16.4.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Setting group handling SETGRPS - -
16.4.2.2 Settings
Table 412: SETGRPS Non group settings (basic)
Name Values (Range) Unit Step Default Description
ActiveSetGrp SettingGroup1 - - SettingGroup1 ActiveSettingGroup
SettingGroup2
SettingGroup3
SettingGroup4
MaxNoSetGrp 1-4 - 1 1 Max number of setting groups 1-4
495
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.4.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Parameter setting groups ACTVGRP - -
IEC09000064_en_1.vsd
IEC09000064 V1 EN
16.4.3.3 Signals
Table 413: ACTVGRP Input signals
Name Type Default Description
ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
16.4.3.4 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
496
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ACTVGRP function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse.
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1 ACTVGRP
Æ ACTGRP1 GRP1
IOx-Bly2
Æ ACTGRP2 GRP2
IOx-Bly3
Æ ACTGRP3 GRP3
IOx-Bly4
Æ ACTGRP4 GRP4
SETCHGD
IEC09000063_en_1.vsd
IEC09000063 V1 EN
497
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
The above example also includes five output signals, for confirmation of which
group that is active.
16.5.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Test mode functionality TESTMODE - -
16.5.2 Functionality
When the Test mode functionality TESTMODE function is activated, protection
functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.
IEC09000219-1.vsd
IEC09000219 V1 EN
16.5.4 Signals
498
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.5.5 Settings
While the IED is in test mode, the ACTIVE output of the function block
TESTMODE is activated. The other outputs of the function block TESTMODE
shows the generator of the “Test mode: On” state — input from configuration
(OUTPUT output is activated) or setting from local HMI (SETTING output is
activated).
While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be unblocked individually regarding functionality
and event signalling.
Forcing of binary output signals is only possible when the IED is in test mode.
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode
(output ACTIVE is activated). When leaving the test mode, that is entering normal
mode, these blockings are disabled and everything is set to normal operation. All
testing will be done with actually set and configured values within the IED. No
settings will be changed, thus no mistakes are possible.
499
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.
When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the
IED will re-enter test mode and all functions will be blocked, also
functions that were unblocked before the change. During the re-
entering to test mode, all functions will be temporarily unblocked
for a short time, which might lead to unwanted operations. This is
only valid if the IED is put in TEST mode by a binary input, not by
local HMI.
Each of the protection functions includes the blocking from the TESTMODE
function block.
The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a maintenance test.
16.6.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Change lock function CHNGLCK - -
16.6.2 Functionality
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.
When CHNGLCK has a logical one on its input, then all attempts to modify the
IED configuration will be denied and the message "Error: Changes blocked" will
be displayed on the local HMI; in PCM600 the message will be "Operation denied
by active ChangeLock". The CHNGLCK function should be configured so that it is
controlled by a signal from a binary input card. This guarantees that by setting that
500
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
IEC09000062-1-en.vsd
IEC09000062 V1 EN
16.6.4 Signals
Table 418: CHNGLCK Input signals
Name Type Default Description
LOCK BOOLEAN 0 Activate change lock
16.6.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600)
The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:
• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
501
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group
The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input Function
1 Activated
0 Deactivated
16.7.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
IED identifiers TERMINALID - -
16.7.2 Functionality
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
16.7.3 Settings
Table 420: TERMINALID Non group settings (basic)
Name Values (Range) Unit Step Default Description
StationName 0 - 18 - 1 Station name Station name
StationNumber 0 - 99999 - 1 0 Station number
ObjectName 0 - 18 - 1 Object name Object name
ObjectNumber 0 - 99999 - 1 0 Object number
UnitName 0 - 18 - 1 Unit name Unit name
Table continues on next page
502
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.8.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Product information PRODINF - -
16.8.2 Functionality
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:
• IEDProdType
• ProductDef
• ProductVer
• SerialNo
• OrderingNo
• ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
16.8.3 Settings
The function does not have any parameters available in the local HMI or PCM600.
16.9.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Primary system values PRIMVAL - -
503
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.9.2 Functionality
The rated system frequency and phasor rotation are set under Main menu/
Configuration/ Power system/ Primary values/PRIMVAL in the local HMI and
PCM600 parameter setting tree.
16.9.3 Settings
Table 421: PRIMVAL Non group settings (basic)
Name Values (Range) Unit Step Default Description
Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
PhaseRotation Normal=L1L2L3 - - Normal=L1L2L3 System phase rotation
Inverse=L3L2L1
16.10.1 Functionality
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.
16.10.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Signal matrix for analog inputs SMAI_20_1 - -
IEC09000137-1-en.vsd
IEC09000137 V1 EN
504
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.10.2.3 Signals
Table 422: SMAI_20_1 Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block group 1
DFTSPFC REAL 20.0 Number of samples per fundamental cycle used
for DFT calculation
REVROT BOOLEAN 0 Reverse rotation group 1
GRP1L1 STRING - First analog input used for phase L1 or L1-L2
quantity
GRP1L2 STRING - Second analog input used for phase L2 or L2-L3
quantity
GRP1L3 STRING - Third analog input used for phase L3 or L3-L1
quantity
GRP1N STRING - Fourth analog input used for residual or neutral
quantity
505
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.10.2.4 Settings
Table 424: SMAI_20_1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current
506
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.10.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Signal matrix for analog inputs SMAI_20_2 - -
IEC09000138-2-en.vsd
IEC09000138 V2 EN
16.10.3.3 Signals
Table 426: SMAI_20_2 Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block group 2
REVROT BOOLEAN 0 Reverse rotation group 2
GRP2L1 STRING - First analog input used for phase L1 or L1-L2
quantity
GRP2L2 STRING - Second analog input used for phase L2 or L2-L3
quantity
GRP2L3 STRING - Third analog input used for phase L3 or L3-L1
quantity
GRP2N STRING - Fourth analog input used for residual or neutral
quantity
507
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
16.10.3.4 Settings
Table 428: SMAI_20_2 Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current
508
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
The output signals AI1 to AI4 in SMAI_20_x function block are direct outputs of
the, in SMT or ACT, connected input group signals to GRPxL1, GRPxL2,
GRPxL3 and GRPxN, x=1-12. GRPxN is always the neutral current. If GRPxN is
not connected, the AI4 output is all zero. The AIN output is the calculated residual
sum of inputs GRPxL1, GRPxL2 and GRPxL3 and is equal to output AI4 if all
inputs, including GRPxN, are connected. Note that function block will always
calculate the residual sum of current/voltage if the input is not connected in SMT
or ACT. Applications with a few exceptions shall always be connected to AI3P.
16.11.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Summation block 3 phase 3PHSUM - -
16.11.2 Functionality
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.
509
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
IEC09000201_1_en.vsd
IEC09000201 V1 EN
16.11.4 Signals
Table 430: 3PHSUM Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block
REVROT BOOLEAN 0 Reverse rotation
G1AI3P GROUP - Group 1 three phase analog input from first SMAI
SIGNAL
G2AI3P GROUP - Group 2 three phase analog input from second
SIGNAL SMAI
510
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.11.5 Settings
Table 432: 3PHSUM Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1-6 - 1 1 Selection of one of the Global Base
Value groups
SummationType Group1+Group2 - - Group1+Group2 Summation type
Group1-Group2
Group2-Group1
-(Group1+Group2)
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
External DFT ref
16.12.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Global base values GBASVAL - -
16.12.2 Functionality
Global base values function (GBASVAL) is used to provide global values,
common for all applicable functions within the IED. One set of global values
consists of values for current, voltage and apparent power and it is possible to have
six different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a
single point for updating values when necessary.
511
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one
out of the six sets of GBASVAL functions.
16.12.3 Settings
16.13.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Authority check ATHCHCK - -
16.13.2 Functionality
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:
16.13.3 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
512
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the User Management Tool.
Once a user is created and written to the IED, that user can perform a Log on, using
the password assigned in the tool. Then the default user will be Guest.
If there is no user created, an attempt to log on will display a message box: “No
user defined!”
If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Configuration/HMI/Screen/1:SCREEN) elapses, the IED returns to Guest
state, when only reading is possible. By factory default, the display timeout is set to
60 minutes.
If one or more users are created with the User Management Tool and written to the
IED, then, when a user attempts a Log on by pressing the key or when the user
attempts to perform an operation that is password protected, the Log on window
opens.
The cursor is focused on the User identity field, so upon pressing the key, one
can change the user name, by browsing the list of users, with the “up” and “down”
arrows. After choosing the right user name, the user must press the key again.
513
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
When it comes to password, upon pressing the key, the following characters
will show up: “✳✳✳✳✳✳✳✳”. The user must scroll for every letter in the
password. After all the letters are introduced (passwords are case sensitive) choose
OK and press the key again.
At successful Log on, the local HMI shows the new user name in the status bar at
the bottom of the LCD. If the Log on is OK, when required to change for example
a password protected setting, the local HMI returns to the actual setting folder. If
the Log on has failed, an "Error Access Denied" message opens. If a user enters an
incorrect password three times, that user will be blocked for ten minutes before a
new attempt to log in can be performed. The user will be blocked from logging in,
both from the local HMI and PCM600. However, other users are to log in during
this period.
16.14.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Authority status ATHSTAT - -
16.14.2 Functionality
Authority status (ATHSTAT) function is an indication function block for user log-
on activity.
IEC09000235_en_1.vsd
IEC09000235 V1 EN
16.14.4 Signals
Table 436: ATHSTAT Output signals
Name Type Description
USRBLKED BOOLEAN At least one user is blocked by invalid password
LOGGEDON BOOLEAN At least one user is logged on
514
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.14.5 Settings
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600)
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated.
16.15.1 Functionality
The Denial of service functions (DOSLAN1 and DOSFRNT) are designed to limit
overload on the IED produced by heavy Ethernet network traffic. The
communication facilities must not be allowed to compromise the primary
functionality of the device. All inbound network traffic will be quota controlled so
that too heavy network loads can be controlled. Heavy network load might for
instance be the result of malfunctioning equipment connected to the network.
16.15.2 Denial of service, frame rate control for front port DOSFRNT
16.15.2.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Denial of service, frame rate control for DOSFRNT - -
front port
515
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
IEC09000133-1-en.vsd
IEC09000133 V1 EN
16.15.2.3 Signals
Table 437: DOSFRNT Output signals
Name Type Description
LINKUP BOOLEAN Ethernet link status
WARNING BOOLEAN Frame rate is higher than normal state
ALARM BOOLEAN Frame rate is higher than throttle state
16.15.2.4 Settings
The function does not have any parameters available in the local HMI or PCM600.
516
Technical Manual
1MRK 502 034-UEN - Section 16
Basic IED functions
16.15.3 Denial of service, frame rate control for LAN1 port DOSLAN1
16.15.3.1 Identification
Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2
identification identification device number
Denial of service, frame rate control for DOSLAN1 - -
LAN1 port
IEC09000134-1-en.vsd
IEC09000134 V1 EN
16.15.3.3 Signals
Table 439: DOSLAN1 Output signals
Name Type Description
LINKUP BOOLEAN Ethernet link status
WARNING BOOLEAN Frame rate is higher than normal state
ALARM BOOLEAN Frame rate is higher than throttle state
16.15.3.4 Settings
The function does not have any parameters available in the local HMI or PCM600.
517
Technical Manual
Section 16 1MRK 502 034-UEN -
Basic IED functions
518
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
The IED shall be earthed with a 16.0 mm2 flat copper cable.
The earth lead should be as short as possible, less than 1500 mm.
Additional length is required for door mounting.
519
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
GUID-C75F6FD4-485D-464D-B7B0-55FD1AA608E9 V1 EN
Figure 251: Protective earth pin is located below connector X102 on the 6U
half 19” case
520
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
17.2 Inputs
The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
521
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
Each signal connector terminal is connected with one 0.5...2.5 mm2 wire or with
two 0.5...1.0 mm2 wires.
522
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
523
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
524
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
17.3 Outputs
Each signal connector terminal is connected with one 0.5...2.5 mm2 wire or with
two 0.5...1.0 mm2 wires.
525
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
526
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
Each signal connector terminal is connected with one 0.5...2.5 mm2 wire or with
two 0.5...1.0 mm2 wires.
527
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
528
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
17.3.3 IRF
The IRF contact functions as a change-over output contact for the self-supervision
system of the IED. Under normal operating conditions, the IED is energized and
one of the two contacts is closed. When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the closed contact drops off and the
other contact closes.
Each signal connector terminal is connected with one 0.5...2.5 mm2 wire or with
two 0.5...1.0 mm2 wires.
529
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
The IED's LHMI is provided with an RJ-45 connector. The connector is intended
for configuration and setting purposes.
The HMI connector X0 is used for connecting an external HMI to the IED. The X0/
HMI connector must not be used for any other purpose.
The events and setting values and all input data such as memorized values and
disturbance records can be read via the front communication port.
Only one of the possible clients can be used for parametrization at a time.
• PCM600
• LHMI
The front port supports TCP/IP protocol. A standard Ethernet CAT 5 crossover
cable is used with the front port.
530
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
• RuggedCom RS900
• RuggedCom RS1600
• RuggedCom RSG2100
531
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
532
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
533
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
534
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
535
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
536
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
537
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
538
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
539
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
540
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
541
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
542
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
543
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
544
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
545
Technical Manual
Section 17 1MRK 502 034-UEN -
IED physical connections
546
Technical Manual
1MRK 502 034-UEN - Section 17
IED physical connections
547
Technical Manual
548
1MRK 502 034-UEN - Section 18
Technical data
18.1 Dimensions
549
Technical Manual
Section 18 1MRK 502 034-UEN -
Technical data
• For 10 s 20 A 100 A
Voltage withstand:
• Continuous 420 V rms
1) Residual current
2) Phase currents or residual current
550
Technical Manual
1MRK 502 034-UEN - Section 18
Technical data
551
Technical Manual
Section 18 1MRK 502 034-UEN -
Technical data
552
Technical Manual
1MRK 502 034-UEN - Section 18
Technical data
storage 96 h at -40ºC
Dry heat tests operation 16 h at +70ºC IEC 60068-2-2
storage 96 h at +85ºC
Damp heat tests steady state 240 h at +40ºC IEC 60068-2-78
humidity 93%
553
Technical Manual
554
1MRK 502 034-UEN - Section 19
IED and functionality tests
• Air discharge 15 kV
• Other ports 4 kV
555
Technical Manual
Section 19 1MRK 502 034-UEN -
IED and functionality tests
556
Technical Manual
1MRK 502 034-UEN - Section 19
IED and functionality tests
557
Technical Manual
558
1MRK 502 034-UEN - Section 20
Time inverse characteristics
20.1 Application
Stage 3
Time
Stage 2 Stage 2
Fault point
position
en05000130.vsd
IEC05000130 V1 EN
559
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
Time
Fault point
position
en05000131.vsd
IEC05000131 V1 EN
The inverse time characteristic makes it possible to minimize the fault clearance
time and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of
following factors, in a simple case with two protections in series:
560
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A1 B1
Feeder
I> I>
Time axis
en05000132.vsd
IEC05000132 V1 EN
where:
t=0 is The fault occurs
t=t1 is Protection B1 trips
At the time t2 the circuit breaker B1 has opened its primary contacts and thus the
fault current is interrupted. The breaker time (t2 - t1) can differ between different
faults. The maximum opening time can be given from manuals and test protocols.
Still at t2 the timer of protection A1 is active.
In most applications it is required that the delay times shall reset as fast as possible
when the current fed to the protection drops below the set current level, the reset
time shall be minimized. In some applications it is however beneficial to have
some type of delayed reset time of the overcurrent function. This can be the case in
the following applications:
561
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
• If there is a risk of intermittent faults. If the current relay, close to the faults,
starts and resets there is a risk of unselective trip from other protections in the
system.
• Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for
other protection functions. It can often be valuable to have a reset delay to
assure the release function.
If current in any phase exceeds the set start current value , a timer, according to the
selected operating mode, is started. The component always uses the maximum of
the three phase current values as the current level used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is
reached or until the current drops below the reset value (start value minus the
hysteresis) and the reset time has elapsed.
The general expression for inverse time curves is according to equation 107.
æ ö
ç A
÷
t[ s ] = ç + B÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN (Equation 107)
where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.
For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can
be seen:
562
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN (Equation 108)
where:
top is the operating time of the protection
The time elapsed to the moment of trip is reached when the integral fulfils
according to equation 109, in addition to the constant time delay:
t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø
EQUATION1191 V1 EN (Equation 109)
For the numerical protection the sum below must fulfil the equation for trip.
næ æ i( j ) ö p ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN (Equation 110)
where:
j=1 is the first protection execution cycle when a fault has been
detected, that is, when
i
>1
in >
EQUATION1193 V1 EN
For inverse time operation, the inverse time characteristic is selectable. Both the
IEC and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 256.
563
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
Operate
time
tMin
Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN
In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current start value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN (Equation 112)
where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current
564
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN (Equation 113)
where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current
The timer will be reset directly when the current drops below the set start current
level minus the hysteresis.
I = Imeasured/Iset
565
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-151, class 5
+ 40 ms
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
566
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
U> = Uset
U = Umeasured
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
567
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
U> = Uset
U = Umeasured
568
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070750 V2 EN
569
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070751 V2 EN
570
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070752 V2 EN
571
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070753 V2 EN
572
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070817 V2 EN
573
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070818 V2 EN
574
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070819 V2 EN
575
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070820 V2 EN
576
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070821 V2 EN
577
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070822 V2 EN
578
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070823 V2 EN
579
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070824 V2 EN
580
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070825 V2 EN
581
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
A070826 V2 EN
582
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
A070827 V2 EN
583
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN
584
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN
585
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN
586
Technical Manual
1MRK 502 034-UEN - Section 20
Time inverse characteristics
GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN
587
Technical Manual
Section 20 1MRK 502 034-UEN -
Time inverse characteristics
GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN
588
Technical Manual
1MRK 502 034-UEN - Section 21
Glossary
Section 21 Glossary
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BI Binary input
BOS Binary outputs status
BR External bistable relay
BS British Standards
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations-sponsored standards body
within the International Telecommunications Union.
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves
two twisted pairs making it possible to transmit information
in both directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves
four twisted pairs, two of which are used for transmitting
data in both directions and two for transmitting clock signals
589
Technical Manual
Section 21 1MRK 502 034-UEN -
Glossary
590
Technical Manual
1MRK 502 034-UEN - Section 21
Glossary
591
Technical Manual
Section 21 1MRK 502 034-UEN -
Glossary
592
Technical Manual
1MRK 502 034-UEN - Section 21
Glossary
593
Technical Manual
Section 21 1MRK 502 034-UEN -
Glossary
595
Technical Manual
596
597
Contact us
www.abb.com/substationautomation