You are on page 1of 4

1 2

61'-1"

1'-0"
1'-0"
3'-0" 3'-0" 54'-1" 3'-0" 3'-0"

2 3
S-04-301 S-04-301

EL -4.50'
3'-1"
1'-0"

A
2'-11"

BLDG ISOMETRIC

1'-0" 5'-0" 1'-0"


5'-0" 1'-0"

Sim
3
1'-0"

1'-0"
S-04-301

1'-0"
RC WALL
5'-1" (TYP)

EL -8.00'
EL -4.50'

EL -14.25'

EL -12.00'
1'-0"

1 1
S-04-301 S-04-301
24'-1"

18'-2"

18'-2"
31'-0"

4'-0"
1'-0"
5'-1"

EL -8.00'
1'-0"

EL -4.50'

1'-0"
3'-0"
1'-0"

B
12" 0' 1' 2' 3' 4' 5' 6' 7'

3/8" = 1'-0"
3'-0"

C.V.W.D. DRAWING APPROVAL


DATE

Checked:
PROJECT ENGINEER
DWG. No.
FOUNDATION PLAN Recommended:
DIRECTOR OF ENGINEER
3/8" = 1'-0"
REVISIONS: DATE APPR.

SCALE
3/16"=1'-0"
COACHELLA VALLEY WATER DISTRICT DRAWING
IN THE CITY OF INDIO, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
FIELD BOOK

DIAL TOLL FREE


DESIGN
WATER RECLAMATION PLANT No.7
PHASE 1 NPW WATER IMPROVEMENTS
UV DISINFECTION BUILDING
S-04-101
811 DRAWN STRUCTURAL OFXX SHEETS
AT LEAST TWO DAYS
BEFORE YOU DIG APPROVED BY
CHECKED
FOUNDATION PLAN DRAWING No.
UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA SYM REVISIONS DATE BY REGISTERED ENGINEER No. DATE LOCATED WITHIN SECTION 15, TOWNSHIP 5 SOUTH, RANGE 6 EAST, SBM

PRELIMINARY - NOT FOR CONSTRUCTION 60% DESIGN


3
1 S-04-301 2

62'-1"

1'-0" 1'-0"
60'-1"

5'-0" 5'-0" 6'-6" 25'-4"


2'-0"

1'-0"
A

3'-10" 5'-0"

6'-5"
6'-11"
TOC EL 0.00'
12" CMU WALL
(TYP)

5'-1"

5'-1"

7'-1"
3'-0"
1
S-04-301
32'-0 3/4"

30'-0 3/4"

12'-0"
31'-0"

6'-0"

4'-0"
3'-0"
5'-1"

5'-1"

7'-1"

10'-0"
6'-5"
1'-0"

3'-4" 2'-10"
2
S-04-301
OPERATING FLOOR PLAN
3/8" = 1'-0"
12" 0' 1' 2' 3' 4' 5' 6' 7'

3/8" = 1'-0"

C.V.W.D. DRAWING APPROVAL


DATE

Checked:
PROJECT ENGINEER
DWG. No.

Recommended:
DIRECTOR OF ENGINEER

REVISIONS: DATE APPR.

SCALE
3/16"=1'-0"
COACHELLA VALLEY WATER DISTRICT DRAWING
IN THE CITY OF INDIO, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
FIELD BOOK

DIAL TOLL FREE


DESIGN
Designer
WATER RECLAMATION PLANT No.7
PHASE 1 NPW WATER IMPROVEMENTS
UV DISINFECTION BUILDING
S-04-102
811 DRAWN STRUCTURAL OFXX SHEETS
AT LEAST TWO DAYS Author
BEFORE YOU DIG APPROVED BY
CHECKED
OPERATING FLOOR PLAN DRAWING No.
UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA SYM REVISIONS DATE BY REGISTERED ENGINEER No. DATE Checker LOCATED WITHIN SECTION 15, TOWNSHIP 5 SOUTH, RANGE 6 EAST, SBM

PRELIMINARY - NOT FOR CONSTRUCTION 60% DESIGN


C
GOVERNING LOAD FOR JOIST

304 LB/FT
4'-0" 4'-0"
(TYP)
1 2

DEAD LOAD (NOTE 1)

61'-1"
80 LB/FT

REFER ARCH DWGS

ROOF LIVE LOAD


A
100 LB/FT
L6X4X3/8 LLV
3'-6"

WIND DOWNWARD LOAD (ASD)


6'-0"

10'-8" 10'-8"

(TYP) (TYP)

101 LB/FT 101 LB/FT


SPAN
80 LB/FT 80 LB/FT
6'-0"

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10

20LH10
L6X4X3/8 LLV

1 ZONE 2 ZONE 1 ZONE 2 ZONE 2 ZONE 1 ZONE 2


S-04-301
31'-0"

INTERIOR JOIST (ASD) EXTERIOR JOIST (ASD)

L6X4X3/8 LLV
1/4" / FT
SLOPE
WIND UPWARD LOAD (ASD)
6'-0"

NOTES:

1. JOIST MANUFACTURER TO DESIGN JOISTS TO SUPPORT GOVERNING LOAD COMBINATIONS SHOWN.


VALUES SHOWN PERTAIN TO ALL BAR JOISTS SHOWN ON ROOF PLAN.

2. ALL LOADS ARE LISTED AT STRENGTH LEVEL AND DESIGN SHALL BE BASED UPON LOAD RESISTANCE
FACTOR DESIGN (LRFD) PARAMETERS.
6'-0"

3. JOIST DESIGNATION SHOWN ON PLANS INDICATE MAXIMUM DEPTH AND MINIMUM WEIGHT.
SP INDICATES SPECIAL JOIST. JOISTS TO BE DESIGNED LOAD COMBINATIONS SHOWN ABOVE AND OTHER
LOADS INDICATED.

4. JOIST BRIDGING REQUIRED FOR ERECTION AND WIND UPLIFT LOADING SHALL BE DESIGNED AND
FURNISHED BY JOIST SUPPLIER. LOCATIONS, QUANTITIES AND DETAILS TO BE SHOWN ON JOIST
SUPPLIER’S PLACEMENT DRAWINGS.
3'-6"

L6X4X3/8 LLV 5. IN ADDITION TO OTHER LOADS INDICATED, JOIST MFR TO DESIGN JOIST SEATS AND TOP CHORD FOR
FACTORED AXIAL LOAD (TENSION AND COMPRESSION) INDICATED IN LOAD COMBINATIONS SHOWN.
B
6. IN ADDITION TO THE LOADS SHOWN, INCLUDE A VERTICAL CONCENTRATED LOAD OF 300 LBS
(UNFACTORED DEAD LOAD) AT ANY LOCATION ALONG THE BOTTOM CHORD FOR DOWNWARD LOAD
COMBINATIONS ONLY.

7. REFERENCE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ROOF TOP UNITS.
SUBCONTRACTOR SHALL COORDINATE ALL EQUIPMENT LOADS WITH JOIST MANUFACTURER.

8. MINIMUM THICKNESS OF TOP CHORD SHALL BE 1/4" TYPICAL AT ROOF JOISTS.

A STEEL JOIST LOADING DIAGRAMS AND NOTES


10'-0" 2 NO SCALE
S-04-301
(TYP)
3'-2"
3'-2"

8' 4' 0' 8' 16'


(TYP)
6'-4"

1/8" = 1'-0"

4' 2' 0' 4' 8'

INTERIOR ZONE (TYP)


1/4" = 1'-0"
ROOF FRAMING PLAN
EDGE ZONE (TYP) 1/4" = 1'-0"
C.V.W.D. DRAWING APPROVAL
DATE

Checked:
PROJECT ENGINEER
CORNER ZONE (TYP)
DWG. No.

Recommended:
DIRECTOR OF ENGINEER

REVISIONS: DATE APPR.

ROOF WIND ZONE PLAN


SCALE
1/8" = 1'-0"
AS INDICATED
COACHELLA VALLEY WATER DISTRICT DRAWING
IN THE CITY OF INDIO, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
FIELD BOOK

DIAL TOLL FREE


DESIGN
Designer
WATER RECLAMATION PLANT No.7
PHASE 1 NPW WATER IMPROVEMENTS
UV DISINFECTION BUILDING
S-04-103
811 DRAWN STRUCTURAL OFXX SHEETS
AT LEAST TWO DAYS Author
BEFORE YOU DIG APPROVED BY
CHECKED
ROOF FRAMING PLAN DRAWING No.
UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA SYM REVISIONS DATE BY REGISTERED ENGINEER No. DATE Checker LOCATED WITHIN SECTION 15, TOWNSHIP 5 SOUTH, RANGE 6 EAST, SBM

PRELIMINARY - NOT FOR CONSTRUCTION 60% DESIGN


1 2

ROOFING REFER ARCH DWGS


(SEE ARCH DWGS)
16" BOND BEAM
W/ 2-#5T&B
TOS EL 17.67'

12" CMU WALL


(TYP)
1'-0"
CONTINUOUSLY GROUT
SOLID BELOW BOND BEAM (TYP)
12" BOND BEAM AT 2'-0" TOC EL 0.00'
OC SPACING VERTICALLY
WITH 2-#5 (TYP)

4'-6"
VERTICAL REINF IN CMU #4@6"EWEF
AND REQUIRED LAP
LENGTH, SEE SCHEDULE
ON DWG S-99-505(TYP)
TOC EL -4.50'

1'-6"
TOC EL 0.00'
#4@6"EWT&B

SECTION
4'-6"

3
TOC EL -3.71' S-04-101 3/8" = 1'-0"
TOC EL -4.50'
1'-6"

TOC EL -8.00'

3 REINF
S-04-301 (TYP)
TOC EL -12.00'

TOC EL -14.25'

1 SECTION
S-04-101 1/4" = 1'-0"

B A

TOM EL 22.67'

1 1/2" METAL DECK


ROOFING REFER ARCH DWGS
(SEE ARCH DWGS)
16" BOND BEAM
W/ 2-#5T&B
TOS EL 17.67'

12" CMU WALL


FULLY GROUTED
(TYP) CONTINUOUSLY GROUT
SOLID BELOW BOND BEAM (TYP)

BOND BEAM AT 2'-0" OC


SPACING VERTICALLY
WITH 2-#5 (TYP)

VERTICAL REINF IN CMU


AND REQUIRED LAP
LENGTH, SEE SCHEDULE
ON DWG S-00-506(TYP)

TOC EL 0.00'

C.V.W.D. DRAWING APPROVAL


4'-6"

DATE

Checked:
PROJECT ENGINEER
TOC EL -4.50'
DWG. No.
1'-6"

Recommended:
DIRECTOR OF ENGINEER

REVISIONS: DATE APPR.


TOC EL -8.00'

2 SECTION
S-04-101 1/4" = 1'-0"

SCALE
1/4"=1'-0"
COACHELLA VALLEY WATER DISTRICT DRAWING
IN THE CITY OF INDIO, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
FIELD BOOK

DIAL TOLL FREE


DESIGN
WATER RECLAMATION PLANT No.7
PHASE 1 NPW WATER IMPROVEMENTS
UV DISINFECTION BUILDING
S-04-301
811 DRAWN STRUCTURAL OFXX SHEETS
AT LEAST TWO DAYS
BEFORE YOU DIG APPROVED BY
CHECKED
SECTIONS DRAWING No.
UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA SYM REVISIONS DATE BY REGISTERED ENGINEER No. DATE LOCATED WITHIN SECTION 15, TOWNSHIP 5 SOUTH, RANGE 6 EAST, SBM

PRELIMINARY - NOT FOR CONSTRUCTION 60% DESIGN