You are on page 1of 3

Key nonstructural changes to 2012 IBC

William E. Koffel, PE, FSFPE


Koffel Associates Inc.,
05/13/2013 Columbia, Md.

The new 2012 International Building Code (IBC) was This complication will likely be resolved in the 2015
published June 9, 2011, and is being adopted as the IBC. Users of the code should consider reviewing the
applicable building code by many states, counties, changes in the 2015 edition for potentially more
cities, and municipalities across the United States. reasonable design direction.
As part of the triennial code development process, Use of the 2015 language should be reviewed with
the 2012 IBC includes many new or revised code the authorities having jurisdiction (AHJ).
requirements not previously included in the 2009
IBC. Fire ratings of exterior walls: A new note “h” has
been added to Table 602 to clarify that nonrated
While it is important for the members of a design or exterior walls are permitted when nonbearing
building assessment team to understand the impact exterior walls with unlimited openings are permitted
of building code changes on all the members of the by Table 705.8.
team, this article focuses on the significant This occurs when the building is protected with
nonstructural changes to the 2012 IBC that typically automatic sprinkler protection and the fire
impact consulting and specifying engineers, other separation distance is at least 20 ft.
than structural and material requirements.
Separate articles would be necessary to discuss the Using sprinklers to achieve a fire resistance rating:
changes to the structural/material requirements and In the past there has been an ICC-ES Evaluation
changes that primarily impact the practice of Report (ESR-2397) that describes a glass assembly
architecture. protected with a specific automatic sprinkler as
For a more complete discussion of these changes in having a fire resistance rating of 2 hours.
the 2012 edition of the IBC, one can refer to The 2012 IBC contains Section 703.4, which restricts
Significant Changes to the International Building the use of automatic sprinklers or any other fire
Code, 2012 Edition, published by the International suppression system when testing an assembly to
Code Council (ICC). achieve a fire resistance rating. When installing a
sprinkler in the furnace, the tested assembly is not
Fire service access elevators: Paragraph 403.6.1 has likely to be exposed to the standard temperature-
been revised to require a minimum of two fire time curve as required by the fire test because
service access elevators in buildings with an operation of the sprinkler will result in a cooling
occupied floor level more than 120 ft above the effect within the furnace.
lowest level of fire department vehicle access. As such, the fire test would not be in strict
The 2009 IBC required only one fire service access compliance with the required fire test standard.
elevator. In addition, the paragraph now includes a That is not so say that an assembly that is protected
requirement that each elevator have a capacity of at with a specific sprinkler or specific sprinkler design
least 3,500 pounds. Under normal conditions, the may not be considered to be equivalent to a fire-
revision results in at least two elevators being rated building element or assembly, but rather that
available for fire suppression personnel in such the sprinkler may not be part of the fire test used to
buildings. In addition, because an elevator may be qualify the building element or assembly.
out of service, the change results in a reasonable The IBC commentary on this code change clarifies
expectation that at least one fire service access that it is not the intent of the code to prohibit the
elevator will be available at all times. use of such sprinklers. Rather, the change implies
that the use of a window sprinkler system to provide
It should be noted that there have also been such rating is to be considered under alternate
revisions to the detailed requirements for fire materials and methods of construction.
service access elevators and occupant evacuation Therefore, such window sprinklers remain a viable
elevators. For the most part, these revisions provide candidate for the right applications.
for the elevators to be able to continue to function
and serve their intended purpose during an
emergency (Sections 3007 and 3008, respectively).
A complication unresolved in the 2012 IBC is related
to the requirement for direct access between the
fire service access elevators and the exit stair
enclosure.
Key nonstructural changes to 2012 IBC
William E. Koffel, PE, FSFPE
Koffel Associates Inc.,
05/13/2013 Columbia, Md.

Refuse and laundry chutes: Section 713.13 contains and the level of exit discharge. However, if there are
a provision to require the use of NFPA 82: Standard floors above the ambulatory care facility, they need
on Incinerators and Waste and Linen Handling not be protected with an automatic sprinkler system
Systems and Equipment, Chapter 5, for determining even if the fire resistance rating of the floor is less
the requirements for refuse and laundry chutes in than what is required to separate fire areas.
buildings of Group I-2.
It should be noted that the 2015 IBC will require the Manufacture, display, and storage of upholstered
use of NFPA 82 for refuse and laundry chutes in all furniture and mattresses: The threshold for
occupancies (FS60-12). mandating sprinkler protection in Groups F-1 and S-1
has been revised to include a requirement for
Elevator lobbies: Elevators that only serve lower sprinkler protection if upholstered furniture or
levels of a high-rise building (less than 75 ft above mattresses are manufactured or stored and the area
the lowest level of fire department access) need not exceeds 2,500 sq ft.
have elevator lobbies since those elevator shafts In addition, the existing requirement for sprinkler
should not experience the same pressure difference protection in Group M occupancies used for the
as the shafts serving the upper floors (Exception No. display and sale of upholstered furniture in excess of
4.3, Paragraph 713.14.1) 5,000 sq ft has been expanded to include the display
and sale of mattresses (Paragraphs 903.2.4, 903.2.7,
Floor penetrations: Historically the IBC has not and 903.2.9).
required a T rating for through penetration firestop
systems when the floor penetration was contained Emergency voice/alarm communication captions: In
and located within the cavity of a wall. stadiums, arenas, and grandstands, the emergency
The 2012 IBC has extended this exemption for the T voice/alarm communication system shall include the
rating to include floor penetrations for floor drains, ability to display captions where audible public
tub drains, and shower drains contained and located announcements are also required to include
within a concealed space of a horizontal assembly captions by Paragraph 1108.2.7.3 (Paragraph
(Exception No. 2, Paragraph 714.4.1.1.2). 907.5.2.2.4).
As with a wall cavity, the provision assumes that a T
rating is not required due to the reduced likelihood Voice alarm systems in schools: The fire alarm
that combustibles will be exposed to any system in Group E occupancies shall now include an
temperature increase of the penetrating item. emergency voice/alarm communication system.
In addition, the threshold for when a fire alarm
Duct penetrations of fire partitions: A new system is required in a Group E occupancy has been
exception has been added to permit the omission of reduced to an occupant load of more than 30
fire dampers where a ducted HVAC system (previously it was 50 or more) (Paragraph 907.2.3).
penetrates a fire partition having a fire resistance As noted below, where automatic sprinkler
rating of 1 hour or less and located in a building protection and emergency voice/alarm
protected throughout with an automatic sprinkler communication systems are provided, lower egress
system. The exception clarifies what is intended by a capacity factors may be used.
“ducted HVAC system,” and the provision is the
same as what was previously permitted for duct College and university residential buildings: Where
penetrations of 1-hour fire barriers (Exception No. 4, there is an interior corridor serving sleeping rooms,
Paragraph 717.5.4). college and university buildings containing a Group
R-2 occupancy are required to have an automatic
Sprinklers in ambulatory care facilities: Recognizing smoke detection system in the corridors, common
that ambulatory care facilities are often located in spaces, laundry rooms, mechanical equipment
office buildings in which the fire resistance rating of rooms, and storage rooms.
the floor may not be adequate to define a separate In addition, the smoke alarms in Group R-2 college
fire area, Paragraph 903.2.2 has been revised to and university buildings are required to be
require automatic sprinkler protection throughout interconnected with the building fire alarm
the entire floor containing an ambulatory care system (Paragraph 907.2.9.3).
facility, all floors below the ambulatory care facility,
and all floors between the ambulatory care facility
Key nonstructural changes to 2012 IBC
William E. Koffel, PE, FSFPE
Koffel Associates Inc.,
05/13/2013 Columbia, Md.

Carbon monoxide detection: A new section (908.7)


has been added to require carbon monoxide alarms William E. Koffel is president of Koffel Associates Inc.
or carbon monoxide detection systems in Group I He has been an active participant in the International
and Group R occupancies where the building Code Council process since the inception of the ICC,
contains fuel-burning appliances or an attached serving on numerous committees and currently
garage. serving on the ICC Code Technology Committee. He
was the 2010 recipient of the ICC Affiliate Award.
Egress capacity factors: Where automatic sprinkler
protection and emergency voice/alarm
communication systems are installed in other than
Group H and I-2 occupancies, a reduced egress
capacity shall be permitted to be used (Section
1005.3).

Floor-level exit signs: Where exit signs are required


in Group R-1 occupancies, additional low-level exit
signs shall be provided in all areas serving guest
rooms.
In addition to increasing the level of safety for the
building occupants, the substantiation also noted
that such signs will also increase firefighter safety
(Section 1011.2).

Attic ventilation: The 2012 Edition of the IBC


provides for reduction in the vent area for attics;
when determined to not be necessary by the
building official, attic ventilation shall not be
required (Section 1203.2).

Photovoltaic systems: New provisions have been


added for photovoltaic elements (modules/shingles
or systems) including requirements to meet the
existing requirements for roofing materials and
rooftop structures (Sections 1505.8, 1507.17,
1509.7, and 3111).

Special inspections: A new requirement for special


inspections of through penetration firestop systems
and fire-resistant joint systems has been added for
high-rise buildings and for buildings assigned a Risk
Category III or IV in accordance with Section 1604.5.
The special inspections are to be conducted in
accordance with ASTM E2174 or ASTM E2393
(Section 1705.16).
In addition to the above items, registered design
professionals should review the 2012 Edition of the
IBC in its entirety to identify all the proposed
changes that may impact their practice of
engineering.

You might also like