Rev :2 Page : 01
Work shall
1.0 Water supply calculation EO-182-CAL-003 1 C
proceed
CPVC pipe size mentioned in the attached One size which was 1 inch was not match, now it is
4
calculation not matching the approved catalogue updated
Velocities at node G69, G70, A21, A13, A09,
5 Noted and updated
A30 are more than specified
Hot water pipe size for G22, G23, G24, G25,
6 Noted and considered
G26 not provided
Water supply to dishwasher in ground floor
7 Noted and complied
pantry not considered
Washing machine fixture unit shall be 3 but in Note and updated, the provided FU was considering
8
calculation it is considered as 1.5, please clarify IPC code.
All dimension is in mm and m; however, FPS is
9 Indicate velocity in FPs also
added
The OD do not add value to the calculation, the
mentioned size is the nominal size beside the inner
Size to mentioned as outer diameter in
10 dia which is the base of the water velocity, for further
calculation sheet
info about the OD we are attached the manufacturer
catalogue which will show more parameter.