PROJECT NAME: FOUR SEASONS PRIVATE RESIDENCES BAHRAIN BAY

COMMENT REPLY SHEET

DOCUMENT COMMENT SHEET

Submittal No.(TR) : 110296-0.5-080-1 Resubmittal Date : 09-05-2022

Rev :1 Page :2

Submission Date : 02-04.2022

Receipt Date : 18-04.2022

Item Titles / Details Document No. Rev. Status Comment

1.0 AIR HANDLING UNIT /AHU/FAHU 110296-0.5-080-1 2 B See Below

Status: A = Approved B = Approved subject to comments C = Revise and Resubmit Subcontractor


approved in principle D = Rejected RP = Response pending
ITE
COMMENTS  COMPLIANCE SUPPLIER / DAIKIN 

Noted  &  Comply:  ‐  Daikin  Europe  (Italy)  is  the  parental 
The  attached  Eurovent  certificate  shows 
Company  which  applies  for  Eurovent  certification  and 
participant  as  Daikin  Italy  Factory  whereas  the 
this certification will for Various manufacturing location 
proposed AHUs are from UAE factory. 
1  as mentioned in the Certification. ( Italy , UK & UAE )  
Noted  &  Comply:  ‐  The  Eurovent  Certificate  only  the 
participant  (Parental)  can  download  from  the  website. 
The  attached  Eurovent  certificate  could  not  The  Performance  of  the  AHU  can  be  verified  from  the 
verified online as mentioned in the certificate.  below  link    https://www.eurovent‐
Provide justification.  certification.com/en/advancedsearch/result?program=A
HU&product_type=MB/MB/MECH&brand%5B0%5D=DA
2  IKIN&keyword=#access‐results 
Comply  –Please  refer  the  attached  latest  Eurovent 
The  attached  Eurovent  certificate  is  expired. 
Certificate. Valid upto 31.12.2022. ( Attachment‐1) 
Provide  the  latest  certificate  showing  the  current 
3  For  the  latest  Software  version  please  refer  the 
software  version  used  for  AHU  technical 
clarification supporting letter from DAIKIN Middles East.    
selections. 
( Attachment‐2) 
Contractor  shall  clarify  why  the  AHU  selection  In  the  selection  sheet  the  Manufacturers  name  as 
sheets  mention  Manufacturer's  name  as  Daikin  Applied Europe, please refer the clarification supporting 
Applied Europe when the proposed units are from  letter from DAIKIN Middles East.      
4  UAE factory.  ( Attachment‐2) 
It is noted that Contractor has not selected vertical 
type  AHUs  as  specified.  Contractor  shall  ensure 
5  the  selected  size  of  the  AHUs  and  FAHUs  are  Comply by TEMCO 
suitable  as  per  the  space  available  in  the  AHU 
Plant rooms. 
_____________________________________________________________________________________________

Page 1 of 3
PROJECT NAME: FOUR SEASONS PRIVATE RESIDENCES BAHRAIN BAY
COMMENT REPLY SHEET

Provide AHU room layouts indicating AHUs as per 
6  the selected sizes and duct routes with service and  Comply by TEMCO 
access space. 
Contractor  shall  provide  the  sequence  of 
7  Comply by TEMCO 
operation of electrical heaters in AHU and FAHUS. 
All  doors  of  AHU  shall  have  glass  window  as 
8  Comply for Filter and Fan Section 
specified in Specifications 
Separate  submittal  shall  be  provided  for  all  the 
9  Comply by TEMCO 
items mentioned in the compliance statement. 
Contractor  has  done  the  ESP  calculation  using 
Ashrae  software  without  showing  any  manual 
calculation  and  supporting  documents,  in  this 
10  Comply by TEMCO 
case,  Contractor  shall  be  fully  responsible  for  the 
resulting values of the ESP and the concurrent unit 
selection. 
Each  fitting,  duct  length  shall  be  numbered  I 
tagged  in  the  ESP  calculation  diagram  and  same 
11  Comply by TEMCO 
no. shall be mentioned in the calculation sheet for 
cross verification. 
Average  noise  levels  of  the  units  are  noted  to  be 
12  higher; Contractor shall be responsible to provide  Comply by TEMCO 
the additional acoustic measures if required. 
Note in AHU  selection sheets that the light fitting 
13  in the AHU shall be without bulb is not acceptable,  Comply ( Light mounted wired to external switch ) 
bulb shall be included. 
Left or Right  CHW coil connection side  shall be in 
14  Comply by TEMCO 
line with the site situation. 
Separate  Panel  and  Bag  filters  for  Wild  Air 
15  Comply by TEMCO 
Application to be provided (if implemented). 

_____________________________________________________________________________________________

Page 2 of 3
CERTIFICATE
N° 14.05.003
Air Handling Unit / Centrales de traitement d'air
Range Name / Nom de Gamme :
D-AHU
Granted on May 13, 2014 - Date 1ère admission 13 mai 2014

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

Participant/Titulaire

DAIKIN Applied Europe S.p.A


S.S.Nettunense,km 12+300
00040 Cecchina, Italy

This product performance certificate is issued by Ce certificat de performance produit est délivré par Eurovent
Eurovent Certita Certification according to the Certita Certification dans les conditions fixées par le
certification rules: référentiel :

ECP AHU - « Air Handling Unit » in force at ECP AHU – « Centrales de traitement d'air » en vigueur à
established date. date d’édition.

Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita
Certification, the right to use the mark ECP shall be Certification, le droit d'usage de la marque ECP, est accordé à
granted to the beneficiary company for the above Range la société qui en est bénéficiaire pour la gamme visée ci-
in the conditions defined by the certification program dessus, dans les conditions définies par le programme de
mentioned. certification mentionné.

Unless withdrawn or suspended, this certificate remains Sauf retrait ou suspension, ce certificat demeure valide tant
valid as long as the requirements for the certification que les conditions du référentiel du programme de certification
program framework are met. The validity of the sont respectées. La validité du certificat est à vérifier sur le site
certificate is to be verified on www.eurovent- Internet www.eurovent-certification.com
certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 22/03/2022
THIS CERTIFICATE HAS BEEN ISSUED ON 22/03/2022 CE CERTIFICAT EST VALIDE JUSQU’AU 31/12/2022
THIS CERTIFICATE IS VALID UNTIL 31/12/2022

Paris, 22 mars 2022


Organisme accrédité n° 5-0517
Certification Produits et Services selon la
norme NF EN ISO/CEI 17065:2012
Portée disponible sur www.cofrac.fr
MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Accreditation #5-0517 Products and
Services Certification according to NF EN
ISO/CEI 17065:2012 –
Scope available on www.cofrac.fr

COFRAC est signataire des accords MLA


d’EA et MLA d’IAF,
COFRAC is signatory of EA MLA and IAF
MLA,
list of EA members is available on
www.european-accreditation.org/ea-members
list of IAF members is available on
www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4

1/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1
CERTIFICATE
N° 14.05.003

Appendix / Annexe

Granted on May 13, 2014 - Date 1ère admission 13 mai 2014

This document is valid at the date of issue - Check the current validity on:
Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com

List of certified products and characteristics is displayed on:


La liste des références et caractéristiques certifiées est disponible sur le site :
www.eurovent-certification.com
This product performance certificate is valid for the following trade names:
Ce certificat de performance produit est valide pour les marques commerciales suivantes:
Trade Name / Marque Commerciale

DAIKIN

This product performance certificate is valid for the following manufacturing places:
Ce certificat de performance produit est valide pour les sites de production suivants:
Manufacturing Place / Site de Production

Caleppio di Settala (Milan), Italy


Cramlington (Newcastle), United Kingdom
Dubai, United Arab Emirates

This product performance certificate is valid for the following software:


Ce certificat de performance produt est valide pour les logiciels de sélection suivants:
Software / Logiciel de sélection

ASTRAWEB 10.1.3.1

2/2
EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_RANGE_REV1.1