KINGSPIPE

Date: 25/4/2022

HAN JARDIN TOWER

Project information

Address Ha Noi

Customer HA HUNG CO, LTD

Calculated By Rocky

Comment Do day cach nhiet PU foam, Jacketing Ton ma kem, khu vuc truc dung, phong may

Project detail CHILLER WATER

Material Medium

Pipe Material STEEL Medium type WATER

Standard Size 15 Temp. medium 6 °C

Outer diameter 21.3 mm

Wall thickness 2.6 mm Insulation

Insulation Material Other


Environment Thermal conductivity 0.024 W/mK

Location Indoor

Temp. ambient 30 °C

Rel.Humidity 85 %

Jacketing

Jacketing/ Cladding 0.10 – Galvanized Steel


– GI, new, bright/ Ton
ma kem

Surface Emissivity 0.1

Page 1
3iTechnologies
www.kingspipe.com.vn
The recommendation provided by this calculation tool is indicative as it is calculated using
standard industry equations, and should not be taken as a guarantee of performance, on behalf of Kingspipe
KINGSPIPE

Result

Dew point : 27.20°C

Minimum Insulation Thickness : 27.73 mm

Select. Insulation Thickness : 50 mm

External surface temperature: 28.33 °C

Heat Gain with insulation : -1.94 W/m

Heat Gain without insulation : -16.92 W/m

Insulation effeciency : 88.56 %

Linear thermal resistancel : 11.54 mK/W

Linear thermal transmittancel 0.08 W/mK


:

Surface heat transfer coeffient: 3.03 W/m²K

Page 2
3iTechnologies
www.kingspipe.com.vn
The recommendation provided by this calculation tool is indicative as it is calculated using
standard industry equations, and should not be taken as a guarantee of performance, on behalf of Kingspipe
KINGSPIPE

STT DN OD Min.Insulation Selected Insulation Heat Gain Insulation Max. Permissible


(mm) Thickness (mm) Thickness (mm) (W/m) Effect (%) Heat Gain (W/m)

1 15 21.3 27.73 50 -1.94 88.56 -3.27

2 20 26.9 30.12 50 -2.16 89.48 -3.58

3 25 33.7 31.85 50 -2.42 90.23 -4.01

4 32 42.4 34.12 50 -2.74 90.88 -4.53

5 40 48.3 35.47 50 -2.95 91.20 -4.82

6 50 60.3 37.87 50 -3.36 91.66 -5.48

7 65 76.1 40.52 50 -3.89 92.06 -6.30

8 80 88.9 42.37 50 -4.31 92.29 -6.90

9 100 114.3 45.49 50 -5.14 92.58 -8.31

10 125 139.7 48.09 50 -5.94 92.76 -9.49

11 150 168.3 50.58 50 -6.84 92.88 -10.97

12 200 219.1 54.23 50 -8.42 93.01 -13.57

13 250 273.0 57.39 50 -10.07 93.07 -16.28

14 300 323.9 59.90 50 -11.62 93.10 -18.84*

15 350 355.6 61.29 50 -12.58 93.10 -20.44*

16 400 406.4 63.31 50 -14.12 93.10 -22.98*

17 450 457.0 65.11 50 -15.63 93.10 -25.52*

18 500 559.0 66.74 50 -18.68 93.07 -30.60*

19 600 610.0 69.61 50 -20.19 93.05 -33.15*

(Maximum Permissible Heat Gain to BS 5422:2009, Chiller water temperatures 5°C – 10°C)
“-“: Direction of heat flow, |Heat Gian| <= |Maximum permissible Heat Gain|

Page 3
3iTechnologies
www.kingspipe.com.vn
The recommendation provided by this calculation tool is indicative as it is calculated using
standard industry equations, and should not be taken as a guarantee of performance, on behalf of Kingspipe