Professional Documents
Culture Documents
PDU-1 (UPS-R3)
PDU-2 (UPS-Y3)
PDU-3 (UPS-B3)
3C x 4mm 2 CABLE
3C x 4mm 2 CABLE
3C x 4mm 2 CABLE
PDU-6 (BUILDING POWER-
REDUNDANCY)
PANEL-3
CCTV-UPS-DB(RAK-AV)
R3
32A
Y3
32A 4C X 16mm 2 XLPE/SWA/PVC CABLE
RYB1
B3 1C X 10mm 2 PVC/Cu CABLE L=97m
32A 40A
300mA LOOP-1 (1.18kW)
R4
VD=00.55V
MCB+RCCB
3C x 4mm 2 CABLE
3C x 4mm 2 CABLE
100A 100A
4P 4P
ISO ISO 3C X 16mm 2 RUBBER CABLE
ELECTRICAL INTERLOCK
WITH ATS TO AVOID L=88m
DOUBLE FEEDING IN ATS
VD=00.72V SECURITY CONTRACTOR:
IN IN
4C X 16mm 2 XLPE/SWA/PVC CABLE
1C X 10mm 2 PVC/Cu CABLE
OUT
ATS
100A, 3-Phase
PANEL-1
IN
MAINTENANCE DB (RAK-AV) PROJECT:
100A CONTROL CABLE
4P
ISO
OUT 4C x 70mm 2 XLPE/SWA/PVC CABLE IN
CCTV UPS OUT CCTV SYSTEM FOR ADNOC
100A 1C x 35mm 2 PVC/Cu CABLE [20kVA 18kW 3 Phase] RAS AL KHAIMA AVIATION DEPO
4P
ISO
4C x 70mm 2 XLPE/SWA/PVC CABLE IN
1C x 35mm 2 PVC/Cu CABLE DRAWING TITLE:
100A
4P
ISO
OUT
2
5C X 16mm RUBBER CABLE CCTV POWER DISTRIBUTION SCHEMATIC
2
5C X 25mm RUBBER CABLE
UPS INPUT/OUTPUT CABLE IS AS DRAWING NO.: PROJECT REF NO.:
PER TCL LOAD
AS-RAKAV-LYT-02
LOCATION : PORTACABIN DESIGNED BY: VERIFIED BY: APPROVED BY: