RC Column - Axially Loaded - NSCP by RGCE
RC Column - Axially Loaded - NSCP by RGCE
: 1
Location : Philippines Revision No. : 0
Designed by : Raymundo Giray, Jr. Date :
Checked by : Date :
Approved by : Date :
Classification of
Reinforcement Bar size Qty./Sp
1
2
y
Figure A - Column Details
Check for Axial Capacity;
Gross area of section [Ag] = 150000 mm2
Area of main reinforcement [Ast] = 4423 mm2
Axial capacity, Ø0.80[ 0.85fc'(Ag - Ast) + fyAst] [Pcap] = 1926.3 kN
Safety factor for Axial, Pcap/Pu [FOS] = 19.3 > 1.0, Safe Design!
Check for Shear Capacity:
Effective depth along X-X [dx] = 442.0 mm
Effective depth along Y-Y [dy] = 242.0 mm
408.7.1 Concrete strength modification factor [λ] = 1.0
411.4.1.2 Concrete shear capacity, 0.17[1 + (Nu/14Ag)]λ sqrt[f'c] bd x [Vcx] = 180.4 kN
411.6.6 Tie shear capacity, Av fy dx /s [Vsx] = 57.9 kN
Total shear capacity of section along X-X, Øv(Vcx + Vsx) Vcap,x = 178.7 kN
Safety factor for Shear Along X-X, Vcap,x/Vu [FOS] = 7.1 > 1.0, Safe Design!
411.4.1.2 Concrete shear capacity, 0.17[1 + (Nu/14Ag)]λ sqrt[f'c] bd y [Vcy] = 59.3 kN
411.6.6 Tie shear capacity, Av fy dy /s [Vsy] = 31.7 kN
Total shear capacity of section along Y-Y, Øv(Vcy + Vsy) Vcap,y = 68.2 kN
Safety factor for Shear Along Y-Y, Vcap,y/Vu [FOS] = 2.7 > 1.0, Safe Design!
Check Code Requirements:
Actual spacing of main reinforcement along X-X = 42.7 mm OK!
Actual spacing of main reinforcement along Y-Y = 92.0 mm OK!
Actual reinforcement ratio [ρ] = 2.95 % OK!
Therefore, use 500mm x 300 mm column with 22 Nos. of 16mm main bars and 10mm @ 150mm o.c. ties.
Email: raymundojr.giray@yahoo.com
Ó 2013 Raymundo J. Giray, Jr.
Project Name : Construction of 2-storey Residential House Sheet No. : 1
Location : Philippines Revision No. : 0
Designed by : Raymundo Giray, Jr. Date :
Checked by : Date :
Approved by : Date :
Email: raymundojr.giray@yahoo.com
Ó 2013 Raymundo J. Giray, Jr.
Revision Revision Date Changes Author
No.
01 01 Feb. 2013 First Release RG