CX PLUS-12R
LIST OF OPTIONS
Designation Explanation
CX plus -06R 6 output / stage relay
-12R 12 output / stage relay
-M Modbus RTU – Connection via RS485 3-wire bus
Connection data
Measuring and supply
voltage
Combined voltage measurement and supply
Range: 90 – 550 V AC, 45 – 65 Hz
Terminals: U1 / U2
A transformer factor can be set when using voltage transformers.
Range 1.0 – 350.0
8
Current measurement
Current measurement
Range: 5 mA – 5 A AC, 45 – 65 Hz.
The use of x/1 and x/5 transformers is possible.
Terminals: S1 (K) / S2 (L)
Transformer factor adjustable from 1 – 9600
Fan relay
Closes the contact when exceeding the pre-set temperature limit 1.
Terminals: F1 / F2
Switching capacity 5 A/ 250 V AC
The fan relay may be used alternatively as 7th or 13th switching
output for a stage.
This function is described in more detail in the chapter
“APPLICATIONS”, paragraph “Additional switching output for a
stage”.
Alarm relay
Normally open contact, closed in normal operating condition.
Opens in case of alarm and in case of a failure of the supply voltage (life
contact).
Terminals: AL1 / AL2
Switching capacity 5 A / 250 V AC
Digital input
Digital input for switching to the second target cos , supressing the I-
LOW alarm or as external alarm input
Adjustable logic: HIGH or LOW active
Terminals: I1 / I2
Input signal: 90 – 250 V AC
Temperature measurement
internal NTC (under the housing cover)
MODBUS interface
only option: -MB
Protocol: MODBUS-RTU
Interface: RS485
Terminals: + / GND / -
TTL interface
Service interface. For service purposes only.