62 100
2-fold analog Limit Monitor 62 100
safety-related
Input 0...22 mA / 0...5.5 V without line diagnosis
or 4...22 mA / 1...5.5 V with line diagnosis
2 outputs 100 mA each with parameterizable line diagnosis
The module can be used in the following applications:
• With 1oo1 architecture in accordance with IEC 61508 for SIL 3
applications
• With redundant architectures, 1oo2 or 2oo3, for SIL 4 applications.
Outputs k
Analog section
Input voltage 0...5.5 V
Input current 0...22 mA (250 Shunt)
Measuring range according to NE 43 (I > 3.6 mA, I < 21 mA)
Input resistance 100 k
Basis error 0.25 % of upper value (+25 °C)
Operating error 0.4 % of upper value
at -25...+70 °C
Resolution 12 Bit (upper value incl. overflow)
Filter constant 10 ms
Digital section
Switching time < 250 ms
Output:
Current limit 110 mA 10 %
Int. voltage drop 2.5 V at max. load
Min. load 12 k (no lamp load)
Max. inductivity 1H
All rights reserved. The technology is subject to changes without notice: 1/24
HIMA Paul Hildebrandt GmbH + Co KG, Postfach 1261, 68777 Brühl
62 100 (1146)
The short-circuit proof outputs can be preset with the following parame-
ters: limit value or rate of change (gradient), hysteresis, triggered direc-
tion, and optionally line diagnosis (monitoring of the output circuit lines for
short-circuit and wire break). The outputs of safety-related limit monitors
can be connected in parallel for increasing the availability.
The module is programmed via five pushbuttons and the LCDs on the front
panel. An additional device or a PC with a special software program is not
required.
Used as a stand-alone system the module can operate without any redu-
cing of the immunity also in a plastic case.
The notes on page 7 of this data sheet for safety-related operation and use
as well as the notes in the System Manual of the Planar4 System must be
regarded.
2/24
62 100 (1146)
Examples of displays
Output 2:
H-Signal
Current value
LB
Wire break, number of the faulty channel is
flashing
LS
Short-circuit, number of the faulty channel is
flashing
3/24
62 100 (1146)
Limit value
0...20 mA / 0...5 V 0.0...110.0 % * 0.1 %
4...20 mA / 1...5 V 0.0...112.5 % * 0.1 %
Hysteresis 0.5/1...100 % 1%
Default value 0.5 %
*at max. 22 mA / 5.5 V
Outputs are switched off if input signals are out off the standard ran-
ge (NE43)
The outputs are switched off if inputs out of the standard range are confi-
gured with the parameter „input signals“. The parameter „input signals“ is
set to «4». If the input signal is outside the standard range
(< 3.6 mA/0.9 V or > 21 mA/5.25 V according to NAMUR recommendation
NE 43) the output d28 (ERR) is TRUE. The LED ERR is on and all limit
value outputs are switched off.
In the operating mode «40» (4...20 mA/1...5 V) the output z16 (Alarm) is
TRUE if the inputs is smaller than 3.6 mA.
Hysteresis 0.5/1...100 % 1%
Default value 0.5 %
4/24
62 100 (1146)
When exceeding the value discrepancy the output z16 (Alarm) is set to
1-signal during the discrepancy period; after this period all the appertai-
ning limit value outputs are switched off.
Rate-of-change monitoring
The changing of an analog input signal is recorded over an adjustable pe-
riod. If the parameterized rate of change is exceeded the concerning limit
value outputs are switched. Selectable during programming are positive
(ascending), negative (descending) and absolute (ascending or descen-
ding) gradients.
Value change
0...20 mA / 0...5 V 0.5...110.0 % * 0.5 %
4...20 mA / 1...5 V 0.5...112.5 % * 0.5 %
The entire time range of all parameterized gradients must not exceed 20 s.
If the rate-of change is not recordable (e. g. due to an out-of-range signal),
the output z16 (Alarm) is set on 1-signal.
Operating mode 7 Segment LED LED Icon 1, 2 Frame round Display Display
Relay
0...109.9 % RDY ERR Icon 1, 2 LB LS
Display of „Value“:
Range 0...22 mA / 0...5.5 V: 0...110 %
Range 4...22 mA / 1...5.5 V: 0...112.5 %
In the operating mode „Rate-of-change“ the value display shows the pre-
sent input value only but not the gradient.
5/24
62 100 (1146)
Displays Meaning
6/24
62 100 (1146)
Screened cables have to be used for the field input circuits, twisted leads
are recommended.
Proof Test
The 62 100 module must be subjected to a proof test in intervals of 10
years.
7/24
62 100 (1146)
Notes
The display is readable only at ambient temperatures higher than -10 °C.
After switching on the power in operating mode RUN (operation) all dis-
play segments are illuminated for approx. 40 seconds during the self tests
of the module. In the operating mode PROG (parameterization) the modu-
le is ready for operation at once.
During mode PROG mode all the outputs are deenergized and the red
LED ERR is flashing.
• The selection of the parameters and the entry of the values is made
by striking the MENUE and VALUE pushbuttons on the front plate
of the module. The stored or entered parameters can be seen on of
the two displays. When striking the right pushbutton MENUE the
entered parameters are shown in the sequence according to the
following table; with the left pushbutton MENUE they are shown in
reverse sequence. With both the pushbuttons VALUE the desired
parameters and values are set or changed into both directions.
• Important: For confirmation of the correct entry the same parame-
ters must be entered in each step at once again: after the first entry
the module switches with the pushbutton MENUE the second entry.
The values of the first entry are shown on the upper display, the
values of the second entry are shown on the lower display. The
next or previous range of parameters can be selected by the push-
buttons MENUE only if the entered value is in the permissible
range, and if the first and second entry are identical.
After the last entry and having pressed the pushbutton ACK then for ap-
prox. 1 second the display "Oc" is shown and the new parameters are ac-
cepted. If the values do not correspond, the display shows E01 or E02,
and the values are not accepted. After striking the pushbutton ACK the sy-
stem returns to the first step of the parameter input.
After parameterization pull out the module again, set the mode switch on
the PCB back to the center position RUN and plug in the module into the
subrack again.
8/24
62 100 (1146)
Channel 2 selected
Channel number 1 or 2
0...20 mA / 0...5 V
5 Signal evaluation Limit value (continued with 5.1) Display: for output 1 (2)
5.1 Limit value selected: limit value Display: for output 1 (2)
5.1.4 Steps since 5 repeated for the second output, then continued with 7
9/24
62 100 (1146)
5.2.4 Steps since 5 repeated for the second output, then continued with 7
6.1 Steps 5 to 5.1.3 or 5 to 5.2.3 repeated for each of the four outputs, then:
minimum values
10/24
62 100 (1146)
or or
11/24
62 100 (1146)
12/24
62 100 (1146)
13/24
62 100 (1146)
14/24
62 100 (1146)
15/24
62 100 (1146)
16/24
62 100 (1146)
Word 0 (16 bit) Word 1 (16 bit) Word 2 (16 bit) Word 3 (16 bit)
Rel. address 0 8......1 25 26 34 . . . . . . 27
Data Mod. type Mod. state Actual value channel 1 Actual value channel 2 none outputs
Word 0 (16 bit) Word 1 (16 bit) Word 2 (16 bit) Word 3 (16 bit)
Rel. address 0 8......1 35 36 34 . . . . . . 27
Data Mod. type Mod. state Additional information + Additional information + none outputs
Channel 1, limit value 1 Channel 1, limit value 2
17/24
62 100 (1146)
Word 0 (16 bit) Word 1 (16 bit) Word 2 (16 bit) Word 3 (16 bit)
Rel. address 0 8......1 37 38 34 . . . . . . 27
Data Mod. type Mod. state Additional information + Additional information + none outputs
Channel 2, limit value 1 Channel 2, limit value 2
Additional information
For a faultless data transfer always all 84 words must be read. With that
all the variables of the modules of one subrack are transferred. For module
locations not in use the values 0 are transferred.
18/24
62 100 (1146)
19/24
62 100 (1146)
20/24
62 100 (1146)
21/24
62 100 (1146)
Safety parameters
The following table specifies the parameters PFD, PFH and SFF for the
62 100 module (1oo1), and for the redundant wiring variants 1oo2
(Seite 15) and 2oo3 (Seite 16).
22/24
Analog Limit Monitor 62 100
Parameterization of the module: Cabinet / Rack _________ Subrack ________ Module location _______
Channel 1 Channel 1
Input 4...20 mA / 1...5 V (with switch-off*) Input 4...20 mA / 1...5 V (with switch-off*)
4...20 mA / 1...5 V (alarm only*) 4...20 mA / 1...5 V (alarm only*)
* when leaving the admissible input range * when leaving the admissible input range
0...20 mA / 0...5 V 0...20 mA / 0...5 V
Line diagnosis of the outputs ON Line diagnosis of the outputs ON
OFF OFF
Signal evaluation of output d18 ______________ Signal evaluation of output d22 ______________
Limit value__________ % Limit value__________ %
Hysteresis __________ % Hysteresis __________ %
Rate of Change ______ % per __________ s Rate of Change ______ % per __________ s
positive negative absolut positive negative absolut
Switching direction Low High Switching direction Low High
Signal evaluation of output d20 ______________ Signal evaluation of output d24 ______________
Limit value__________ % Limit value__________ %
Hysteresis __________ % Hysteresis __________ %
Rate of Change ______ % per __________ s Rate of Change ______ % per __________ s
positive negative absolut positive negative absolut
Switching direction Low High Switching direction Low High
Remarks
__________________________________________ __________________________________________
__________________________________________ __________________________________________
__________________________________________ __________________________________________
__________________________________________ __________________________________________