You are on page 1of 15

Journal of Cleaner Production 286 (2021) 125312

Contents lists available at ScienceDirect

Journal of Cleaner Production


journal homepage: www.elsevier.com/locate/jclepro

The viability of solar photovoltaic powered off-grid Zero Energy


Buildings based on a container home
A.B. Kristiansen , B.Y. Zhao , T. Ma , R.Z. Wang *
Institute of Refrigeration and Cryogenics, MOE Engineering Research Center of Solar Energy, Shanghai Jiao Tong University, Shanghai, 200240, China

a r t i c l e i n f o a b s t r a c t

Article history: With strongly decreasing prices of photovoltaics (PV) and battery storage in the past decade, together
Received 22 September 2020 with incentives for modular construction in China, shipping containers have been suggested as suitable
Received in revised form building modules. Transportable modules will ease the process of returning the modules to the factory
26 November 2020
for reuse and recycling of structural steel at the end of their lifetime. A previous comparison between the
Accepted 26 November 2020
proposed case studies has shown that the off-grid case can reduce the global warming potential by 76%
Available online 10 December 2020
in Shanghai when compared to a business-as-usual scenario. Generally, there is only a limited number of
Handling editor: Prof. Jiri Jaromir Klemes studies of container buildings with a simulation of the annual energy need in the literature. Particularly
there is a lack of studies of residential buildings designed for off-grid operation. This study expands a
Keywords: previous study of the case buildings by improved control strategies in TRNSYS to reduce the required PV
Zero energy building capacity and thereby the embodied emissions. For instance, thermal storage has been included to reduce
Residential building the amount of dumped energy. Also, ventilation and indoor temperature have been controlled based on
Off-grid ambient temperature, state of charge, day, and time. In cold climates, Photovoltaic thermal (PVT), floor
Solar PV
heating, and a generator have been added to increase the heating load. The results show that providing
Modular construction
thermal comfort in the heating season is the main challenge, both because of the lower coefficient of
Climate change
performance for the heat pump and due to the lower PV generation. According to the predicted effects of
climate change, the energy need for space heating is predicted to be reduced by on average 23% towards
2050 for the five climate zones in China which are considered, which would make it easier to provide
thermal comfort. The current study helps to provide a reference to lower the costs for planning and
improve the quality. The study is significant because China, who account for about 50% of new con-
struction globally, is targeting to increase its prefabricated construction by 30% within ten years.
© 2020 Elsevier Ltd. All rights reserved.

1. Introduction number of off-grid systems deployed in 2016 outpaced the grid


connections (REN21, 2018). Based on the increase in off-grid
The electricity demand for buildings is expected to grow with rooftop solar PV systems and modular construction, can a ship-
60% on average by 2040, where 90% of the growth will come from ping container be a suitable module to provide affordable and
developing countries (Roser, 2019). Since the major growth will be sustainable off-grid homes?
from countries in Africa and Asia with excellent solar resources, Significant Greenhouse gas (GHG) emission reduction may be
photovoltaics (PV) is usually the most economical way to supply the obtained if the containers replace structural steel in new buildings.
growth in electricity demand in a sustainable way (IEA, 2018). In Three Life Cycle Assessments in China have highlighted the high
addition, the price of Li-ion batteries has decreased rapidly, with an impact of steel in residential buildings. Li et al. (2019) studied four
average decrease of 14% between 2007 and 2014 (Nykvist and reinforced concrete structures and concluded that steel contributed
Nilsson, 2015). In Australia, PV with energy storage has become to 40e53% of the embodied GHG emissions. Yang et al. (2018) found
cheaper than electricity from the grid in several regions (REN21, that although steel only accounted for 2.6% of the mass of a resi-
2018). Similarly, in countries such as Kenya and Uganda, the dential building, steel contributed to 28% of the embodied GHG
emissions. The emission reduction when containers are reused for
building purposes can therefore be significant.
* Corresponding author.
Container homes have the lowest embodied energy and GHG
E-mail address: rzwang@sjtu.edu.cn (R.Z. Wang). emissions per square meter in a recent overview of prefabricated

https://doi.org/10.1016/j.jclepro.2020.125312
0959-6526/© 2020 Elsevier Ltd. All rights reserved.
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

negative perception in the market (Gan et al., 2017). Does this imply
Abbreviations that container buildings should be written off?
Many of these problems exist because the technology is
ACH50 Air Changes per Hour at 50 Pa pressure difference maturing. It can be economical to mass-produce buildings in fac-
ASHRAE The American Society of Heat, Refrigerating and tories in the same way as cars, but it requires thousands of identical
Air-Conditioning Engineers buildings to be produced. Individual customization needs to be
DHW Domestic Hot Water reduced in order to make it more economical to produce buildings
EER Energy Efficiency Ratio in factories than on-site (Olivares, 2010). More experience and the
g Solar Heat Gain Coefficient (commonly referred to use of BIM (Building Information Modeling) will lead to improved
as SHGC) standardized units over time.
GHG Greenhouse gas This article builds on a review of solar powered Zero Energy
HVAC Heating, Ventilation, and Air Conditioning Buildings (ZEBs) by Kristiansen et al. (2019) that clarifies the state
IPCC Intergovernmental Panel on Climate Change of the art for ZEBs, give design recommendations for container
LCA Life Cycle Assessment homes, and evaluates renewable energy supply options. A previous
IWEC International Weather for Energy Calculation comparative Life Cycle Assessment (LCA) study calculated a 76%
(database) reduction in Global Warming Potential (tCO2eq) from the built
PV Photovoltaics case-building described in this article without PV-battery system
PVT Photovoltaic thermal (grid-connected) compared to the off-grid case (Satola et al., 2020).
Rated COP The rated power divided by the rated input power This is due to the significant electricity consumption of the built
SEER Seasonal Energy Efficiency Ratio defined case building and the high environmental impacts of grid electricity
according to the European Union standards in Shanghai, which is mostly based on hard coal combustion. The
EN14511 and EN14825, corresponding to China’s study concludes that further research should explore additional
domestic standard GB21455 design strategies to decrease the building electricity load and the
SoC State of Charge resulting off-grid system size and embodied life-cycle impacts. The
SCOP Seasonal Coefficient of Performance, defined off-grid case in that article has the same thermal properties as the
according to the European Union standards compact case in this study, except for the floor construction and a
EN14511 and EN14825, corresponding to China’s larger window area.
domestic standard GB21455 In general, there is only a limited number of other studies of
VIP Vacuum Insulation Panel container buildings with a simulation of the annual energy need in
ZEB Zero Energy Building the literature. An overview of these studies is presented in Table 1.
The model by Taleb et al. (2019) does not include the energy
need for plug loads, which is significant for residential buildings. It
is said that the indoor temperature was set to 21  C all year round,
buildings (Tavares et al., 2019). Because containers already have an which will cause a high cooling load during the cooling season.
infrastructure for transportation, it becomes easier to transport the Schiavoni et al. (2017) achieve the lowest annual energy need of
building back to the factory at the end-of-life for deconstruction all the studies with 56 kWh/m2a. The main reason for the lower
and recycling of the structural steel. This can help to reduce con- energy need is that plug-loads, ventilation, and cooking is not
struction waste, which, thus far, has often been overlooked in China included.
(Chi et al., 2020). Recycling steel from buildings has proven to be Dara et al. (2019) modeled a residential building where four
profitable (Wang et al., 2018) with a recycling rate in China of 90% 12.2 m shipping containers are joined into a 12.2 m long and 9.75 m
(Li and Chen, 2017). A 22% reduction in embodied GHG emissions wide two-story home for 3 persons. The container walls are insu-
was obtained with a 90% recycling rate of the structural steel for a lated with foam insulation on the inside, while OBS sheathing
net-zero energy container building in Shanghai (Satola et al., 2020). covered with a hard plank siding are added on the outside. The
In addition to the reduction of GHG emissions, there is also the building façade also has an air barrier to ensure an airtightness of
political will for prefabrication. The Chinese government is strongly 0.6 ACH50, which means 0.6 air changes at 50 Pa pressure differ-
promoting industrial prefabricated construction because it can ence. The energy need is summed up as 108 kWh/m2a in the article,
improve construction quality and productivity (Cao et al., 2015). A but that is actually a combination of thermal and electric energy.
comparison with traditional construction of a residential building The article assumes an average COP of 3, which gives a total annual
showed a 20% reduction in energy consumption and a 36% reduc- electric energy need of 67 kWh/m2a.
tion in resource depletion (Cao et al., 2015). In 2016, China’s State Bowley and Mukhopadhyaya (2017) model an off-grid building
Council set the target to increase the amount of new construction with a rated PV capacity of 7 kW. The storage capacity of the battery
that was built through prefabrication from less than 1%e30% within bank is not given. 91% of the domestic hot water demand is covered
10 years (China, 2016). By 2019 there had been an increase, but still, by a solar collector. The remaining 9% is covered by an air-to-water
less than 5% of construction was built using prefabricated compo- heat pump. The space heating demand is fully covered by internal
nents (Yi, 2019). However, some obstacles remain. loads, which together with the high heat loss from the windows
Hong and Shen (Hong et al., 2018) compared eight residential makes the energy need higher than in the compact case. The energy
buildings and showed that those which were constructed using simulation is performed in the software HOT2000, which is not a
prefabrication technology were 26.3%e72.1% more expensive than dynamic simulation software (Otsubo, 2015). For off-grid simula-
those built with the traditional model. Industrial construction tion, it is important to use dynamic simulation software to capture
resulted in higher costs for investment in the factory, paperwork to the system dynamics and make sure that the load is met.
get a building permit, contract negotiation, and education and Among the few available studies, only one is designed for off-
salaries for highly skilled workers (Wu et al., 2019). The number of grid operation. The existing studies often fail to consider all rele-
drawings is 3e5 times higher than for a traditional building (Hong vant loads, especially plug-loads. This article aims to investigate the
et al., 2018). The lack of design norms and standards for off-site viability of reaching off-grid operation with reasonable thermal
construction together with a lack of quality control has led to a comfort for a container home within five different climates in
2
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Table 1
Previous studies of container buildings with a simulation of the annual energy need.

Study Location Tamb,avg Area Energy need Comments


[m2] [kWh/m2a]

Grid-connected residential building (Taleb Aswan, 26.8  C 261 1251 1


Uwall ¼ 0.87 W/m2K. Uglazing ¼ 1.6 W/m2K.
et al., 2019) Egypt 622 2
Uwall ¼ 0.19 W/m2K.
Residential nearly ZEB (Schiavoni et al., Perugia, 12.6  C 16 56 Uwall ¼ 0.085 W/m2K. 50 mm VIP in walls, roof and floor.
2017) Italy
Grid-connected residential building (Dara Calgary, 3.4  C 119 3003 3
Uwall ¼ 0.23 W/m2K.4 Uwall ¼ 0.11 W/m2K Adds shading, high airtightness,
et al., 2019) Canada 1084 PCM, and increased thermal mass.
Off-grid container house (Bowley and Victoria, 9.8  C 76 158 Passive house standard. Uwall ¼ 0.15 W/m2K. Uwindow ¼ 1.0 W/m2K.
Mukhopadhyaya, 2017) Canada
(Tumminia et al., 2018) Messina, 18.4  C 45 80 Prefabricated building with light steel structure. Uwall ¼ 0.3 W/m2K.
Italy Uglazing ¼ 1.1 W/m2K.

China. Through improved control and energy efficiency, the goal is thermal bridge value.
to reduce the size of the off-grid energy system and consequently A computer with a touch screen mounted on the wall (Fig. 2c)
the embodied GHG emissions. The study is significant because serves as the webserver for the energy management system.
China is accounting for about 50% of new construction globally (Ji OpenHAB (openHAB, 2020), an open-source home automation
et al., 2017). software, is connected to a MySQL database that logs the data from
The target audience is mainly researchers, engineers, and de- the sensors, which are transferred to the computer through the
signers who plan similar buildings. Starting from measurements of Modbus protocol. OpenHAB was chosen because it is a mature
the heating and cooling load from a real demonstration building in platform that can connect to nearly any hardware. The building can
Shanghai, the TRNSYS simulation is calibrated based on measur- be remotely controlled through the OpenHAB app or a browser
ments from an on-site weather station for the same period. Finally, (Fig. 4). It also makes it easy to monitor the system as well as adding
the potential impact of climate change is discussed before the re- schedules, for instance for the air conditioner temperature setpoint.
sults are compared with other studies. This strengthens consumer engagement, while the off-grid design
push towards degrowth and sustainable consumer attitudes.
The sizing of the PV and battery storage was based upon a
2. Case studies
comparison of Net Present Values of possible system configurations
in HOMER Pro (Energy, 2020) with an initial simulation load as
The two case studies described in this article are small apart-
input. The PV system (see module specifications in Table A1.2) in
ments made from a single shipping container. Fig. 1 shows the
the base case was designed with a theoretical peak power of
model and Fig. 2 shows the built design for the first case, with 9 m
5.5 kW.
external length. The internal length is 7.3 m as the remaining space
Totally, 24 lead-carbon batteries (see specifications in
was reserved for the roof rainwater storage tank.
Table A1.3) are connected in series, giving a total capacity 24 kWh at
In Fig. 3, an alternative case study with improved insulation and
48 V. The manufacturer suggests a Depth of Discharge (DoD) limit
less window area is proposed.
of 70% to maintain its expected lifetime of 4600 cycles. To account
The south-facing windows provide daylight and passive heat
for that the DoD at the end of the lifetime of the battery can be
gain from the sun during winter. To save water, a waterless, com-
expected to be 50%, a constant DoD of 60% is modeled.
posting toilet from Separett (2020) with low energy consumption
was chosen (Fig. 2a). Natural ventilation had previously been found
to provide the best compromise between energy use and cost for 3. Methodology
the building, compared to mechanical and hybrid ventilation
(Kristiansen et al., 2020). The hypothesis is that the proposed shipping container build-
Table 2 and Table 3 present the specification for the two studied ings have the potential to achieve off-grid operation with thermal
cases. The U-values are calculated in TRNSYS based on the layers of comfort in five major climate zones in China. To test the hypothesis
the structure and the building material properties. A concrete floor at a reasonable cost, simulation based on a verified building model
was used to utilize floor heating in the compact case. The U-value of from a built case building in Shanghai was chosen. TRNSYS
the windows and glass door are from the TRNSYS 18 library for (TRNSYS, 2019) was selected as the modeling software because IDA
double glazing (Window ID 3416) and triple glazing (Window ID ICE (EQUA, 2020) was found to be too pricey and Energy Plus (NREL,
11302), respectively. The installation of VIP was found to reduce the 2020) considers all buildings to be grid connected.
effect of thermal bridges, as studied through a 2D-heat flow anal- The energy consumption connected with equipment use has
ysis of the façade in THERM and through thermography of the been minimized, assuming that the occupants are living a simple
façade (Kristiansen et al., 2020), leading to a low normalized lifestyle for economic and environmental reasons.

Fig. 1. a) The south façade of the SketchUp model; b) Roof rainwater harvesting c) Floor plan.

3
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Fig. 2. The built demonstration building. a) Composting toilet; b) Living room and bedroom; c) Humidity and temperature sensor on the wall beside the touch screen of the energy
management system. d) South façade; e) Bird’s view.

Fig. 3. Compact design. a) North façade b) East façade c) South façade.

Table 2
Specification of design properties of two case studies.

Base case (as-built) Compact (Fig. 3)

PV, rated power [kW] 5.5 kW 2.75 kW


External dimensions 9.0m∙3.0m∙2.9m 6.1m∙2.4m∙2.9m
Heated floor area 7.3m∙2.8m 5.8m∙2.2m
Window-to-wall ratio 19% 9%
Upper and lower opening area (doors and windows) for natural 3 m2 þ 3 m2 with an average height difference of 3.1 m2 þ 1.8 m2 with an average height difference of
ventilation 1 m. 1 m.
Airtightness ACH50 1.7/h 1/h
U-values for Doors and windows, including the frame 2.80 W/m2∙K 0.71 W/m2∙K
Solar Heat Gain Coefficient (SHGC) of windows 0.76 0.37
Normalized thermal bridge value 0.1 W/m2∙K 0.1 W/m2∙K
Occupancy [persons] 2 2

Table 3
Building partitions with their total heat transfer coefficient, U [W/m2K].

Case U [W/m2K] Building materials from outside to inside

Built case Floor 0.99 2 mm steel, 20 mm polyurethane, 20 mm wood, 2 mm PVC


Roof and external walls 0.26 2 mm steel, 50 mm mineral wool, 8 mm VIP, 3 mm bamboo
Compact case Floor 0.13 2 mm steel, 20 mm polyurethane, 150 mm concrete
Roof and external walls 0.10 2 mm steel, 60 mm mineral wool, 24 mm VIP, 3 mm bamboo

The main elements in the TRNSYS model are displayed in Fig. 5. in the weather file was adjusted by subtracting 12 in accordance
The printers and online plotters have been removed for clarity. with the built case study orientation.
Some additional information about the settings for the components The convective heat transfer coefficient, hext (kJ/hm2K), for the
can be found in Table A1.1. external wall, windows and roof was adjusted according to the
wind speed in the weather file according to McAdams correlation
for rough surfaces (Equation (1)) (TRNSYS, 2017):
3.1. The building model (type 56)
hext ¼ 3:6,ð3:8 , vwind þ 7:4Þ (1)
The building geometry was generated in TRNSYS3D, a plugin for
SketchUp (Fig. 6). The outdoor room towards the east is simplified The convection coefficient for the ground floor was set to 0.001
as a shading surface. Because the building only contains one HVAC kJ/hm2K according to the recommendation in the TRNSYS manual
system, it was modeled as a single thermal zone. The solar azimuth for a direct connection to the ground (TRNSYS, 2017).
4
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Fig. 4. Screenshot from the developed smart home control system in openHAB.

Fig. 5. Screenshot from the model in TRNSYS 18.

Fig. 6. Building model from TRNSYS3D a) south and east facade b) north and west facade.

The infiltration was initially set to 1 h1, but a comparison be- am and 6e10 p.m. In addition, heat gain from 2 persons, appliances,
tween measurements and simulation based on real weather data and the hot water tank was added.
measured on-site in Section 4.1 shows that the real infiltration may To define the thermal capacity of the zone, the TRNSYS manual
be as high as 1.7 h1. This was because the moisture barrier was not recommends to multiple the air only capacity by 5e15. The air
installed in accordance with the construction requirements. This capacitance was therefore multiplied by 10 and set to 780 kJ/K due
shows the problem with the lack of experience many construction to the relatively large amount of furniture and interior wall surface
workers have in constructing energy-efficient buildings, which is a area compared to the zone volume.
reason that industrial construction might provide better results. In The exhaust fan in the bathroom was set to be on when the
a factory, airtightness testing at 50 Pa pressure difference according bathroom lights were on (6e7 am, 6e7:30 p.m., and 9:30e10 p.m.)
to ISO 9972:2015 can be a part of the quality control. with an airflow rate of 53 m3/h, which is the minimum according to
All the LED lights, totally 30 W, are expected to be on from 6 to 7 the Chinese standard (China, 2012). When the occupants are home,

5
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

they can ventilate by opening windows. Outside of occupancy gradually reduced to zero as the SoC drops below 80% towards the
hours, the exhaust fan is turned on for the purpose of cooling at minimum SoC which is set to 40% (Figure A1.1).
200 m3/h when and the indoor temperature is both above 26  C and
more than five degrees above the ambient temperature. 3.4. Equipment
The Capacitance Humidity Model was used with a Humidity
capacity ratio of 10 (TRNSYS, 2017). According to the German passive house plan, more than 40% of
primary energy is consumed by household appliances (Voss and
3.2. The heat pump model and indoor temperature set-points Musall, 2013). In an off-grid building, however, it is essential to
keep this load low in weeks when there is expected to be limited PV
The air-to-air heat pump (Table A1.4) is modeled outside Type generation. The peak load from electric equipment is set to 500 W,
56, with Type 119c. The heat pump is modeled in Type 56 as a according to the schedules in Fig. 7 on weekdays and weekends.
ventilation unit, with the supply airflow rate, air temperature, and The peaks are related to cooking. It is assumed that a slow cooker is
relative humidity set by the measured values from the output of used to improve energy efficiency and reduce the peak load from
Type 119c. The temperature and relative humidity of the air that is cooking.
entering the indoor heat pump unit is given by the output from
Type 56. To prevent the heat pump from turning on and off at the 3.5. Occupancy schedules
same temperature, the dead band is set to 2  C. Since the heat pump
model only has on/off control, the simulation time step is set to Occupant behavior is a leading source of uncertainty in pre-
5 min (TRNSYS, 2017). dicting building energy use. The occupancy schedules have been set
The COP of the heat pump was adjusted at each timestep since it up based on a survey of 3424 homes in four Chinese cities (Hu et al.,
was not possible to obtain enough data from the manufacturer to 2019). That study showed that the occupancy schedules are quite
generate a.dat file for the exact heat pump model. Therefore, the stable over the year for the same home but varies dramatically from
ASHP_Cooling.dat and ASHP_Heating.dat from TRNSYS 18 example home to home. Generally, there is only someone at home 40%e50%
files were used. The rated EER of the installed heat pump in cooling of the time, while full space occupancy in all rooms is assumed in
mode is 4.17, according to the data in Table A1.4, found by dividing Chinese building codes. A more realistic occupancy schedule will
the rated cooling power by the rated cooling input power. The rated reduce the energy need for heating and cooling, as it is common
COP of the heat pump model in Cooling.dat is 3.12. The electric practice to turn off the air conditioner when there is no one home.
energy need for the compressor for cooling is consequently Based on the main results from that study (Cluster L1, B2, S2, and
adjusted by a factor 4.17/3.12 ¼ 1.34. The electric energy need for K4) and by combining the results for rooms with multiple func-
the compressor for heating is similarly adjusted by a factor 1.06. tions, the schedules in Fig. 8 has been obtained:
This simplified method assumes that the COP variation due to Since it is assumed that the persons who live in the container
operating condition changes is equally proportional for different building are young and are working, it was further simplified by
heat pumps. assuming that there is no one home between 7 a.m. and 6 p.m. on
The heating setpoint is lowered during the night and outside weekdays. On the weekend the two persons were assumed to
occupancy hours between 10 p.m. and 4 p.m. on the weekdays and present under design conditions.
between 10 p.m. and 6 a.m. on the weekends. In addition, the
heating setpoint is increased when the SoC is above 95%. It is 3.6. Climates and locations
decreased during months where the minimum ambient tempera-
ture is below 5 , except in the last stage of the modeling of the cold Totally 5 locations with different temperature profiles ranging
climates where a generator is added to increase the energy supply. from Guangzhou in the south to Harbin in the north of China were
Similarly, the cooling setpoint is increased on weekdays outside selected (Table 4 and Fig. 9).
of occupancy hours between 7 a.m. and 4 p.m. In addition, the Energy Plus provides IWEC files from ASHRAE for these loca-
cooling setpoint is lowered when the SoC is above 95% and the tions based on weather data from 1982 to 1999 (Thevenard and
minimum monthly ambient temperature is above 15 . When the Brunger, 2001). The main simulations were based on these
SoC is below 50% the cooling setpoint is increased to save energy. weather files, but sensitivity analysis was made based on climate
change predictions for 2020 and 2050. The weather files have then
3.3. Domestic hot water been morphed in Excel through the CCWorldWeatherGen (Jentsch
et al., 2013). The climate change prediction is based on emission
The hot water load for showering for two persons is estimated scenario A2 in IPCC Report AR3 (IPCC, 2001) and AR4 (IPCC, 2007).
based on the calculation in Appendix 1. In the simulation, the According to the generated weather files, the average temperature
temperature of the water that is supplied to the hot water tank is in Shanghai increase from 16.3  C with the IWEC weather file to
set equal to the mains water temperature from the weather file. 17.2  C in 2020 and 18.5  C in 2050, as seen in Fig. 10. Based on
Since water heating is a deferable load, the water was supposed to comparison with weather data from Solargis (2020), where the
be heated during sunshine hours (09:00e15:00), when there will average temperature in Shanghai is 17.5  C the climate change
be PV generation. predictions seem reasonable.
Domestic Hot Water (DHW) is either provided from a storage
tank with an electric heating coil. The heating coil is turned on if 3.7. The simulation process
there is excess electric energy at the inverter that would otherwise
be dumped and the tank temperature is below the higher cutoff The online plotter was used to get an overview of the system
limit. The cutoff limit is 95 during the heating season and 65 behavior, particularly SoC, indoor temperature, and dumped en-
otherwise to reduce internal heat gain during the cooling season. If ergy. It was observed that the heating turned off as the lower SoC
the tank temperature is above 45  C, DHW will be provided by the was reached during periods in the winter with low PV generation.
thermal storage. If not, DHW will be provided by auxiliary heating. Consequently, the load and indoor temperature setpoints were
The tank heat loss is set equal to 1 kJ/(h∙m2∙K). reduced in months with low ambient temperature to prevent that
The DHW load is increased by 30% if the SoC is above 90% and the lower state of charge was reached. It was also observed that the
6
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Fig. 7. Schedules of the load factor for plug loads in the weekdays and weekends.

Fig. 8. Occupancy schedules based on a study of Chinese households (Hu et al., 2019).

7
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Table 4
Climate, average temperature, and annual precipitation in the selected locations.

City € ppen-Geiger classification (Beck et al., 2018)


Climate according to Ko Average annual temperature Annual precipitation

Guangzhou Humid-subtropical (Cfa) 22.2  C 1720 mm


Shanghai Humid-subtropical (Cfa) 16.1  C 1066 mm
Kunming Warm and temperate (Cwb) 15.2  C 999 mm
Lanzhou Local steppe climate (BSk) 9.9  C 327 mm
Harbin Cold and temperate (Dwa) 3.4  C 562 mm

Fig. 9. Monthly average temperatures for the five simulated locations in China.

Fig. 10. Monthly averages for ambient temperature and global horizontal radiation in Shanghai-based the generated climate files and measurements.

Fig. 11. Comparison of simulation and measurements in January.

amount of dumped energy was high, so loads were increased when angles. The output (.out) file from the simulation was copied into an
SoC was near to full charge to prevent dumped energy. Excel sheet. Other sheets in the same workbook analyzed the data
Parametric studies were used to evaluate the sensitivity to through references to the output sheets.
changed parameters, for instance different tank sizes and PV tilt

8
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

4. Results and analysis water pump, and fans. “Dumped” is the percentage of the PV
generation that would be dumped unless the energy use is
4.1. TRNSYS building model calibration increased before periods with excess energy, which typically occur
on sunny days outside of occupancy hours. The places that are
To calibrate the heating and cooling load in the building model, simulated are Harbin (HA), Guangzhou (GU), Kunming (KU),
real-time measurements were performed for a week in January and Shanghai (SH), and Lanzhou (LA). D is the change from the base case
a week in June. The power meters and Pt 100 temperature sensors to the compact case. Indoor temperature and “Hours per year” only
have an uncertainty of ±10 Wh and ±0.35  C, respectively. A consider the 5110 h of the year from 5 p.m. to 7 a.m. when the
weather file was generated in Elements (BigLadder, 2015) based on building is occupied every day. The building is particularly
measurements of dry bulb temperature, relative humidity, dew vulnerable to periods with little PV generation and colder weather,
point temperature, wind speed, and solar irradiation from an onsite because of the high temperature difference between the ambient
weather station. The simulation was then performed under actual temperature and the setpoint combined with a low COP for the heat
weather conditions. Originally, the calibration was meant to be pump. For detailed results, see monthly averages in Appendix 2 and
done based on a longer measurement period, but due to intermit- joint average values for all 5 locations in Table A3.1.
tent operation due to ongoing testing of the building automation
system followed by a component error in July only two weeks with
data during stable operation was obtained before August 2019. 4.2.1. The base case
Because the weather station was out of order between August 2019 For the five locations, the energy need for heating contributes to
and June 2020, it was not possible to generate a weather file for an 30% of the energy use on average, twice as much as for cooling. Plug
extended period. loads (35%) and DHW (17%) are the other major loads.
It was found that when the infiltration was adjusted to 1.7 it was According to Table 5, the base case can achieve off-grid opera-
a good match between the model and the measurements (Figs. 11 tion with thermal comfort in Guangzhou. A study of Fig. 14b later
and 12). As seen from Fig. 11, the simulated indoor temperature also shows that there will be thermal comfort in Kunming, as the
fluctuates slightly more than the measured, following the outdoor hours with low temperature at nighttime is acceptable. For the
temperature. This is because the TRNSYS heat pump compressor other three locations, thermal comfort is gradually reduced as the
has on-off control, while the actual heat pump has variable speed. climate gets colder. In the coldest climate, Harbin, the indoor
But most importantly, the validation shows that the heating load is temperature is below 15  C around half of the time the occupants
equal when the average indoor temperature is equal. From January are at home.
21 to January 27 the average measured and simulated heat pump The amount of energy that is dumped is high, on average 36%.
load was 428 W and 432 W, respectively. This energy is mostly dumped outside of occupancy hours during
The peak in Fig. 11 is caused by that the heat pump turns on at the spring and the autumn when there is a low energy need for the
almost full capacity for a short period. Hourly logging was used heat pump. Part of this energy could be used by increasing the use
during this measurement period so it may seem from Fig. 11 that of plug loads and hot water in advance based on forecasts. Alter-
the heat pump is operating at high power for a longer time, but it is natively, deferable loads like a washing machine or a room dehu-
actually just capturing the startup power in a short moment. midifier could automatically be powered on when there is excess
From June 4 to June 10 the average measured and simulated heat electricity.
pump load was 118 W and 115 W, respectively. Due to the good There is a significant span in the energy generation for the same
match between the measured and simulated heat pump load, amount of PV in the five locations, with a 59% higher generation in
which is the main load in the building, the building model was Harbin than in Guangzhou. None of the locations have problems
accepted. with overheating, as the PV generation also tends to be high during
the cooling season. In addition, a lower temperature difference
between the ambient temperature and the indoor temperature
4.2. Energy and indoor climate simulation during the summer leads to a 64% higher COP for heating than for
cooling on average. During the coldest days in winter, when the
The same control strategies and design have been applied for all energy need is highest, the COP is lowest. The energy need for
locations to compare the performance under similar conditions. heating of domestic hot water will also follow the ambient tem-
The simulation results are presented in Table 5. Two cases are perature if an uninsulated storage tank is placed above the ground
studied, the Base case (BC) and the Compact case (CC) according to as in Fig. 1.
Table 2. PV is the generation from photovoltaics. Heatingel and The colder climates have less energy need for plug loads due to
Coolingel are the energy use for the heat pump. Plug-loads repre- the load shedding in the control system that directs the electric
sent electric appliances. The category “Other” represent Lights, energy towards the heat pump. The average SoC is 82%, which

Fig. 12. Comparison of simulation and measurements in June.

9
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Table 5
Overview of the annual building performance of the base case based on TRNSYS simulation.

Energy per square meter floor area [kWh/m2a] Dumped SoC COP Indoor Temp. [ C] Hours per year

Place Case PV Heatingel Coolingel Plug-loads DHW Other % % Cooling Heating Ti avg Ti max Ti min Ti < 15 Ti < 5 Ti < -5

HA BC 357.5 102.9 11.1 36.7 26.2 5.3 36.7% 76.6 3.9 1.8 13.4 29.1 19.7 2316.4 1224.8 618.1
HA CC 272.3 67.4 12.7 53.4 35.8 7.8 20.2% 77.3 3.8 1.7 17.0 29.1 12.3 1613.8 875.4 187.3
D e 34.5% 14.4% 45.5% 36.5% 48.5% 16.4% 0.9% 1.1% 5.6% 4 0 7 703 349 431
GU BC 225.4 4.2 51.1 61.9 26.8 5.5 20.7% 76.7 3.8 2.7 23.4 27.5 9.9 229.5 0.0 0.0
GU CC 171.7 1.4 43.2 61.5 29.0 8.4 1.8% 64.5 3.8 2.6 24.4 29.0 13.3 50.6 0.0 0.0
D e 67.9% 15.5% 0.6% 8.2% 52.8% 18.9% 15.9% 0.4% 3.1% 1 1 3 179 0 0
KU BC 313.6 16.8 9.4 66.3 30.8 5.6 0.5% 93.0 3.8 2.5 21.4 29.1 10.8 484.2 0.0 0.0
KU CC 238.9 5.3 12.3 83.6 36.2 8.6 0.3% 86.8 3.8 2.4 23.6 29.0 14.4 6.6 0.0 0.0
D e 68.6% 30.0% 26.1% 17.3% 54.6% 0.2% 6.7% 0.9% 3.1% 2 0 4 478 0 0
SH BC 271.0 31.8 30.0 52.5 23.2 5.5 33.7% 83.7 3.7 2.4 20.7 28.5 2.1 978.8 24.8 0.0
SH CC 206.4 14.1 27.2 66.6 27.8 8.5 12.5% 80.8 3.8 2.3 22.8 29.0 11.0 227.6 0.0 0.0
D e 55.7% 9.2% 26.9% 19.9% 55.7% 21.2% 3.5% 1.3% 3.2% 2.1 0.5 8.9 751.2 24.8 0.0
LA BC 325.5 69.8 11.7 44.9 23.9 5.3 39.4% 81.6 3.9 2.2 18.5 29.2 4.7 1498.3 351.3 0.0
LA CC 248.0 37.9 14.4 68.1 32.6 8.5 17.6% 84.9 3.8 2.1 21.1 29.1 3.6 799.4 11.1 0.0
D e 45.7% 23.4% 51.7% 36.5% 60.0% 21.7% 4.1% 0.7% 4.1% 2.6 0.1 8.3 698.8 340.3 0.0

indicates that the energy coverage is good, it is only the peak load of dumped energy between November and June (Fig. 14c) means
that creates a challenge in off-grid operation. that it would often be possible to increase the indoor temperature a
For Guangzhou, the challenge is the first three months of the little or use more plug loads or hot water during this period.
year. Table A2.1 confirms that the reason for the low indoor tem- For Shanghai, January and February are not only the two months
perature (Fig. 13b) and the low SoC (Fig. 13a) in the first four with the highest energy need for heating but also the two months
months is the low PV generation. Although the average ambient with the lowest PV generation. This causes periods with low SoC
temperature is almost equal in December and February, there is (Fig. 15a) and lower indoor temperatures (Fig. 15b) when it is
more dumped energy in December (Fig. 13c) because the PV gen- cloudy, but the thermal comfort is still acceptable. Compared to
eration is almost three times higher. From the weather file, it can be Guangzhou (Table A2.1), Shanghai (Table A2.3) have a higher SoC
observed that the average global horizontal radiation in February is due to higher PV generation and lower ambient average tempera-
only half of the average for December. The average indoor relative ture between June and August. As expected, the periods with most
humidity level is 60%, without including humidity generation from dumped energy is in the spring and autumn (Fig. 15c). The average
cooking, showering, and occupants. That means that dehumidifi- indoor relative humidity level is 58% without considering internal
cation is needed to ensure a healthy indoor environment. sources of humidity, so again dehumidification is needed.
Kunming has the best SoC profile among all the five locations In Lanzhou, the winter, particularly December and January, is
and never reaches the lower limit of 40%, which is positive for much colder than the three previous locations (Fig. 9). Therefore,
prolonging the lifetime of the batteries (Fig. 14a). Some energy the SoC goes frequently down to the lower limit, causing freezingly
saving is obtained by lowering the indoor temperature outside of cold indoor temperatures at night and outside of occupancy hours
occupancy hours and during the night (Fig. 14b). The high amount (Fig. 16).

Fig. 13. Simulation of the base case in Guangzhou. a) State of Charge; b) Indoor temperature; c) Dumped energy as the percentage of the PV generation.

10
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Fig. 14. a) Simulation of the base case in Kunming. State of Charge; b) Indoor temperature; c) Dumped energy as the percentage of the PV generation.

Fig. 15. Simulation of the base case in Shanghai. a) State of Charge; b) Indoor temperature; c) Dumped energy as the percentage of the PV generation.

Harbin has extreme cold winter, as seen in Fig. 9. From April to will be hard to achieve a high standard of thermal comfort in lo-
October, however, the fact that Harbin has the highest PV genera- cations with cold winters, the compact case was simulated
tion among the studied location at the same time as there is almost (Table 6). The benefit of the compact case is that a small container is
no need for mechanical cooling contributes to a high SoC (Fig. 17a) easier to transport by a truck to the site. Fewer windows also reduce
and some dumped energy (Fig. 17c). Another peak source for the amount of structural steel that is needed during construction.
heating together with better insulation is needed (Fig. 17b). Compared to the base case, Table A3.1 shows that the number of
Otherwise, installing PVT and connecting the flat plat collectors to a hours with temperature under 15  C is reduced by 562 h on
thermal storage tank to supplement the heating from the heat average, although the installed PV capacity has been halved. For the
pump with low-temperature floor heating would be a solution to compact case, thermal comfort is good in both Guangzhou,
improve the thermal comfort. Shanghai, and Kunming. The amount of cooling per square meter is
reduced by 3% on average compared to the base case, meaning that
the increased insulation level does not cause overheating. The
4.2.2. Energy and indoor climate simulation of the compact case compact case has 20% lower dumped electric energy on average.
As the measurements and base case simulations indicate that it
11
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Fig. 16. Simulation of the base case in Lanzhou. a) State of Charge; b) Indoor temperature; c) Dumped energy as the percentage of the PV generation.

Fig. 17. Simulation of the base case in Harbin. a) State of Charge; b) Indoor temperature; c) Dumped energy as the percentage of the PV generation.

The amount of heating is reduced by 56% on average, allowing more


energy for plug loads and hot water compared to the base case. In
addition, the minimum temperature is increased by 6  C, and the
Table 6
number of hours below 15  C is halved. The embodied emissions
Average electric energy need for the case studies with PV considering climate
change. are reduced by 3.6 ton CO2eq due to 50% less installed PV capacity
than in the original design, according to the Ecoinvent 3.6 Global
Location Annual energy need [kWh/m2]
dataset.
BC, IWEC CC, IWEC CC, 2020 CC, 2050 By installing PV/T, thermal storage, and floor heating the ther-
Guangzhou 130.3 136.5 134.5 133.8 mal comfort in Lanzhou becomes acceptable with only 320 h a year
Shanghai 121.8 134.1 132.9 137.7 with an indoor temperature below 15  C, with a minimum indoor
Kunming 98.3 133.0 139.5 147.5 temperature of 9  C (Table A3.3). In Harbin, PV/T especially helps to
Lanzhou 131.8 140.1 150.1 149.5
Harbin 157.9 161.7 159.6 156.0
reduce the number of hours with indoor temperature below 5  C.

12
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

However, more heating is still needed as the indoor temperature is average for Kunming and Lanzhou. The difference in the DHW load
below 5  C for more than 500 h a year. is mainly caused by that the current study considers an occupancy
A generator would require around 837 and 1168 L diesel per year of two persons, while Schiavoni et al. (2017) consider an occupancy
in Lanzhou and Harbin, respectively. This means that it would be of a single person. In addition, the year is divided into a cooling
required to have truck delivery of diesel. In Lanzhou, this would season and a heating season, so there is never heating and cooling
help to raise the minimum indoor temperature to 15  C. In both at the same day. This might lead to a compromised thermal comfort
locations, the amount of domestic hot water would also be more part of the year. The compact case ends up with a similar energy
than doubled (Table A3.3). However, it is questionable whether it is need as the case study modeled by Schiavoni et al. (2017), but with
practical and affordable to have the diesel delivered and stored. In less costly insulation thanks to better control and the upgrade to
Harbin, it could be a solution to stack a group of containers three-layer glazing for the windows. According to a previous Net
together. Thereby is as the containers would have more adjacent Present Cost evaluation of energy conservation measures for the
surfaces and less external surfaces. External insulation of the con- container home, upgrading the windows is more profitable than
tainers could also be considered, as long as it would still be practical investing in more VIP insulation (Kristiansen et al., 2020) because
to transport the modules. To reduce the heat loss to the ground, the the additional cost for triple glazing is typically only 25% higher
foundation could also be insulated. (Howell, 2020).
The study by Dara et al. (2019) is mainly an LCA study and lacks
4.2.3. Predictions of the impact of climate change towards 2050 detailed information about the energy simulation. It is reasonable
As buildings often are planned with a 50-year lifetime they that the DHW load and the plug-loads only contribute to 22.9 kWh/
should be planned with the possible climate change in mind. m2a and 13.1 kWh/m2a since the floor area is large, but how can the
Table 6 presents the annual energy need per square meter for the electric energy need for heating and cooling be only 21.6 kWh/m2a?
case study building based on simulations with the weather files The external surface area is not that much smaller than in the
presented in section 2. Here the part of the energy for heating of compact case study and the U-value for the external walls are twice
DHW that comes from the thermal storage is withdrawn, only the as high.
electric auxiliary heating is included. Therefore, the sum of the The window area in the model by Taleb et al. (2019) is almost
elements in Table 5 is higher than the results in Table 6. twice as high as in the compact case and the U-value of the win-
Although climate change is not desirable when all consequences dows is more than twice as high. Shading is not discussed, but the
are taken into account, the predicted climate change improves the improved windows have a low emissivity coating. It is questionable
thermal comfort for the compact case in all the locations how the energy need could become so low as 62 kWh/m2a with the
(Table A3.1). The energy need for space heating during the chal- ambient temperature reaching over 45  C during the summer, but
lenging heating season could be reduced by 10% and 23% in 2020 the solution with a green roof is said to reduce the cooling load to
and 2050, respectively. Although the energy need for cooling on almost half due to the high thermal mass. The roof thickness of over
average may increase by 19% in 2020 and by 42% in 2050 compared 70 cm would also make it more difficult to ship the container. The
to the simulation based on IWEC data, the energy system is able to mean annual temperature is 4.8  C higher than in Guangzhou,
provide enough cooling to prevent the maximum indoor temper- where the energy need without plug-loads is 82 kWh/m2a.
ature from increasing. Tumminia et al. (2018) model a Net Zero Energy Building (NZEB)
in Messina, which has a slightly colder climate than Guangzhou.
4.2.4. Comparison with previous studies One of the reasons for that the energy need is 71% lower than for
The electric energy need for the compact case is in the range the compact case in Guangzhou is that it is modeled as an office
133e161 kWh/m2a based on the IWEC weather files. The average building with no need for domestic hot water. The building is also
energy need for the five previous studies in Table 1 is 110 kWh/m2a. only occupied 45 h a week. The main loads are appliances (71%) and
The models with lower occupancy rate per square meter, for heating and cooling (27%). Ventilation is only activated through
instance Taleb et al. (2019), naturally have a lower energy need per opening windows when the outdoor temperature is between 18
square meter for domestic hot water. The locations with high or low and 26  C. Thereby, ventilation neither requires energy for fans nor
average temperatures naturally have a higher energy need, while increase the energy need for heating and cooling.
the two studies from Italy in the Mediterranean climate need less
heating and cooling. 5. Conclusions
The compact case has almost the same U-value for the wall as in
the study by Schiavoni et al. (2017), but only use half the amount of A detailed TRNSYS simulation has considered control strategies
VIP by combining VIP with less expensive mineral wool insulation. and solutions for heating and cooling to achieve off-grid operation
Thereby, substantial cost savings are achieved as 8 mm VIP panels in five major climate zones in China. A central part of the off-grid
currently has a price of 125 ¥/m2 (18.6 USD/m2) in China. Schiavoni design is to prioritize among the loads. Heating and cooling have
et al. (2017) also use foam insulation on the inside and outside of been prioritized in the simulation by gradually shedding DHW
the container wall, which is also more expensive than traditional consumption and plug-loads as the batteries state of charge is
insulation materials. Together with the wooden cladding, this lowered. To reduce the size of the off-grid energy system, and
makes the design more costly, but for cooling dominated climates it thereby the embodied emissions, the system performance is
can pay back in terms of reduced investment cost for energy gen- increased by:
eration and storage. The mean ambient temperature is similar to
the one in Kunming and Lanzhou. If the only internal heat gain is  introducing thermal storage to reduce the amount of dumped
from the occupancy of 1 person it is understandable that the energy
cooling load is only around 7 kWh/m2a. Plug-loads contribute to  shifting deferable loads
68.1 kWh/m2 and 83.6 kWh/m2a for the compact case in Lanzhou  adding control of ventilation and indoor temperature based on
and Kunming, respectively. The total for Lanzhou and Kunming in ambient temperature, SoC, day, and time.
Table 6 without plug-loads is 72.0 kWh/m2a and 49.4 kWh/m2a,
respectively. The domestic hot water load is around 14 kWh/m2 in Thereby the embodied emissions of the PV array are reduced by
the study by Schiavoni et al. (2017), while it is 34.4 kWh/m2a on 3.6 ton CO2eq due to 50% less installed PV capacity than in the built
13
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

design. The study provides a reference for the thermal comfort that Environ. 163, 106332.
Energy, H., 2020. HOMER Pro. https://www.homerenergy.com/products/pro/index.
can be achieved. The base case with PV can achieve off-grid oper-
html. (Accessed 13 October 2020).
ation with thermal comfort in a temperate or subtropical climate. In EQUA, 2020. IDA indoor climate and energy. https://www.equa.se/en/ida-ice.
colder climates, it is recommended to lower the U-values of the (Accessed 26 November 2020).
envelope and add PVT, floor heating, and a generator to avoid in- Gan, Y., Shen, L., Chen, J., Tam, V.W., Tan, Y., Illankoon, I., 2017. Critical factors
affecting the quality of industrialized building system projects in China. Sus-
door temperatures below 0  C. This makes it more expensive to tainability 9 (2), 216.
achieve off-grid operation with thermal comfort in climates with Hong, J., Shen, G.Q., Li, Z., Zhang, B., Zhang, W., 2018. Barriers to promoting pre-
cold winters. The case studies are vulnerable to periods with low PV fabricated construction in China: a costebenefit analysis. J. Clean. Prod. 172,
649e660.
generation and cold weather, due to low COP for the heat pump and Howell, B., 2020. Triple glazing costs 2020: how much can you save? https://www.
higher energy need for heating of domestic hot water. An air-to-air theecoexperts.co.uk/windows/triple-glazing. (Accessed 15 October 2020).
heat pump with higher COP in the winter is therefore suggested in Hu, S., Yan, D., An, J., Guo, S., Qian, M., 2019. Investigation and analysis of Chinese
residential building occupancy with large-scale questionnaire surveys. Energy
climates with cold winters. Build. 193, 289e304.
The predicted climate change will improve the thermal comfort IEA, 2018. World Energy Outlook 2018.
in the building for all climate zones as the heating demand is IPCC, 2001. Climate Change 2001: the Scientific Basis. Contribution of Working
Group I to the Third Assessment Report of the Intergovernmental Panel on
reduced and the cooling system can counteract the increased Climate Change Cambridge (United Kingdom and New York, NY, USA).
cooling demand. IPCC, 2007. Climate Change 2007: Synthesis Report. Contribution of Working
Future research should look at how a micro-grid of container Groups I, II and III to the Fourth Assessment Report of the Intergovernmental
Panel on Climate Change. Geneva, Switzerland.
buildings with a shared energy system could reduce the embodied
Jentsch, M.F., James, P.A., Bourikas, L., Bahaj, A.S., 2013. Transforming existing
emissions and increase the reliability of supply. weather data for worldwide locations to enable energy and building perfor-
mance simulation under future climates. Renew. Energy 55, 514e524.
Ji, Y., Zhu, F., Li, H.X., Al-Hussein, M., 2017. Construction industrialization in China:
CRediT authorship contribution statement
current profile and the prediction. Appl. Sci. 7 (2), 180.
Kristiansen, A.B., Satola, D., Lee, K., Zhao, B., Ma, T., Wang, R.Z., Gustavsen, A.,
A.B. Kristiansen: Visualization, Methodology, Data curation, Novakovic, V., 2020. Feasibility study of an off-grid container unit for industrial
Formal analysis, Writing - original draft, Writing - review & editing. construction. Sustain. Cities and Soc. 61, 102335.
Li, H., Deng, Q., Zhang, J., Xia, B., Skitmore, M., 2019. Assessing the life cycle CO2
B.Y. Zhao: Investigation, Software. T. Ma: Supervision. R.Z. Wang: emissions of reinforced concrete structures: four cases from China. J. Clean.
Funding acquisition, Project administration, Resources, Prod. 210, 1496e1506.
Conceptualization. Li, L., Chen, K., 2017. Quantitative assessment of carbon dioxide emissions in con-
struction projects: a case study in Shenzhen. J. Clean. Prod. 141, 394e408.
NREL, 2020. EnergyPlus. https://energyplus.net/. (Accessed 26 November 2020).
Declaration of competing interest Nykvist, B., Nilsson, M., 2015. Rapidly falling costs of battery packs for electric ve-
hicles. Nat. Clim. Change 5 (4), 329e332.
Olivares, A.A.P., 2010. Sustainability in Prefabricated Architecture: A Comparative
The authors declare that they have no known competing Life Cycle Analysis of Container Architecture for Residential Structures: a Thesis
financial interests or personal relationships that could have Submitted to the Victoria University of Wellington in Fulfilment of the Re-
appeared to influence the work reported in this paper. quirements for the Degree of Master of Architecture. Victoria University of
Wellington.
openHAB, 2020. Documentation - introduction. https://www.openhab.org/docs/.
Acknowledgments (Accessed 13 June 2020).
Otsubo, M., 2015. Understanding the Energy Performance Gap: Case Studies of
Energy Efficient Homes. University of Toronto, Toronto, Canada.
Special thanks to Dr. Irvin Xu for designing the Energy Man-
REN21, 2018. Renewables 2018 Global Status Report.
agement System in OpenHAB and for connecting the electrical Roser, H.R.M., 2019. Renewable energy. https://ourworldindata.org/renewable-
system. We would also like to thank Phillip Vernon for proofreading energy. (Accessed 12 June 2019).
the manuscript. This paper has been written with funding support Satola, D., Kristiansen, A.B., Houlihan-Wiberg, A., Gustavsen, A., Ma, T., Wang, R.Z.,
2020. Comparative life cycle assessment of various energy efficiency designs of
from NSFC (Grant No.: 51521004). a container-based housing unit in China: a case study. Build. Environ. 186,
107358.
Appendix A. Supplementary data Schiavoni, S., Sambuco, S., Rotili, A., D’Alessandro, F., Fantauzzi, F., 2017. A nZEB
housing structure derived from end of life containers: energy, lighting and life
cycle assessment. Build. Simul. 10 (2), 165e181.
Supplementary data to this article can be found online at Separett, 2020. Urine diverting toilet Villa 9010. https://www.separett.com/en-gb/
https://doi.org/10.1016/j.jclepro.2020.125312. our-products/toilets/urine-diverting-composting-toilets/urine-diverting-toilet-
villa-9010. (Accessed 13 October 2020).
Solargis, 2020. Weather data and software for solar power investments. https://
References solargis.com/.
Taleb, H., Elsebaei, M., El-Attar, M., 2019. Enhancing the sustainability of shipping
Beck, H.E., Zimmermann, N.E., McVicar, T.R., Vergopolan, N., Berg, A., Wood, E.F., container homes in a hot arid region: a case study of Aswan in Egypt. Architect.
2018. Present and future Ko €ppen-Geiger climate classification maps at 1-km Eng. Des. Manag. 15 (6), 459e474.
resolution. Scientific Data 5, 180214. Tavares, V., Lacerda, N., Freire, F., 2019. Embodied energy and greenhouse gas
BigLadder, 2015. Elements user guide - create from scratch. https:// emissions analysis of a prefabricated modular house: the “Moby” case study.
bigladdersoftware.com/projects/elements/docs/user-guide/tutorial-create- J. Clean. Prod. 212, 1044e1053.
from-scratch.html. (Accessed 10 March 2020). Thevenard, D., Brunger, A., 2001. RP-1015 Typical weather years for international
Bowley, W., Mukhopadhyaya, P., 2017. A sustainable design for an off-grid passive locations, ASHRAE Research Project. https://www.techstreet.com/ashrae/
container house. Int. Rev. Appl. Sci. Eng. 8 (2), 145e152. standards/rp-1015-typical-weather-years-for-international-locations?gateway_
Cao, X., Li, X., Zhu, Y., Zhang, Z., 2015. A comparative study of environmental per- code¼ashrae&product_id¼1719102.
formance between prefabricated and traditional residential buildings in China. TRNSYS, 2017. Volume 9 - Tutorials, TRNSYS Documentation. Solar Energy Labora-
J. Clean. Prod. 109, 131e143. tory, University of Wisconsin-Madison.
Chi, B., Lu, W., Ye, M., Bao, Z., Zhang, X., 2020. Construction waste minimization in TRNSYS, 2019. TRNSYS transient system simulation tool. http://www.trnsys.com/.
green building: a comparative analysis of LEED-NC 2009 certified projects in (Accessed 26 November 2020).
the US and China. J. Clean. Prod. 256, 120749. Tumminia, G., Guarino, F., Longo, S., Ferraro, M., Cellura, M., Antonucci, V., 2018. Life
China, 2012. GB 50736-2012: Design Code for Heating Ventilation and Air Condi- cycle energy performances and environmental impacts of a prefabricated
tioning of Civil Buildings. National Standard of the People’s Republic of China. building module. Renew. Sustain. Energy Rev. 92, 272e283.
China, 2016. China to promote prefabricated construction. http://english.www.gov. Voss, K., Musall, E., 2013. Net Zero Energy Buildings: International Projects of Car-
cn/policies/latest_releases/2016/09/30/content_281475455281032.htm. bon Neutrality in Buildings.
(Accessed 25 July 2020). Wang, J., Wu, H., Duan, H., Zillante, G., Zuo, J., Yuan, H., 2018. Combining life cycle
Dara, C., Hachem-Vermette, C., Assefa, G., 2019. Life cycle assessment and life cycle assessment and Building Information Modelling to account for carbon emission
costing of container-based single-family housing in Canada: a case study. Build. of building demolition waste: a case study. J. Clean. Prod. 172, 3154e3166.

14
A.B. Kristiansen, B.Y. Zhao, T. Ma et al. Journal of Cleaner Production 286 (2021) 125312

Wu, H., Qian, Q.K., Straub, A., Visscher, H., 2019. Exploring transaction costs in the building in China. J. Clean. Prod. 183, 729e743.
prefabricated housing supply chain in China. J. Clean. Prod. 226, 550e563. Yi, Y., 2019. Experts promote prefabricated building for country’s green develop-
Yang, X., Hu, M., Wu, J., Zhao, B., 2018. Building-information-modeling enabled life ment. http://www.xinhuanet.com/english/2019-06/29/c_138184485.htm.
cycle assessment, a case study on carbon footprint accounting for a residential (Accessed 26 November 2020).

15

You might also like