You are on page 1of 5

Contractor

MINISTRY OF PETROLUEM & MINIRALS


SUDANESE PETROLEUM COORPORATION (SPC)
Sub-Contractor

OWNER PMC HAYA DEPOT EXPANSION PROJECT

HAYA DEPOT EXPANSION PROJECT

CAUSE EFFECT MATRIX FOR FIREFIGHTING AND FIRE


DETECTION SYSTEM

Issued For Husam Moh. Ahmed Sami


A 5-2-19 Moh. Mahdi
Review A.elkarim Abdelrhman Elmogtaba Elhabob
Rev. Date Description Prepared By Checked By Reviewed By Approved By PMC/REP

TITLE: Cause effect matrix for firefighting and fire detection system Page 1 of 5
Rev. : A Contract No.: SPC-HDEP/072018 Document No.: HDEP-E-IC-CA-0004
Contractor
MINISTRY OF PETROLUEM & MINIRALS
SUDANESE PETROLEUM COORPORATION (SPC)
Sub-Contractor

OWNER PMC HAYA DEPOT EXPANSION PROJECT

OPEN Pneumatic valve Pn.V-01


OPEN Pneumatic valve Pn.V-02

OPEN cooling Valves DV-01

OPEN cooling Valves DV-05


OPEN cooling Valves DV-02

OPEN cooling Valves DV-03


OPEN cooling Valves DV-04

Activate Outdoor fire horn


Activate Indoor Sounder
(Civil defense building)

(Civil defense building)


Activate Strobe & Siren

Activate Strobe & Siren

Activate Strobe & Siren


Hazard - output to ESD

Hazard - output to ESD


Hazard - output to ESD

(feeding ESD Valve –

(Gasoil Pump Shed)


Effect

Battery limit)

(Tank -02)
(Tank -01)
( Zone-1)

( Zone-2)
Cause

Heat signal from (PS-01) – (Pressure


Switch - Wet pilot sprinklers
detection system). X X X
Heat signal from (PS-02) – (Pressure
Switch - Wet pilot sprinklers
detection system). X X X
Zone-1 Fire is confirmed from (PS-01 and PS-
Tank-01 02) – (Pressure Switch - Wet pilot X X X X
sprinklers detection system). X X X X X X X

Heat signal from (linear heat


detector – Tank roof). X X X
Heat signal from (linear heat
detector – Tank shell). X X X

TITLE: Cause effect matrix for firefighting and fire detection system Page 2 of 5
Rev. : A Contract No.: SPC-HDEP/072018 Document No.: HDEP-E-IC-CA-0004
Contractor
MINISTRY OF PETROLUEM & MINIRALS
SUDANESE PETROLEUM COORPORATION (SPC)
Sub-Contractor

OWNER PMC HAYA DEPOT EXPANSION PROJECT

Fire is confirmed from (Tank roof


linear heat detector and Tank shell X X X X
linear heat detector). X X X X X X X
Fire is confirmed from (PS-01 or PS-
02) and (Tank roof linear heat
detector Or Tank shell linear heat X X X X X X X X X X X
detector).
Fire is confirmed from (PS-01 or PS-
02) and Operator. X X X X X X X X X X X
Fire is confirmed from (Tank roof
linear heat detector Or Tank shell X X X X
linear heat detector) and Operator. X X X X X X X

Leak detection from (Gas Detector). X X X X X


Manual call point energized
X X X
Zone-2 Heat signal from (PS-03) – (Pressure
Tank-02 Switch - Wet pilot sprinklers
detection system). X X X
Heat signal from (PS-04) – (Pressure
Switch - Wet pilot sprinklers X X X
detection system).

TITLE: Cause effect matrix for firefighting and fire detection system Page 2 of 5
Rev. : A Contract No.: SPC-HDEP/072018 Document No.: HDEP-E-IC-CA-0004
Contractor
MINISTRY OF PETROLUEM & MINIRALS
SUDANESE PETROLEUM COORPORATION (SPC)
Sub-Contractor

OWNER PMC HAYA DEPOT EXPANSION PROJECT

Fire is confirmed from (PS-03 and PS-


04) – (Pressure Switch - Wet pilot X X X
sprinklers detection system). X X X X X X X X
Heat signal from (linear heat
detector – Tank roof). X X X
Heat signal from (linear heat
detector – Tank shell). X X X
Fire is confirmed from (Tank roof
linear heat detector and Tank shell X X X
linear heat detector). X X X X X X X X
Fire is confirmed from (PS-03 or PS-
04) and (Tank roof linear heat
detector Or Tank shell linear heat X X X X X X X X X X X
detector).
Fire is confirmed from (PS-03 or PS-
04) and Operator. X X X X X X X X X X X
Fire is confirmed from (Tank roof
linear heat detector Or Tank shell X X X
linear heat detector) and Operator. X X X X X X X X

Leak detection from (Gas Detector). X X X X X


Manual call point energized
X X X

TITLE: Cause effect matrix for firefighting and fire detection system Page 2 of 5
Rev. : A Contract No.: SPC-HDEP/072018 Document No.: HDEP-E-IC-CA-0004
Contractor
MINISTRY OF PETROLUEM & MINIRALS
SUDANESE PETROLEUM COORPORATION (SPC)
Sub-Contractor

OWNER PMC HAYA DEPOT EXPANSION PROJECT

Heat signal from (linear heat


detector). X X X
Heat signal from (thermal heat
detector). X X X
Fire is confirmed from (linear heat
detector and thermal heat detector) X X X X X X X X
Zone-3 Fire is confirmed from (linear heat
Pump Shed detector Or thermal heat detector) X X X
and Operator. X X X X X

Leak detection from (Gas Detector). X X X X X


Manual call point energized
X X X
Heat signal from (thermal heat
detector). X X
Zone-4
Smoke signal from (Smoke detector).
Civil X X
defense
building Manual call point energized
X X
Evacuation push button X X X
X X

TITLE: Cause effect matrix for firefighting and fire detection system Page 2 of 5
Rev. : A Contract No.: SPC-HDEP/072018 Document No.: HDEP-E-IC-CA-0004