Fire Prevention Department

General Directorate of Civil Defense


Ministry of Interior, State of Qatar
ALL DUCTS USED FOR MECHANICAL VENTILATION SYSTEM SHALL BE 2 HOURS FIRE RATED DUCT
FIRE FIGHTING /
SMOKE STOP
STAIRCASE.01 STAIRCASE.02 SMOKE STOP B1- PARKING B1- PARKING B2- PARKING B2- PARKING B3- PARKING B3- PARKING FIRE PUMP ROOM GENERATOR ROOM FIRE COMMAND CENTER MV ROOM TX ROOM LV ROOM WATER PUMP ROOM IRRIGATION PUMP ROOM
LOBBY
LOBBY
PF - 03 PF - 01 PF - 02 PF - 04
EX.A.F-01 F.A.F-01 EX.A.F-01 F.A.F-01 EX.A.F-02 F.A.F-02 EX.A.F-02 F.A.F-02 EX.A.F-03 F.A.F-03 EX.A.F-03 F.A.F-03 EX.A.F-04 F.A.F-04 EX.A.F-05 F.A.F-05 EX.A.F-06 F.A.F-06 EX.A.F-07 EX.A.F-08 EX.A.F-09 EX.A.F-10 EX.A.F-11
17719 cfm 17719 cfm 16821 cfm 1564 cfm
17230/10338 CFM 14646/8788 CFM 17230/10338 CFM 14646/8788 CFM 17456/10474 CFM 14838/8903 CFM 17456/10474 CFM 14838/8903 CFM 16320/9792 CFM 13872/8323 CFM 16320/9792 CFM 13872/8323 CFM 905/542 CFM 905/542 CFM 281/169 CFM 281/169 CFM 191/114 CFM 191/114 CFM 1083/650 CFM 1190/713 CFM 1068/640 CFM 165/99 CFM 165/99 CFM
Pressure relief damper
with area of 1 m2
PF - 01 PF - 01 PF - 02 PF - 04
17719 cfm 17719 cfm 16821 cfm 1564 cfm

Pressure relief damper


with area of 1 m2

VCD VCD VCD VCD

(QCD Officer's Signature)


1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD

1181 CFM
SG 250X300
Δp>=5 pa
1181 CFM
SG 250X300
Δp>=5 pa
1121 CFM
SG 400X350
Δp>=12.5 pa
104 CFM
SG 100X200
Δp>=12.5 pa
Application/PS No. Reviewing Engineer's Signature/Date
VCD VCD VCD VCD

1181 CFM 1181 CFM 1121 CFM 104 CFM

Date :
SG 250X300 SG 250X300 SG 400X350 SG 100X200

Δp>=5 pa

VCD
Δp>=5 pa

VCD
Δp>=12.5 pa

VCD
Δp>=12.5 pa

VCD
N/2022/0003504
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD CONSULTANT'S ENDORSEMENT


1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

I, ENGR. ROMEO BENID PLASENCIA AN MECHANICAL ENGINEER WITH UPDA/QCD REGISTRATION NO. 1239,
1181 CFM
VCD

1181 CFM
VCD

1121 CFM
VCD

104 CFM
VCD

BEING THE CONSULTANT, HEREBY CERTIFY THAT THE FIRE SAFETY WORKS SHOWN ON THIS AIR CONDITIONING
AND MECHANICAL VENTILATION (ACMV) ARE IN ACCORDANCE WITH THE QCD TECHNICAL REQUIREMENTS
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD


GUIDE 2022.
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

FURTHER, I HEREBY CERTIFY THAT I AM FULLY AWARE ON THE APPROVAL OF FIRE SAFETY ENGINEERING
VCD VCD VCD VCD

1181 CFM
SG 250X300
1181 CFM
SG 250X300
1121 CFM
SG 400X350
104 CFM
SG 100X200
PLANS AND DO NOT RELIEVE MYSELF OF BEING THE CONSULTANT ON THE RESPONSIBILITY IN CONTINUED
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

COMPLIANCE TO THE QCD TECHNICAL REQUIREMENTS GUIDE 2022, APPLICABLE/ACCEPTABLE NFPA CODES,
1181 CFM
VCD

1181 CFM
VCD

1121 CFM
VCD

104 CFM
VCD

STANDARDS, PROCEDURES AND PRACTICES IMPLEMENTED BY THE GDCD.


SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD AFFIXED IS MY NAME AND COMPANY STAMP TO ATTEST WITH THE ABOVE UNDERTAKING.
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD

1181 CFM
SG 250X300
1181 CFM
SG 250X300
1121 CFM
SG 400X350
104 CFM
SG 100X200
(SIGNATURE OF CONSULTANT)
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

ENGR. ROMEO BENID PLASENCIA


P. O. BOX 2118 , DOHA QATAR.
VCD VCD VCD VCD
TEL. 44443445 FAX. 44443224
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200

Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD


UPDA Reg. No./Grade : 1239/A Qatar ID No : 26860805861
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 SG 100X200

09/03/2025 23/07/2023
Δp>=5 pa Δp>=5 pa Δp>=12.5 pa Δp>=12.5 pa

VCD VCD VCD VCD


Validity : Validity :
1181 CFM 1181 CFM 1121 CFM 104 CFM
SG 250X300 SG 250X300 SG 400X350 Δp>=12.5 pa SG 100X200 Δp>=12.5 pa
Δp>=5 pa Δp>=5 pa

VCD VCD VCD VCD

1181 CFM 1181 CFM 1121 CFM 104 CFM

DEVELOPMENTCONSULTINGENGINEERINGCO.
SG 250X300 SG 250X300 SG 400X350 Δp>=12.5 pa SG 100X200 Δp>=12.5 pa
Δp>=5 pa Δp>=5 pa

QATARIPRIVATESHAREHOLDINGCOMPANY
DESIGN-SUPERVISION-PROJECTMANAGEMENT

SCHEDULE OF SPLIT TYPE AC AT FIRST BASEMENT SCHEDULE OF AC'S AT 2nd,4th,7th & 8th FLOORS
COOLING CAPACITY POWER SUPPLY POWER CONSUMED COOLING CAPACITY POWER SUPPLY POWER CONSUMED
Reference Qty REMARKS Reference QTY REMARKS
NOMINAL (TR) V/PH/HZ (KW) NOMINAL (TR) V/PH/HZ (KW)

SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE DSPU-01 1.0 240/1/50 1.2 3.0 DUCTED SPLIT TYPE

SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE DSPU-02 1.5 240/1/50 1.8 11.0 DUCTED SPLIT TYPE

SPU-03 2.0 240/1/50 2.4 6.0 WALL MOUNTED SPLIT TYPE DSPU-03 2.0 240/1/50 2.4 --- DUCEDT SPLIT TYPE

SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE DSPU-04 2.5 240/1/50 3.0 3.0 DUCTED SPLIT TYPE (Head Offices Signature)
DSPU-05 3.0 240/1/50 3.6 9.0 DUCTED SPLIT TYPE

SCHEDULE OF SPLIT TYPE AC AT SECOND BASEMENT DSPU-06 4.0 240/1/50 4.8 --- DUCTED SPLIT TYPE

COOLING CAPACITY POWER SUPPLY POWER CONSUMED SPU-01 1.0 240/1/50 1.2 3.0 WALL MOUNTED SPLIT TYPE
UPDA Reg. No./Grade : 285/A Qatar ID No : 25782802368
Reference Qty REMARKS
NOMINAL (TR) SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE
V/PH/HZ (KW)

SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE


SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE Validity : 15/05/2023 Validity : 19/08/2022
240/1/50 1.8 --- SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE
SPU-02 1.5 WALL MOUNTED SPLIT TYPE

SPU-03 2.0 240/1/50 --- WALL MOUNTED SPLIT TYPE SPU-05 3.0 240/1/50 3.6 --- WALL MOUNTED SPLIT TYPE
2.4

SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE


CLIENT/OWNER

SCHEDULE OF AC'S AT 3rd FLOOR


COOLING CAPACITY POWER SUPPLY POWER CONSUMED
SCHEDULE OF SPLIT TYPE AC AT THIRD BASEMENT Reference QTY REMARKS
NOMINAL (TR) V/PH/HZ (KW)
COOLING CAPACITY POWER SUPPLY POWER CONSUMED
Reference Qty REMARKS
NOMINAL (TR) DSPU-01 1.0 240/1/50 1.2 3.0 DUCTED SPLIT TYPE
V/PH/HZ (KW)
DSPU-02 1.5 240/1/50 1.8 11.0 DUCTED SPLIT TYPE
SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE
DSPU-03 2.0 240/1/50 2.4 --- DUCEDT SPLIT TYPE
SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE
--- DSPU-04 2.5 240/1/50 3.0 3.0 DUCTED SPLIT TYPE
SPU-03 2.0 240/1/50 WALL MOUNTED SPLIT TYPE
MR IBRAHIM HASSAN AL-ASMAKH
2.4
DSPU-05 3.0 240/1/50 3.6 9.0 DUCTED SPLIT TYPE
SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE
DSPU-06 4.0 240/1/50 4.8 --- DUCTED SPLIT TYPE

SPU-01 1.0 240/1/50 1.2 3.0 WALL MOUNTED SPLIT TYPE

SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE


SCHEDULE OF AC'S AT GROUND FLOOR
SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE
COOLING CAPACITY POWER SUPPLY POWER CONSUMED
Reference QTY SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE
REMARKS
NOMINAL (TR) V/PH/HZ (KW)
SPU-05 3.0 240/1/50 3.6 --- WALL MOUNTED SPLIT TYPE
DSPU-01 1.0 240/1/50 1.2 4.0 DUCTED SPLIT TYPE

DSPU-02 1.5 240/1/50 1.8 4.0 DUCTED SPLIT TYPE SCHEDULE OF AC'S AT 5th & 6th FLOORS
DSPU-03 2.0 240/1/50 2.4 1.0 DUCEDT SPLIT TYPE
COOLING CAPACITY POWER SUPPLY POWER CONSUMED
DSPU-04 2.5 240/1/50 3.0 1.0 DUCTED SPLIT TYPE Reference QTY REMARKS
NOMINAL (TR) V/PH/HZ (KW)
DSPU-05 3.0 240/1/50 3.6 3.0 DUCTED SPLIT TYPE
DSPU-01 1.0 240/1/50 1.2 3.0 DUCTED SPLIT TYPE
DSPU-06 4.0 240/1/50 4.8 1.0 DUCTED SPLIT TYPE
DSPU-02 1.5 240/1/50 1.8 11.0 DUCTED SPLIT TYPE
SPU-01 1.0 240/1/50 1.2 6.0 WALL MOUNTED SPLIT TYPE
DSPU-03 2.0 240/1/50 2.4 --- DUCEDT SPLIT TYPE PROJECT TITLE
SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE
DSPU-04 2.5 240/1/50 3.0 3.0 DUCTED SPLIT TYPE
SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE
DSPU-05 3.0 240/1/50 3.6 9.0 DUCTED SPLIT TYPE
SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE
DSPU-06 4.0 240/1/50 4.8 --- DUCTED SPLIT TYPE
SPU-05 3.0 240/1/50 3.6 --- WALL MOUNTED SPLIT TYPE
SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE

SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE

SCHEDULE OF AC'S AT FIRST FLOOR SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE

COOLING CAPACITY SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE
POWER SUPPLY POWER CONSUMED
Reference QTY REMARKS 240/1/50
NOMINAL (TR) SPU-05 3.0 3.6 --- WALL MOUNTED SPLIT TYPE
V/PH/HZ (KW)

PROPOSED(3B+G+10) RESIDENTIAL
DSPU-01 1.0 240/1/50 1.2 3.0 DUCTED SPLIT TYPE

DSPU-02 1.5 240/1/50 1.8 11.0 DUCTED SPLIT TYPE SCHEDULE OF SPLIT TYPE AC AT ROOF FLOOR
DSPU-03

DSPU-04
2.0

2.5
240/1/50

240/1/50
2.4 ---

3.0
DUCEDT SPLIT TYPE

DUCTED SPLIT TYPE


Reference
COOLING CAPACITY POWER SUPPLY POWER CONSUMED
Qty REMARKS
APARTMENT BUILDING
3.0 NOMINAL (TR) V/PH/HZ (KW)

DSPU-05 3.0 240/1/50 3.6 9.0 DUCTED SPLIT TYPE SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE
DSPU-06 4.0 240/1/50 4.8 --- DUCTED SPLIT TYPE SPU-02 240/1/50 1.8 1.0
1.5 WALL MOUNTED SPLIT TYPE
SPU-01 1.0 240/1/50 1.2 3.0 WALL MOUNTED SPLIT TYPE SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE
SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE SPU-04 2.5 240/1/50 ---
3.0 WALL MOUNTED SPLIT TYPE
SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE

SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE

SPU-05 3.0 240/1/50 3.6 --- WALL MOUNTED SPLIT TYPE

SCHEDULE OF AC'S AT 9th & 10th FLOORS


Location : MUSHAIREB Pin No. : 13230013
COOLING CAPACITY POWER SUPPLY POWER CONSUMED
Reference QTY REMARKS
NOMINAL (TR) V/PH/HZ (KW)

DSPU-01 1.0 240/1/50 1.2 3.0 DUCTED SPLIT TYPE Total Area : Street : Plot No. :
DSPU-02 1.5 240/1/50 1.8 11.0 DUCTED SPLIT TYPE

DSPU-03 2.0 240/1/50 2.4 --- DUCEDT SPLIT TYPE

DSPU-04 2.5 240/1/50 3.0 3.0 DUCTED SPLIT TYPE


DRAWING TITLE/SHEET CONTENT
DSPU-05 3.0 240/1/50 3.6 9.0 DUCTED SPLIT TYPE

DSPU-06 4.0 240/1/50 4.8 --- DUCTED SPLIT TYPE

SPU-01 1.0 240/1/50 1.2 2.0 WALL MOUNTED SPLIT TYPE


SCHEMATIC RISER DIAGRAM
& SCHEDULE OF EQUIPMENT
SPU-02 1.5 240/1/50 1.8 --- WALL MOUNTED SPLIT TYPE

SPU-03 2.0 240/1/50 2.4 --- WALL MOUNTED SPLIT TYPE

SPU-04 2.5 240/1/50 3.0 --- WALL MOUNTED SPLIT TYPE

SPU-05 3.0 240/1/50 3.6 --- WALL MOUNTED SPLIT TYPE

Revision : 01 SHEET NO : 18/22 DRWG. NO.

Date : 28/08/2022 SCALE : NTS ACMV-18