Design Factors:
h
l = 800mm
h = 720mm
t = 30mm
Density d = 26000 N/m3
t l Weight = l x h x t x d
= 450 N
Wall Structure:
WALL
Cavity C = 60mm
C
Projection K = 80mm
K
STONE (M)ART CLADDING SYSTEMS
Structure - edge spacing:
a) Minimum distance from the corner of the slab to the pin center should be 2.5 times
the slab thickness i.e. 2.5 x t = 2.5 x 30 = 75mm
Maximum distance from the corner of the slab to the pin center is 1/4th of the length
of the slab i.e. ¼ x h = ¼ x 720 = 180mm.
b) The minimum pin center distance to the edge of the slab (across thickness) should
be 15mm.
The proposed pin center distance is 15mm.
Application type:
Load Principles:
Vertical (Dead Load) and Horizontal (Wind Load) loads are determined according to the
following diagram. The following principle is applied before designing a fixing system:
Considering the design dead load and wind load, the following bracket systems are
suggested (refer enclosed data sheet):
The actual bracket (from among the ones specified) will depend upon the cavity and
projection.