Professional Documents
Culture Documents
CONTROL INTERFACE
Set Output - (V/I): Multi turn potentiometer - 1no. (Lockable)
Rectifier On: Illuminated Push Button
Rectifier Stop / EM Stop: Mushroom head Push Button
Fault / Fault reset: Illuminated Push Button
Auto/Manual: Illuminated Selector Switch
* - Breaker and LC Filter are optional
TECHNICAL DATA
Output Direct Voltage range: 150 V - 1000 V* PowerKraft OPTIONS
Output Direct Current range: 1500 A - 10 kA**
Input 3-phase AC Voltages: 380, 415, 440, 480 V, Additions
6.6 kV - 33 kV (Higher voltages on request) - Remote control box ’basic version’ with DC meter, potentiometers, fault reset etc.
Frequency: 50/60 Hz - Harmonic filter panel + PF correction bank.
Auxiliary supply: ≤ 480 VAC ±10%, 3-phase - AC/ DC busduct.
Certificate: CE marking - Water cooling system for rectifier.
EMC conformity: IEC 61000-6-4 (Emissions) and IEC 61000-6-2 (Immunity) - HT isolator panel, Feeder panel, Polarity Reversal.
Design Standards: *** IEC 60076, IEC 61378, IEC 60146
Protection class: IP 20 (Air cooled), IP 44 (Water cooled) Harmonics
Topology: 6 Pulse, 12 Pulse Active Harmonic Filter (AHF)
Power factor: > 0.9 lagging at rated output and nominal input voltage Total current harmonic distortion: < 7 % of rated nominal current
Efficiency: > 0.9 at rated nominal current < 5% of rated nominal current
Ambient temperature: +5/+40°C (Up to 50°C on request) Harmonic mitigation performance:Up to the 50th harmonic
Cooling: Rectifier — Forced air (AF) / Water Cooled Protection: Overheat, overvoltage and undervoltage,
Transformer - Dry Type (AF), Oil Immersed (ONAN / ONAF) summary fault indication
Humidity: 10-90% RH, non-condensing Communication interface: PROFINET
Control precision: ±1% Protection: IP20/IP21 (Option)
Regulation range: Stepless at constant voltage or current 10—100% Certification: CE, UL, ROHS
Ripple filter: < 5% at rated output (Available on request)
Duty ratio: Continuous operation at rated load Power Factor
Protection: Overcurrent, Overvoltage, Thyristor Overtemperature, General: > 0.9 Lagging. Up to 15-100% of nominal output*
Thyristor fuse failure, Transformer Overtemperature, PFC bank: Modular System
Emergency Stop * Depending on customer requirement
Communication interface: PROFINET, Hardwired - Classic Solution
Container Solution