CORPORATION OF GREATER MUMBAI, INDIA
EYE HOSPITAL (BYCULA)
BOQ
SR. DESCRIPTION
DSR SPECIFICATION QTY. UNIT RATE TOTAL AMOUNT
NO.
Part A ‐Airconditioning High Side
1 SITC of Capacity (R‐410A /R‐407c or eco‐friendly Refrigerant) Air Cooled type OUTDOOR UNITS of
VRF system having hermetically sealed scroll inverter compressor, condenser coil fabricated from
Seamless Copper tube & Plate type Al. Fins of Multi Row, Axial Flow, upward throw condenser fan,
Condenser fan ‐ motor unit, insulated refrigeration piping, power / control wiring, and
earthing, external wiring between Indoor & Outdoor units, all system controls‐safety. Each Outdoor
units with High Pressure switch, Fan driver overload protector, Over current relay, Inverter
Overload Protector & Fusible Plug. The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC
supply, and IP 55 protection. The out door unit Shall be installed on M.S. platform duly painted, as
per specifications.
2 Indoor Units :‐ Ductable for VRF
a Supply, installation, testing and commissioning of VRV / VRF based ductable type, high static indoor
unit (IDU) having nominal cooling capacity of 4.1TR ( 1640 cfm )to 5.0TR ( 2000 cfm ) having EER as
per BEE standards and specifications with evaporator fan with motor, copper tube aluminium fin
evaporator coil, washable air filter, insulated drain tray, expansion device, cordless remote control
with necessary controls and electrical terminal to receive power supply, etc. having anti‐corrosive
coating suitable for coastal area, with suitable ceiling suspension arrangement, with an electronic
control console and any additional refrigerant and oil charge as per requirement during installation
connected with the system complete.
3 Indoor Units :‐ Compact cassette type for VRF
a 1.5 TR Four way Cassette Type R2‐ME‐9‐14‐d 2 NOS 37656 75,312.00
4 Indoor Units :‐ Large cassette type for VRF
a 2 TR Four way Cassette Type R2‐ME‐9‐13‐c 15 NOS 52979 7,94,685.00
b Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette
indor unit (IDU) compact / standard size of nominal cooling capacity 2.6TR ( 918 cfm ) to 2.8TR (
1100 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with
swing louvers and adjustable blades from sides. Indoor Units complete with in‐built drainage
arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air
port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to
operate on 1‐phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil
charge as per requirement during installation and connected to the system complete.
5 Indoor Units :‐ Hi‐Wall unit for VRF
a 1.5 TR Hi‐Wall unit R2‐ME‐9‐15‐d 10 NOS 28177 2,81,770.00
b 2.0 TR Hi‐Wall unit R2‐ME‐9‐15‐f 5 NOS 31035 1,55,175.00
6 SITC OF DOUBLE SKIN AIR HANDLING UNITS for OT with AHU Kit
a 4.0 TR Double skin air handling units of EUROVENT Certified. Designed for minimum 6 ACPH SEH‐HVAC‐F1 1 NOS 300000 3,00,000.00
Outdoor Air and AHU's shall be of Double skinned panels of 40+/‐2 mm thick. Double Skin Panels
shall be made of 0.6mm Pre‐coated GSS on outside and 0.6mm Galvanized sheet inside with CFC –
FREE P.U. insulation of 40 (+/‐ 5%) kg/Cu M injected in between with an internal gasket between
the skins to interrupt the thermal bridge of the panel.,Single decker type suit at Site.Mixing
Chamber , Fresh & Return Air Dampers, Prefilter section with, 10 micron (EU 4) Pre filters, Filter
section with 3 micron (EU 9) Fine Filters.
Cooling coil section with 6 rows deep cooling coil for AHU with Heater
Installation of UV Lamps, space required in AHU for UV lamps.
Fan section with backward curved Plug fan with Aerofoil design blades with IE2 Motors with VFD's,
HP /LP SENSORS with Pressure relief damper control.
THERMOSTAT automatic temperture control
7 Supply, Installation, Testing and Commissioning of Refnets as specified of pipe sizes from 1/4 " to 2"
R2‐ME‐9‐10‐l 119 NOS 8440 10,04,360.00
8 Supply, Installation, Testing and Commissioning of Central remote controller must be integrable
with the VRV/VRF system Complete operation & monitoring of VRV air conditioning system shall be
possible through the control system.Following functions shall be possible i.) Controlling indoor units
ii.) Zone control iii.) Malfunction code display iv.) All the functions available with wired remote
controller v.) It should be possible to wire the remote to 1000m vi.) Remote start / stop of indoor
units vii.) Mal function report. viii.) Colour LCD touch panel icon display ix.) Fault History up to 100
R2‐ME‐9‐10‐m 1 NOS 103881 1,03,881.00
actions. x.) Simple Interlock Function xi.) Fire Alarm System interface Required hardware shall be
suitable for operation between ‐10 Deg C to 50 Dg C & humidity range, of 0% to 98%, without
condensation
TOTAL OF HIGH SIDE 1,96,22,907.00
Par B ‐Airconditioning Low Side
1 SITC of Seamless heavy gauge REFRIGERATION COPPER PIPING for VRF/ VRV system in 18 gauge,
duly insulated with 13 mm/19 mm thickness. Nitrile Rubber Insulation. Refrigeration piping will
have to be taken in the piping rack / Support individually connecting to Indoor units, including
necessary supports, fittings, valves, Cable tray for exposed piping where ever required will be
R2‐ME‐9‐10‐k 1346.511144 RMT 3740 50,35,951.68
included.. The pipe sizes from 1/4 " to 1".(13 mm insulation) and 1‐1/8 " to 2"(19 mm insulation)
shall be used.
2 2C x 1.5 Sq.mm
R2‐ME‐2‐3‐a 1834.175 Mtr. 80 1,46,734.00
4 Supply Installation Testing & commissioning AHU Controller / distribution kit of suitable capacity
for connecting multi VRF ODU to DX AHU, with a) built in auto restart function, c) with necessary
electrical wiring & remote controller. R2‐ME‐9‐10‐j 6 NOS 58173 3,49,038.00
5 Providing & fixing of platform and M.S. Railing for Outdoor units of Split AC to facilitate smooth
R2‐ME‐9‐2‐g 25 Job 10921 2,73,025.00
access to technician to safely carry out maintenance .
6 Supply, installation, commissioning & testing of Exhaust/fresh fans in accordance with and meeting
the intents & specifications, drawings and data sheets complete with:
'i) Centrifugal Fan with dual speed drive motors , as specified.
'ii) Mild steel mounting frame
iii) Vibration mounts.
iv) Fire retardant flex. connections .
v) Epoxy coated cabinet.
vi) Isolator panel (IP‐ 56) with starter as required
vii) with canvas connection
a 900 CFM @50TSP SEH‐HVAC‐F3 10 NOS 12600 1,26,000.00
b 300 CFM @50TSP SEH‐HVAC‐F4 1 NOS 4200 4,200.00
c 2500 CFM HEAVY DUTY (FIRE MODE 5000 CFM 1 NOS 70000 70,000.00
Static Pressure : 40 mmwg
SEH‐HVAC‐F5
Temperature : Class F 55ºC at continious operation
Mounting : Insiude Shaft /Ceiling Suspended
7 ALUMINUM DUCTING :‐Supply fabrication installation testing and commissioning of Aluminum R2‐ME‐9‐48
sheet metal ducting with:a) Sealants, b) Gaskets c) structural support systems d) nuts & bolts, e)
angles.f). Closed cell neoprene gaskets etc (20 SWG) Aluminum Sheet
12 UNDERDECK INSULATION
Supply & installation of under deck roof insulation with teak wood frame and 50mm thick TF qulaity
themocol covered with foam sheet R2‐ME‐9‐44 340.55 Sqm 4477 15,24,622.00
TOTAL OF LOW SIDE 1,02,91,419.18
Part C‐ TOILET AREA VENTILATION
1
Supply, installation, commissioning & testing of Exhaust/fresh fans in accordance with and meeting
the intents & specifications, drawings and data sheets complete with:
'i) Centrifugal Fan with dual speed drive motors , as specified.
'ii) Mild steel mounting frame
iii) Vibration mounts.
iv) Fire retardant flex. connections .
v) Epoxy coated cabinet.
vi) Isolator panel (IP‐ 56) with starter as required
vii) with canvas connection
2
GSS Ducting:‐ Supplying fabrication installation testing and commissioning of GI. Sheet metal
ducting. Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive
elastomeric foam gasket, Support etc as per SMACNA specification.
a 24 SWG R2‐ME‐9‐47‐c 1092 sqm 1665 18,18,180.00
b 22 SWG R2‐ME‐9‐47‐b 312 sqm 1838 5,73,456.00
c 20 SWG R2‐ME‐9‐47‐a 16 sqm 1938 31,008.00
d Providing fresh air damper with crowl piece,bird screen and removable type prefilters R2‐ME‐9‐31 43 sqm 15187 6,53,041.00
4 Readymade 2500mm standard length, prefabricated, Ladder type cable tray from MS sheet and
then hot dip galvanised, of following sizes and associated accessories such as coupler plates, tees,
elbow etc. 50 mm side flanges shall be provided. Galvanisation thickness shall be minimum 86
Micron.
TOTAL OF LIFT WELL PRESSURIZATION 39,81,395.34
Part D‐LIFT SHAFT PRESSURIZATION
1 FANS
Staircase And Lifts Pressurisation Fan Sections Supply,installation,testing and commissioning of
DIDW centrifugal AMCA certified fans type fan section with motor,drives,set mounting frame,GI
sheet casing of 16 Guage and its fans shall be AMCA certified the units shall be complete as per
specifications and drawings of below capacities for staircase,lifts and lift lobby pressurisation. It
should be complete as per manufacturer's specifications & as directed by Engineer‐in‐charge.
2
GSS Ducting:‐ Supplying fabrication installation testing and commissioning of GI. Sheet metal
ducting. Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive
elastomeric foam gasket, support etc as per SMACNA specification.
a 20 SWG R2‐ME‐9‐47‐a 50 sqm 1928 96,400.00
b Providing fresh air damper with crowl piece,bird screen and removable type prefilters R2‐ME‐9‐31 3 sqm 15187 45,561.00
TOTAL OF LIFT WELL PRESSURIZATION 5,91,961.00
Part E ‐ Comprehensive Service Maintenance Contract
1 CSMC cost for Next 5 Years after initial warranty/DLP of 1 year. The warranty & AMC will be comprehensive
and all cost of repairs / replacement of parts, accessories, etc. will be borne by the successful tenderer. The
CSMC payments will be released six monthly after successful completion of the period. Comprehensive
AMC includes
A) Servicing and maintenance of supplied ACs,
B) Repairing and replacement of any electrical parts such as fan, switches, MCBs. Faulty Cables, pipeline
leakage attend,
C)Refilling of oil and gas and consumables etc.
D) Periodical (Monthly/Quarterly, Yearly) servicing etc.
The above list is only indicative and agency has to carry out complete preventive and Corrective
maintenance to keep the system in the good working condition.
a 1st year 478.00 HP 2200 10,51,600.00
b 2nd year 478.00 HP 2310 11,04,180.00
c 3rd year 478.00 HP 2426 11,59,628.00
d 4th year 478.00 HP 2547 12,17,466.00