Professional Documents
Culture Documents
保护测控装置
NF801/4 Four side DIF Protection & Monitoring Device
instructions
技
术
说
明
书
广东南丰电气自动化有限公司
Guangdong Nanfeng Electric Automation Co., Ltd
目 录
Contents
NF801/4 微机四侧差动保护测控装置...........................................................................1
NF801/4 FOUR SIDE DIF PROTECTION & MONITORING DEVICE.....................................1
一、 装置概述 DEVICE SUMMARY...................................................................................1
二、装置原理和结构 DEVICE PRINCIPLE AND STRUCTURE...........................................4
三、人机接口 MAN-MACHINE INTERFACE.....................................................................5
四、 主要保护功能 PRIMARY PROTECTION FUNCTION...................................................9
五、 主要技术指标 PRIMARY TECHNICAL SPECIFICATIONS..........................................9
六、 模拟输入 ANALOG INPUT.....................................................................................9
七、 保护原理 PROTECTION PRINCIPLE.........................................................................10
八、 定值 VALUE..........................................................................................................13
九、 装置端子图及端子定义 DEVICE TERMINAL DEFINITION DIAGRAM....................16
十、 控制回路图 CONTROL CIRCUIT DIAGRAM............................................................17
十一、 外形及安装尺寸 SHAPE & INSTALLATION SIZE................................................19
订货须知 Ordering Information:..................................................................................20
本说明书和产品今后有可能性会有小变动,届时恕不另行通知;产品与说明书不符者,以实际产品为准。
The instructions and product may be a small change in the future,then without notice;If the product
does not match with the description, to the actual product.
第二版 ver:2.0
Second Edition ver:2.0
NF801/4 微机四侧差动保护测控装置
1
1). 装置特点: 1). Device characteristics:
集保护和测控功能于一体; Integrating protection and control
functions;
2). 装置参数:
1、额定数据
2). Device Parameters:
1、Rating data
交直流电源:220V,允许偏差+15%, -
AC/DC power supply: 220V , allowable
20%
deviation +15%,-20%
交流电压:100V,57.7V
AC voltage : 100V,57.7V
交流电流:5A,1A
AC current : 5A,1A
频率:50Hz
Frequency: 50Hz
2、功 耗 2、Power consumption
交流电压回路:<0.5VA/相 ( 额 定 电 压 AC voltage circuit:<0.5VA / phase(Rating
下) voltage)
交流电流回路:<0.5VA/相 (In=1A) AC current circuit : <0.5VA /
<1VA/相 (In=5A) phase(In=1A)
直流回路:正常< 15W <1VA / phase(In=5A)
跳闸< 25W DC circuit: Normal< 15W
Trip < 15W
7、过载能力 7、Overload
(1) 交流电流回路:2 倍额定电流连续 (1)AC current circuit: two times the rated
工作;10 倍额定电流工作 10S;20 current continuously; 10 times the rated
倍额定电流工作 1S。 current job 10S; 20 times the rated current job
1S.
交流电压回路:1.2 倍额定电压连续工作 AC voltage circuit: 1.2 times the rated
voltage continuously.
主程序模块:进行循环的测量计 算,并且完成实时时钟和
E2PROM 的读写; calculate the loop, and complete
real-time clock and E2PROM read
main modules: measurements to and write;
5mS 中断模块:完成通讯数据和 5mS interrupt module: data
进程的处理。 processing and communication
processes;
以太网中断模块:接收以太网数 Ethernet interrupt
据; module:Receiving Ethernet data;
RS485 通讯中断模块:接收和发 RS485 communication interrupt
送 RS485 通讯接口数据; module: RS485 communication
interface to receive and send data;
测频中断模块:进行频率跟踪并 Interruption frequency
计算频率; measurement modules: frequency
track and calculate the frequency;
采样中断模块:完成保护、测量、 Sampling interrupt module:
录波的采样并进行保护计算和保 sample protection, measurement,
护过程。 and to protect the recorded wave of
computing and protection process.
测量数据
信号量
信号量 Measuring data
signal
定值查询
信号量 Fixed check
定值修改
Fixed modify
定值固化
Fixed solid
系数参数用以对测量量进行修正;地
址参数是通讯中装置的本地地址;端口参 System parameter is used to revise the
数对通讯口的波特率、校验方式等进行处理; measurement signals; Address parameter
密码是装置的密码,所有用到密码的地方 refers to the local address of device in
都与此处设定的密码相关;时间设置是用 communication; Port parameter is used to deal
以修改装置自身的实时时钟的。 with communicative baud rate and testable
methods; Password refers to the password of
device, and all the places using passwords is
related to the set password here. Time set is
used to modify the device’s own real-time
5.开关控制主要对控制回路与装置相连的几 clock.
个设备进行控制,在差动保护中,此项功 5. Switch control The control circuit and
能备用。 the device connected to several devices to
control, in the differential protection, this
feature is spare.
当差电流大于整定定值时,说明内部肯定 出现了严重故障,差动保护应不进行任何制动
而立即动作于跳闸。差电流速断保护动作定值 When the differential current surpasses its
应按躲过各种不平衡电流和涌流整定。 fixed value, indicating that there must be a serious
internal failure, differential protection should take
no action on the brake, and it should trip
immediately. The fixed value of differential
quickbreak protective action should be regulated to
2. 二次谐波制动的比率差动保护 avoid all kinds of imbalanced current and spill.
Iop Iop
Isds Isds
其中: Among of them: Iop ― the every-side same phase
et Iop ― 各侧同相的差电流(计算得到); et
K2
Ires ― 制动电流(最大差电流相四侧电流 differential currentK2
(it is calculated);
动 作 action
绝对值和的 制动区
0.5 倍); Ires ― break current (Brake
The maximum difference
区 区
between the currentzone
phase of the current side
Is1、Is2 拐点 1、2(由用户整定);
K
Icds K1、K2 一、二段折线斜率(由用户整 Icds K1
of the absolute value of 0.5 times);
et 1 et Inflexion current 1、2(organized by users);
定);
Isdset ― 差电流速断定值; K1、K2 slope of two step broken lines(organized
Is Is
Icdset ― 比率差动定值。 Ires byIsusers);Is Ires
1 2 1 2
Isdset ― ixed value of differential current
quickbreak;
Icdset ― fixed value of ratio differential
protection。
3. 二次谐波闭锁原理 3. Second harmonic latching principle
装置采用三相差电流中二次谐波与基波 Devices adopt the ratio of secondary harmonic
的比值作为励磁涌流的判据。当任一相差动电 and basal wave in the three-phase different
流中的二次谐波比值大于定值,即满足闭锁 current to be the base of excitation spill. When
条件,则闭锁三相比率差动保护。 secondary harmonic in any phase different
current is bigger than the fixed value,
the locking condition is attained, and then the
three-phase ratio differential protection is
latched.
4. CT 断线闭锁 4. CT disconnection
CT 断线的判定条件为: CT disconnection to determine the conditions for:
A、 一侧三相电流中有一相减小为零, A, one side of the three-phase current is reduced
其它两相电流和另外两侧的电流不 to zero, the other two-phase current and the other
变。 side of the current unchanged.
B, the maximum side of the current phase is
B、 本侧最大相电流大于 0.2 倍 IE。 greater than 0.2 times IE.
5.各侧电流相位与平衡补偿
5. Side current phase and balance compensation
为消除各侧 CT 变比选择而造成的不平衡
In order to eliminate the imbalance current
电流,需要计算变压器各侧电流回路的调整
caused by the selection of the CT ratio on each
系数,将其输入装置,通过软件将由此造成
side, it is necessary to calculate the adjustment
的不平衡电流完全补偿。各侧的电流互感器二
coefficient of the current loop on each side of the
次电流相位由软件校正,本装置可对 Y/Δ11
transformer, and input it to the device to
接线方式进行相位校正。
compensate the unbalanced current caused by the
software. Each side of the current transformer
secondary current phase by the software
correction, the device can Y / Δ11 wiring phase
correction.
6. 非电量保护 6. Nonelectric Quantity protection
本装置设有故障录波功能,记录的模拟
量 为
Ia0、Ib0、Ic0、Ia1、Ib1、Ic1、Ia2、Ib2、Ic2、Ia3、Ib
3、Ic3,记录的状态量为开关位置。 The device is provided with the function of
trouble recording wave, analog recording about
Ia0、Ib0、Ic0、Ia1、Ib1、Ic1、Ia2、Ib2、Ic2、Ia3、Ib
3、Ic3, state recording about switch position.
八、定值 Value
四侧差动保护测控装置定值
序号 定值名称 整定范围 整定步长 备 注
1 差动速断 5.00~99.99A 0.01A
2 比率差动 1.00~30.00A 0.01A
3 拐点 1 电流 1.00~99.99A 0.01A
4 拐点 2 电流 1.00~99.99A 0.01A
5 斜率 1 K1 0.10~0.90 0.01
6 斜率 2 K2 0.10~0.90 0.01
7 谐波制动比 0.1~0.3 0.01
8 I1 调整率 0.10~7.90 0.01
9 I2 调整率 0.10~7.90 0.01 I0 为调整率基准
10 I3 调整率 0.10~7.90 0.01
11 差流告警值 0.10~4.99 0.01
以下整定控制字,控制字位置“1”相应功能投入,置“0”相应功能退出
1 差动速断投入 0(×)/1(√)
2 (差动速断)启动录波投入 0(×)/1(√)
3 比率差动投入 0(×)/1(√)
4 谐波制动投入 0(×)/1(√)
5 经 CT 断线闭锁投入 0(×)/1(√)
6 (比率差动)启动录波投入 0(×)/1(√)
7 I2 投入 0(×)/1(√)
运行参数
8 I3 投入 0(×)/1(√)
9 I0 进行相位调整 0(×)/1(√)
I1 为相位调整基
10 I2 进行相位调整 0(×)/1(√)
准
11 I3 进行相位调整 0(×)/1(√)
定值整定说明
本装置可以适合多种接线方式,比如全星形(Y/Y/Y/Y)、全三角形(△/△/△/△)、星
三角混接等,在星三角混接方式中三角侧的相位相对星形应为 11 点方向,也即通常
使用的 YD11(Y/△11)接线。
电流平衡系数 K1、K2、K3
此种情况,0 侧和 2 侧需要进行相位调整。
即在 Y/△混接方式中,电流平衡系数三角形(△)侧的乘以 的系数,而星形(Y)
侧不乘;相位调整是星形(Y)进行调整,而三角形(△)侧不调整。
在全星形(Y/Y/Y/Y)、全三角形(△/△/△/△)中,相位调整项皆为不调整;电流平衡
系数各侧皆不乘 这个系数。
CT 接线要点:
在 CT 的接线上要注意,流向保护区内方向为各侧电流正方向!
Set value setting instructions
The device can be suitable for a variety of wiring methods, such as the whole star (Y / Y / Y /
Y), full triangular (△ / △ / △ / △), star delta mixed, etc., in the star delta mixed way triangular
side Of the phase relative to the star should be 11 o'clock direction, that is commonly used YD11
(Y / △ 11) wiring.
In the protection of the I0 side and I1 side must access the current, I2 side and I3 side can not
access the current. In the Y / △ mixing mode, the I0 side must be connected to the star (Y) side,
and I1 must be connected to the triangular line (△) side.
Note: The adjustment of the adjustment rate is based on I0; the setting of the phase is based
on I1.
I0 side for the star connection, I1 side for the triangular connection, I2 side for the star
connection, I3 side for the triangular connection, for example, the side of the adjustment rate
algorithm is as follows