You are on page 1of 27

NF801/4 微机四侧差动

保护测控装置
NF801/4 Four side DIF Protection & Monitoring Device
instructions





广东南丰电气自动化有限公司
Guangdong Nanfeng Electric Automation Co., Ltd
目  录
Contents

NF801/4 微机四侧差动保护测控装置...........................................................................1
NF801/4 FOUR SIDE DIF PROTECTION & MONITORING DEVICE.....................................1
一、 装置概述 DEVICE SUMMARY...................................................................................1
二、装置原理和结构 DEVICE PRINCIPLE AND STRUCTURE...........................................4
三、人机接口 MAN-MACHINE INTERFACE.....................................................................5
四、 主要保护功能 PRIMARY PROTECTION FUNCTION...................................................9
五、 主要技术指标 PRIMARY TECHNICAL SPECIFICATIONS..........................................9
六、 模拟输入 ANALOG INPUT.....................................................................................9
七、 保护原理 PROTECTION PRINCIPLE.........................................................................10
八、 定值 VALUE..........................................................................................................13
九、 装置端子图及端子定义 DEVICE TERMINAL DEFINITION DIAGRAM....................16
十、 控制回路图 CONTROL CIRCUIT DIAGRAM............................................................17
十一、 外形及安装尺寸 SHAPE & INSTALLATION SIZE................................................19
订货须知 Ordering Information:..................................................................................20

本说明书和产品今后有可能性会有小变动,届时恕不另行通知;产品与说明书不符者,以实际产品为准。
The instructions and product may be a small change in the future,then without notice;If the product
does not match with the description, to the actual product.
第二版 ver:2.0
Second Edition ver:2.0
NF801/4 微机四侧差动保护测控装置

NF801/4 Four side DIF Protection & Monitoring Device


一、装置概述 Device Summary

1
1). 装置特点: 1). Device characteristics:
 集保护和测控功能于一体;  Integrating protection and control
functions;

 主 CPU 采用高速 DSP(数字信号  The main CPU adopts high speed


处理器)芯片; DSP (digital signal processor )chips.
 提供工业以太网或 RS485 等通讯 Provide industrial Ethernet or
方式; RS485communication way;
 集成 IEC60870-5-103、IEC60870-  Integrated IEC60870-5-
5-104 等标准通讯规约以及 CDT 103、IEC60870-5-104 standard
等部颁规约; communication protocols and the
CDT customer code;

 采用 128×64 带背光液晶显示器,  Use 128 x 64 with a backlit LCD


显示内容丰富明了,外形美观; display, shows rich content and
clear, beautiful appearance;

 低功耗设计,整机功耗不大于  Design of low power consumption,


35W; the power consumption is lower than
35W;
 确保在-30℃~+70℃环境下运行;  Ensure that run in -30 to +70 DEG
C environment;
 所有对外引出的电气端子抗过压  The electrical
和浪涌; terminals all output can be anti over-
voltage and surge;
 主板元件全表贴安装,4 层印刷  motherboard component fully
线路板,抗干扰能力强; installed paste, 4 layer printed
circuit board, strong anti-jamming
ability;
 硬件和软件设计均模块化,便于  Hardware and software design are
升级和扩展功能。 modular, easy to upgrade and extend
the functionality.

2). 装置参数:
1、额定数据
2). Device Parameters:
1、Rating data
交直流电源:220V,允许偏差+15%, -
AC/DC power supply: 220V , allowable
20%
deviation +15%,-20%
交流电压:100V,57.7V
AC voltage : 100V,57.7V
交流电流:5A,1A
AC current : 5A,1A
频率:50Hz
Frequency: 50Hz
2、功 耗 2、Power consumption
交流电压回路:<0.5VA/相 ( 额 定 电 压 AC voltage circuit:<0.5VA / phase(Rating
下) voltage)
交流电流回路:<0.5VA/相 (In=1A) AC current circuit : <0.5VA /
<1VA/相 (In=5A) phase(In=1A)
直流回路:正常< 15W <1VA / phase(In=5A)
跳闸< 25W DC circuit: Normal< 15W
Trip < 15W

3、遥测量计量等级 3、Remote measurement metrology grade


电流:0.2 级 Current : 0.2 level
其他:0.5 级 Other: 0.5 level

4、遥信分辨率 4、Remote resolution


< 2ms < 2ms

5、信号输入方式 5、Input way of signal


无源节点 Passive node

6、模拟量输入 6、Analog input

外部电流及电压输入经隔离互感器隔 After the external current and voltage


离变换后,由低通模拟滤波器输入至模数 input isolation transformer isolation after
变换器,CPU 经采样数字处理后构成各种 conversion from analog low-pass filter input
保护继电器,并计算各种遥测量。 to the analog to digital converter, constitute
the CPU handle a variety of sampled digital
protection relay, and calculate various remote
measurements.
保护电流经过装置的保护 CT(一般为 filtering and remove interference’s devices, 进
100A/7.07V,可根据特殊要求进行选配) , 行保护。测量 CT 与保护 CT 分开,电压 UA
电压信号(UA,UB,UC,U0 等)经过 同时作为测频电路的输入。
PT(150V/7.07V),转换成电压信号,然
后经过低通滤波和抗干扰器件、保护电路、
运算放大器后输入到可以输入±10V 的 A/D
转换器,转换成数字信号进入 CPU,经过
运算后
Protection current through protection CT
device (typically 100A / 7.07V, can be protection circuits, after the op amp input to ±
selected according to the special 10V can enter the A / D converter,
requirements),Voltage signal (UA, UB, UC, converted into a digital signal into the CPU,
U0, etc.) through the PT (150V / 7.07V), into After the operation for protection.Separate
the voltage signal,Then through the low-pass measurement CT and protection CT, Voltage
UA same time as the input frequency measurement circuit.
每个装置输入的电压电流量都不相同, Each device input voltage is not the same
但原理是一致的,在装置说明部分只列出 amount of current, but the principle is the
输入的模拟量。 same, only lists the analog input device
described in the section.

7、过载能力 7、Overload
(1) 交流电流回路:2 倍额定电流连续 (1)AC current circuit: two times the rated
工作;10 倍额定电流工作 10S;20 current continuously; 10 times the rated
倍额定电流工作 1S。 current job 10S; 20 times the rated current job
1S.
交流电压回路:1.2 倍额定电压连续工作 AC voltage circuit: 1.2 times the rated
voltage continuously.

(2) 电源回路:80% – 120%额定电压 ( 2 ) Power circuit: 80% - 120% of rated


正常工作。 voltage to work properly.

8、绝缘性能 8、Insulating properties


(1) 所有电路与外壳间的绝缘电阻在标 (1)The insulation resistance between the
准实验条件下不小于 100MΩ。 housing and all circuits under standard
experimental conditions of not less than
100MΩ.
(2) 所有电路与外壳间的介质强度能耐 (2) Dielectric strength between all circuits and
受交流 50Hz、电压 2kV(有效值)、 the shell can withstand AC 50Hz, voltage 2kV
历时 1min 的试验而无绝缘击穿或 (Valid values), which took 1min test without
闪络现象。 dielectric breakdown or flash-over.

二、装置原理和结构 Device principle and structure


1). 硬件原理 1). Hardware principle
2). 结构设计 2). Structure design
装置采用标准 6U 机箱后插拔设计,分为 design , divided CPU / power plug 、 IO
CPU/电源插件、IO 插件和 PT/CT 插件。 plugins and PT / CT plugin.See the definition
具体结构参见各装置端子定义图。 of the specific structure of the terminal device
With standard 6U chassis plug map.

3). 程序框架结构 3). Program frame


程序共分为 6 个模块,每个模块独立 Program is divided into six modules,Each
运行,合理安排了优先级顺序,充分利用 module is run independently,Reasonable
资源并且尽量互不联系,增强了可靠性。6 arrangements for the priority order,Full use of
个模块及功能如下(优先级逐次升高): resources and try not to touch each other, and
enhance reliability.6 modules and functions
are as follows (priority successive rises).

 主程序模块:进行循环的测量计 算,并且完成实时时钟和
E2PROM 的读写; calculate the loop, and complete
real-time clock and E2PROM read
 main modules: measurements to and write;
 5mS 中断模块:完成通讯数据和  5mS interrupt module: data
进程的处理。 processing and communication
processes;
 以太网中断模块:接收以太网数  Ethernet interrupt
据; module:Receiving Ethernet data;
 RS485 通讯中断模块:接收和发  RS485 communication interrupt
送 RS485 通讯接口数据; module: RS485 communication
interface to receive and send data;
 测频中断模块:进行频率跟踪并  Interruption frequency
计算频率; measurement modules: frequency
track and calculate the frequency;
 采样中断模块:完成保护、测量、  Sampling interrupt module:
录波的采样并进行保护计算和保 sample protection, measurement,
护过程。 and to protect the recorded wave of
computing and protection process.

三、人机接口 Man-machine interface


人机接口为整套保护提供管理功能和外 Man-machine interface provides management
部通信功能,NF801/4 微机四侧差动保护 functions and external communications
测控装置采用了带背光的 128*64 液晶显示 functions for the entire-protection,NF801/4 
器,提供友好的人机操作界面。 Four side DIF Protection & Monitoring Device
装置面板如下所示。 uses 128 * 64 with a backlit LCD display,
friendly man-machine interface.
Device panel as shown below.
1). 按键说明 1). Button note
▲ --光标向上滚动或菜单向上翻页 ▲-- Cursor scroll up or menu turn up the page

▼ --光标向下滚动或菜单向下翻页 ▼-- Cursor scroll down or menu turn down page

◄ --光标向左移动 ◄ --Cursor Shifts to the left


► --光标向右移动 ► --Cursor Shifts to the right
+ --字母数字增加 + --Increase
- --字母数字减小 - --Reduce
ENT -- 确认 ENT -- Confirm
ESC -- 取消 ESC -- Cancel
复归 -- 复位事故和告警信号 Reset -- Reset the trouble and alarm signals
注:面板上有 6 个指示灯,分别是: Note: There are six panel indicators, namely:
运行 -- 工作状况指示灯,装置正常运行时 Run -- The pilot lamp for working status, when
不停的闪烁,反之一直亮(绿); working normally, the lamp flickers ceaselessly;
otherwise the lamp is lit in green all the time.
备用 --暂无用途(绿); Spare-- Currently useless, this lamp is it in
green.
备用 --暂无用途(红); Spare-- Currently useless, this lamp is it in red.

事故-- 当装置所监视的系统有故障信号时 Trouble--When there are trouble-signals, this


点亮(红); lamp is lit in red.
告警 -- 当装置所监视的系统有告警信号时 Alarm-- When there are alarm-signals, this
点亮(红); lamp is lit in red.

备用 --暂无用途(绿)。 Spare-- Currently useless, this lamp is it in green.

2). 操作简要说明 2). Operation Brief Description


整套保护采用了统一风格的人机界面, The entire protection devices adopt the man-
界面友好。按照分层的菜单方式,可以根据 machine interfaces with unified style. The
提示方便地进行操作。这里只简要介绍一下 interface is friendly in accordance with the
菜单的内容。 layered menu manner, so you can easily operate
by hint. Here it’s only a brief presentation of the
contents of this menu.

主菜单如下: Main Menu as follows:


实时数据 开关控制
事件记录 语言选择 Real-time data Switch control
Events record Language select
定值管理
Fixed Value
系统管理
System Para

1.实时数据包括测量数据和信号量,选定后 1. Real-time data which includes measurement


可以显示相应数据和信号量的状态。 data and signals can display corresponding data
after it is selected;

测量数据
信号量
信号量 Measuring data
signal

2.事件记录显示最近发生的 20 个事件,显 occurring


示在第一页下面的一个是最新的事件。装置 recently, the one displayed at the bottom of
掉电后事件不丢失。 the first page is the latest incident.

2.Incident records can display 20 events


3.定值管理包括三个菜单: 3.Fixed Value Management includes three

定值查询
信号量 Fixed check
定值修改
Fixed modify
定值固化
Fixed solid

定值的查询和修改有同样的界面,前 Fixed Value inquiry has the same interface


者与后者的差别是后者可以修改定值,前 with Fixed Value Revision, the difference
者不能。当定值修改过后,退到这个界面选 between the former and the latter is that the latter
定“定值固化”菜单按确认键,在输入密 can modify the fixed value, but the former can’t.
码后可以固化定值。 After the fixed value has been modified, we
return to this interface to choose the menu of
“fixed value solidification”, then press the
“ENT” and input the password to solidify the
fixed value.

定值按照功能分成若干个组,有如下 Fixed Value can be divided into some


定值组: groups according to different functions, its
fixed Value is as following:

差动速断 DIF action cut-off


信号量
调整率 Adjustment rate
比率差动 Ratio differential
其他 Other ▼
neg

4.系统管理包括: 4.System Management includes:

系数参数 时间设置 System Para Set-up Time


地址参数 遥信参数 Address Para Remote Signal Para
端口参数 Port Para
密码修改 Change password

系数参数用以对测量量进行修正;地
址参数是通讯中装置的本地地址;端口参 System parameter is used to revise the
数对通讯口的波特率、校验方式等进行处理; measurement signals; Address parameter
密码是装置的密码,所有用到密码的地方 refers to the local address of device in
都与此处设定的密码相关;时间设置是用 communication; Port parameter is used to deal
以修改装置自身的实时时钟的。 with communicative baud rate and testable
methods; Password refers to the password of
device, and all the places using passwords is
related to the set password here. Time set is
used to modify the device’s own real-time
5.开关控制主要对控制回路与装置相连的几 clock.
个设备进行控制,在差动保护中,此项功 5. Switch control The control circuit and
能备用。 the device connected to several devices to
control, in the differential protection, this
feature is spare.

6.信号复归功能用于对装置的告警和事故信 6. The signal reset function is used to reset


息进行复归,相当于常规保护的掉牌复位。 the alarm and accident information of the
device, which is equivalent to the
conventional protection.

四、主要保护功能 Primary protection function


1)差动速断保护; 1) DIF action cut-off;
2)二次谐波制动的比率差动保护; 2) Ratio differential protection of the
secondary harmonic break;
3)CT 断线检测和闭锁功能; 3) CT disconnection and locking function;

4)非电量保护; 4) Nonelectric Quantity protection ;


5)故障录波功能。 5) Trouble recording wave.

五、主要技术指标 Primary Technical Specifications

1) 差动速断保护 1) Without time limit over-current protection;


电流定值: 2In – 12 In Current setting: 2In –12In
定值误差:< 5% Setting error: < 5%
2) 二次谐波制动的比率差动保护 2) Overload protection;
过流定值:0.2In – 10In Current setting: 0.2 In –102In
定值误差:< 5% Setting error: < 5%

六、模拟输入 Analog input


IA0, IB0, IC0, IA1, IB1, IC1, IA2, IB2, IC2,
IA0、IB0、IC0、IA1、IB1、IC1、IA2、IB2、
IA3, IB3, IC3 are Four Side differential protection
IC2、IA3、IB3、IC3 为四侧差动的保护 CT
CT output current as differential protection. Which
输出电流,作为差动保护量。其中 I3 和 I4
I3 and I4 whether the input can be achieved
是否投入可以通过软件实现,相应侧选择
through the software, the corresponding side of the
不投入则该侧的 CT 电流不予采集。
choice does not put the side of the CT current is
not collected.

七、保护原理 Protection principle

1. 差动速断保护 1. Over-current protection ;

当差电流大于整定定值时,说明内部肯定 出现了严重故障,差动保护应不进行任何制动
而立即动作于跳闸。差电流速断保护动作定值 When the differential current surpasses its
应按躲过各种不平衡电流和涌流整定。 fixed value, indicating that there must be a serious
internal failure, differential protection should take
no action on the brake, and it should trip
immediately. The fixed value of differential
quickbreak protective action should be regulated to
2. 二次谐波制动的比率差动保护 avoid all kinds of imbalanced current and spill.

比率制动的差动保护,动作特性如图示。 2. Ratio differential protection of the secondary


harmonic break
It adopts the ratio break differential protection,
the action characteristics are the same as the figure.

Iop Iop

Isds Isds
其中: Among of them: Iop ― the every-side same phase
et Iop ― 各侧同相的差电流(计算得到); et
K2
Ires ― 制动电流(最大差电流相四侧电流 differential currentK2
(it is calculated);
动 作 action
绝对值和的 制动区
0.5 倍); Ires ― break current (Brake
The maximum difference
区 区
between the currentzone
phase of the current side
Is1、Is2 拐点 1、2(由用户整定);
K
Icds K1、K2 一、二段折线斜率(由用户整 Icds K1
of the absolute value of 0.5 times);
et 1 et Inflexion current 1、2(organized by users);
定);
Isdset ― 差电流速断定值; K1、K2 slope of two step broken lines(organized
Is Is
Icdset ― 比率差动定值。 Ires byIsusers);Is Ires
1 2 1 2
Isdset ― ixed value of differential current
quickbreak;
Icdset ― fixed value of ratio differential
protection。
3. 二次谐波闭锁原理 3. Second harmonic latching principle
装置采用三相差电流中二次谐波与基波 Devices adopt the ratio of secondary harmonic
的比值作为励磁涌流的判据。当任一相差动电 and basal wave in the three-phase different
流中的二次谐波比值大于定值,即满足闭锁 current to be the base of excitation spill. When
条件,则闭锁三相比率差动保护。 secondary harmonic in any phase different
current is bigger than the fixed value,
the locking condition is attained, and then the
three-phase ratio differential protection is
latched.

4. CT 断线闭锁 4. CT disconnection
CT 断线的判定条件为: CT disconnection to determine the conditions for:
A、 一侧三相电流中有一相减小为零, A, one side of the three-phase current is reduced
其它两相电流和另外两侧的电流不 to zero, the other two-phase current and the other
变。 side of the current unchanged.
B, the maximum side of the current phase is
B、 本侧最大相电流大于 0.2 倍 IE。 greater than 0.2 times IE.

C, the maximum phase current (three sides) less


C、 最大相电流(三侧)小于 1.2 倍 IE。 than 1.2 times IE.
CT disconnection issued after the alarm signal,
CT 断线后发出告警信号,并可根据控制 and according to the control word to choose
字进行选择是否闭锁差动保护;CT 断线判据 whether to latch the differential protection; CT
对于 CT 突然断线有用,而对 CT 接点电阻逐 disconnection criterion for the CT sudden
渐变大到断路不起作用,但因为有差流告警, disconnection useful, and the CT contact resistance
可以起到 CT 断线告警的作用。 gradually become large to the circuit does not work,
but because there is Differential flow alarm, you
can play the role of CT disconnection alarm.

5.各侧电流相位与平衡补偿
5. Side current phase and balance compensation
为消除各侧 CT 变比选择而造成的不平衡
In order to eliminate the imbalance current
电流,需要计算变压器各侧电流回路的调整
caused by the selection of the CT ratio on each
系数,将其输入装置,通过软件将由此造成
side, it is necessary to calculate the adjustment
的不平衡电流完全补偿。各侧的电流互感器二
coefficient of the current loop on each side of the
次电流相位由软件校正,本装置可对 Y/Δ11
transformer, and input it to the device to
接线方式进行相位校正。
compensate the unbalanced current caused by the
software. Each side of the current transformer
secondary current phase by the software
correction, the device can Y / Δ11 wiring phase
correction.
6. 非电量保护 6. Nonelectric Quantity protection

非电量保护包括重瓦斯、油温高、压力异 heavy gas,oil-temperature high , pressure


常,同时具有轻瓦斯告警和油温升高报警功能 abnormal,light gas,over temperature trip .

Nonelectric Quantity protection include

7 遥测、遥信功能 7. Measurement, signal function

遥测量主要有:三相不平衡电流,这些 Measurement mainly include: Three-phase


量都在当地实时计算。 unbalanced current, these quantities are
calculated locally in real time.
遥信量主要有:16 路遥信开入、装置变位 Signal mainly include: 16 loop remote
遥信及事故遥信,并作事件顺序记录。 information into the device, remote sensing and
remote information, and the order of events
recorded.

8.事件记录功能 8. Event recording function

装置可记录保护动作事件、告警事件以及 Protection device can record motion events,


遥信变位事件。 alarm events, and remote communication
displacement event.
保护动作事件记录保护动作时间,作用 Protection action event record protection time,
于跳闸的保护类型、以及故障时的短路电流。 the role of the type of protection tripping, as well
as short-circuit current value.

告警事件记录 CT 断线、过负荷等系统告 Alarm event recording records CT


警信号。 disconnection、Overload warning signals and so
on.
遥信变位记录遥信量的变位情况。 Remote communication position change
records the position of remote communication
position change.

9.故障录波 9.Trouble recording wave

本装置设有故障录波功能,记录的模拟
量 为
Ia0、Ib0、Ic0、Ia1、Ib1、Ic1、Ia2、Ib2、Ic2、Ia3、Ib
3、Ic3,记录的状态量为开关位置。 The device is provided with the function of
trouble recording wave, analog recording about
Ia0、Ib0、Ic0、Ia1、Ib1、Ic1、Ia2、Ib2、Ic2、Ia3、Ib
3、Ic3,  state recording about switch position.
八、定值 Value
四侧差动保护测控装置定值
序号 定值名称 整定范围 整定步长 备 注
1 差动速断 5.00~99.99A 0.01A
2 比率差动 1.00~30.00A 0.01A
3 拐点 1 电流 1.00~99.99A 0.01A
4 拐点 2 电流 1.00~99.99A 0.01A
5 斜率 1 K1 0.10~0.90 0.01
6 斜率 2 K2 0.10~0.90 0.01
7 谐波制动比 0.1~0.3 0.01
8 I1 调整率 0.10~7.90 0.01
9 I2 调整率 0.10~7.90 0.01 I0 为调整率基准
10 I3 调整率 0.10~7.90 0.01
11 差流告警值 0.10~4.99 0.01
以下整定控制字,控制字位置“1”相应功能投入,置“0”相应功能退出
1 差动速断投入 0(×)/1(√)
2 (差动速断)启动录波投入 0(×)/1(√)
3 比率差动投入 0(×)/1(√)
4 谐波制动投入 0(×)/1(√)
5 经 CT 断线闭锁投入 0(×)/1(√)
6 (比率差动)启动录波投入 0(×)/1(√)
7 I2 投入 0(×)/1(√)
运行参数
8 I3 投入 0(×)/1(√)
9 I0 进行相位调整 0(×)/1(√)
I1 为相位调整基
10 I2 进行相位调整 0(×)/1(√)

11 I3 进行相位调整 0(×)/1(√)

Four side differential protection monitoring and control device setting


Nu Set up
Value name Set up range Note
mber step length
1 DIF action cut-off 5.00~99.99A 0.01A
2 Ratio differential 1.00~30.00A 0.01A
3 Inflexion current 1 1.00~99.99A 0.01A
4 Inflexion current 2 1.00~99.99A 0.01A
5 slope of 1 k1 0.10~0.90 0.01
6 slope of 2 K2 0.10~0.90 0.01
7 Harmonic braking ratio 0.1~0.3 0.01
8 I1 Adjustment rate 0.10~7.90 0.01 I0 is the
9 I2 Adjustment rate 0.10~7.90 0.01 adjustment rate
10 I3 Adjustment rate 0.10~7.90 0.01 reference
Differential current
11 0.10~4.99 0.01
alarm value
The following setting control word, control word position "1" corresponding function input,
set "0" corresponding function exit
1 DIF action cut-off input 0(×)/1(√)
2 (DIF action cut-off) Start recording input 0(×)/1(√)
3 Ratio differential protection input 0(×)/1(√)
4 Harmonic braking ratio input 0(×)/1(√)
5 CT disconnection 0(×)/1(√)
6 (Ratio differential) Start recording input 0(×)/1(√)
7 I2 input 0(×)/1(√) Running
8 I3 input 0(×)/1(√) parameters
9 I0 Phase adjustment 0(×)/1(√) I1 is the
10 I2 Phase adjustment 0(×)/1(√) phase adjustment
11 I3 Phase adjustment 0(×)/1(√) reference

定值整定说明

本装置可以适合多种接线方式,比如全星形(Y/Y/Y/Y)、全三角形(△/△/△/△)、星
三角混接等,在星三角混接方式中三角侧的相位相对星形应为 11 点方向,也即通常
使用的 YD11(Y/△11)接线。

在保护中 I0 侧和 I1 侧必须接入电流,I2 侧和 I3 侧可以不接入电流。在 Y/△混接


方式中,I0 侧必须接星形(Y)侧,I1 必须接三角行(△)侧。

注意:调整率的整定以 I0 为基准;相位的整定以 I1 为基准。


以 I0 侧为星形接法,I1 侧为三角形接法,I2 侧为星形接法,I3 侧为三角形接法为例,
其各侧调整率的算法如下

电流平衡系数 K1、K2、K3

其中:U0e、U1e、U2e、U3e 分别为 0、1、2、3 侧的额定电压。


定值整定说明
Kct0、Kct1、Kct2、Kct3 分别为 0、1、2、3 侧电流互感器变比。

此种情况,0 侧和 2 侧需要进行相位调整。

即在 Y/△混接方式中,电流平衡系数三角形(△)侧的乘以 的系数,而星形(Y)
侧不乘;相位调整是星形(Y)进行调整,而三角形(△)侧不调整。

在全星形(Y/Y/Y/Y)、全三角形(△/△/△/△)中,相位调整项皆为不调整;电流平衡
系数各侧皆不乘 这个系数。

CT 接线要点:

在 CT 的接线上要注意,流向保护区内方向为各侧电流正方向!
Set value setting instructions

The device can be suitable for a variety of wiring methods, such as the whole star (Y / Y / Y /
Y), full triangular (△ / △ / △ / △), star delta mixed, etc., in the star delta mixed way triangular
side Of the phase relative to the star should be 11 o'clock direction, that is commonly used YD11
(Y / △ 11) wiring.
In the protection of the I0 side and I1 side must access the current, I2 side and I3 side can not
access the current. In the Y / △ mixing mode, the I0 side must be connected to the star (Y) side,
and I1 must be connected to the triangular line (△) side.
Note: The adjustment of the adjustment rate is based on I0; the setting of the phase is based
on I1.
I0 side for the star connection, I1 side for the triangular connection, I2 side for the star
connection, I3 side for the triangular connection, for example, the side of the adjustment rate
algorithm is as follows

Current balance coefficients K1, K2, K3


among them: U0e, U1e, U2e, U3e are 0,1,2,3 side of the rated voltage.
Kct0, Kct1, Kct2, Kct3 are 0,1,2,3 side current transformer ratio.
In this case, the 0 side and 2 sides need to adjust the phase.
(Y) side of the current balance coefficient triangle (△) multiplied by the coefficient, while
the star (Y) side is not multiplied; phase adjustment is the star (Y) to adjust, and the triangle (△ )
Side does not adjust.
In the full star (Y / Y / Y / Y), full triangle (△ / △ / △ / △), the phase adjustment items are
not adjusted; current balance coefficient on each side do not take this coefficient.
CT wiring points:
In the wiring of the CT should pay attention to the direction of the direction of the
protection zone for the side of the current positive direction!
九、装置端子图及端子定义 Device terminal definition diagram
十、控制回路图 Control circuit diagram
十一、外形及安装尺寸 Shape & installation size
订货须知 Ordering Information:
1. 产品名称、型号、数量。 1.Product name, model, number;
2. 工作电源:DC220V□ AC220V □; 2.Power supply: DC220V □ AC220V□;
3. 交流电流输入:5A □ 1A □; 3.AC current input: 5A □ 1A □;
4. 交流电压输入:100V □ 110V □; 4.AC input voltage: 100V □ 110V □;
5. 通讯接口:以太网 □ RS485 □; 5.Communication Interface: Ethernet□RS485 □;
6. 显示语言:中文 □ 英文 □; 6.Language: Chinese □ English □;
7. 变压器接线组别 ______________。 7. Transformer wiring group ______________.