4006-4008TRS KRONOS20 setting procedure

1) Engine off, set parameter 5400_ClosedOrOpenLoop= 0 for open loop mode


2) Run the engine, cold and with no load O2 should be 4.5-5.5%
3) ZPR setting: rotate clockwise less gas and more O2.
4) Check Timing, with Detcon on should be 24°BTDC, with Detcon off 14-15°BTDC
5) Adjust param 1530_AnalogIn3_RefLow to the value read by the load sensor
3531_AnalogIn3_Value
6) Gradually put load and verify that the intake temp remains <55°C, NOx level should be
around NOx 180ppm (max 220) and O2 around 9%
7) Roughly adjust emissions by modifying parameter 1462_RichLeanMixtureCorr, <100%
means leaner mixture so more O2 and less NOx (typical range: 90/110%)
8) At full load adjust param 1531_AnalogIn3_RefHigh to the value read by the load sensor
3531_AnalogIn3_Value
9) Go to no load and set parameter 5400 ClosedOrOpenLoop = 1 for closed loop mode
10) Gradually put load and verify that the intake temp remains <55°C, NOx level should be
around NOx 180ppm (max 220) and O2 around 9%
11) Thoroughly adjust emissions by modifying parameter 1462_RichLeanMixtureCorr, <100%
means leaner mixture so more O2 and less NOx (typical range: 90/110%)
12) Switch engine off, power off Kronos then power on again and check param are stored

Relevant Parameters to record

Kronos Elektra Pandaros


2000 Speed 2000 Speed 2000 Speed
2302 StepperPos 2300 ActPos 2031 SpeedSetp
2332 StepperPosSetpoint 2330 ActPosSetpoint 2300 ActPos
2912 ManifoldPressure 2906 AirPressure1 2330 ActPosSetpoint
2907 AirPressure2
2913 ManifoldTemp 2908 AirTemp 2902 LoadCtrlInput
2914 MeasuredPower 2910 GasTemp 2903 SyncInput
3411 CalculatedPower 2914 GasPressure 3521 AnalogIn2_Value
3531 AnalogIn3_Value 2915 GasDeltaPressure
2916 Vent1DeltaPressure
2917 Vent2DeltaPressure
2918 MeasuredPower
3300 MeasElectricPower
3301 EngineThermalPower
3339 Lambda
3511 AnalogIn1_Value
3530 AnalogIn3 3510 AnalogIn1 3511 AnalogIn1_Value
3540 AnalogIn4 3531 AnalogIn3_Value
3541 AnalogIn4_Value 3510 AnalogIn1
3520 AnalogIn2
3530 AnalogIn3
3800 EmergencyAlarm 3800 EmergencyAlarm 3800 EmergencyAlarm
3801 CommonAlarm 3801 CommonAlarm 3801 CommonAlarm
3802 EngineStop 3802 EngineStop 3802 EngineStop
3803 EngineStopped 3803 EngineStopped 3803 EngineStopped
3804 EngineStarting 3804 EngineStarting 3804 EngineStarting
3805 EngineRunning 3805 EngineRunning 3805 EngineRunning
3806 EngineReleased 3806 EngineReleased 3806 EngineReleased
3830 Phase 3830 Phase 3830 Phase
4016TRS KRONOS30 (Elektra) setting procedure

1) Engine off, verify parameter 5308_LambdaSetpCorrPCOn= 1 (allow adjustment of emissions)


and 918_AssignIn_MeasPower= 1 (read the electrical power measure). Set gas parameter as
per gas spec 1303_NormGasGravity,1320_AFRAtStoichiometry,1340_GasLowHeatingValue
2) Set parameter 5340_AFRClosedOrOpenLoop= 0 for open loop mode
3) Run the engine with no load
4) Check Timing, with Detcon on should be 26°BTDC, with Detcon off 14-15°BTDC
5) Adjust param 1510_AnalogIn1_RefLow to the value read by the load sensor
3511_AnalogIn1_Value
6) Gradually put load and verify that the intake temp remains <55°C, NOx level, from mid to full
load, should be around NOx 180ppm (max 220) and O2 around 9%
7) Roughly adjust emissions by modifying parameter 1302_LambdaSetpointCorrPC, increasing
means leaner mixture so more O2 and less NOx (typical range 90%/110%)
8) At full load adjust param 1511_AnalogIn1_RefHigh to the value read by the load sensor
3511_AnalogIn1_Value
9) Go to no load and set parameter 5340_AFRClosedOrOpenLoop = 1 for closed loop mode
10) Gradually put load again and verify that the intake temp remains <55°C, NOx level, from mid to
full load, should be around NOx 180ppm (max 220) and O2 around 9%
11) Thoroughly adjust emissions by modifying parameter 1302_LambdaSetpointCorrPC, increasing
means leaner mixture so more O2 and less NOx (typical range 90%/110%)
12) Adjust bank-to-bank NOx if diff>100ppm from mid to full load by modifying parameter
1951_FeedbackRef_100% Adjust at low load (<200kW) increase value if A bank<B bank (A bank
right from Flywheel) step of 500 then lower, typical range: 50000/60000)
13) Switch engine off, power off Elektra then power on again and check param are stored

Relevant Parameters to record


Kronos Elektra Pandaros
2000 Speed 2000 Speed 2000 Speed
2302 StepperPos 2300 ActPos 2031 SpeedSetp
2332 StepperPosSetpoint 2330 ActPosSetpoint 2300 ActPos
2912 ManifoldPressure 2906 AirPressure1 2330 ActPosSetpoint
2907 AirPressure2
2913 ManifoldTemp 2908 AirTemp 2902 LoadCtrlInput
2914 MeasuredPower 2910 GasTemp 2903 SyncInput
3411 CalculatedPower 2914 GasPressure 3521 AnalogIn2_Value
3531 AnalogIn3_Value 2915 GasDeltaPressure
2916 Vent1DeltaPressure
2917 Vent2DeltaPressure
2918 MeasuredPower
3300 MeasElectricPower
3301 EngineThermalPower
3339 Lambda
3511 AnalogIn1_Value
3530 AnalogIn3 3510 AnalogIn1 3511 AnalogIn1_Value
3540 AnalogIn4 3531 AnalogIn3_Value
3541 AnalogIn4_Value 3510 AnalogIn1
3520 AnalogIn2
3530 AnalogIn3
3800 EmergencyAlarm 3800 EmergencyAlarm 3800 EmergencyAlarm
3801 CommonAlarm 3801 CommonAlarm 3801 CommonAlarm
3802 EngineStop 3802 EngineStop 3802 EngineStop
3803 EngineStopped 3803 EngineStopped 3803 EngineStopped
3804 EngineStarting 3804 EngineStarting 3804 EngineStarting
3805 EngineRunning 3805 EngineRunning 3805 EngineRunning
3806 EngineReleased 3806 EngineReleased 3806 EngineReleased
3830 Phase 3830 Phase 3830 Phase