Professional Documents
Culture Documents
130
269
§ 183.200 46 CFR Ch. I (10–1–98 Edition)
feet) in length carrying not more than suitable construction and corrosion-re-
12 passengers, may comply with the sistant.
following requirements instead of com-
plying with the requirements of this § 183.220 General safety provisions.
part in their entirety: (a) Electrical equipment and installa-
(1) Section 183.420; and tions must be suitable for the roll,
(2) The following American Boat and pitch, and vibration of the vessel un-
Yacht Council (ABYC) Projects where derway.
applicable: (b) All equipment, including switch-
(i) E–8, ‘‘Alternating Current (AC) es, fuses, lampholders, etc., must be
Electrical Systems on Boats;’’ suitable for the voltage and current
(ii) E–9, ‘‘Direct Current (DC) Elec- utilized.
trical Systems on Boats;’’ and (c) Receptacle outlets of the type
(iii) A–16, ‘‘Electrical Navigation providing a grounded pole or a specific
Lights.’’ direct current polarity must be of a
(b) A vessel with an electrical instal- configuration that will not permit im-
lation operating at less than 50 volts proper connection.
may meet the requirements in 33 CFR (d) All electrical equipment and cir-
183.430 instead of those in § 183.340 of cuits must be clearly marked and iden-
this part. tified.
(e) Any cabinet, panel, box, or other
[CGD 85–080, 61 FR 997, Jan. 10, 1996; 61 FR
20557, May 7, 1996, as amended by CGD 97–057, enclosure containing more than one
62 FR 51050, Sept. 30, 1997] source of power must be fitted with a
sign warning persons of this condition
and identifying the circuits to be dis-
Subpart B—General Requirements connected.
§ 183.200 General design, installation,
and maintenance requirements. Subpart C—Power Sources and
Electrical equipment on a vessel Distribution Systems
must be installed and maintained to:
(a) Provide services necessary for § 183.310 Power sources.
safety under normal and emergency (a)(1) Each vessel that relies on elec-
conditions; tricity to power the following loads
(b) Protect passengers, crew, other must be arranged so that the loads can
persons, and the vessel from electrical be energized from two sources of elec-
hazards, including fire, caused by or tricity:
originating in electrical equipment, (i) The vital systems listed in § 182.710
and electrical shock; of this chapter;
(c) Minimize accidental personnel (ii) Interior lighting except for deco-
contact with energized parts; and rative lights;
(d) Prevent electrical ignition of (iii) Communication systems includ-
flammable vapors. ing a public address system required
under § 184.610 of this chapter; and
§ 183.210 Protection from wet and cor- (iv) Navigation equipment and lights.
rosive environments. (2) A vessel with batteries of ade-
(a) Electrical equipment used in the quate capacity to supply the loads
following locations must be dripproof: specified in paragraph (a)(1) of this sec-
(1) A machinery space; tion for three hours, and a generator or
(2) A location normally exposed to alternator driven by a propulsion en-
splashing, water washdown, or other gine, complies with the requirement in
wet conditions within a galley, a laun- paragraph (a)(1) of this section.
dry, or a public washroom or toilet (b) Where a ship service generator
room that has a bath or shower; or driven by a propulsion engine is used as
(3) Another space with a similar a source of electrical power, a vessel
moisture level. speed change, throttle movement or
(b) Electrical equipment exposed to change in direction of the propeller
the weather must be watertight. shaft rotation must not interrupt
(c) Electrical equipment exposed to power to any of the loads specified in
corrosive environments must be of paragraph (a)(1) of this section.
270
Coast Guard, DOT § 183.330
271
§ 183.340 46 CFR Ch. I (10–1–98 Edition)
working space behind the switchboard are acceptable as meeting the require-
is less than 455 millimeters (18 inches). ments of this section;
(f) Nonconducting mats or grating (5) Not be installed with sharp bends;
must be provided on the deck in front (6) Be protected by metal coverings
of each switchboard and, if accessible or other suitable means if in areas sub-
from the rear, on the deck in the rear ject to mechanical abuse. Horizontal
of the switchboard. pipes used for protection shall have 6
(g) All uninsulated current carrying millimeter (.25 inch) holes for drainage
parts must be mounted on noncombus- every 1,520 millimeters (5 feet);
tible, nonabsorbent, high dielectric in- (7) Be suitable for low temperature
sulating material. and high humidity if installed in re-
(h) Equipment mounted on a hinged frigerated compartments;
door of an enclosure must be con- (8) Not be located in a tank unless
structed or shielded so that a person the cable provides power to equipment
will not accidentally contact energized in the tank; and
parts of the door mounted equipment (9) Have sheathing or wire insulation
when the door is open and the circuit compatible with the fluid in a tank
energized. when installed as allowed by paragraph
(i) In the design of a control, inter- (b)(8) of this section.
lock, or indicator circuit, the dis- (c) Conductors in power and lighting
connect device and its connections, in- circuits must be No. 14 American Wire
cluding each terminal block for termi- Gauge (AWG) or larger. Conductors in
nating the vessel’s wiring, must not control and indicator circuits must be
have any electrically unshielded or No. 22 AWG or larger.
uninsulated surfaces. (d) Cable and wire for power and
(j) Switchboards and distribution lighting circuits must:
panels must be sized in accordance (1) Meet Section 310–13 of the NEC
with § 111.30–19(a) in subchapter J of (NFPA 70), except that asbestos insu-
this chapter. lated cable and dry location cables can-
[CGD 85–080, 61 FR 997, Jan. 10, 1996, as not be used;
amended by CGD 97–057, 62 FR 51050, Sept. 30, (2) Be listed by Underwriters Labora-
1997] tories (UL), as UL Boat or UL Marine
cable; or
§ 183.340 Cable and wiring require- (3) Meet § 111.60–1 in subchapter J of
ments. this chapter for cable, and § 111.60–11 in
(a) If individual wires, rather than subchapter J of this chapter for wire.
cable, are used in systems greater than (e) Cable or wire serving vital sys-
50 volts, the wire must be in conduit. tems listed in § 182.710 of this chapter
(b) All cable and wire must: or emergency loads must be routed as
(1) Have stranded copper conductors far as practicable from high risk fire
with sufficient current carrying capac- areas, such as galleys, laundries, and
ity for the circuit in which they are machinery spaces.
used; (f) Cable or wire serving duplicated
(2) Be installed in a manner to avoid equipment must be separated so that a
or reduce interference with radio re- casualty that affects one cable does not
ception and compass indication; affect the other.
(3) Be protected from the weather; (g) Each connection to a conductor or
(4) Be installed with metal supports terminal part of a conductor must be
spaced not more than 610 millimeters made within an enclosure and have ei-
(24 inches) apart, and in such a manner ther:
as to avoid chafing and other damage. (1) A pressure type connector on each
The use of plastic tie wraps must be conductor;
limited to bundling or retention of (2) A solder lug on each conductor;
multiple cable installations, and not (3) A splice made with a pressure
used as a means of support, except that type connector to a flexible lead or
on vessels of not more than 19.8 meters conductor; or
(65 feet) in length, installations in ac- (4) A splice that is soldered, brazed,
cordance with paragraph 14.h of ABYC or welded to a flexible lead or conduc-
E–8, and paragraph 15.h of ABYC E–9, tor.
272
Coast Guard, DOT § 183.340
(h) A connector or lug of the set (2) For a vessel receiving alterations,
screw type must not be used with a a cable may be spliced to extend a cir-
stranded conductor smaller than No. 14 cuit;
AWG except if there is a nonrotating (3) A cable having a large size or ex-
follower that travels with the set screw ceptional length may be spliced to fa-
and makes pressure contact with the cilitate its installation; and
conductor. (4) A cable may be spliced to replace
(i) Each pressure type wire connector a damaged section of the cable if, be-
and lug must meet UL 486A, ‘‘Electric fore replacing the damaged section, the
Wire Connectors and Soldering Lugs insulation resistance of the remainder
of the cable is measured, and it is de-
for Use With Copper Conductors,’’ or
termined that the condition of the in-
other standard specified by the Com-
sulation is unimpaired.
mandant. The use of twist-on type wire (n) All material in a cable splice
nuts is permitted under the following must be chemically compatible with
conditions: all other material in the splice and
(1) The connections must be made with the materials in the cable.
within an enclosure and the insulated (o) Ampacities of wires must meet
cap of the connector must be secured Section 310–15 of the NEC (NFPA 70), or
to prevent loosening due to vibration; other standard specified by the Com-
and mandant. Ampacities of cable must
(2) Twist-on type connectors may not meet table A6 of Institute of Electrical
be used for making joints in cables, fa- and Electronic Engineers (IEEE)
cilitating a conductor splice, or ex- Standard 45, ‘‘Recommended Practice
tending the length of a circuit. for Electrical Installations on Ship-
(j) Each terminal block must have 6– board,’’ or other standard specified by
32 terminal screws or larger. the Commandant. Ampacities for Navy
(k) Wire connectors utilized in con- cable must meet NAVSEA Design Data
junction with screw type terminal Sheet (DDS) 304–2 ‘‘Electrical Cable,
Ratings and Characteristics’’ as appro-
blocks must be of the captive type such
priate.
as the ring or the flanged spade type.
(p) Conductors for direct current sys-
(l) A cable must not be spliced in a tems must be sized so that the voltage
hazardous location. drop at the load terminals does not ex-
(m) A cable may be spliced in a loca- ceed 10 percent. Table 183.340(p) indi-
tion, other than a hazardous location, cates the size of conductor required for
under the following conditions: corresponding lengths and steady state
(1) A cable installed in a subassembly (stable) values to obtain not more than
may be spliced to a cable installed in this voltage drop at the load terminals
another subassembly; of a two conductor circuit.
TABLE 183.340(P)—CONDUCTOR SIZES FOR AMPERES—LENGTHS
Total cur- Length of conductor in meters (feet) from source of current to most distant fixture
rent on
circuit, 3.1(10) 4.5(15) 6.1(20) 7.6(25) 9.2(30) 10.7(35) 12.2(40) 13.7(45) 15.2(50) 16.8(55) 18.3(60)
amperes
273
§ 183.350 46 CFR Ch. I (10–1–98 Edition)
(a constant representing the resist- (h) Batteries used for engine starting
ance of copper). are to be located as close as possible to
I=Load current, in amperes. the engine or engines served.
L=length of conductor from center of [CGD 85–080, 61 FR 997, Jan. 10, 1996; 61 FR
distribution, in meters (feet). 20557, May 7, 1996]
E=Voltage drop at load, in volts.
(q) If used, each armored cable metal- § 183.352 Battery categories.
lic covering must: This section applies to batteries in-
(1) Be electrically continuous; and stalled to meet the requirements of
(2) Be grounded at each end of the § 183.310 for secondary sources of power
run to: to vital loads, or sources of power to
(i) The metallic hull; or final emergency loads.
(ii) The common ground plate on (a) Large. A large battery installation
nonmetallic vessels; and is one connected to a battery charger
having an output of more than 2 kilo-
(3) Have final sub-circuits grounded
watts (kw), computed from the highest
at the supply end only.
possible charging current and the rated
(r) A portable or temporary electric
voltage of the battery installation.
cord or cable must be constructed and
(b) Small. A small battery installa-
used in compliance with the require-
tion is one connected to a battery
ments of § 111.60–13 in subchapter J of
charger having an output of 2 kw or
this chapter for a flexible electric cord
less, computed as above.
or cable.
[CGD 85–080, 61 FR 997, Jan. 10, 1996, as
[CGD 85–080, 61 FR 997, Jan. 10, 1996; 61 FR amended by CGD 97–057, 62 FR 51050, Sept. 30,
20557, May 7, 1996, as amended by CGD 97–057, 1997]
62 FR 51050, Sept. 30, 1997; CGD 85–080, 62 FR
51358, Sept. 30, 1997] § 183.354 Battery installations.
§ 183.350 Batteries—general. (a) Large batteries. Each large battery
installation must be located in a lock-
(a) Where provisions are made for er, room or enclosed box solely dedi-
charging batteries, there must be natu- cated to the storage of batteries. Ven-
ral or induced ventilation sufficient to tilation must be provided in accord-
dissipate the gases generated. ance with § 111.15–10 in subchapter J of
(b) Each battery must be located as this chapter. Electrical equipment lo-
high above the bilge as practicable, se- cated within the battery enclosure
cured to protect against shifting with must be approved by an independent
the roll and pitch of the vessel, and laboratory for Class I, Division 1,
free from exposure to water splash or Group B hazardous locations and meet
spray. § 111.105 in subchapter J of this chapter.
(c) Batteries must be accessible for (b) Small batteries. Each small battery
maintenance and removal. installation must be located in a well
(d) Connections must be made to bat- ventilated space and protected from
tery terminals with permanent type falling objects. A small battery instal-
connectors. Spring clips or other tem- lation must not be in a closet, store-
porary type clamps are prohibited. room or similar space.
(e) Batteries must be mounted in
trays lined with, or constructed of, a § 183.360 Semiconductor rectifier sys-
material that is resistant to damage by tems.
the electrolyte. (a) Each semiconductor rectifier sys-
(f) Battery chargers must have an tem must have an adequate heat re-
ammeter connected in the charging moval system that prevents overheat-
circuit. ing.
(g) If the batteries are not adjacent (b) Where a semiconductor rectifier
to a distribution panel or switchboard system is used in a propulsion system
that distributes power to the lighting, or in other vital systems it must:
motor, and appliance circuits, the bat- (1) Have a current limiting circuit;
tery lead must have a fuse in series as (2) Have external overcurrent protec-
close as practicable to the battery. tion; and
274
Coast Guard, DOT § 183.378
(3) Meet Sections 35.84.2 and 35.84.4 of (e) Cable armor must not be used to
the American Bureau of Shipping ground electrical equipment or sys-
(ABS), ‘‘Rules for Building and tems.
Classing Steel Vessels,’’ or other stand-
ard specified by the Commandant. § 183.376 Grounded distribution sys-
tems (neutral grounded).
§ 183.370 General grounding require-
ments. (a) If a grounded distribution system
is provided, there must be only one
(a) A vessel’s hull must not carry connection to ground, regardless of the
current as a conductor except for the number of power sources. This ground
following systems: connection must be at the switchboard
(1) Impressed current cathodic pro- or at the common ground plate, which
tection systems; or must be accessible.
(2) Battery systems for engine start- (b) Each propulsion, power, lighting,
ing. or distribution system having a neutral
(b) Receptacle outlets and attach- bus or conductor must have the neutral
ment plugs for portable lamps, tools, grounded.
and similar apparatus operating at 100
(c) The neutral of each grounded gen-
volts or more, must have a grounding
eration and distribution system must
pole and a grounding conductor in the
be grounded at the generator switch-
portable cord.
board and have the ground connection
(c) Each nonmetallic mast and top
accessible for checking insulation re-
mast must have a lightning ground
conductor. sistance of the generator to ground be-
fore the generator is connected to the
§ 183.372 Equipment and conductor bus, except the neutral of an emer-
grounding. gency power generation system must
(a) All metallic enclosures and be grounded with:
frames of electrical equipment must be (1) No direct ground connection at
permanently grounded to the hull on a the emergency switchboard;
metallic vessel. On a nonmetallic ves- (2) The neutral bus permanently con-
sel, the enclosures and frames of elec- nected to the neutral bus on the main
trical equipment must be bonded to- switchboard; and
gether to a common ground by a nor- (3) No switch, circuit breaker, or fuse
mally non-current carrying conductor. in the neutral conductor of the bus-tie
Metallic cases of instruments and sec- feeder connecting the emergency
ondary windings of instrument trans- switchboard to the main switchboard.
formers must be grounded. (d) On a metallic vessel, a grounded
(b) On a nonmetallic vessel, where a alternating current system must be
ground plate is provided for radio grounded to the hull. On a nonmetallic
equipment, it must be connected to the vessel, the neutral must be connected
common ground. to the common ground, except that
(c) Equipment grounding conductors aluminum grounding conductors must
must be sized in accordance with Sec- not be used.
tion 250–95 of the NEC (NFPA 70), or
other standard specified by the Com- § 183.378 Ungrounded systems.
mandant.
(d) Each insulated grounding conduc- Each ungrounded system must be
tor of a cable must be identified by one provided with a suitably sensitive
of the following means: ground detection system located at the
(1) A green braid or green insulation; respective switchboard that provides
(2) Stripping the insulation from the continuous indication of circuit status
entire exposed length of the grounding to ground with a provision to momen-
conductor; or tarily remove the indicating device
(3) Marking the exposed insulation of from the reference ground.
the grounding conductor with green [CGD 85–080, 62 FR 51358, Sept. 30, 1997]
tape or green adhesive labels.
275
§ 183.380 46 CFR Ch. I (10–1–98 Edition)
276
Coast Guard, DOT § 183.530
panel, must be provided for each radio- Lights,’’ or other standard specified by
telephone installation. the Commandant.
277
§ 183.540 46 CFR Ch. I (10–1–98 Edition)
278